Slant/Fin GXHA-200 User Manual

CONTENTS .........................................................................PAGE
Dimensions..................................................................................2
Installation Requirements:
Boiler Location........................................................................3
Boiler Foundation....................................................................3
Chimney Requirements............................. .............................3
Minimum Clearance.....................................................................3
Vent Piping..............................................................................4
Gas Piping...................................................................................4
Boiler Room Air Supply and Ventilation..................................5
Draft Hood Installation.............................. ..............................5
Piping at Boiler—Steam Boilers................... ..........................6
Steam Controls Assembly and Installation.............................6
Piping a Steam Boiler.........................................................6,7
Vent Damper.......................................... ..............................8,9
Operating Instructions:
Filling and Venting Steam Systems...................................9-10
Initial Start, Safety and Lighting Instructions...................10-11
Controls, Safety Check.........................................................12
Low Water Cut-off Check-Out....................................................12
Pressure Control Check-Out .....................................................12
Blowing Off a Steam Boiler........................................................13
Care and Maintenance.................................. ............................14
Safety Check for Control System..........................................14
Water Treatment....................................................................14
Sequence of Operations............................................................15
Wiring Diagrams...................................................................16-17
Troubleshooting Guide...............................................................18
Replacement Parts....................................................................19
Appendix A ................................................................................19
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS AND
STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
The installation must conform to the requirements of the authori­ty having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition, where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
WARNING
This boiler, gas piping and accessories must be installed, con­nected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed or otherwise qualified, in compliance with the authority having jurisdiction.
Printed in U.S.A. 1114 PUBLICATION GGS-41
Part No. 41-0881
INSTALLATION AND OPERATING INSTRUCTIONS
LOW PRESSURE STEAM—Models GXH-230 through GXH-300H LOW PRESSURE STEAM—Models GXHA-100 through GXHA-200
GALAXY
GAS-FIRED CAST IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
STEAM BOILERS
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
WARNING
SEE “WARNING” ON PAGE 3 FOR LIQUEFIED
PETROLEUM (L.P.) PROPANE GAS-FIRED BOILERS
2 GALAXY STEAM BOILER
ORIFICE SIZES indicated for Sea Level are factory installed in
boiler unless otherwise specified by the local authority. See VII, page 11 for burner input adjustment.
GAS VALVE CONNECTION Size is 1/2" f.p.t. for all sizes. COMBUSTIBLE FLOOR KIT increases all height dimensions by 1". RAISED SLAB - When mounting boiler on a raised slab, the slab
must extend at least 2" beyond the boiler cabinet on all sides. CHIMNEY HEIGHT: 15 ft. minimum from draft hood skirt to top of chimney. CHIMNEY INSIDE DIAMETER must be same as Dimen­sion “C” or larger. Larger diameter and/or height may be required if two or more boilers or a boiler and another appliance are vented to a single chimney.
GXHA-100 GXHA-120 GXHA-160 GXHA-200
GXH-230 GXH-250 GXH-275 GXH-300H
A ––––29
3
4 321⁄2 321⁄2 321⁄2
B 161⁄2 161⁄2 20 231⁄4 231⁄4 26 26 26 C 5667 777 9 D ––––55
1
2 551⁄2 551⁄2 591⁄8
E 14 14 14 15 F 10 10 11
3
4 131⁄2 13 143⁄4 143⁄4 143⁄4
G ––––1
1
2 11⁄2 11⁄2 11⁄2
H ––––2
1
2 21⁄2 21⁄2 21⁄2
J –– ––3
1
2 31⁄2 31⁄2 31⁄2
K ––––9
3
4 93⁄4 93⁄4 93⁄4
M 285⁄8 285⁄8 285⁄8 285⁄8 ––– –
GXH AND GXHA SERIES STEAM BOILERS - DIMENSIONS IN INCHES
RIGHT SIDE
GXH-PZT-PPZT
RIGHT SIDE
GXH-PZ
GXH-230 Natural 44 45 45 45 46 47 47 48 48 49 through 275 Propane 54 54 55 55 55 55 55 56 56 56
GXH-300H Natural
Gas* 43 44 44 44 45 45 46 47 47 48
GXHA
Natural 45 46 47 47 47 48 48 49 49 50
Propane 55 55 55 55 56 56 56 56 56 57
BOILER MODEL
GAS TYPE
2,000
ELEVATION–FEET
ORIFICE SIZES AT HIGH ALTITUDES
INCLUDES 4% INPUT REDUCTION FOR EACH 1000 FEET
3,000
4,000
5,000 6,000
7,000
8,000
9,000 10,000
Orifice
Size for
Sea Level
*For L.P. Propane gas, consult factory.
BOILER DIMENSIONS
GXHA Series
GALAXY STEAM BOILER 3
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the author­ity having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition.
This installation must also conform to the additional require­ments in this Slant/Fin instruction book. Installation and service to be performed by a qualified installer, service agency or the gas supplier.
NATURAL GAS-FIRED BOILER LOCATION—
Provide a level, solid foundation for the boiler. Location should be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
Automatic gas ignition system components shall be installed so these components will not be subjected to dripping water during installation or service.
CHIMNEY REQUIREMENTS—
A. Galaxy boilers may be vented into a masonry vitreous tile-
lined chimney or UL LISTED Type “B” Venting system NOT EXPOSED to the OUTDOORS below the roof line. Venting and sizing of venting system must be in accordance with National Fuel Gas Code ANSI Z223.1, NFPA 54, -latest edition which will be referred to as the National Fuel Gas Code. Local codes apply. If a masonry chimney is exposed to the outdoors on one or more sides below the roof line (exterior chimney), ONE of the following options apply:
1. Chimney must be re-lined with a UL LISTED metallic liner. When this is done, the chimney will be considered NOT exposed to the outdoors and the requirements of the National Fuel Gas Code for NON-exposed chimneys and/or local codes will apply.
2. If an exposed tile-lined chimney is to be used WITHOUT a
UL LISTED metallic liner, the boiler must first meet the requirements of the following tables and paragraphs of the National Fuel Gas Code:
B. If an existing boiler is removed from a common venting sys-
tem, the common venting system may be too large for prop­er venting of the remaining appliances connected to the common vent. Follow the test procedure shown in Appendix "A" on page 19 of this manual to insure proper operation of venting system and appliances.
C. Inspect for proper and tight construction. Any restrictions or
obstructions must be removed. An existing chimney may require cleaning.
D. Chimney or vent must extend at least 3 feet above its pas-
sage through a roof and at least 2 feet above any ridge with­in 10 feet of the chimney.
MINIMUM CLEARANCES FROM COMBUSTIBLE CON­STRUCTION
A. Minimum boiler clearances shall be as follows:
BOILER FOUNDATION
A. Provide a solid, level foundation, capable of supporting the
weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of boilers,
page 2. B. For installation on non-combustible floors only.* C. If boiler is to be located over buried conduit containing elec-
tric wires or telephone cables, consult local codes or the
National Board of Fire Underwriters for specific require-
ments.
* The Combustible Floor Kit part number printed on the boiler rating plate is
the only one to be used when installing on combustible floors. The boiler must NOT be installed on carpeting. DO NOT place boilers above floor area containing radiant tubing.
WARNING
SPECIAL ATTENTION FOR LIQUEFIED PETROLEUM
(L.P.) PROPANE GAS-FIRED BOILER INSTALLATIONS
LPG appliances (boilers) shall be installed in accordance with applicable provisions of NFPA 58 ( Liquefied Petroleum Gas Code) latest edition for installations in US and CAN/CGA B149.1 latest edition for installations in Canada.
Liquefied Petroleum (LP) propane gas is heavier than air therefore Propane gas accumulate at floor level. If you sus­pect a leak, do not attempt to operate boiler. A spark or flame from the appliance (boiler) or other sources may ignite the accumulated propane gas causing an explosion or fire. It is recommended that inspections for gas leaks be performed periodically by licensed professional and that leak detection devices be installed as a further safety measure.
4 GALAXY STEAM BOILER
B. Provide accessibility clearance of 24" on sides requiring ser-
vicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clearances in order to maintain the minimum clearances of others.
D. Clearance from steam and hot water pipes shall be 1". **
** At points where hot water or steam pipes emerge from a floor, wall or ceil-
ing, the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2". Each such opening shall be covered with a plate of noncombustible material.
SAFETY—
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
VENT PIPING—
A. Vent piping installation must be in accordance with ANSI
Z223.1-latest edition, National Fuel Gas Code, Part 7, Venting of Equipment. Other local codes may also apply and must be followed.
B. Boiler vent pipe must be the full diameter of the boiler draft
hood outlet. See dimensions, page 2. If a vent damper is added, its diameter must be equal to the hood outlet and must be located past the hood outlet. See installation instructions furnished with vent damper and in the section "Vent Damper Installation" of this instruction book.
C. If more than one appliance vents into a common breeching,
the area of the breeching must be equal to the area of the largest vent plus 50% of the area of the additional vent areas. Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. Horizontal breeching or vent pipe should be as high as possible, con­sistent with codes, so that vertical vents from appliances will have a high rise above draft diverter openings. All horizontal runs must slope upwards not less than 1/4 inch per foot of run. Horizontal portions of the venting system must be sup­ported to prevent sagging by securing each joint with metal screws and by providing hangers spaced no greater than 5 feet apart.
D. Vent or breeching into chimney should not be inserted past
the inside wall of the chimney liner.
E. All venting means should be inspected frequently. See Care
and Maintenance and separate User's Information Manual.
GAS PIPING—
A. Local installation codes apply. The pipe joint compound used
on threads must be resistant to the action of liquefied petro-
leum gases. B. The gas supply line to the boiler should be run directly from
the meter for natural gas or from the fuel tank for L.P.
propane gas. See page 2 for location of union and manual
main shut-off valve that may be specified locally.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas (BTU/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow
in piping (cu. ft. per hour).
4. Use table below to select proper pipe size.
Example: Boiler model GXH-300H is to be installed. Distance from gas meter to the boiler is 50 ft. Heating value of natural gas is 1020 BTU/cu. ft. Select proper pipe size.
At 50 ft. length of pipe, match required capacity from table below (choose higher capacity, in this case is 440 cu. ft. per hour). Required pipe size is 1-1/4". Improper gas pipe sizing will result in pilot flame outages, insufficient heat and other installation difficulties. For more information and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested before
placing the boiler in operation. Use liquid soap solution for all gas leak testing. DO NOT use open flame. This boiler and its individual shut-off valve must be discon­nected from the gas supply piping system during any pres­sure testing of that system at test pressures in excess of 1/2 PSIG. This boiler must be isolated from the gas supply piping sys­tem by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap must be provid­ed, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
GXH SERIES GXHA SERIES
MODELS GXH-230 TO GXH-300H, MINIMUM CLEARANCE FOR COMBUSTIBLE CON­STRUCTION. MINIMUM ALCOVE CLEARANCE. Front Alcove Rear 6" Left Side 6" Right Side 18" Top 36" Flue Connector 6" Type 'B' Vent 1"
MODELS GXHA-100, GXHA-120, GXHA-160 & GXHA-200 MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUCTION. CLOSET AND ALCOVE CLEARANCE. Front 6" Rear 6" Left Side 6" Right Side 18" Top 18" Flue Connector 6" Type 'B' Vent 1"
1/2 3/4 1 1-1/4 1-1/2
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Length of Pipe in Feet
Gas Flow In Piping — cu. ft. per hr.
Iron Pipe Size (IPS) — inches
Gas flow = 300,000 BTU/hour = 294 cu. ft. per hour
1020 BTU/cu. ft.
GALAXY STEAM BOILER 5
ELECTRICAL CONTROLS AND WIRING—
A. The electrical power to the boiler must be on a separately
fused and live circuit.
B. If an external electrical source is utilized, the boiler, when
installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in absence of such requirements, with the National Electrical Code, ANSI/NFPA No. 70-latest edition.
C. Basic control wiring diagrams are given on pages 16-17.
Other control systems may be factory supplied, see User's Information Manual and Instructions packed with control system supplied.
D. After placing the boiler in operation, the safety shut-off
device must be tested. See page 12 safety check.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required to obtain combustion and ventilation. Room temperature over 100°F may cause nuisance tripping of the Blocked Vent Safety Switch.
ALL AIR MUST COME FROM OUTSIDE, directly through wall openings to the boiler or through unsealed openings around windows, doors, etc. in the whole building. When buildings are insulated, caulked and weather-stripped, now or later on, direct opening to outside may be required and should be provided. If the boiler is not on an outside wall, air may be ducted to it from outside wall openings.
The National Fuel Gas Code, ANSI Z223.1-latest edition speci­fies openings for air under various conditions. Local codes may specify minimum opening sizes and locations. The following recommendation applies to buildings of energy-saving construc­tion, fully caulked and weather-stripped:
Provide one GRILLED opening near the floor and one near the ceiling on an outside wall near the boiler (or duct from such openings to the boiler), EACH opening to be a minimum of one square inch per 2000 Btuh input to ALL APPLIANCES in the area. For a total appliance input of 200,000 Btuh, each open­ing will be 100 square inches. A grilled opening 10" x 10" has 100 square inches of area. If fly screen must be used over openings, double the area and inspect and clean the screen frequently.
Openings must NEVER be reduced or closed. If doors or win­dows are used for air supply, they must be locked open. Protect against closure of openings by snow and debris. Inspect frequently.
NO MECHANICAL DRAFT EXHAUST OR SUPPLY FANS ARE TO BE USED IN OR NEAR THE BOILER AREA.
The flow of combustion and ventilating air to the boiler must NOT be obstructed.
DRAFT HOOD—
The draft hood supplied is part of the listed boiler assembly. DO NOT alter the hood. See dimensions, page 2.
SPECIAL FLUSHING INSTRUCTIONS
Installation of new boiler may break loose a heavy accumulation of sediment and scale from old piping and radiators. It is extremely important to blow down your McDonnell Cut-off 67 more frequently the first week. First week — 3 times Thereafter — at least once a week * Exception: McDonnell Cut-off 42A must be blown down daily. See "CARE AND MAINTENANCE" for instructions.
Steam Control Assembly
6 GALAXY STEAM BOILER
PIPING A LOW PRESSURE STEAM BOILER
Boilers must be piped with good engineering practice and must conform to the requirements of ANSI/ASME Boiler and Pressure Vessel Code section IV and to the authority having jurisdiction.
NOTES:
1. Slant/Fin makes no recommendation, nor does Slant/Fin imply that One Pipe Parallel and Counterflow Gravity Condensate Return systems shown on page 7 are the pre­ferred systems. These systems are merely two examples of many possible systems. Determination of the proper system is based upon the application and is therefore beyond the scope of this instruction.
2. The 18" minimum height shown in figures 1-3, is the mini­mum height between the top of the jacket of the boiler and the 2-1/2" x 12" header centerline in the supply piping from the boiler. It must NOT be confused with the minimum height between the water level and the lowest return bend of the steam supply main. This height is "H" as shown in fig­ures 2 and 3. The minimum height of "H" must be at least equal to the sum of the pressure drop of the system plus three times the friction loss of the wet return, but not less than 18" for a sys­tem with a 1/8" psi steam pressure drop and not less than 28" for a system with a 1/2" psi steam pressure drop.
3. Modern steam boilers are smaller in water content than the boilers that they replace, therefore a mechanical return sys­tem (pump, receiver, etc.) must be employed if conditions exist such that uniform condensate return flow to the boiler cannot be maintained. Pocketing of condensate and the inability to maintain the correct minimum height between the steam supply main and the water level in the boiler are but a few of the many condi­tions that indicate the use of a mechanical return system. Any use of a receiver and pump must be coordinated with the makeup water and controlled by the boiler water level control on the boiler. This description is typical of a boiler feed pump as opposed to a condensate pump that pumps condensate regardless of the water level in the boiler.
4. In any steam system one of the requirements is the removal of air from the system. A mechanical return system in most cases has an air vent on the receiver. A gravity return sys­tem has no receiver, so provisions for air removal must be made on the piping itself. A one pipe system has the air vents on the radiation, the heat exchanger and near the end of the steam supply main (see figures 2 and 3). Main air vents should be located fifteen inches from the drip and if possible eight inches above the pipe so that water hammer does not damage the vent and render the vent inoperable. For more information on air vents, check with any manufac­turer of steam accessories (steam traps, boiler feed pumps, air vents, etc.).
Attach the hood to the boiler flue outlet. Connect flue pipe full size of hood outlet. If a vent damper is added, it must be installed on the outlet side of the hood. See Vent Piping, on page 4.
INSTALLATION INSTRUCTIONS FOR GXH OR GXHA LOW PRESSURE STEAM BOILERS EQUIPPED WITH TANKLESS OR PROVISION FOR TANKLESS AND McDONNELL & MILLER TYPE 67 LOW WATER CUT-OFF. STEAM CONTROLS ASSEMBLY AND INSTALLATION INSTRUCTIONS
Steam kit components for Galaxy packaged models are packed as follows: A. 1.Low water cut-off control
2. Fittings
3. L.W.C.O. instruction sheet
B. 1.Pressure gauge
2. High pressure limit control
3. Water level gauge
4. Fittings
5. Instruction sheet and assembly drawing
6. Steam safety valve and 3/4" street coupling
7. Drain cock
Assemble above components exactly as shown in steam con­trols assembly. Two 1/2" tappings are on right side of boiler for this assembly. Two holes are pre-punched in jackets. For con­venience, start assembling in the following steps:
1. Install 1/2" x 5-1/2" brass nipple onto tee of L.W.C.O.
2. Mount 1/2" x 5-1/2" brass nipple into lower boiler tapping by rotating low water cut-off.
3. Assemble 90° brass tubing to tee adapter and L.W.C.O.
4. Install 1/2" x 6" brass nipple and 1/2" x 5/8" adapter tee in upper boiler tapping.
5. Install syphon, high pressure limit and pressure gauge with 1/4" brass fittings.
6. Install water level gauge (without glass) and its fittings.
7. Install water level glass, and mark the glass 25-1/2" from the bottom of the steel boiler base for the water level. (The steel boiler base should not be confused with a combustible floor kit when making the 25-1/2" measurement.)
8. Drain cock will be installed in return tee at the lower right side of casting.
9. Safety valve and 3/4" street coupling should be installed in 3/4" tapping on top of boiler.
Loading...
+ 14 hidden pages