SkyLink TS-101 User Manual

Temperature Sensor
C/F
C/F
Model TS-101
1. INTRODUCTION
The Temperature Sensor is designed to monitor the temperature of a specific area, whether that is the indoor temperature or outdoor temperature. It works in conjunction with the AAA+TM Control Panel, as well as other Skylink’s alarm system such as SC-001 or AD-433S etc. When the actual temperature exceeds the preset limit, the control panel will either alert you or alarm will be triggered.
In this package, you should find the temperature sensor, 2 lithium batteries, an external measuring probe for measuring outdoor temperature and mounting accessories.
External
Temperature Sensor (Batteries inside)
2 pcs
3.5 x 20 screws
Please follow the instructions below to set up the temperature sensor.
2. LEARN SENSOR TO AAA+TM CONTROL PANEL
In order for the sensor to communicate with the control panel properly, the sensor must be programmed to the control panel. Follow the brief instructions below or refer to the detail instructions from the AAA+ User’s Instructions to program the sensor to the control panel. Before proceeding, please remove the battery isolator from the sensor.
Step Keys Function Description Note
1
2
3
4
[PROG] [MPIN]
[3]
[0] to [9]
Activate the sensor by pressing the red “Panic” button on the temperature sensor.
Enter Program­ming mode
Select learn sensor programming
Select sensor location
Activate sensor
®
measuring probe
Enter master password to programming mode
Refer to the dia­gram below to select the sensor location, which includes the zone and sensor number.
Once the sensor is activated, the signal will be trans­mitted to the Con­trol Panel which will be stored.
External dry contact cable
TM
3 beeps for valid password. 1 long beep for invalid password.
After [3] is entered, some zone LEDs will flash once, or twice, some will be off. The zone LEDs represent whether that zone is already occupied by another sensor. **See Table A below.
After you have selected the zone, that zone LED will be on.
You will hear [Zone X Sensor Y Accepted], where X and Y are the zone and sensor numbers you have selected.
This row : Buttons for Sensor 1
Zone LED : Flash once
This row : Buttons for Sensor 2
Zone LED : Flash twice
2. LEARN SENSOR TO AAA+TM CONTROL PANEL (CONT)
ZONE LED DESCRIPTION
Off Zone is not occupied by any sensor Flashes once This zone is occupied by sensor 1. Flashes twice This zone is occupied by sensor 2. Flashes once, then twice This zone is occupied by sensors 1 and 2.
** Table A: Zone LED status for learning sensors.
3. LEARN SENSOR TO SC-001, AA-433 AND AD-433S
To program the temperature sensor to other Skylink’s receivers, such as SC-001, AA-433, AD-433S etc, please follow the instructions below:
1) Activate the programming mode of your Skylink’s receiver (refer to the owner’s instructions of your Skylink’s receiver)
2) To transmit the signal from the temperature sensor, press the red button (panic button) on the temperature sensor.
3) Follow the rest of the instructions from the Skylink’s receiver to complete the programming procedure.
4. PROGRAMMING
There are several things you need to program:
1) Clock
2) Upper temperature limit
3) Lower temperature limit
4) Set the temperature unit (Fahrenheit / Celsius)
Clock
The current time will be displayed when the “HOUR” or “MIN” button is pressed.
To set the hour:
1. Press and hold the “HOUR” button.
2. Whiling holding on to the “HOUR” button, press “UP” or “DOWN” to select the hour.
3. Release all buttons after setting the hour.
To set the minute:
1. Press and hold the “MIN” button.
2. Whiling holding on to the “MIN” button, press “UP” or “DOWN” to select the minute.
3. Release all buttons after setting the minute.
Upper Temperature Limit
When the actual temperature is above the upper temperature limit, the temperature sensor will send a signal to the control panel. To set the upper temperature limit:
1. Press and hold the “HI” button.
2. Whiling holding on to the “HI” button, press “UP” or “DOWN” to select the upper temperature limit.
3. Release all buttons after setting the upper temperature limit.
Lower Temperature Limit
When the actual temperature is below the lower temperature limit, the temperature sensor will send a signal to the control panel. To set the lower temperature limit:
1. Press and hold the “LO” button.
2. Whiling holding on to the “LO” button, press “UP” or “DOWN” to select the lower temperature limit.
3. Release all buttons after setting the lower temperature limit.
Set the temperature unit (Fahrenheit / Celsius)
The temperature sensor can operate and display temperature in Fahrenheit or
Remove back cover
Celsius. To select the desire unit, open the back cover you will see a jumper connector for “C/F” as shown below. To select Fahrenheit, place a jumper on this “C/F” connector. To select Celsius, remove the jumper from this connector.
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
SENSOR 1 Button [1]
Button [2] Button [3] Button [4] Button [5]
SENSOR 2 Button [6]
Button [7] Button [8]
Button [9] Button [0]
Note: Each location is allowed to learn one sensor only. Learning a sensor to a location will clear the memory of the sensor previously learnt.
Fahrenheit Celsius
Note: The temperature sensor can monitor the temperature within this range: 157°F (69°C) to -3°F(-19°C).
You have now programmed the temperature sensor and you can mount the sensor to the desired location.
5. INSTALLA TION
7. SENSOR FAILURE OR LOW BA TTERY (CONT)
The temperature sensor should be mounted onto the wall by 2 screws. Follow the procedures below:
1. Use a template to mark the location for the 2 screws correctly.
2. Tighten the screws onto the wall half way.
3. Hang the temperature sensor onto the 2 screws.
Note: The temperature sensor is not designed to be used outdoor, it must be installed indoor. To monitor outdoor temperature, an external measuring probe can be used, while the temperature sensor is installed indoor.
6. OPERA TION
The temperature sensor must be enabled in order to monitor the temperature and communicate with the control panel. You may enable the upper temperature limit only, or lower temperature limit only, or both. To enable the upper or lower temperature limit, simply press “HI” or “LO”. If the display shows “HI”, that means the upper temperature limit is enabled. If the display shows “LO”, that means the lower temperature limit is enabled. If the display shows both “HI” and “LO”, that means both upper and lower temperature limits are enabled. To disable the tempera­ture limits, simply press the same button again, until the “HI” or “LO” doesn’t show up on the display.
External Temperature
If you would like to monitor the external temperature (i.e. outdoor tem­perature), you may use the external measuring probe. Plug in the external testing probe as show on the back of the sensor. Ensure to select the “EXT” on the front panel. If no external measuring probe is plugged in, but “EXT” is selected, the display will not show any temperature.
External Dry Contact (Normal Open)
External Dry Contact
You may connect the temperature sensor to other devices by the N/O dry contact. Simply plug in the cable into the socket on the back of the sensor as shown. Connect the other end of the cable to the device that you would like to con­nect to. When the temperature is
External Temperature
above or below the preset limits, the contact will be closed momentary therefore activating the connected device.
When you see the low battery indication, replace the batteries following the procedures below:
1) Remove the screw on the back of the temperature sensor as shown.
2) Rotate the battery compartment, the batteries can be removed.
3) Place the new batteries into the compartment, pay attention on the polarity, as indicated on the diagram.
4) Tighten the screw.
8. OTHER AAA+TM ACCESSORIES
The AAA+TM control panel can work with different accessories include: Garage door monitorTM sensor, Indoor/outdoor motion sensor, Audio sensor, Remote control, Audio Alarm, etc. Please visit www.skylinkhome.com or contact us at support@skylinkhome.com for more information of how to fully utilize your Temperature Sensor.
9. FCC
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
WARNING:
Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
NOTE:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful inter­ference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment dose cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
The maximum ratings of the N/O relay contact is 2A / 24V DC, therefore do not connect an external device which exceeds this rating. The relay contact is not designed for AC connection, DO NOT CONNECT AC DEVICE TO THIS N/O CONTACT.
7. SENSOR FAILURE OR LOW BATTERY
Sensor Failure
The control panel constantly monitors its sensors, if the control panel fails to communicate with any sensors, it will notify the user by:
1. The zone LED of the failed sensor will be on steadily;
2. Voice announcement “zone X sensor Y failure” will be played. When sensor failure occurs, try the following:
1. Check if the sensor is located at where it should be, and whether there is any physical damage to the sensor.
2. If the failed sensor is not physically damaged, try to activate the sensor and see if the control panel reacts to such activation.
3. If not, try to remove the sensor from its location, and bring it closer to control panel and activate the sensor. It is possible that the sensor is installed too far from the control panel and it cannot establish a steady communication with the control panel. If this is the case, please install the sensor closer to the control panel.
Sensor Low Battery
Two CR-2032 lithium batteries are used to operate the temperature sensor. When the sensor is in low battery condition, the low battery LED indicator will be on. Temperature sensor will also send a wireless low battery signal to the AAA+TM Control Panel.
10. CE
Declaration of Conformity
This equipment complies with the requirements relating to electromagnetic compatibility, EN 301489-3:2002, EN300220-3:2000. This equipment conforms to the essential requirement of the Directive (1999/5/EC) of the European Parliament and of the Council.
11. W ARRANTY
If, within one year from date of purchase, this product should become defective (except battery), due to faulty workmanship or materials, it will be repaired or replaced, without charge. Proof of purchase and a Return Authorization are required.
12. CUSTOMER SERVICE
If you would like to order Skylink’s products or have difficulty getting them to work, please :
1. visit our FAQ section at www.skylinkhome.com, or
2. email us at support@skylinkhome.com, or
3. call our toll free at 1-800-304-1187 from Monday to Friday, 9 am to 5 pm EST. Fax (800) 286-1320
CUSTOMER SERVICE
17 Sheard Avenue, Brampton, Ontario, Canada L6Y 1J3 Email:support@skylinkhome.com http://www.skylinkhome.com
P/N. 101Z468 US Patent. 6243000B1 ©2007 SKYLINK GROUP
Loading...