Slant/Fin B-200A, B-120A User Manual

Page 1
his manual must be left with owner and should be
T
ung on or adjacent to the boiler for reference.
BOBCAT
h
DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER HOT WATER MODELS B-120A and B-200A
GAS-FIRED BOILERS FOR NATURAL AND L.P. PROPANE GASES
INSTALLATION AND OPERATING INSTRUCTIONS
TABLE OF CONTENTS
Dimensions, Rating and Orifice Sizes ........................................2
Identification of Parts..................................................................3
Installation Requirements ...........................................................4
Contamination Prevention...........................................................5
Mounting the boiler on a wall......................................................6
Venting Application .....................................................................6
Boiler Room Air Supply and Ventilation......................................6
Non-Direct Vent Installation ........................................................6
Flue Gas Venting Requirements.................................................7
Additional Installation Requirements for Massachusetts............7
Vent and Air Intake Material .......................................................8
PVC/CPVC Pipe General Assembly Method..............................8
Vent and Air Intake Restrictions .................................................8
Sidewall Venting, Non-Direct Vent ............................................10
Vent Termination Location and Clearance ................................10
Non-Direct Vent Vertical Venting...............................................10
Direct Vent Installation ..............................................................10
Sidewall Venting, Direct Vent ....................................................10
Vent/Air Intake Termination Installation.....................................16
Direct Vent, Venting and Air Intake through a Roof ..................17
Venting and Air Intake Regular Inspection ...............................18
Condensate Removal System..................................................18
Gas Piping ................................................................................18
Electrical Wiring........................................................................19
Wiring Diagram.........................................................................20
Single and Multi Zoning............................................................22
Water Piping .............................................................................24
Operating Instructions...............................................................30
Boiler Control Display...............................................................30
Boiler Control Sequence of Operation
Gas Input Rate Adjustment ......................................................37
Safety Check ...........................................................................38
Care and Maintenance .............................................................41
General Troubleshooting Guide ................................................42
version to Propane.............................................................43
Con
............................................................................30
.............................................................36
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
INSTALLATION INSTRUCTIONS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition where required by the authority having juris­diction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
IMPORTANT
BEFORE READING THE
WARNING
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
NATURAL
WARNING
The venting system of this boiler is under positive pressure. Leakage from this system can be hazardous and if not avoided can result in death or serious injury. In addition to the recommen­dations within this manual and the User’ venting system, from the flue collector to the outdoor discharge, must be carefully checked annually by a qualified service agency.
Heating Contractor
Address
Phone Number
Printed in U.S.A. 808 Part No. 86-5756000 Publication No. BA-40
s Information Manual, the
This boiler installed, connected, serviced and repaired by a
ained, e
tr precautions required f licensed or otherwise qualified, in compliance with the authority having jurisdiction.
, gas piping and accessories must be
ienced service technician, f
xper
Boiler Model Number
Boiler Serial Number
Installation Date
WARNING
amiliar with all
or gas-fired equipment and
Page 2
FRONT
LEFT SIDE
RIGHT SIDE
7
41/2
D
C
21/4
4
1/4
B
A
1
4
13/4
E
4
GAS
SHUTOFF
VALVE
PRESSURE
RELIEF VALVE
2
Bobcat Models B-120A and B-200A
RATINGS AND DIMENSIONS
Figure 1. Dimensions data
Dimension B-120A B-200A
A 22 30 B 23 7/8 31 7/8 C 33 38 D 35 40 E 7 10
SPECIFICATIONS:
Fuel Rate Input:
Boiler Water Volume:
Water Piping
Connections:
Weight of Boiler
(uncrated):
Gas orifice siz
Gas Piping Connection:
Vent Connection:
B-120A Boiler B-200A Boiler
120,000 BTUH max
30,000 BTUH min
1.0 gallon (8.3 lbs) 1.4 gallon (11.07 lbs)
145 lbs. 200 lbs.
1” NPT (male)
Natural Gas - No or
e:
Propane - .2025” inside
diameter
**
1/2” NPT (female)
pipe (PVC
nominal I.D
3”
.
200,000 BTUH max
50,000 BTUH min
ifice used*
Propane - .2600” inside
diameter
**
, CPVC or stainless steel)
Bobcat Boiler
Air Intake Connection:
No or
*Note:
**See page 42 f
3” nominal I.D. pipe (PVC, CPVC or stainless steel)
ifice changes are required f
or conversion procedure to propane.
or high altitude installations
.
Page 3
Bobcat Models B-120A and B-200A
LOCATION AND IDENTIFICATION OF PARTS
3
Figure 2.
Location and identification of parts (model B-120A is shown)
Page 4
4
: 2" FOR ENCLOSED
*
1"
3"
6"
*
2"
2"
Bobcat Models B-120A and B-200A
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition.
This installation must also conform to the additional require-
ents in this Slant/Fin Instruction Book.
m
BOILER LOCATION
Provide a level, solid foundation or vertical wall for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct. (See paragraph heading “Vent Termination Location and Clear­ance” on page 9.) The location should also be such that all boiler components are protected from water (dripping, spray­ing, rain, etc.) during appliance operation and service (circu­lator replacement, control replacement, etc.).
WARNING LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED BOILER LOCATION
REQUIRES SPECIAL ATTENTION Liquefied Petroleum (L.P.) propane gas is Therefore, propane boilers, piping, valves should NOT be installed in locations where propane leaking from defective equipment and piping will "pool" in a basement or other space below the leak.
A spark or flame from the boiler or other source may ignite the accumulated propane gas causing an explosion or fire. Provide a level, solid foundation for the boiler. Location should be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
The UNIFORM MECHANICAL CODE may be in effect in your geographic area.
The following precautions are cited by the 1994 UNIFORM MECHANICAL CODE, section 304.6:
"LPG Appliances. Liquefied petroleum gas-burning appliances shall not be installed in a pit, basement or similar location where heavier-than-air-gas might collect. Appliances so fueled shall not be installed in an abo grade under-floor space or basement unless such loca­tion is pro
unbur Consult Chapter 5 of the 1994 UNIFORM MECHANICAL CODE f remov
BOILER FOUNDA
A. Provide a solid, level foundation or vertical wall capable of
suppor
xtending at least 2" past the jac
e
dimensions of boilers, page 2. See also figure 4a & 4b for
mounting the boiler on the wall.
Boiler can be installed on both comb
.
B
non-comb
above carpeting. C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or
the National Board of Fire Underwr
requirements.
vided with an approv
ned gas."
or design criter
al of unbur
ned gas
ting the w
le floors, but must NOT be installed on or
ustib
ia of the "approv
.
TION
eight of the boiler filled with w
ed means for remo
heavier than air.
val of
le and
or
ater
, and
ed" means f
ket on all sides. See
ustib
or specific
iters f
ve-
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTIONS
. Minimum clearances to the exterior surfaces of the boiler
A
shall be as follows:
INIMUM ALCOVE AND CLOSET CLEARANCE
M
or Combustible Recommended
F
Surf
ace Construction for Service
ront 6" 18"
F Rear 0" 0" Left Side 2" 8" Right Side 2" 8"
op 3" 18"
T Flue Connector:
Enclosed — 2" 6" Uninclosed — 1" 6"
B. Provide accessibility clearance of 8" on sides requiring
servicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clear­ances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
t points where hot water pipes emerge from a floor,
** A
the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2 inch. Each such opening shall be covered with a plate of uncombustible material.
Figure 3. Bobcat boiler min. clearances for combustible construction.
SAFETY
THE BOILER AREA CLEAR AND FREE FR
KEEP COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
wall or ceiling,
OM
Page 5
Bobcat Models B-120A and B-200A
CONTAMINATION PREVENTION
The combustion air supply must not be susceptible to contami­nation sources, whether the combustion air comes from the interior or exterior of the building. Contaminated air can cause
orrosion or other damage to the heat exchanger and compo-
c nents of the boiler, causing failure of these parts or unsafe operation.
Below is a list of products and areas which may cause contaminated combustion air:
PRODUCTS TO AVOID
• Spray cans containing chloro/fluorocarbons
• Permanent wave solutions
• Chlorinated waxes/cleaners
• Chlorine-based swimming pool chemicals
• Calcium chloride used for thawing
• Sodium chloride used for water softening
• Refrigerant leaks
• Paint or varnish removers
• Hydrochloric acid/muriatic acid
• Cements and glues
• Antistatic fabric softeners used in clothes dryers
• Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
• Adhesives used to fasten building products and other similar products
5
Figure 4a. Wall bracket securement
AREAS LIKELY TO HAVE CONTAMINANTS
• Dry cleaning/laundry areas and establishments
• Swimming pools
• Metal fabrication plants
• Beauty shops
• Refrigeration repair shops
• Photo processing plants
• Auto body shops
• Plastic manufacturing plants
• Furniture refinishing areas and establishments
• New building construction
• Remodeling areas
• Garages with workshops
Figure 4b. Mounting boiler on the wall
Page 6
6
MOUNTING THE BOILER ON A WALL
Be sure that the wall is vertically plumb and capable of carrying the weight of the boiler and the system piping, when full of water. See page 2 for the boiler weight.
e sure that there are studs available in the proper locations,
B for securing the boiler wall bracket and back panel. (See Figures 4a and 4b).
For wood stud walls, use lag screws or wood screws with a coarse thread and a minimum of 3” in length.
For metal stud walls, use toggle-style bolts that are specifically
esigned for such and maximum capacity exceeds the weight
d of the boiler and the system piping when full of water.
DO NOT use anchors driven into sheetrock to hold the boiler up on the wall. If mounting the boiler on a cement wall, use anchors that are specifically designed for such, and maximum capacity exceeds the weight of the boiler and the system piping, when full of water.
A. INSTALL THE WALL BRACKET. SEE FIGURE 4a.
1. Remove the wall bracket from the boiler jacket rear panel, by unfastening the single screw that holds it in place, for shipping purposes only.
2. Select the location on the wall where the boiler will be mounted. The upward facing tabs of the wall bracket will align with the top surface of the boiler jacket, and 3 feet of open wall space will be needed to accommodate the boiler jacket rear panel below this.
Bobcat Models B-120A and B-200A
. Lift the boiler up against the wall, with the top edge of the
4
acket slightly above the wall bracket tabs. There are 2
j holes in the upper corners of the jacket rear panel, that can visually be aligned with the 2 larger diameter holes in the wall bracket, to ensure that the wall bracket tabs line up and engage with the boiler jacket near top lip notches properly.
. There are 2 fastener holes in the lower area of the boiler
5
ear panel, just below the flue collector, for insuring the
r
oiler does not move off the wall bracket. Mark these 2
b holes, with the boiler in place, then lift the boiler off the wall bracket.
6. Determine which fastener type will best engage with the wall construction at the location of the 2 market holes. Drill out the appropriate diameter and depth holes for the fasteners, where marked.
7. Lift the boiler up onto the wall bracket again, as described in Step 4. Secure the boiler to the wall, with the 2 fasteners in the lower rear panel area.
8. If able to, the 1/2” diameter lifting pipe should be removed from the boiler rear panel.
9. The 4 boiler legs may be removed at this time, if desired. 2 screws hold each leg in place, from inside the jacket panel.
10. The boiler side panels can be replaced at this time, but the front panel should be left off, for the startup procedure later in the installation.
3. For sheetrock and stud construction, locate the studs and determine which set of holes in the wall bracket best align with the center of the studs. For cement walls, determine a location for the wall bracket to mount where the anchors will be secure, devoid of seams or cracks.
4. Place the bracket in the selected location, with the 2 tabs positioned up and facing outward, level it out, and mark the holes to be used. A minimum of 4 of these holes must be utilized, regardless of w
5. Drill the appropriate diameter and depth holes for the fasteners used in the wall, where marked.
6. Fasten the wall bracket to the wall, being sure that the tabs face upward and outward, and the fasteners have engaged the w
B. INSTALL THE BOILER ON THE WALL. SEE FIGURE 4b.
1. Remove the boiler jacket front cover, by turning the 2 black screws 1/4 turn to the open position, then lifting off.
2. Remove both the boiler jacket side panels, by removing the 2 sheetmetal screws in the top and bottom front edge, then lift off.
3. To aid in lifting the boiler, a 3 foot long, 1/2” inside diameter steel pipe can be slid through the holes in the sides of the boiler rear panel. Let the pipe extend out each side of the jacket evenly, for hand-holds, and pick up the boiler without letting it tilt, for safety.
all proper
all material.
ly.
VENTING APPLICATION
The Bobcat B-120 and B-200 are sealed combustion type boilers, they may be installed and vented either as a direct vent boiler which all air for combustion is obtained directly from out­side or as a non-direct vent boiler which air for combustion is taken from inside the boiler room.
The Bobcat B-120 and B-200 boilers must be vented by 3" diameter PVC/CPVC schedule 40 pipe, or the proper 3” diame­ter stainless steel venting system (see “vent material” on page
7) through the roof or sidewall.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required for combustion and ventila­tion. When buildings are insulated, caulked and weather­stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an outside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Ventila­tion, of the National Fuel Gas Code, ANSI Z223.1-latest edi tion, or applicable provisions of the local building codes. The following recommendation applies to buildings of energy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES
O UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR
TW INTO THE BOILER ROOM:
-
Page 7
Bobcat Models B-120A and B-200A
7
A. NON-DIRECT VENT INSTALLATION
1. Air drawn horizontally from outdoors DIRECTLY through n outside wall;
a
ne louvered opening near the floor and
o one louvered opening near the ceiling, each opening with a minimum FREE air passage area of
1 square inch per 4000
Btuh of total appliances’ input.
2.
Air drawn horizontally through HORIZONTAL DUCTS;
ne opening near the floor and one opening near the ceiling,
o each opening with a minimum FREE air passage area of
1
square inch per 2000 Btuh of total appliances’ input. Air drawn VERTICALLY from outdoors; one opening at the
3. floor and one opening at the ceiling, each opening with a
inimum FREE air passage area of
m
square inchper 4000
1
Btuh of total appliances’ input.
4.
Air drawn from inside the building; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of
1 square inch per 1000
Btuh of total appliances’ input.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
B. DIRECT VENT INSTALLATION
Adequate air supply should be provided to prevent overheating of the boiler controls and boiler room. Openings for passage of air into the boiler room for direct-vent installation must be at least
1
2 of the openings required for the non-direct vent as mentioned above.
If additional non-direct vent appliances are installed in the same space and adequate air openings are provided for them, there are no additional air openings required for the Bobcat B-120 and B-200 boilers.
For both direct and non-direct installation, the following must be considered:
- Openings must never be reduced or closed. If doors or
windows are used for air supply, they must be locked open.
- Protect against closure of openings by snow and debris.
Inspect frequently. No mechanical draft exhaust or supply fans are to be
-
used in or near the boiler area.
- Boiler area must never be under negative pressure.The
w of combustion and v
flo
entilating air to the boiler m
ust
not be obstructed.
FLUE GAS VENTING REQUIREMENTS
The Bobcat B-120 and B-200 series boilers are high efficiency, mechanically f
enting arrangements than natural draft, lower efficiency boilers.
v
THE FOLLO READ AND FOLLO
orced draft boilers and, theref
WING INSTR
UCTIONS MUST BE CAREFULL
WED IN ORDER T
ore, require different
VOID ANY HAZ-
O A
Y
ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION OF THE AIR INTAKE AND FLUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these
uctions and with ANSI Z223.1-latest edition NA
instr
TIONAL FUEL GAS CODE, Part 7, Venting of Equipment. Other local codes may also apply and must be followed. Where there is a conflict betw shall apply boiler ser
.
ies.
een these requirements
The use of a v
ent damper is NOT permitted on this
, the more str
ingent case
ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
When the Bobcat is installed and used in the Commonwealth of Massa­chusetts, the following additional requirements pursuant to Massachusetts code 248 CMR MUST be met:
(1). Exisiting chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manual reset device that will automatically shut off gas to the burner in the event of a sustained back-draft.
(2)(a). For all side wall horizontally vented gas fueld equipment installed in every dwelling, building or structure used in whole or part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finsihed grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each addi­tional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic, the hard wired carbon monoxide
k up may be installed on the next adja-
detector with alarm and batter cent floor le
b. In th event that the requirements of this subdivision can not be met at the time of completion of installation, the o ty (30) days to comply with the above requirements; provided, however, that dur detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the hori-
ontally v
z read, in print size no less that one-half (1/2) inch in size,
DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector obser signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. Required TO Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equip­ment installed in a room or str ing or structure used in whole or part for residential purposes.
vel.
ing said thir
SIGNA
ented gas fueled heating appliance or equipment. The sign shall
The equipment listed in Chapter 10 entitled
ty (30) day period, a battery operated carbon monoxide
A metal or plastic identification plate shall be per
GE.
y bac
es carbon mono
v
ucture separ
wner shall have a period of thir-
manently
“GAS VENT
xide detectors and
“Equipment Not
ate from the dw
elling, build-
Page 8
8
Bobcat Models B-120A and B-200A
ENT AND AIR INTAKE MATERIALS
V
The vent and air intake system for direct or non-direct vent installation must be 3” diameter PVC/CPVC schedule. 40 pipe, or UL listed single wall 3” diameter AL29-4C* stainless steel
aterial. The following manufacturers’ systems are approved
m for use within a specified minimum and maximum equivalent vent length in this manual.
Manufacturer
Heat-Fab. Inc. Saf-T Vent Not Required
ProTech System, FasNSeal Not Required Inc.
Flex-L StaR-34 GE-IS806 International, Inc.
Z-Flex, Inc. Z-Vent GE, RTV 106
N/A PVC pipe, PVC primer
N/A CPVC pipe, CPVC primer
*AL29-4C is a registered Trademark of Allegheny Ludlum Corp
Type/System
EZ Seal
Schedule 40 and cement
Schedule 40 and cement
Sealant
When joining the various components of the listed stainless steel vent systems, the manufacturers’ instructions should be closely followed to insure proper sealing. Use sealant specified by vent system manufacturer for sealing of pipe and fittings, if required. When joining the PVC/CPVC pipe and fittings, follow the instructions provided in this manual. All connections must be liquid and pressure tight. DO NOT use galvanized flue pipe or any plastic-type materials other than PVC/CPVC Schedule
40.
The integral adapters on the boiler are designed to accommo­date either PVC/CPVC Schedule 40 pipe or the listed stainless steel vent systems.These adapters have built-in sealing rings, so no additional sealant is required. Make sure the pipes are round and burr-free, and push down into the appropriate step of the adapter, until sn
ug. (See Figure 5).
PVC/CPVC PIPE GENERAL ASSEMBLY METHOD
The following are the recommended methods for cutting, cleaning and connecting PVC and CPVC pipe, for both the vent and air intake piping system:
1. When laying out the piping system, work from the boiler vent and air intake adapter to the point of outside
ermination.
t
2. Cut the PVC/CPVC pipe to the required lengths, and pre-assemble the entire system, before sealing. Disassembly after sealing, to make any corrections, will not
e possible.
b
3. Once the pre-assembled PVC/CPVC pipe vent and air intake system is verified to be of the proper length pipe and fitting orientation, begin disassembling and preparing the pipes and fittings for the sealing process.This can be done section by section, or the complete vent and air intake system can be disassembled. It is recommended to mark the various parts, before complete disassembly, to eliminate the possibility of errors during re-assembly.
4. De-burr the inside and outside of every PVC/CPVC pipe, to ensure that they engage fully into the fittings, and flow is not compromised. A small chamfer on the outside of each pipe can particularly aid in the final assembly process.
5. Wipe or knock out any debris from inside the PVC or CPVC pipe, which may have accumulated there from the cutting process or storage. Debris can cause operational problems with the boiler combustion components.
6. Thoroughly clean the outside ends of each pipe, and the inside of each fitting. The surfaces must be dry for the sealing agents to work properly. Handle the prepared pipe lengths away from the cleaned ends, and handle the cleaned fittings, from the outside, to avoid contamination.
7. Re-assembly of the PVC or CPVC pipe should be done in sections, to avoid the primer and cement drying before the parts are engaged.
8. For each joint, first apply a coat of primer to the outside sealing surface of the pipe and the inside sealing surface of each fitting. Use only the primer type that is specified for either the PVC or CPVC pipe that is bing utilized.
9. Before the primer dries, apply a coat of cement over it. A second coat of cement can be applied, if necessary, but must be done quickly and in a manner that avoids unnecessar
uild-up that w
y b
ould cause obstr the system. Use only the cement type that is specified f either the PVC or CPVC pipe that is being utiliz
uction inside
or
ed.
10. Before the cement dries, insert the pipe into the fitting. A slight twisting motion while pushing the pipe into the fitting will aid in distrib par
ts fully engage.
uting the cement evenly and ensuring the
11. Quickly wipe the excess cement from the outside areas of the joint.
Discard an
ags used to a
y r
void later getting the
cement on hands, clothes and equipment.
Figure 5. Adapter
Vent and Air Intake Pipe installation into Boiler
.
VENT AND AIR INTAKE RESTRICTIONS
1. Maximum allowed equivalent vent and air intake length for
all of the approved vent and air intake materials is 100 feet for B-120 and 50 feet for B-200.
2. Equivalent of vent or air intake length is sum of the
straight pipe lengths and equivalent length of elbows as
wn in the tab
sho
le on this page.
Page 9
Bobcat Models B-120A and B-200A
Figure 6.
3. The vent termination is in addition to the allowed equivalent lengths.
4. Minimum vent length is 2 feet of straight pipe, plus the one 90˚ elbow that is required.
5. Vent length restriction is for both direct and non-direct vent installations.
9
. The B-120 and B-200 boilers are equipped with a built-in
6
ondensation drain and trap.The trap must be filled with
c water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain must dispose of possibly large quantities of condensate, which may require a neutralizing system. Refer to the “Condensate Drainage” section of this manual. No additional condensation drain and trap is required on the vent piping system itself.
. The horizontal vent pipe must be sloped upward from the
7
boiler at a pitch of at least 1/4” per 1 foot of run, so that the condensate from the vent system runs to the boiler vent adapter pipe, then out the built-in condensation drain and trap.
8. The horizontal vent and air intake pipes must be supported with pipe straps, at intervals no greater than 5 feet, when PVC/CPVC pipe is utilized. This support spacing applies also to stainless steel vent pipe, unless the manufacturer’s instructions permit otherwise. The vertical vent and air intake pipes also must be supported, wherever the building construction provides allowance for it, such as ceiling or roof passage openings where a firestop and support or braces can be affixed.
9. Minimum clearances of vent pipes from combustible constructions must be maintained (see Page 4). No clearance is required between the vent and air intake pipes of this boiler.
EXAMPLE: Boiler model B-120 is to be installed. The combustion air is provided by air intake piping directly to the boiler (direct-vent installation). The vent piping will be PVC and installation location will require the use of 4 elbows for the vent to run the termination. The air intake piping will also be PVC, and also will require the use of 4 elbows.
In this case, the maximum straight pipe vent length that can be utilized with the 4 elbows would be: 100’ - (4’ x 5’) = 80’. Since the air intake pipe also is PVC and requires the use of 4 elbows, the maximum straight pipe air intake length that can be utilized is also 80 feet.
If the air for combustion were taken from the boiler room (non-direct vent installation), still the maximum straight vent length would be 80 feet.
Equivalent Length of Various 90-Degree Elbows
Manufacturer
, Inc. Saf-T Standard 3
ab
Heat-F
Heat-Fab, Inc. Saf-T, tight radius elbow 6
ech System, Inc.
ProT Flex-L International, Inc. StaR-34 6
Z-Flex, Inc. Z-Vent 6 N/A PVC, Schedule 40 5
N/A
ype/System
T
elbow
asNseal
F
, Schedule 40
CPVC
Equivalent
Length (Feet)
6
5
10. Common venting with other appliances or another Bobcat boiler is not allowed.
11. DO NOT install a vent damper or similar devices in vent system or on the boiler.
12. DO NOT insulate venting system.
Page 10
10
Bobcat Models B-120A and B-200A
VENTING INSTALLATION
Only PVC/CPVC and approved stainless steel materials listed on page 8 may be used for the venting system installation. If stainless steel vent systems are used, follow the manufactur-
r’s instructions, in conjunction with these instructions.
e
I. Non-Direct Vent Installation
The air for combustion is taken from the ambient air surrounding the boiler; therefore, ample supply of air is required for combustion and ventilation (see page 7.)
DO NOT use this installation method if the surrounding of the boiler is contaminated. See page 5 for the list of harmful contaminants and their sources, to avoid.
A. SIDEWALL VENTING - NON-DIRECT VENT
Figures 7 and 8 show typical horizontal sidewall venting. For combustible wall passage of vent piping, a UL listed thimble or flashing and sealing boot must be used, providing the wall thickness from 3" minimum up to 12" maximum. The vent piping must terminate with a screened tee or elbow termination facing down.
CAUTION: Flue gasses exiting from the vent terminal will condense. Building materials in the area of the vent terminal should be protected from discoloration and degradation.
VENT TERMINATION LOCATION AND CLEARANCES
1. The venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.
2. The venting system shall terminate at least 12 inches below or 12 inches horizontally from any door, window or gravity air inlet into any building.The bottom of the vent terminal or air intake terminal shall be at least 12 inches above grade or the normal snow level whichever is greater.
3. Through the wall vents shall not terminate over public walkways or over areas where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equip­ment. Minimum clearance of 4 feet horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
B. NON-DIRECT VENT - VERTICAL VENTING
Figure 9 shows typical venting through the roof.The vent pipe must pass through the ceiling, floor and the roof vertically
hrough a 6" minimum diameter cutout. A fire stop is required
t
or each ceiling and floor penetration. For roof passage, an
f appropriate UL listed roof flashing must be used.
An existing chimney (see Figure 10) may be used as a chase for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe within the chimney.
The vertical vent piping must terminate with a screened tee,
ombination of 45˚ elbow and a 90˚ screened elbow termina-
c tion or a rain cap termination.
II. Direct Vent Installation
Air intake piping from outside to the boiler air intake adapter provides the air for combustion.The boiler surrounding may be contaminated (See page 5). Piping the air intake to the outside can prevent contaminants from the boiler surrounding from entering the combustion air supply.
A. SIDEWALL DIRECT VENTING
Figures 11 and 12 show typical sidewall direct venting, using a Slant/Fin vent/air intake termination. There are 2 different mod­els of vent/air intake termination available. One is designed specifically for PVC/CPVC venting, and the other is designed specifically for stainless steel venting systems. Only these 2 models of vent/air intake termination are approved for this method of installation. Refer to the Slant/Fin Bobcat B-120 and B-200 boilers Parts List (publication number B-10PL) for the appropriate model for the vent material to be used.
CAUTION: Flue gasses existing from the vent terminal will con­dense. Building materials in the area of the terminal should be protected from discoloration and degradation, in addition to the requirements of the vent termination location and clearances stated in this manual.
4. Vent termination must not be located in any confined space (i.e. any overhang or deck.Vent termination should not allow flue gas discharge towards neighbor’s windows or where personal injury or property damages can occur.
window w
ells
es, narrow alleys) or under
v
, alco
Page 11
Bobcat Models B-120A and B-200A
9 IN. MAX.
6
IN. MIN.
A
IR INTAKE
(DO NOT BL0CK)
O
UTSIDE WALL
SLOPE UP 1/4 IN. PER FOOT MIN. F
ROM BOILER TO
V
ENT TERMINATION
12" MIN
SNOW LINE
(
SEE DEFINITION)
T
ERMINATION 90˚ ELBOW
WITH SCREEN
90˚ ELBOW
S/FP/N 440695 (ADJUSTABLE
3 IN. DIA. PVC/CVPC P
IPE FOR
V
ENT
A U/L LISTED FLASHING AND SEALING BOOT MUST B
E USED ON COMBUSTIBLE
WALLS.
9 IN. MAX.
6 IN. MIN.
AIR INTAKE (DO NOT BL0CK)
OUTSIDE WALL
SLOPE UP 1/4 IN. PER FOOT MIN. FROM BOILER TO VENT TERMINATI ON
12" MIN
SNOW LINE
(SEE DEFINITION)
OUTSIDE VENT TERMINATION 90˚ ELBOW WITH SCREEN
STAN DARD 90˚ ELBOW
S/FP/N 440695 (ADJUSTABLE
3 INCH. DIA. STAINLESS STEEL VENTING MATE RIAL FOR VENT
A U/L LISTED WALL THIMBLE MUST BE USED ON COMBUSTIBLE WALLS. S/F P/N 440695 (ADJUSTABLE 5 IN.TO 8 IN.) MAY BE USED. ABOVE THIMBLE MUST BE USED WITH HEAT-FAB SLIP JOINT CONNECTOR
BOBCAT MODELS B-120 and B-200 NON-DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 7).
11
Figure 7. Non-direct vent, side wall venting - utilizing PVC/CPVC pipe for venting.
Figure 8.
** Definition of Sno
Non-direct vent, side wall venting - utilizing stainless steel vent materials for venting.
wledge of local conditions will re
Kno
w Line:
The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED
*
TRADEMARK OF ALLEGHENY LUDLUM CORP
eal the maxim
v
.
um height that repeated sno
alls accumulate to.
wf
Page 12
12
1 FT MIN.
SLOPE UP 1/4 IN.
PER FOOT MIN.
2" MIN
3 IN. DIA. PVC/CPVC PIPE OR STAINLESS STEEL
VENTING MATERIAL FOR VENT
1
0 FT. MIN
RAIN CAP TERMINATION MAY BE USED
AIR INTAKE
(DO NOT BLOCK)
3 IN. DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERIAL FOR VENT
90˚ ELBOW
FIRESTOP AND SUPPORT
F
LASHING AND
STORM COLLAR
VENT TERMINATI ON TEE WITH SCREEN
90˚ TERMINATION ELBOW WITH SCREEN
FIRESTOP AND
SUPPORT
ALTERNATE VERTICAL TERMINATION
45˚ ELBOW
*
*
Bobcat Models B-120A and B-200A
BOBCAT MODELS B-120 and B-200 NON-DIRECT VENT, VENTING THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 7).
Figure 9. Bobcat models B-120 and B-200 - non-direct vent, venting through the roof
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP
*
.
Page 13
Bobcat Models B-120A and B-200A
SEAL CHIMNEY OPENING WITH MORTAR OR COVER PLATE
1 FT MIN.
SLOPE UP 1/4 IN.
PER FOOT MIN.
AIR INTAKE
(DO NOT BLO CK)
3 INCH DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERIAL FOR VENT
10FT.MIN.
CHIMNEY TOP PLATE
RAIN CAP TERMINATION MAY BE USED
VENT TERMINATI ON TEE WITH SCREEN
90˚ TERMINATION ELBOW WITH SCREEN
ALTERNATE VERTICAL TERMINATION
45˚ ELBOW
3 INCH DIA. PVC/CPVC PIPE OR STAINLESS STEEL VENTING MATERIAL FOR VENT
90˚ ELBOW
*
*
BOBCAT MODELS B-120 and B-200 NON - DIRECT VENT, UTILIZING AN EXISTING
CHIMNEY AS A CHASE
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 7).
13
Figure 10. Bobcat models B-120 and B-200 - non-direct vent, utilizing an existing chimney as a chase.
AL 29-4C IS A REGISTERED
*
TRADEMARK OF ALLEGHENY LUDLUM CORP
.
Page 14
14
SLOPE UP 1/4" PER FOOT MIN. FROM BOILER TO VENT TERMINATION
90˚ ELBOW
3" DIA. PVC/CPVC PIPE FOR AIR INTAKE
SNOW
LIN
E**
(SEE
DEF
INIT
ION
)
AIR
INT
AKE
LOU
VER
S
12"MIN
O
UTSIDE
W
ALL
3
"
D
IA. PVC/CPVC
C
OUPLING WITH SCREEN
SLANT/FIN VENT/AIR INTAKE TERMINATION UNIT PART # 860802
3"
– 16
" THICK WALL
3"
DIA. PVC/CPVC PIPE FOR VENT
SLOPE UP 1/4” PER FOOT MIN. FROM BOILER TO VENT TERMINATION
90˚ ELBOW
3" DIA. STAINLESS STEEL VENTING MATERIAL FOR VENT
3" DIA. PVC/CPVC PIPE FOR AIR INTAK E
AIR
IN
TAK
E
LOU
VER
S
SNO
W L
INE
**
(SEE
DE
FIN
ITIO
N)
12"MIN
OUTSIDE WALL
STRAIGHT SCREENED VENT TERMINATI ON
SLANT/FIN VENT/AIR INTAKE TERMINATION UNIT PART # 451138
3-12" THICK WALL
3
"
DIA. HEAT-FAB SLIP JOINT CONNECTOR
Bobcat Models B-120A and B-200A
BOBCAT MODELS B-120 and B-200 - DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 7).
Figure 11. Direct vent, sidewall venting illustration; utilizing PVC/CPVC pipe for venting
wall venting illustration;
w Line:
side
wledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.
Kno
Figure 12.
Direct vent,
** Definition of Sno The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED
*
TRADEMARK OF ALLEGHENY LUDLUM CORP
utilizing stainless steel vent materials f
.
or venting.
Page 15
Bobcat Models B-120A and B-200A
WALL (
3"-18" THICK)
S
CREW
3" DIA.
P
VC/CPVC
PIPE FOR
A
IR INTAKE
S
TOP FOR AIR/VENT OUTSIDE TERMINAL
3" DIA. PVC/CPVC P
IPE FOR
VENT
F
LUE
GASES
W
ALL
(3"-12" THICK)
OUTSIDE TERMINATION PLATE
COMBUSTION AIR
SEAL H
ERE
O
UTSIDE
T
ERMINATION
PLATE
I
NSIDE
T
ERMINATION
P
LATE
I
NSIDE
T
ERMINATION
PLATE
3
" DIA. PVC/CPVC COUPLING W
ITH SCREEN
L
OUVERS
3" DIA. P
VC/CPVC PIPE FOR A
IR INTAKE
3" DIA. PVC/CPVC P
IPE FOR VENT
SCREW
3
" DIA. PVC/CPVC C
OUPLING WITH SCREEN
WALL (3"-12" THICK)
SCREW
3" DIA. PVC/CPVC PIPE FOR AIR INTAKE
STOP FOR AIR/VENT OUTSIDE TERMINAL
4" GALV. PIPE (WALL THIMBLE FOR COMBUSTIBLE WALLS ONLY)
3" DIA. AL29-4C S.S.VENT PIPE (SLIP JOINT CONNECTOR)
FLUE GASES
WALL (3"-12" THICK)
OUTSIDE TERMINATION PLATE
COMBUSTION AIR
SEAL HERE
DO NOT SEAL HERE
OUTSIDE TERMINATION PLATE
INSIDE T
ERMINATION
PLATE
INSIDE TERMINATION PLATE
STRAIGHT SCREENED TERMINATION
STRAIGHT SCREENED TERMINATION
LOUVERS
4" GALV. PIPE (WALL THIMBLE)
3" DIA. PVC/CPVC P
IPE FOR
AIR INTAKE
3" DIA. AL29-4C S.S.VENT PIPE (SLIP JOINT CONNECTOR)
SCREW
15
Figure 13a. Vent/Air intake termination; utilizing PVC/CPVC pipe for venting.
Figure 13b. Vent/Air intake termination; utilizing stainless steel venting materials.
Page 16
16
Bobcat Models B-120A and B-200A
ENT/AIR INTAKE TERMINATION FOR PVC/CPVC
V
ENTING INSTALLATION
V
This termination is designed specifically for 3” diameter PVC or CPVC Schedule 40 pipe to be used as the vent and air intake piping material, only. It can be used on a combustible wall, provided the 1” minimum clearance of the vent pipe to any combustible surface is maintained.
. Termination must be installed horizontally.
1
. Refer to Figure 13a for installation details.
2
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and clearances” explained on page 9.
5. Cut a rectangular opening with the following dimensions in the wall. Height: 5 Width: 12
1
4
3
4
6. From outside of the wall, install outside termination plate using 4 screws. Make sure the louvers are at left side. Seal the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the out side termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #9.
8. From inside, install the inside termination plate, using 4 screws. Make sure that the holes for the vent and air intake pipe visually line up with the vent passage hole and air intake collar on the outside termination plate.
9. Cut the PVC or CPVC air intake pipe to the proper dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #7.
Cut the PVC or CPVC vent pipe so that it will extend out
10. past the outer surface of the outside termination plate by 2”.
11. Cement a 3” diameter PVC or CPVC coupling onto the PVC or CPVC vent pipe, and install a stainless steel screen into the coupling.
ENT/AIR INTAKE TERMINATION FOR STAINLESS STEEL
V
ENTING INSTALLATION
V
This termination is designed specifically for Heat-Fab Saf-T vent 3” diameter stainless steel venting system to be used as the vent, and 3” diameter PVC or CPVC schedule 40 pipe to be used as the air intake piping material, only. It can be used on a combustible wall, provided a length of 4” diameter galva­nized pipe is installed as a thimble around the vent pipe, for the
all passage.
w
. Termination must be installed horizontally.
1
2. Refer to Figure 13b for installation details.
3. Wall thickness should be 3” to 12” thick.
4. Follow instruction for “vent termination location and clearances” explained on this page.
5. Cut a rectangular opening with the following dimensions in the wall. Height: 5 Width: 12
1
4
3
4
6. From outside of the wall, install outside termination plate using 4 scre
ws. Make sure the louvers are at left side. Seal
the plate perimeter with silicon.
7. Apply a bead of silicon around the outer surface of the outside termination plate air intake collar, about 1/2” from the edge. This will seal the air intake pipe to the air intake collar, in step #11.
8. For combustible wall a 4” galvanized pipe must be used as a wall thimble.The length of the 4” galvanized pipe should be approximately 1” shorter than the wall thickness.
9. From inside the building, fit galvanized pipe over 4” collar of the outside plate.
10. From inside, install inside termination plate using 4 screws. Make sure the 4” collar on the plate, penetrated into the
anized pipe.
galv
Cut the PVC or CPVC air intak
11.
e pipe to the proper dimension to fit onto the air intake collar of the terminal. Slide the air intake pipe through the inside termination plate and onto the air intake collar, where the sealant was pre-applied in Step #7.
12. From outside the wall, insert the bare end of the PVC or CPVC vent pipe through the outside and inside terminal plates, until the coupling is flush with the outside wall plate.
13. From inside, proceed with the air intake and vent pipe installation. Follow the proper PVC/CPVC assembly
actices specified on page 8, and v
pr
enting system
restrictions specified on page 8 of this manual.
12. Assemble and seal straight screened termination to the slip joint connector.
rom outside of the building, insert vent pipe (slip joint
F
13. connector and termination assembly) through the 3” holes of the outside and inside termination plate.
14. From inside, proceed with air intake and vent pipe installation. Follow vent manufacturer’s instructions and restrictions specified on page 8 of this manual.
Page 17
Bobcat Models B-120A and B-200A
SNO
W L
INE
1 FT.MIN.
1 FT.MIN.
STRAIGHT TERMINATI ON WITH SCREEN
10 FT. MIN
FIRESTOP AND SUPPORT
2" MIN.
SLOPE UP 1/4 IN. PER FOOT MIN.
3
"
DIA. PVC/CPVC OR STAINLESS STEEL VENTING MATERIAL FOR VENT
3
"
DIA. PVC/CPVC OR STAINLESS STEEL PIPE FOR AIR INTAKE
FIRESTOP AND SUPPORT
PIPE SUPPORT
FLASHING AND STORM COLLAR
AIR INTAKE 180˚ ELBOW WITH SCREEN
or PVC/CPVC pipe, follow the proper assembly practices
B. DIRECT VENT - VENTING AND AIR INTAKE
THROUGH A ROOF
F
pecified on page 8, and venting system restrictions specified
s on page 8 of this manual. For stainless steel venting systems,
igure 14 shows typical vertical venting. The vent pipe must
F
ass through the ceiling, floor and the roof vertically through a
p
follow the vent manufacturer’s instructions and the restrictions
specified on page 8 of this manual 6” minimum diameter cutout. A fire stop is required for each ceiling and floor penetration. For roof passage an appropriate UL listed roof flashing must be used.
The vertical vent piping must terminate with a screened straight termination. The air intake termination should be a screened 180˚ elbow facing down.The air intake opening must
e at least 1 foot below the vent opening.
b
BOBCAT MODELS B-120 and B-200 - DIRECT VENT, VENTING AND AIR INTAKE
THROUGH A ROOF
All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AL29-4C S.S.*. venting materials (See page 7).
17
Figure 14. Direct vent, venting and air intake through a roof.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. The height should be used as the SNOW LINE.
AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP
*
.
Page 18
18
CONDENSATE TRAP, FILLED WITH WATER
DRAIN VACUUM BREAKER, LEAVE OPEN
PLASTIC TUBING
NEUTRALIZING UNIT (IF REQUIRED)
CONDENSATE PUMP (IF REQUIRED)
DRAIN INSIDE BUILDING
VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION
A. Inspect the system regularly for condensation, corrosion,
agging and/or physical damage. A qualified professional
s should service the boiler annually and include such an inspection at that time. The homeowner should look over the system monthly for damage, water stains, any signs of rust, other corrosions or separation of the vent and air intake piping (if direct-vent).
B. Should an inspection turn up signs of condensation, corrosion,
sagging or damage, the boiler should be shut down immediate­ly and the condition should be corrected by a qualified professional.
CONDENSATE REMOVAL SYSTEM
The Bobcat B-120 and B-200 boilers are equipped with a built-in condensation drain and trap.The trap must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. Periodic inspection should be made of this assembly for deterioration of the tubing and to insure that the trap is not plugged. If it is plugged or appears to have exces­sive sediment in it, it should be removed from the drain assembly, straightened out to clear the obstruction, reformed, filled with water and reinstalled as before.
A 3/4”
PVC tee, located on the right side of the boiler jacket, is provided to run the condensate liquid from the boiler. Connect the plastic tubing that will be run to the drain to the bottom take-off of the tee. Leave the top take-off of the tee open, to act as a vacuum breaker. If the building drain is above the bottom portion of the tee, a condensate removal pump will be required.This pump must have an overflow switch, and be compatible with the acidic con­densate liquid, as must all fittings and the tubing used in this con­densate removal system. (See Figure 15).
No part of the condensate removal system can be exposed to freezing temperatures, or any other conditions that could cause blockage. DO NOT run drain tubing to the outside of the building. In addition, certain jurisdictions or drain pipe materials may require a neutralization unit to be installed in the condensate removal sys­tem. Any piping other than plastic types will be subject to corrosion
ioration from the acidic condensate
or deter
vel as low as 3.0. A condensate filter containing lime, marble, or
le phosphate chips can neutralize the condensate to a pH level
, which may have a pH
Bobcat Models B-120A and B-200A
bove 6.5, which is safe for all drain piping materials. (See Figure
a
5). The neutralizing filter medium will require periodic changing,
1 to ensure it’s affectiveness. Replacing the medium on an annual basis is recommended, or refer to the manufacturer’s instructions for systems that are available for neutralizing condensate.
COMMONWEALTH OF MASSACHUSETTS SPECIAL REQUIREMENT
When the Bobcat B-120A and B-200A are installed and used in the Commonwealth of Massachusetts, a neutralization unit MUST be installed in the condensate removal system.
GAS PIPING
A. Local installation codes apply. The pipe joint compound used
on threads must be resistant to the action of liquefied petrole­um gases.
B. The gas supply line to the boiler should run directly from the
meter for natural gas or from the fuel tank for L.P. propane gas. A manual gas supply shut-off valve is provided on the boiler’s gas supply pipe. (See Figure 2, on page 3). Local codes may specify a manual main gas supply shut-off valve to be 5’ above the floor, and a disconnection union at the gas piping entrance to the boiler. In this case, unless the boiler is wall mounted at the right height, the gas supply shut-off valve must be relocated to the specified location. If the gas supply pipe must be upsized for flow considerations, then the same size main gas supply shut-off valve must be used.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas (Btu/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow in piping (cu. ft. per hour).
4. Use table below to select proper pipe size.
EXAMPLE: Boiler model B-120 is to be installed. Distance from gas meter to the boilers is 30ft. Heating value of natural gas is 1020 Btu/cu. Ft. Select proper pipe size.
Gas flow = 120,000 Btu/hour
1020 Btu/cu. ft.
= 118 cu. ft. per hour
Figure 15. Condensate disposal system
Page 19
Bobcat Models B-120A and B-200A
19
t 30 ft. length of pipe, match required capacity from table on
A
his page (choose higher capacity, in this case is 152 cu. ft. per
t hour). Required pipe size is
mproper gas pipe sizing will result in flame outages, insuffi-
I
3
4".
cient heat and other installation difficulties. For more informa­tion and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested
before replacing the boiler in operation. Use liquid soap solution for all gas leak testing. DO NOT use open flame. This boiler and it’s individual shutoff valve must be disconnected from the gas supply piping system during and pressure testing of that system at test pressures in excess
1
of
2 PSIG. This boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
1
2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap is integrally provided, as illustrated on page 3.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
Length of pipe in Feet
Gas Flow In piping -- cu. ft. per hr.
Iron Pipe Size (IPS) — inches
1/2
3
/4 11
1
/4
11/2
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
vity = 0.6.
At pressure drop of 0.3 in. w
, specific gr
ater
a
oiler must be electrically grounded in accordance with the
B
equirements of the authority having jurisdiction, or, in the
r absence of such requirements, with the National Electrical Code, ANSI/NFPA 70-latest edition.
Proper polarity is critical for the power supply connections. Reversed polarity will cause system lockout. Proper ground­ing is critical for boiler operation, connect the ground wire to the green ground screw next to the line voltage terminal
trip.
s
2. Circulator(s)
A set of terminals are provided for the boiler (primary loop) circulator. Only wire this circulator to these terminals, additional (secondary loop) circulators for space heating require the use of relays and a separate power source.
For multiple zoning, either zone valves or circulators maybe used.
For zone valve system (See Figure 17a).
For pump zoning system (See Figure 17b and 17c).
DO NOT use boiler transformer to power external accessories like zone valve and relays, overload and/or burned out transformer and boiler malfunction can result. Use separate transformer to power such components.
A second set of terminals are provided for the domestic hot water tank circulator (if used). The primary loop circulator is always de-energized when the DHW tank circulator is energized, for priority.
3. SPACE HEATING THERMOSTAT(S)
Install thermostat on an inside wall and away from any heat sources, sunshine and drafts. A set of terminals are provid­ed for connection of 24 volt style thermostats, relays or zone valve end switches (isolated contacts). (See wiring diagram Figure 16a).
Thermostat heat anticipator: For a non-zoned system set thermostat heat anticipator to 0.1 Amps, for zoned system set to match power requirements of zone valves or relays. Refer to man see instr
uctions with ther
ufacturer’
s instructions and specifications. Also
mostat.
ELECTRICAL WIRING
All field wiring to the boiler is connected to the 2 sets of
minal str
ter
ips, located under the jacket top panel.
(See Figure 2, on page 3)
DANGER: Before wiring always turn off electric power supply. Otherwise, shock or death can result.
1. Power Supply
A separately fused circuit is recommended. Use standard 15 Amp. fuse or breaker and 14 gage conductors in BX
le or conduit.
cab
Provide disconnect means and overload protection as
am (Figure 16a) boiler
required.
See boiler wir
ing diag
r
control (Figure16b) and ladder diagram (Figure 16c).
4. DOMESTIC HOT WATER TANK THERMOSTAT
A set of terminals are provided for connection of the DHW tank thermostat (if used). (See wiring diagram Figure 16a).
5. OUTDOOR AIR SENSOR
A set of terminals are provided for connection of an outdoor air sensor (if this method is used). (See wir
ing diagr
am
Figure 16a).
Mount on
The outdoor air sensor m
ust be a 12k ohm type
. an outside wall, shielded from direct sunlight or flow of heat or cooling form other sources. See instructions provided with sensor.
6. LOW WATER CUTOFF
or connection of a LWCO. If
A set of ter this de
minals are pro
vice is used, remove the factory installed jumper from
vided f
these terminals. (See wiring diagram Figure 16a).
Page 20
20
WIRE LEGEND:
1
M
CAUTION:
1
2
3
4
5
6
7
8
9
10
11 12
13 14 15
16
12
3
4
5
6
78
HN
H
N
HN
1
2
3
4
5
6
1
J5
J2
J6
J13
2
3
1
2
3
4
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.
PROPER OPERATION AFTER SERVICING".
WW
BL
R
BL
GY
DISPLAY
GY
W
G
BK
G
M
BK
G
W
G
ROUND
R
Y
PR
PK
B
R
GY
PR
BK
W
M
1
2
3
4
5
6
7
J9
BK
R
G
W
BL
1
W
W
W
BK
GY
GY
G
Y
G
Y
GY
FACTORY WIRED FIELD WIRED, FIELD SUPPLIED
PROVIDE DISCONNECT MEANS & OVERLOAD PR OTECTION AS REQUIRED.
IF ANY OF THE ORIGINAL WIRE AS SUPPLIEDWITH THE APPLIIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105˚C OR ITS EQUIVALENT.
24V ROOM
T
HERMOSTAT
WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. "VERIFY
FIELD WIRING
TERMINALS
120V/24V
TRANSFORMER
DHW
C
IRCULATO R
(
IF USED)
DHW TANK
THERMOSTAT
(IF USED)
2
PIN
C
ONNECTOR
G
AS VALVE
HONEYWELL
VK8115
3 PIN
CONNECTOR
W
ATER HIGH
LIMIT
(WHITE CONNECTOR)
SUPPLY WATER SENSOR
(RED CONNECTOR)
R
ETURN WATER SENSOR
(BLUE CONNECTOR)
FLUE GAS SENSOR
(CLEAR CONNECTOR)
POWER ON/OFF S
WITCH
BOILER
CIRCULATO R
L
2
NEUTRAL
L1
HOT
120V 60HZ
1
2 K ohm
OUTDOOR
S
ENSER
(IF USED)
LOW WATER
C
UT OFF
(IF USED,REMOVE
7
-8 JUMPER)
5 PIN
C
ONNECTOR
COMBUSTION
B
LOWER
Bobcat Models B-120A and B-200A
Figure 16a. Schematic wiring diagram.
Page 21
Bobcat Models B-120A and B-200A
ARGUS CONTROL PHC794-S1
J5
J2
J
6
J9
FUSE
GROUND
S
PARK
CABLE
SPARK IGNITOR
J13
J12
T2
GND
NEUTRAL
HOT
L2
L1
120V/60HZ
120V
10V
120V
24V
M
M
DISPLAY
M
CHASSIS
GND
DISCONNECT
SWITCH
SPARK
ELECRODE
DHW CIRCULATO R
(IF USED)
BOILER
CIRCULATO R
COMBUSTION
BLOWER
BOILER ON/OFF
SWITCH
GAS
VALVE
SUPPLY WATER
SENSOR
RETURN WATER
SENSOR
FLUE GAS
SENSOR
OUTDOOR SENSER
(IF USED)
MICRO PROCESSOR
ON CONTROL BOARD
120V SECTION OF
CONTROL BOARD
LOW WATER CUT OFF
(IF USED) OR JUMPER
DHW THERMOSTAT
(IF USED) OR SENSOR
ROOM
THERMOSTAT
WATE R HIGH
LIMIT
21
Figure 16b. Boiler Control.
Figure 16c. Ladder wiring diagram.
Page 22
22
1
END
SWITCH
T
H-TR
MOTOR
2
T
TT T TT TT TT TT T TT
T
T
3
456
S
PAC E
HEATING
S
YSTEM
CIRCULATOR
END
S
WITCH
TH-TR
MOTOR
Z
ONE 2
THERMOSTAT
V8043E/F
END
S
WITCH
T
H-TR
MOTOR
ZONE 3
THERMOSTAT
V8043E/F
1 2 3 4 5 6 7 8
FIELD WIRING
T
ERMINALS
O
N BOILER
JUMPER
R
845A
R
ELAY
LI L2
1
ZONE 1
THERMOSTAT
120V/24V
T
RANSFORMER
1
POWER SUPPLY, P ROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MULTIZONING OF "BOBCAT" BOILER;
ZONE VALVE SYSTEM USING V8043E/F ZONE VALVES AND R845A RELAY
DISCONNECT
SWITCH
V8043E/F
1 2 3 4 5 6 7 8
FIELD WIRING
TERMINALS
ON BOILER
1
2
TT
3456
TT TT
LI
L2
DISCONNECT
SWITCH
1
R845A
RELAY ZONE 3
CIRC.
ZONE 3
R845A
RELAY ZONE 2
CIRC.
ZONE 2
R845A
RELAY ZONE 1
CIRC.
ZONE 1
ZONE 3
THERMOSTAT
ZONE 2
THERMOSTAT
ZONE 1
THERMOSTAT
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MULTIZONING OF "BOBCAT" BOILER;
PUMP ZONING SYSTEM USING R845A RELAY
1
23456
1
23456
Bobcat Models B-120A and B-200A
Figure 17a. Multizoning of Bobcat boiler; zone valve system.
Figure 17b.
Multizoning of Bobcat boiler;
pump zoning system using R845A rela
y
.
Page 23
Bobcat Models B-120A and B-200A
LI
L2
1
DISCONNECT
SWITCH
120V/24V
T
RANSFORMER
FIELD WIRING
TERMINALS ON BOILER
C
IRC.
ZONE 3
ZONE 3
THERMOSTAT
1
P
OWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
MULTIZONING OF "BOBCAT" BOILER;
PUMP ZONING SYSTEM USING R882A/B RELAYS
C
IRC.
ZONE 2
R882A/B
R882A/B
ZONE 2
THERMOSTAT
C
IRC.
ZONE 1
R882A/B
ZONE 1
T
HERMOSTAT
120V/60HZ
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1
2
TT
3
4
56
LI
L2
1
1
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DISCONNECT SWITCH
R845A RELAY
THERMOSTAT
CIRCULATOR
FIELD WIRING TERMINALS ON BOILER
LI
L2
1
1
1 2 3 4 5 6 7 8
POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DISCONNECT SWITCH
THERMOSTAT
CIRCULATOR
R 882A/B RELAY
120 V / 24 V TRANSFORMER
FIELD WIRING TERMINALS ON BOILER
23
Figure 17c. Multizoning of Bobcat boiler; pump zoning system using R882A/B relays.
Figure 17d. Single zoning of Bobcat boiler; pump zoning system using R845A relay.
Figure 17e. Single zoning of Bobcat boiler; pump zoning sys­tem using R882A/B relay.
Page 24
24
Bobcat Models B-120A and B-200A
WATER PIPING
1. Connection of system to boiler:
rimary/secondary piping of the system is recommended, to
P
nsure the proper flow through the boiler. (See Figures 20
e through 22). The boiler loop piping must be the same diameter as the water outlet (supply) and inlet (return) piping connections provided on the boiler, particularly on longer loops. See page 2 for piping connection size.
2. Circulator Pumps:
The boiler loop piping must utilize the Taco 0011 circulator for
-120 and 0013 for B-200 that is supplied with the boiler, to
B
nsure the proper flow through the boiler. Refer to Figure 19
e for the boiler water side pressure drop and Table 2a and 2b for the recommended pump models for the domestic hot water system. Install the pumps in the orientation shown in Figures 20 through 22.
3. Relief Valve(supplied with boiler):
Tee the relief valve into the boiler water outlet (supply) piping as close to the water outlet (supply) connection as possible. (See Figure 18). The relief valve’s discharge piping must be the same size or larger than the relief valve’s outlet, and must terminate 6” minimum from floor with a plain (no threads) end. Place a bucket under pressure relief valve discharge. Make sure discharge is always visible. DO NOT hard-pipe to drain piping, or any place where freezing could occur. No shut-off valve is permitted between the relief valve and boiler, or in the discharge line.
4. Air Control System:
An appropriately sized diaphragm-type expansion tank must be used to control the system pressure. See boiler volume data on page 2, and the recommended location in Figures 20 through 22. An air vent is recommended to be installed on an air separator in close proximity to the expansion tank.
5. Cold Water Fill:
A pressure reducing (fill) valve, with a shut-off valve upstream of it, should be installed in close proximity of the expansion tank. (See Figures 20 through 22). Use a back flow check valve in the cold water supply as required by local codes.
w Water Cutoff:
6. Lo
On a hot water boiler installed above radiation level, the boiler must be provided with a low water cutoff device at the time of installation by the installer (see Figure 18 for piping arrangement).
7. Water Treatment and Freeze Protection:
A good water treatment program will not only extend the useful life of this boiler but it will also save much of the time
nd expense of repairs made necessary by preventable
a
ccurrences. A reputable water treatment company should be
o consulted to evaluate and determine the best overall treatment program for your boiler equipment.
The heat exchanger is made of aluminum, so the system water must be maintained between 7.0 and 8.5 PH level.
horoughly flush the system, before connecting the boiler, to
T
emove any sediment or glycol.
r
Anti-freeze is sometimes used in hydronic systems to protect against freez-up in the event of power failure or boiler shut down in the cold winter.
(Propyleneglycol with Pro-Tek 922 inhibitor) by Rhomar Water Management, Inc.
instructions for proper application and proper mixture for
um ambient temperature.
minim
other than that supplied by Slant-Fin or specifically approved and/or recommended for use by Slant-Fin will void this warranty. Never use Ethylene Glycol as it is toxic to humans.
Never use any types of automotive or standard gylcol freeze protection fluids.
8. Piping a heating - cooling system to a water boiler and chiller:
Figure 22 illustrates a method of piping a heating-cooling system to a water boiler and a chiller. Hand valves (shown) or automatic valves must be installed to prevent circulation of chilled water in the boiler or hot water in the chiller.
The air control system and pressure control system must operate with chiller only, or the boiler only, being valved to the piping system. Separate control devices on the boiler and chiller may be used, or a single set of air and pres­sure controls on the common piping may be preferred.
If the boiler is used to supply hot water to heating coils in air handling units, flow control valves or other devices must be installed to prevent gravity circulation of water in the coils during the cooling cycle.
Follow the manufacturer’s
Use RhoGard
y use of anti-freeze
An
Page 25
Bobcat Models B-120A and B-200A
W
AT ER OUTLET PIPING,TO REST OF SYSTEM
LOW WAT ER CUTOFF MANIFOLD (IF LWCO UTILIZED)
PROBE-TYPE LOW WATER CUTOFF (IF REQUIRED)
1" X 1" X 3/4"
NPT TEE
WAT ER OUTLET (SUPPLY)PIPE, 1" NPT MALE
WAT ER INLET (RETURN) PIPE, 1" NPT MALE
RELIEF VALVE DISCHARGE PIPING
PRESSURE RELIEF VALVE (SUPPLIED WITH BOILER)
3/4" NPT STREET ELBOW
25
Figure 18. Relief Valve and Low Water Cutoff Installation
Page 26
26
0
5
10
15
20
25
0
5 10 15 20
Head
(feet w.c.
)
Flow Rate (GPM)
B-200
B
-120
Figure 19. Boiler water side pressure drop
Bobcat Models B-120A and B-200A
Flow Rate
(gpm)
Temp
Rise
(˚F)
Boiler
Head Loss
(Feet w.c.)
Domestic Water
Tank Piping
Head Loss **
(Feet w.c.)
10.8 20˚ 10.0' 3.0'
Available Head Capability Left for Various Model
Circulators to Overcome DHW Tank Head Loss
(Feet w.c.) ***
Taco 0012 Taco 0014 Taco 0011
Not Recommended
4.0' 9.5'
7.2 30˚ 5.0' 2.5' 5.0' 10.5' 17.5'
5.4* 40˚ 3.0' 1.5' 8.5' 14.5' 23.5'
Table 2a. Recommended pump models for domestic hot water tank piping to the Bobcat model B-120 boiler.
Flow Rate
(gpm)
Temp
Rise
(˚F)
Boiler
Head Loss
(Feet w.c.)
Domestic
Tank Piping
Head Loss **
(Feet w.c.)
18.0 20˚ 23.0' 4.0'
14.5 25˚ 16.5' 3.5'
Water
Taco 0011 Taco 0013
Not
Recommended
Not
Recommended
Available Head Capability Left for Various Model
Circulators to Overcome DHW Tank Head Loss (Feet w.c.) ***
aco
T
1400-20
s
Not
Recommended
Not
Recommended
(2 in Series) Taco 0011
s
3.0' 13.0'
(2 in Series) Taco 0013
3.5' 17.0' 27.0' 6.0' 15.5'
1400-45
s
12.0 30˚ 12.5' 3.0' 5.5' 10.5' 26.5' 36.5' 12.0' 21.5'
9.0 * 40˚ 7.5' 2.5' 14.0' 18.0' 38.0' 46.0' 19.5' 28.5'
aco
T
6.5'
s
Table 2b. Recommended pump models for domestic hot water tank piping to the Bobcat model
Notes:
This is the minimum flow rate recommended for each of the boiler models.
*
** Domestic water tank piping head is based on 1” inside diameter piping and full port valves.
*** Refer to the DHW Tank Manufacturer’s water flow rate requirements and associated pressure drop head loss, to select
the appropriate circulator.
s If 2 circulators are specified, the
circulator(s) m
ust be supplied through an appropr
ust be piped in ser
y m
ies in order to pro
iate rela
y to protect the boiler control’
vide the head capacity sho
s fuse
B-200 boiler.
P
wn.
.
er to
w
o
Page 27
Bobcat Models B-120A and B-200A
FROM REST
OF SYSTEM
TO REST
OF SYSTEM
BOBCAT BOILER
ADDITIONAL
ZONES
SPAC E HEAT
ZONE #1
ISOLATION VALVE
ISOLATION VALVE
F
LOW CHECK
V
ALVE
ZONE
C
IRCULATOR
D
O NOT EXCEED 1
2" APART
AIR VENT
AIR SEPARATOR
ISOLATION V
ALVE
MAKE UP
WATE R SUPPLY
SHUTOFF VALVE
PRESSURE REDUCING VALVE
BACK FLOW P
REVENTOR
(
IF REQUIRED)
PURGE/ DRAIN V
ALVE
ISOLATION VALVE
BOILER LOOP C
IRCULATOR (SUPPLIED WITH THE BOILER)
FLOW CHECK VALVE
HOT WATER
OUTLET
COLD INLET
WATE R
SHUTOFF VALVE
DRAIN VALVEDRAIN VALVE
DOMESTIC HOT WATER
TANK
T + P RELIEF VALVE
BOILER WATER OUTLET (SUPPLY)
RELIEF VALVE
FLOW CHECK VALVE
DHW CIRCULATOR
ISOLATION VALVE
E
XPANSION TANK
(DIAPHRAM TYPE)
BOILER WATER INLET (RETURN)
27
Figure 20. Zoning with circulators.
Page 28
28
P
SYSTEM
CIRCULATOR
D
IFFERENTIAL
P
RESSURE BYPASS
VALVE (IF USED)
BOBCAT BOILER
ADDITIONAL
ZONES
SPAC E HEAT
ZONE #1
I
SOLATION
V
ALVE
ZONE VALVE
DO NOT EXCEED
12" APART
A
IR VENT
A
IR
S
EPARATOR
I
SOLATI ON
VALVE
MAKE UP
WATE R SUPPLY
SHUTOFF VALVE
P
RESSURE
R
EDUCING
VALVE
BACK FLOW PREVENTOR (IF REQUIRED)
PURGE/ D
RAIN
VALVE
ISOLATION V
ALVE
BOILER LOOP CIRCULATO R (SUPPLIED WITH THE BOILER)
FLOW CHECK VALVE
HOT WATER
OUTLET
COLD
INLET
WATE R
SHUTOFF VALVE
DRAIN VALVEDRAIN VALVE
DOMESTIC HOT WATER
TANK
T + P RELIEF VALVE
BOILER WATE R OUTLET (SUPPLY )
RELIEF VALVE
FLOW CHECK VALVE
DHW CIRCULATOR
ISOLATI ON VALVE
EXPANSION TANK (DIAPHRAM TYPE)
BOILER WATE R INLET (RETURN)
Bobcat Models B-120A and B-200A
Figure 21. Zoning with zone v
alves.
Page 29
Bobcat Models B-120A and B-200A
P
SYSTEM
CIRCULATOR
DIFFERENTIAL PRESSURE BYPASS VALVE (IF USED)
BOBCAT BOILER
ADDITIONAL
ZONES
SPAC E HEAT
ZONE #1
ISOLATION VALVE
ZONE V
ALVE
D
O NOT EXCEED
12" APART
A
IR VENT
AIR SEPARATOR
ISOLATI ON VALVE
MAKE UP
WATE R
SUPPLY
SHUTOFF VALVE
PRESSURE R
EDUCING
VALVE
BACK FLOW PREVENTOR (
IF REQUIRED)
PURGE/ DRAIN VALVE
ISOLATION VALVE
B
OILER LOOP
C
IRCULATO R (SUPPLIED WITH T
HE BOILER)
FLOW CHECK VALVE
HOT WATER
OUTLET
COLD INLET
WATE R
SHUTOFF VALVE
DRAIN VALVEDRAIN VALVE
DOMESTIC
HOT WATER
TANK
T + P RELIEF VALVE
BOILER WATE R OUTLET (SUPPLY )
RELIEF VALVE
FLOW CHECK VALVE
DHW CIRCULATOR
ISOLATI ON VALVE
EXPANSION TANK (DIAPHRAM TYPE)
BOILER WATE R INLET (RETURN)
FLOW CHECK VALVE
I
SOLATION
V
ALVE
WATE R
CHILLER
UNIT
STRAINER
B
ALANCING
V
ALVE
29
Figure 22. Piping a heating-cooling system to the boiler and a chiller.
Page 30
30
OPERATING INSTRUCTIONS
I. FILLING AND VENTING WATER SYSTEMS
Bobcat Models B-120A and B-200A
. While “t” is blinking, DHW tank temperature may be
3
et to desired temperature (if tank is equipped with
s sensor). The setting range is between 104˚ to 185˚F.
. Fill the system with water. Vent or purge of air.
A
B. Fire the boiler as soon as possible (see following warning
and instructions) and bring water temperature in the system.
C. Vent air and add water as needed to achieve operating
pressure on boiler gauge. Pressure must be between
pproximately 12 psi (cold water) and 25 psi at water
a
emperature setting of high limit control, for boilers
t equipped with 30 psi relief valves. Boilers rated for a higher pressure and equipped with a matching relief valve may operate at a higher pressure, but no higher than 5 psi
w the relief valve opening pressure.
belo
D. Check for and repair any leaks before placing system in
service.
BEFORE FIRING BOILER, make these checks:
Before firing boiler, review the “Boiler Control and Display Features” section of this manual. Understanding the features and programming the applicable parameters is essential for setting up the boiler to operate properly on the heating system it is installed on.
1. System is full of water. Air is vented or purged.
2. Relief valve is installed in accordance with ASME Boiler and Pressure Vessel Code, Section IV. Valve opening is not closed or reduced in size.
3. Venting is installed according to instructions under “FLUE GAS VENTING REQUIREMENTS”.
4. View actual boiler supply & return water tempera­ture, domestic hot water tank temperature (if tank equipped with sensor), flue temperature and outside temperature (if outside sensor is used) on “Temperature Display” by selecting 1, 2, 3, 4, or 5 on
Mode Display”.
• These numbers are steady on display and are
not settable.
• All sensor inputs to the control must be
connected to a 12k ohm sensor.
C.
Viewing and changing system setting:
A trained, experienced service technician or installer should perform following adjustments. See table 5 for details.
1. Space heating and DHW post pump time may be changed.
2. Space heating and DHW modes may be chosen.
3. Weather compensation slope and set point temperature may be changed (if outside sensor is used). (See Figure 24 for graph).
4. Read actual blower RPM
5. Adjust blower RPM for high and low input adjustment.
6. Read flame current in micro amp.
7. Run boiler on high, low or ignition input steady for 20 minutes for test purposes.
Display and push buttons:
D.
4. All wiring is completed, following applicable wiring diagrams.
5. Using soap solution, check for gas leaks in all gas piping from meter to boiler gas supply pipe flame.
II. BOILER CONTROL AND DISPLAY FEATURES
(See Figure 23)
A. Boiler Operation Status:
“Mode Display” shows status of boiler operation (see table 3).
.
B
View and Changing Temperatures:
Setting boiler supply w temperature (see table 4). Press “Select” button for viewing following different modes on “Mode Display”
1. While “c” is blinking, boiler supply water temperature for space heating may be set to desired temperature The setting r
“d”
While
2. for DHW may be set to desired temperature. The setting range is between 104˚ to 185˚F.
ater temperature and water tank
ange is betw
linking, boiler supply w
is b
DO NOT use open
.
een 90˚ to 185˚F
ater temper
.
ature
1. Reset - Used to clear a Lock out error (indicated with an
“A” in the “Mode Display”).
Select - Used to scroll through the modes in the “View
2. and Changing Temperatures” and “Viewing and Changing System Setting” men
Enter - Used to store values that are changed in the “View
3. and Changing Temperatures” and “Viewing and Changing System Setting” menus.
4.
Up- Used to increase v Temperatures” and “Viewing and Changing System Setting” menus.
wn -
5.
Do
Changing Temperatures” and “Viewing and Changing System Setting”
Used to decrease v
us.
alues in the “View and Changing
alues in the “View and
.
us
men
Page 31
Bobcat Models B-120A and B-200A
*
"MODE" DISPLAY
"TEMPERATURE" DISPLAY (3 DIGITS)
"UP" PUSH BUTTON
"DOWN" PUSH BUTTON
"ENTER" PUSH BUTTON
"SELECT" PUSH BUTTON
"RESET" PUSH BUTTON
"BURNER STATUS"
STEADY DOT = BURNER ON
BLINKING DOT = BURNER OFF
Table 3
Table 3
Table 3
Table 3
Table 3
Table 3
Table 1
Table 3
31
Figure 23. Display Board
Table 3
BOBCAT BOILER DISPLAY BOARD
“Boiler Operation Status”
MODE
DISPLAY
Reset button must be pressed to resume normal operation.
DESCRIPTION & TEMPERATURE DISPLAY
Boiler is on stand-by mode.
Temperature display shows supply water Temp.
Space heating mode.
Temperature display shows supply water Temp.
Domestic hot water mode.
Temperature display shows supply water Temp.
Frost protection mode. **
Temperature display shows supply water Temp.
Lockout (Alarm) condition.
ature Display indicates the lockout code
emper
T
Error Condition. *
Temperature display indicates the error code.
Warning Condition. ***
Temperature display indicates the error code.
NO
TE:
Blinking dot on Steady dot indicates b
Error m
*:
The boiler loop circulator is energiz
**:
Error m
***:
the “Reset” button is not required.
ust be corrected to resume boiler oper
ust be corrected to resume DHW oper
“Mode Displa
ner is on.
ur
indicates activ
y”
e heating control, b
ation.
ed, if the boiler w
ation.
Pressing the
ater temper
Space heating not aff
urner off.
“Reset”
ature drops belo
utton is not required.
b
.
w 50˚F
Pressing
ected.
Page 32
32
T
able 1
T
able 3
Table 1
Table 3
T
able 1
T
able 3
T
able 3
Table 3
Table 3
T
able 3
Table 3
Bobcat Models B-120A and B-200A
Table 4
VIEWING AND CHANGING TEMPERATURES
Press “SELECT” button for viewing different modes on “MODE DISPLAY”
ODE
M
DISPLAY
Space heating supply water temperature could be changed by
blinking
Domestic hot water supply temperature could be changed by
blinking
blinking
DESCRIPTION & TEMPERATURE DISPLAY
pressing “Up/Down” button. Settable from 90˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 1)
pressing”Up/Down” button. Settable from 104˚F to 185˚F
(steps of 1 F). The default value is 176˚F.
Press “Enter” button to store.
(see note 2)
Domestic hot water tank temperature could be changed by
pressing “Up/Down” button. Settable from 104˚F to 160˚F
(steps of 1 F). The default value is 140˚F.
Press “Enter” button to store.
(see note 3)
NOTE:
Temperature display shows actual supply water temperature.
Temperature display shows actual return water temperature.
Temperature display shows actual DHW tank temperature.
(if the water tank is equipped with sensor).
Temperature display shows actual flue gas temperature.
Temperature display shows actual outside temperature.
(if outdoor sensor is used)
or space heating mode “0”
1- F 2- For DHW mode “2” (storage tank with Aquastat) 3- For DHW mode “1” (storage tank with sensor)
(boilers not utilizing outdoor sensor))
Page 33
Bobcat Models B-120A and B-200A
Table 3
Table 3
Table 3
Table 3
Table 3
VIEWING AND CHANGING SYSTEM SETTING - Table 5
“To change system setting or perform system test”
he menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To change
T
system setting: Press “UP or DOWN” button, then press “ENTER”
WARNING: Only a trained, experienced service technician or installer should use this table.
33
MODE DISPLAY
*
*
*
*
*
*
*
DESCRIPTION
Changing space heating post pump time. Settable from 10 to 900 seconds.
(steps of 10 seconds). The default value is 30 seconds.
Changing DHW post pump time. Settable from 1 to 255 seconds.
(steps of 1 seconds). The default value is 15 seconds.
hanging space heating control mode
C
0: Thermostat only (default) - boiler without outdoor sensor
: Outside sensor and Thermostat
1
Outside sensor only
2: 3: Permanent heat demand (boiler circulator always on)
C
hanging domestic hot water (DHW) mode
0: No DHW 1: Storage tank with sensor 2: Storage tank with thermostat (default value)
Plate heat e
3:
Changing DHW or space heating priority mode
0: DHW priority (no time limit) 1: Space heating priority (no time limit) 2: DHW priority for limited time (default) 3: Space heating priority for limited time
Changing priority limited time. Settable from 20 to 80 minutes.
Boiler model selection, value is 0 for model B-120 and 4 for model B-200
xchanger
The default value is 30 minutes.
**
**
*
*
*
*
*
*
*
*
Boiler model confirmation, value is 0 for model B-120 and 4 for model B-200
Weather compensation supply water reference temperature
(space heating mode 1 or 2). Settab
Changing compensation slope (space heating mode 1 or 2).
Changing weather compensation set point (space heating mode 2 only).
Displa
Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).
Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).
Settable from 32˚F to 122˚F (steps of 1˚F).
y sho
System test – Display shows flame current
The def
Settable from 0.1 to 5.0 (steps of 0.1).
The default value is 1.0.
The default value is 68˚F.
ws blower RPM (mutiply reading by 10 for actual RPM)
Display shows flame current in micro amps
0: System test off L: Steady low input (20 minutes) I: Steady ignition input (20 minutes) H: Steady high input (20 minutes)
le from 16˚F to 122˚F (steps of 1 F).
alue is 86˚F.
ault v
Not Utilized
NOTE: *: Alternating **: Steady
Page 34
34
70
70 60 -20-10 -3001020304050
Outdoor Temp. (°F)
Water
Supply
Target Temp.
(°F)
185 °F
140
150
130
190
180
170
160
120
110
100
80
90
2
00
S
l
o
p
e
=
4
.
0
S
l
o
p
e
=
3
.
0
S
l
o
p
e
=
0
.
1
(
m
i
n
.
)
S
l
o
p
e
=
2
.
0
S
l
o
p
e
=
0
.
5
S
l
o
p
e
=
1
.
2
S
l
o
p
e
=
5
.
0
(
m
a
x
.
)
-40
S
l
o
p
e
=
1
.
5
S
l
o
p
e
=
1
.
0
(
d
e
f
a
u
l
t
)
S
l
o
p
e
=
1
.
8
Ma
ximum water target temp.
Water reference temp.(default of86°F)
Minimum watertarget temp.
68°F
Bobcat Models B-120A and B-200A
Figure 24. Space Heating mode with outside sensor water set point graph.
Page 35
Bobcat Models B-120A and B-200A
GAS SUPPLY SHUTOFF VALVE I
N "OPEN" POSITION
GAS SUPPLY SHUTOFF VALVE I
N "CLOSED" POSITION
TURN 90˚ TO CLOSE
T
URN 90˚
TO OPEN
III. INITIAL START
Safe lighting and other performance criteria were met when testing various gas manifold and control assemblies used on the Bobcat B-120 and B-200 boilers under the ANSI Z21.13 - latest edition.
Instructions
Follow the lighting instructions in this manual.These instructions are also attached to the boiler.
. Use only your hand to turn the gas supply shut-off valve.
C
Never use tools. If the supply shut-off valve will not turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
STOP! Read the safety information above.
1.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
35
Figure 25. Gas supply shutoff valve operation.
SAFETY INFORMATION
For Your Safety Read Before Operating
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
This appliance does not have a pilot. It is equipped with
A.
an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
BEFORE OPERATING smell all around the appliance area
.
B
for gas. Be sure to smell next to the floor because some gas
.
vier than air and will settle on the floor
is hea
WHAT TO DO IF YOU SMELL GAS:
• DO NOT try to light any appliance.
• DO NOT touch any electric switch: DO NOT use any phone in your building.
• Immediately call you gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
tment.
depar
5. Open the gas supply shut-off valve, by turning the handle to be parallel to the gas piping (See Figure 25).
6. Wait five (5) minutes (longer for propane) to clear out any gas, then smell for gas, including near the floor. If you then smell gas, STOP! Follow “B” in the safety information above on this page. If you don’t smell gas, go to next step.
7. Turn on all electric power to the appliance.
8. Set thermostat to desired setting. If the appliance will not operate, follow the instructions “To Turn Off Gas to Appliance” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting.
n off all electric po
ur
T
2. be perf
ormed.
er to the appliance if ser
w
vice is to
3. Close the gas supply shut off valve, by turning the handle to be per
pendicular to the gas piping. (See Figure 25).
Page 36
36
Bobcat Models B-120A and B-200A
BOBCAT BOILER MODELS B-120 and B-200 SEQUENCE OF OPERATION
THERMOSTAT CALLS FOR HEAT
CIRCULATOR(S) ON
COMBUSTION BLOWER ON
(AT MEDIUM SPEED)
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 33”
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 03”
NO
NO
BLOWER SPEED CONFIRMED?
YES
5 SECOND PRE-PURGE
TRIAL FOR IGNITION - 6 SECONDS
SPARK IGNITOR ENERGIZED
GAS VALVE OPENS
WATER HIGH LIMIT CLOSED?
YES
GAS VALVE REMAINS OPEN
FOR 4 SECONDS
PERIOD
NO
3 TRIALS FOR
IGNITION
WITH NO FLAME SENSED?
2 TIMES RETRIALS
FOR IGNITION
CONTROL LOCKOUT
DISPLAY SHOWS
ERROR “A 01”
YES
SPARK IGNITOR DE-ENERGIZED
NO
FLAME SIGNAL SENSED?
YES
GAS VALVE REMAINS OPEN. CONTROL
CONTINUOUSLY MONITORS
, HIGH LIMIT, WATER
T
THERMOST
SENSORS, BLOWER SPEED, FLAME
SIGNAL, AND LWCO (IF USED).
THERMOST
10 SECOND
15 SECOND
A
CALL FOR HEAT ENDS
T
A
CLOSES
VE
AL
V
GAS
POST PURGE.
WER
BLO
CIRCULATOR POST PURGE.
GAS VALVE CLOSED.
BLOWER POST PURGE
10 SECONDS.
Page 37
Bobcat Models B-120A and B-200A
37
IV. CHECK COMBUSTION AND FUEL INPUT RATE
A. Remove the boiler jacket front panel, by turning the 2
black screws 1/4 turn to the open position. Lift off panel.
. Start and run the burner at the high firing rate, by using the
B
“System Test” mode in the “View and changing system setting” menu. Refer to Table 5 on page 32.
1. Measure the CO, and CO2of the flue gas. A flue sample port is provided in the vent pipe (See Figure 2 on page 3). The CO should not exceed 100 ppm, when the combustion is correct. The CO2
hould be in the range listed in Table 6.
s
2. If the CO2is not within the range specified for that gas type at the high firing rate, then adjust the venturi throttle to the nominal value shown in Table 6. Turn the throttle clockwise to decrease the CO the throttle counter-clockwise to increase the CO value. See Figure 26.
3. Once the correct combustion is confirmed at the high firing rate, check the fuel input rate on the gas meter.
BTUH INPUT = cu. ft. metered in 3 minutes x
heating value of the gas* x 20
* The higher heating value of the gas can vary for
different localities. Consult the gas supplier for this value in BTU/cu.ft.
value.Turn
2
2
C. In the “System Test” mode in the “View and Changing
System Setting” menu, use the “down” push button to switch to the low firing rate. Refer to Table 5 on page 32.
1. Measure the CO and CO2of the flue gas. The CO hould not exceed 30 ppm, when the combustion
s
s correct. The CO
i
isted in Table 6.
l
2. If the CO2is not within the range specified for that
gas type at the low firing rate, then adjust the gas valve offset to the nominal valve shown in Table 6. (See Figure 26) for the location of the offset adjustment. Remove the cap that covers the offset screw.
Turn the offset clockwise to increase the CO2value. Turn the offset counter-clockwise to decrease the CO
value. Replace the offset cap when adjustment
2
is complete
3. Once the correct combustion is confirmed at the
low firing rate, check the fuel input rate of the gas meter. BTUH Input = cu. ft. metered in 3 minutes x heating valve of the gas * x 20.
.
hould be in the range
s
2
4. If the fuel input is not at the rate specified on page 2 at the high firing rate, then the blower speed should be adjusted to attain the specified input rate. This can be done by using the “Change blower RPM for high input” mode in the “View and changing System Setting” menu. Refer to Table 5 on page 32. Increasing the blower rpm will increase the fuel input rate, and decreasing the blower rpm will decrease the fuel input r
Propane
Fuel
Nat. Gas
ate.
CO
Firing
Rate
min. nom. max.
High 8.7% 9.0% 9.3%
Low 7.7% 8.0% 8.3%
High 10.2% 10.5% 10.8%
Low 9.2% 9.5% 9.8%
2
Figure 26. Gas valve and venturi adjustment.
Table 6. Combustion values for Natural Gas and Propane.
Page 38
38
Bobcat Models B-120A and B-200A
4. If the fuel input is not at the rate specified on page 2
at the minimum firing rate, then the blower speed should be adjusted to attain the specified input rate. This can be done by using the “Change blower RPM for low input” mode in the “View and Changing System Setting” menu. Refer to Table 5 on page 32.
ncreasing the blower rpm will increase the fuel input
I rate, and decreasing the blower rpm will decrease the fuel input rate.
D. Exit the “System Test” mode, once the combustion and fuel
input rate has been checked and adjusted, if necessary. Refer to Table 5 on page 32.
V. SAFETY CHECK
A. Check for gas leaks:
Using soap solution, check for gas leaks from meter to gas valve including all pipes and fittings and gas valve connections. Use liquid soap solution for all gas testing. DO NOT use open flame.
Thermostat Test:
.
B
Set thermostat setting to low enough to end call for heat. Gas valve should close and burner should stop firing.
A. LOCKOUT ERRORS: Indicated by an “A” in the mode display. The reset button must be pressed to clear the error
and retry operation. The temperature display shows the error code.
Blower and circulator pump should go into a post purge, then shut off.
Control Safety Shutdown test:
C.
With the burner firing, disconnect the spark cable from the spark ignitor. Gas valve should close and burner should
top firing. The boiler will try for ignition three times after
s this, then should lock out with an “A 01” error shown on the display. Reconnect the spark cable to the spark ignitor, and press the “Reset” button to return to normal operation.
VI. DIAGNOSTIC ERROR CODES
WARNING:
should perform troubleshooting. Turn off all electric power to the boiler before service.
Only a trained, experienced service technician
ERROR CODE INDICATION REMEDY
Check for steady sparking at electrodes. If spark not steady - check spark gap to be .125”, clean or replace spark ignitor, check power supply voltage and grounding. If spark is steady - check for proper gas supply pressure.
01
Ignition Failure - 3 unsuccessful
ignition attempts in a row.
Check combustion, if able to ignite, or replace gas valve.
Check for proper combustion, at both max. and min.
02
Flame Failure - 3 losses of flame
signal dur
ing one demand.
input fir specified in Table 6 on page 36, clean or replace spark
ing rates. If combustion is within the range
ignitor, check power supply voltage and grounding.
Check to see if the water outlet temperature reaches
03
Water High Limit Open
203˚F. If it does, replace the water outlet 12k ohm sensor. If it does not, replace the water high limit switch.
04,
05, 09, 10,
12, 13, 14, 15,
16, 18, 32
Control Failure
Replace control board. Make sure the proper boiler model selection and confirmation code is entered.
Table 5 on page 32.
See
If a flame is still observed after a call for heat is stopped,
If the burner seems to be shutting
19, 20
Flame Detected at
Wrong Time
replace the gas v
alve
.
down properly, replace the spark ignitor.
33
an Failure - RPM error
F
Check wire harness connections going to the blower. Replace blower.
Page 39
Bobcat Models B-120A and B-200A
B. BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the
condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset”
utton is not required.
b
ERROR CODE INDICATION REMEDY
Check wire harness connections going to the
01
02
03
Water Outlet Sensor Open
Water Inlet Sensor Open
Flue Gas Sensor Open
sensor. Replace the sensor.
Check wire harness connections going to the sensor. Replace the sensor.
Check wire harness connections going to the sensor. Replace the sensor.
39
11 12 13
19, 42, 45,
46, 47, 48
20
21
22
24
Water Outlet Sensor Shorted Replace the sensor.
Water Inlet Sensor Shorted Replace the sensor.
Flue Gas Sensor Shorted Replace the sensor.
Replace control board. Make sure the proper
Control Failure
Flame Detected at Wrong Time
Polarity Error Reverse the hot and neutral power supply wires.
Frequency Error
Earth Connection Faulty Check grounding of control and boiler chassis.
boiler model selection and confirmation code is entered. See Table 5 on page 32.
If a flame is still observed after a call for heat is stopped, replace the gas valve, If the burner seems to be shutting down properly, replace the spark ignitor.
Check power supply frequency to be 60 hz, certain power supplies may not provide the proper frequency
.
contin
ued on pa
g
e 39
Page 40
40
continued from page 38
ERROR CODE INDICATION REMEDY
30
31
32
Excess Flue Temperature
Low Water Cutoff Error
Excess Water Inlet Temperature
Bobcat Models B-120A and B-200A
Check flue gas temperature, at the maximum firing rate and high water temperature. If the flue gas temperature reaches 212˚F, check the fuel input rate and combustion. Check the condition of the heat exchanger. If the flue gas temperature does not reach 212˚F, replace the flue sensor.
If a low water cutoff is installed, check the system water pressure and content. Check the condition of the LWCO. If no LWCO is installed, check the jumper is in place at the wiring terminal board. See Figure 16a on page 19.
Check that the wire harnesses to the water inlet and outlet sensors are not reversed.The water inlet sensor harness should have a blue colored connector, the water outlet sensor harness should have a red colored connector. Check that the pumping flow direction is correct.
51
52
ARNING ERR
C. W
ed, and the warning is displayed intermittently. Operation of the DHW mode is automatically restored, once the condition is fixed. The temperature display shows the error code. Pressing the “reset” button is not required.
04
ORS:
Indicated b
Domestic Hot Water Tank Sensor Open
14
Reset Button Error
Boiler Model Selection Error
“H” in the mode display
y an
Domestic Hot Water Tank
Sensor Shorted
Try turning power supply off and on again. If error returns, replace the display board.
Check that the proper boiler model selection and confirmation code is entered in the display. See Table 5 on page 32.
Operation of the space heating mode is not aff
.
If sensor is utilized, check wire harness connections going to the sensor sor is utilized, check the proper DHW mode is pro-
ammed.
r
g
If sensor is utilized, replace the sensor. If no sensor is utiliz grammed. See Table 5 on page 32.
See Table 5 on page 32.
ed, chec
, or replace the sensor
k the proper DHW mode is pro
. If no sen-
-
ect-
Page 41
Bobcat Models B-120A and B-200A
41
CARE AND MAINTENANCE
This section must be brought to the attention of the owner by the installer so that the owner can make the necessary arrange­ments with a qualified service agency for the periodic care and maintenance of the boiler.The installer must also inform the owner that the lack of proper care and maintenance of this boiler and any fuel burning equipment may result in a hazardous condi­tion. Installer should discuss contents of the User’s Information Manual (Publication B-UIM) with the owner.
A trained and qualified service technician should perform the inspection listed in these instructions before each heating season and at regular intervals.
I. GENERAL MAINTENANCE
A. Safety check, see page 37.
B. Vent and air intake system inspection
1. Check for obstruction, condensation, corrosion and physical damage.
2. Check outside termination. Screen and louvers should be free of any debris and must be cleaned as required.
3. Perform “Venting and Air intake System Regular Inspection”, see page 17.
B. Check venting system. See “Venting and Air Intake System
Regular Inspection” on page 17.
C. Check condensation drain trap to be full of water. Check for
deterioration of the tubing. Check that the trap is not plugged.
. The combustion blower does not require or have provisions
D
or lubrication.
f
E. If required, lubricate the circulator as per the manufacturer’s
instruction.
III. CLEANING
A. Heat Exchanger: In the unlikely event of flue passage or
water passage blockage, service to remedy situation must be performed only by an authorized Slant/FIn representative.
Burner: In the unlikely event of blockage or deterioration,
B.
service to remedy situation must be performed only by an authorized Slant/Fin representative.
WARNING:
The ceramic combustion chamber in the burner box contains crystalline silica.
Wear proper dust mask and gloves when servicing combustion chamber or burners.
C. Piping
Check the following:
1. Water piping and accessories for leaks. Slightest leaks should be corrected.
2. System to be full of water and pressure to remain stable at correct setting on gauge.
3. Air-control system. Noise and air binding in radiation should not occur.
4. Low water cutoff for operation (see instruction furnished with unit).
D. Boiler Room Air Supply
Check air vents for continuous positive supply of air as required. installation is non-direct vent method. Air vents must open and free of obstruction.
WARNING: The flow of combustion and ventilating air to the
II. INSPECTION DURING HEATING SEASON
A. Check water pressure regularly and add water slowly to
system when needed. If m necessary indicate either a system leak, or a f a faulty automatic fill valve.
Air needs are greatest in cold weather if boiler
boiler should not be obstructed.
enting ma
Regular loss of w
.
uch water is added, v
ater from boiler system may
aulty air control system, or
Crystalline Silica has been identified as carcinogenic or possibly carcinogenic to humans.
IF REPLACEMENT PARTS ARE NEEDED
When parts are needed, refer to boiler model and serial number shown on the boiler name/rating plate. Refer to publication number B-10PL replacement parts for part numbers. Whenever possible refer to the original order by number and date.
Control identification and replacement should not be attempted by unskilled personnel. Only, simple easily - identified controls and parts may be obtained locally. All other control and parts should be identified by and ordered form Slant./Fin. Relief/Safety valves must be ASME rater for the pressure and gross output of the boiler.
For replacement parts, heating contractors should contact their Slant/Fin boiler distributor.
y be
Page 42
42
Bobcat Models B-120A and B-200A
GENERAL TROUBLESHOOTING GUIDE FOR SERVICE PERSONNEL
WARNING: Only a trained, experienced service technician should perform troubleshooting.
Turn off all electrical power to the boiler before servicing.
A. BURNER FAILS TO OPERATE - NO HEAT
CA
USE REMEDY
1. No power, display off, power switch off. Main electric 1. Close switch. Check or replace fuse. switch open. Blown or defective line fuse.
2. Gas supply valve shut off. 2. Open gas supply valve. Check gas pressure.
3. Harnesses plug-in connectors are not securely connected. 3. Check connectors on boiler control.
4. Operational problem, detected by control. 4. Error code on display can be correlated to
specific problems and remedy. Refer to page 37-39 for error codes.
B. NOT ENOUGH HEAT
1. Thermostat setting is too low. 1. Set thermostat at higher setting.
2. Boiler water maintained at too low temperature. 2. Increase space heating set point temperature.
Refer to Table 4 on page 31.
3. Circulator not running. 3. With thermostat calling for heat, check for power
to circulator. If power is O.K. but circulator is not running, replace circulator.
4. Boiler water level too low. 4. Carefully snap open relief valve handle to
determine if boiler is full of water, if not full of
, check for system leaks and check water
ater
w pressure regulator. Repair any system leaks. Adjust or replace water pressure reducing valve.
5. Fuel input rate too low. 5. Check the maximum fuel input firing rate.
Refer to page 36 for the procedure.
C. FUMES AND GAS ODORS
1. Leaks in gas piping or accessories. 1. Locate leaks and repair.
2. Gas leaks in service line or meter connections. 2. Close service supply valve - shut down boiler
and notify utility.
3. Condensation trap is not full of water. 3. Check and fill with water
4. Venting system is physically damaged. 4. Check carefully and repair. Also, see “Venting
System Regular Inspection”.
5. Over - firing or poor combustion. 5. Check the maximum fuel input firing rate and
combustion. Refer to page 36 for procedure.
Page 43
Bobcat Models B-120A and B-200A
43
Figure 27. Propane orifice installation.
CONVERTING TO PROPANE
WARNING:
Only a trained, experienced Service Technician or Installer
should perform the conversion procedure.
A conversion kit, complete with the appropriate orifice disk and conversion label, is available for performing this procedure. Refer to the Bobcat model B-120’s boiler’s parts list publication B-10PL for the kit part number.This conversion kit can only be used for the B-120 boiler. The following procedure for perform­ing the conversion to Propane is intended for a Bobcat boiler that is not yet installed. If the boiler is already installed, be sure to turn the gas and power supply off, before proceeding. Once the boiler is installed, the combustion should be checked, as per the instructions and specifications on page 36. The fuel input
ate for Propane will be appro
r when the supply pressure is in the range of 10” to 14” w.c
ve boiler jacket front cover, by turning the 2 black
Remo
1. scre
ws 1/4 turn to the open position. Lift off panel.
2. Remove the blower box cover, held in place by the 8 screws, to access the gas valve and venturi. (See Figure 28).
3. Loosen gas pipe union.
4. Remove the 2 Phillips screws securing the venturi to the blower.
5. Remove the 3 Phillips screws securing the gas valve to the venturi. (See Figure 27).
ximately as specified on page 2,
.
7. Remove the black rubber grommet from the underside of the gas valve, where the venturi was attached.
8. Place the Propane orifice disk into the black rubber grommet, confirm the stamp on the orifice disk matches the number specified on page 2 of this manual for the boiler model being converted.
9. Replace the black rubber grommet, with the Propane orifice disk, into the gas valve pocket from which it was removed.
10. Replace the venturi, being careful that the grommet and gask venturi is secured.
11. Reinstall and tighten the 2 Phillips screws that secure the venturi to the blower.
Reinstall and tighten the 3 Phillips scre
12. the venturi to the gas valve.
Affix the Propane conv
13. rating plate.
14. If the boiler is in the process of being installed, it is best to check the combustion and make any necessary adjustments before replacing the blower box cover. See page 36 of this manual. If the boiler installation is to occur at a future time, the blower box cover and jacket front cover can now be reinstalled, and the combustion
k should be perf
chec
ept in the proper positions until the
et are k
ersion label next to the boiler
med after the boiler is installed.
or
ws that secure
6. Remove the venturi, taking note of the position of the gasket behind it, for reassembly purposes.
Page 44
©Slant/Fin Corp. 2008.
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
AX: (516) 484-5921
F
Canada:
Slant/Fin
TD/LTEE
L
, Mississauga, Ontar
www.slantfin.com
io
Loading...