Look at the climatology of the location to establish the duration of 0oC to
+4oC. Don’t just look at the extreme temps, look at the mean overnight
temp and duration
•
If the ambient air temp rarely dips below +4oC or does so for short
periods then you can use this simple calculation...
3.3 x electricity input kW = output kW.
•
If the mean overnight ambient air temp is between 0oC and +4oC change
the calculation to 2.5 x electricity input kW = output kW
•
Skyline Energy will not warranty a heat-pump that has been undersized
for its application.
Foundations & Drainage
1/ When siting the heatpump at ground level, the simplest method of
mounting the heatpump is to use 2 or 3 concrete house stumps lying on
their sides
2/ If a slab has been prepared, it is still best to use the stumps to raise the
unit above the ground.
3/ There are many drain holes directly under the unit.
4/ Heatpumps generate a large amount of condensate. If placed over gravel
or earth the condensate will drain away, but if the unit is placed over a
paved area additional drainage will be required to deal with condensate.
5/ The buffertank however can be placed directly on a paved area or paving
slab.
6/ If you are concerned about airflow due to installation in a pathway etc...
Try mounting the heat-pump about 1 meter high on wall brackets, this
will allow the cold air to fall away from the unit.
Water flow-rate in the primary circuit:
Before anything else you MUST plan to achieve the required water flow rate in
the primary circuit between the heatpump and buffertank.
Adequate water flow-rate is critical to achieve maximum efficiency.
(Just because a unit is heating does not mean its running efficiently)
Avoid restrictive plumbing. Use large diameter pipes for the primary flow and
return, and limit elbows and sharp bends.
The temperature rise across the heatpump inlet and outlet ports is directly
proportional to the water flow-rate.
Generally, the lower the temp rise = higher flow rate = higher efficiency
Use enquiry code “A5” and “A6” to read the temperature rise which should be
4oC or lower for all models.
Airflow:
1/ In general, all Skyline Energy single-compressor hydrocarbon hydronic
heatpumps require clearance on all sides.
2/ If possible, do not place large objects within 2 meters in front of the
fans. If this is not possible, the heatpump should be sited for example,
at the corner of a building where there is good airflow potential around
the corner.
3/ Fresh air flow is critical... You must avoid the possibility of waste cold air
back-feeding to the unit and driving down its efficiency.
4/ Do not place trellis in front of the fans... If the unit must be hidden, then
it is best to use louvers.
5/ Do not place the unit under the building, in a garage, or any other
confined space.
Buffertanks:
Skyline Energy 200Lt 3-zone buffertank dimensions April 2019
Buffertanks: (continued)
Skyline Energy 200Lt 2-zone buffertank dimensions April 2019
Buffertanks: (continued)
Skyline Energy 100Lt 2-zone buffertank dimensions April 2019
Electrical install notes:
1/ Room thermostat wiring to be 1.0mm or 1.5mm TPS.
2/ Room thermostats to be placed in a horizontal wall plate @ 1500mm
above floor level.
3/ Locate room thermostats away from heat sources e.g. ovens, radiators,
aircons or sunlight.
4/ The minimum capacity circuit breaker is as per the table, but be aware of
higher than normal grid voltage that can make the units draw more
current than posted. If circulation pumps are on the same circuit, they
will add to the load.
5/ Power supply is to be connected to the enclosure with the 2 pole RCD
6/ Thermostats to be connected their relevant test switch.
7/ Although the control panel indicates a Flow-switch is installed, there is
no flow-switch and its input is bridged-out.
8/ The “Stat test” switch is provided to bridge-out the room themostats
during commissioning and testing... Holding the stat test switch closed
for about 15 seconds will energise the controller and energise the latch
relay if the buffertank water temperature is lower than the programmed
start up temperature.
9/ Latest models have GPOs fitted for the pumps
10/ The buffertank water temperature sensor MUST be pushed to the
bottom of the sensor-well or it will read low. Best to fill the back of the
gland with foam to make sure the cable is clamped... Be aware that
sensors tend to migrate out of the sensor-well if not secured in firmly.
Skyline Energy SX-13CCZA hydrocarbon hydronic heatpump performance graph
• kW input and output, and amps are rated at 230 volt... Higher
supply voltages can drive the imput current a lot higher than
specified.
• * Circulation pump loads are not included in kW input ranges,
however an allowance for these loads has been made in circuit
size recommendations
• *Specifications are subject to change without notice – contact
Skyline Energy for support.
Real World Testing:
Unlike most heat-pump manufacturers, we test every unit in the ambient
temperature range where they are really meant to operate.
We test and fine-tune EVERY unit prior to dispatch and ensure that it’s C.O.P. is
as high as possible.
Claims by others of C.O.P.’s of 4 or 5, may be correct in a lab with a standard
test condition of 20oC ambient and a water temp of 15oC, but the C.O.P.’s of
these units will be much lower at lower ambient air temperature and higher
starting/returning water temperatures.
Most other brands of heatpumps are set-up specifically for pool heating or
potable hot water heating under a variety of climatic conditions. Our
heatpumps are set-up specifically for hydronic and are fine-tuned to operate
specifically between 35oC to 55oC water temperature, and -5oC to +15oC
ambient air temperature.
Sound level – locating the heatpump:
1/ High capacity heatpumps can create relatively high noise, so please be
considerate of neighbours when locating the heatpump. A good location
would be behind a solid barrier such as a shed, garage, water tank etc...
2/ Do not site a sidedraft unit with its fans facing toward close neighbours.
3/ Sound will dissipate more rapidly the higher the unit is installed. On a
steeply sloping property, uphill is better than downhill.
4/ The buffertank can be installed right next to the heatpump, or 40meters
or more away. The primary flow & return lines to and from the
buffertank should be well insulated to ensure minimal heatloss. Ensure
the correct water flowrate is maintained and a booster-pump, and
possibly larger diameter pipe may be necessary to overcome friction
loss. Flowrate is critical to efficiency and must be kept within specs.
5/ Placing the heatpump close to a carport or veranda can amplify sound
level.
6/ Skyline Energy will not be responsible for poor placement of heatpumps
that create noise problems.
Configurations:
1/ The heatpump and buffertank can be sited side-by-side or the heatpump
located 50 or more metres from the buffertank, but in all cases the
primary flow and return water pipes should be of adequate size, and the
primary circulation pump of adequate size to provide the required water
flow rate.
2/ The primary flow and return water pipes should be well insulated, and if
trenched they must be sealed inside an outer casing such as flexible
unslotted drainage pipe, or stormwater pipe to keep the insulation dry
and minimise heat-loss.
3/ The primary water circulation pump can be placed at the tank or
heatpump, and in some models they may be installed inside the
heatpump cabinet.
4/ Heatpump control systems are usually fixed to the cabinet, but systems
can be ordered for remote location such as a plantroom.
5/ Multi-zoned systems with multiple zone connections to the buffertank,
should always have the buffertank placed as close as possible to a
floorcoil manifold, radiator manifold etc. Only single zoned systems may
have the buffertank placed remotely from the manifold/radiator system.
6/ The expansion tank sub-system (pressure gauge, pressure relief valve,
cold-fill valve etc.) can be placed anywhere in the system, but more
commonly fitted close to the buffertank.
7/ Buffertanks, all circulation pumps, expansion sub-systems etc, should all
be installed sheltered from the weather if possible, to minimise heat-loss
and increase service life. (They can be installed fully exposed to weather
but it is best practice to maximise efficiency.)
8/ Heatpumps must be installed where continuous fresh air is available,
generally they should not be in any enclosed space. If this can not be
avoided, then clean airflow is required through ductwork, or at the very
least through unobscured mesh or louvered wall/enclosure.
Typical installation diagram:
Bleeding and Buffertank
:
1/ The most common failure at commissioning is created by excess air, an
air blockage causing no water flow.
2/ If the compressor shuts down about 20 seconds after starting
95% CHANCE, YOU HAVE AN AIR-LOCK
3/ After initial commissioning, the auto air bleed valve on the top of the
tank should expel most of the air.
4/ Other places for bleeding are the floorcoil manifolds, radiators, and the
big Silver screws on the pumps.
5/ It is good practice to place an auto air bleed valve at any high points in
the plumbing.
Onsite-testing heatpump output:
1/ There is an onsite test to prove the efficiency of the system, measuring
the time it takes for the buffertank to heat. This test will always give a
slightly lower result because of the losses that will be in any buffertank
system. Our test rig has so much plumbing, pumps, valves, flow meter
with minimal insulation that the tank warm-up calculation provides a
result typically 20% less that the standard skyline test across the heat
exchanger.
2/ How to do a site test
a/ Load the system without running the heatpump to get the
buffertank water temperature down to about 35oC. Can do this by
pressing the power key to stop the heatpump operating, and then
increase the room thermostat to call for heat.
b/ When the buffertank water temperature is down to about 35oC
Press the power key on the heat-pump to display the heat icon.
c/ Turn off the room thermostat.
d/ Close the zone valve(s) to isolate the load (house) from the
buffertank as the primary water flow and return circuit circulation
pump will tend to push water through the zones and add extra
load.
e/ Now there is known heatload, equivalent to the capacity of the
buffertank + primary plumbing + heat pump. (Typically about 10Lt
more than the capacity of the buffertank)
f/ Time the duration for the water in the buffertank to rise by 10oC
g/ After the test, remember to OPEN THE ZONE VALVE(S).
Onsite-testing heatpump output - continued:
Formula to Calculate Kilojoules;
4816 x LOAD x RISE / 1000/60/TIME = kW OUTPUT
LOAD = Tank capacity plus plumbing
TIME = Duration of test
RISE = 10C
4186 x 210 x10/1000 = 8790kj
EXAMPLE:
200Lt buffertank +10Lt plumbing, LOAD = 210
Temperature rise was 10C, RISE= 10
4186 x 210 x10/1000 = 8790kj
Conversion kj to kW;
Stopwatch says it took 15 minutes, TIME= 15
8790/60/15 = 9.77kW output
Shut off valve... Dual check valve... Auto fill valve...
typical
Operation:
1/ The system is primarily driven from the room thermostat(s).
2/ Room thermostat(s) directly controls the zone circulation pump(s) and
may kickstart the buffertank controller.
3/ Zone pump delivers water to the floorcoils or radiators.
4/ When the room thermostat(s) call for heat, the buffertank controller
fires-up and will make a decision based on the buffertank water
temperature, to energize the primary circulation pump and start the
heatpump.
5/ The buffertank controller will stay latched ON once a decision to start
the heatpump has been made. The buffertank controller will only stop
the heatpump after the buffertank water temperature has reached its
set temperature, regardless of the room thermostat turning on or off.
6/ The room thermostat cannot stop the heatpump, it can only start the
heatpump when the buffertank water temperature is lower than the set
temperature differential.
7/ The “latching” procedure described above is designed to prevent the
heat-pump “short-cycling” when a room thermostat turns off and on
rapidly.
8/ The “test” switch provided next to the controllers is a simple bridge
across the room thermostat. It will only do what the room thermostat
will do and is used for convenient commissioning and fault-finding.
9/
Important. The system will not operate unless the
“power” button on the controller needs has been
pushed, state is ON, and the “water heat” icon is
displayed.
Part 1: Operating panel introduction
1. Display interface
2. Buttons function
↓↓↓↓
↓↓↓↓
↓↓↓↓
↓↓↓↓
↓↓↓↓
Clock M + - power
2.1 “Power” button
● Press and hold the Power button for 1 second to turn ON and turn OFF (change State to ON
Off) the heatpump. (water heat icon is displayed when ON)
● Press the Power button at any time to quickly exit to home screen .
● Press and hold the Power button for 5 seconds to unlock other buttons.
2.2 “M” button
● Under main interface, press the “M” button to query the working status parameters
2.3 “+”and “-“ buttons
● Press the “+” and “-“ buttons to navigate through the query parameters and pages, and to
change the setting values when in the settings interface.
● Combine the “M” and the “+” and “-“ buttons to query and set parameters
● When the heatpump is ON and the water heat icon is displayed, press the “+” and “-“
buttons to change the “set” water temperature
2.4 “clock” button
● Press the “clock” button for 10seconds to enter the clock setting interface
● Press the “clock” button to enter the timer ON/OFF setting, and combine with the “+” and
“-“ buttons to set the timer.
3. Operating
3.1 Parameters query and setting
①①①①
Working status parameters query
To enter the working status query section, press the “M” button, and scroll through the
parameter settings display.
Working status parameters (table 1)
Code Parameter
No code Water tank temp (oC)
A1 Air heat exchanger1 lowest tube temp (oC)
A2 Inlet gas temperature of compressor 1 (oC)
A3 Outlet gas temperature of compressor 1 (oC)
A4 Ambient air temperature (oC)
A5 Outlet water temperature (oC)
A6 Inlet/return water temperature (oC)
A7 Reserved
A8 Compressor 1 current (Amps)
A9 Electric expansion valve 1 open degree
A10 Reserved
B1 Air heat exchanger 2 lowest tube temp (oC)
B2 Inlet gas temperature of compressor 2 (oC)
B3 Outlet gas temperature of compressor 2 (oC)
B8 Compressor 2 current (Amps)
B9 Electric expansion valve 2 open degree
C1 Reserved
E6
E1
~
History error code
Error code (table2)
(NOT USED)
Error code Parameter
Er01 Wrong phase error
Er02
Er03
Er05
Er06
Er07
Er08
Er09
Er11
Er12
Er13
Er15
Er16
Er17
Er18
Er19
Lack phase error
Water flow switch error
Outlet gas pressure of compressor 1 is too high error
Inlet gas pressure of compressor 1 is too low error
Outlet gas pressure of compressor2 is too high error
Inlet gas pressure of compressor 2 is too low error
Communication error
Time limit for locking heatpump reached
Outlet gas temp of compressor 1 too high error
Outlet gas temp of compressor 2 too high error
Buffertank temp sensor error
Air heat exchanger 1 lowest tube temp sensor error
Air heat exchanger 2 lowest tube temp sensor error
Outlet gas temp sensor of compressor 1 error
Outlet gas temp sensor of compressor 2 error
Er21
Er22
Er25
Er27
Er29
Er30
Er35
Er36
Er44 Ambient temp too low protection
Er45 Outlet water temp too high error
Ambient air temp sensor error
Return water temp sensor error of water tank
Water level switch error
Outlet water temp sensor error
Inlet gas temp sensor of compressor 1 error
Inlet gas temp sensor of compressor 2 error
Compressor 1 current too high error
Compressor 2 current too high error
②②②②
User parameters query and setting (works in both ON and OFF state)
To enter the USER parameters query and settings interface:
◆
Under the main interface, press and hold the “M” button for 3seconds, then press
“+”and “-“ buttons, to scroll through settings.
◆
To change a setting, enter the interface as described above, navigate to the parameter you
want to change, press the “M” button again, and press “+”and “-“ buttons to increase or
decrease the value, then press the “M” button again to save the new setting and return to the
query interface.
◆
Under USER parameters query interface and setting interface, if there is no button press
for 30 seconds the system will automatically quit user parameter query or setting interface,
and return to main interface, (you can also press “Power” button to immediately return to
the main interface also)
USER parameters query and setting (table 3)
Code Meaning Setting range Factory setting
20
℃
~
℃
~25℃
℃
℃
℃
F1
~
F1
~25℃
~60℃
5℃
/// Buffertank water temp setting
L2 Compressor restart temperature drop 2
L3
L4 Reserved
L5
L6
L7
Preset buffertank water temperature
of heating mode
Ambient air temperature below
which electric heater is allowed to
start (NOT USED)
Return water temperature from
buffertank
Buffertank temperature below which
allow to compensate cool water
value
30
value
-25
20oC~65℃
20
55℃ (SET at the main interface)
55℃
NOT USED
20℃ (20℃: compensate cool water
is not limited by water tank
temperature)
L8 Compressor current
L9 Reserved
0~40A 0(0: will not detect current)
③③③③
Factory parameters query and setting (works in both ON and OFF state)
To enter the FACTORY parameters query and settings interface:
◆
Under main interface, press “Power” button and “+” button at the same time for 3
seconds, enter factory parameters password interface, will display “0.0.0.0”, press “clock”
button, to jump between the four figures of password, press “+” or “-“ buttons, to change
the value the four figures, their value should be “0.8.1.4”, then press “M” button to confirm
password, if password is correct, will enter factory parameter query interface
◆
At factory parameter query interface, press “M” button to enter current parameter setting
state, press “+” or “-“ buttons to change current parameter value, then press “M” button, to
return to query state.
◆
At factory parameter query interface and setting interface if there is no button press for
30 seconds the system will automatically quit FACTORY parameter query or setting
interface, and return to main interface, (you can also press “Power” button to immediately
return to the main interface also)
℃
FACTORY parameters query and setting (table 4)
Code Meaning Setting range
Ambient air temperature below
H2
H3 Defrost period setting
H4
H5 Longest defrosting time setting
H6
H7
H8
P1
P2 Target superheat temp setting
P3
P4
P5 Min open degree of EEV
P6
P7 EEV step by manual
F1
F2
F3
F4
F5
F6
F7 Reserved
F8
Remarks: F4 only valid for cascade connection way.
which heat pump will stop
working to protect
Air HE lowest tube temp below
which system will enter defrost
Air HE lowest tube temp above
which system will quit defrost
The temp difference between
ambient temp and air HE lowest
tube temp higher than which
system will enter defrost
Ambient temp below which
system will enter defrost
Action period setting of electric
expansion valve
Outlet gas temp at which EEV
will adjust to keep the temp
EEV open degree when
defrosting
EEV choice for automatically and
manually
Upper limit of water tank temp
setting
Circulating water pump choice
when only electric heater
working
Temp difference of displaying
temp and real temp of water tank
Water flow switch installing way
choice
Water pump working state when
heat pump standby
Outlet water temp too high
protection at heating mode
Outlet gas temp setting for too
high protection
-30℃~0℃-10℃
20min
90min
-15℃~ -1℃-3℃
5min ~20min
1℃~40℃13℃
0℃~+15℃2℃
0 ~ 20℃10℃
20s ~90s
-5℃~10℃4℃
80℃~110℃95℃
2 ~50
2 ~ 30
0(manual
\1(auto)
2~45
30℃~90℃60℃
0/1 1
-5℃~15℃2℃
0 /1 0
0/1 1
35℃~85℃62℃
100
~
~
126℃
Factory
setting
55min
8min
30s
50
12
)
1
35
115℃
Remarks
0:work/1:not work
0:independent/1
share
0: non-stop
1: stop
:
④④④④
Time limit setting
To enter the time limit setting parameters query and settings interface, the process is same
as factory parameter query and setting, password is “8.5.6.3”
Time limit query and setting (table 5)
Code
FF
Limited weeks after which heat pump will
3.2 Other operation
①①①①
Clock setting
◆
At main interface, press “clock” button for 5 seconds, enter clock setting interface
◆
At clock interface, press “clock” button, then “hour” flash, press “+”or “-”button,can
set hour.
◆
After finish setting hour, press “clock” button, then “minute” flash, now press “+”or“-
Meaning
not allowed work
Setting
range
0~99
Initial
value
0
Remarks
The unit is “week”
“0”means not time
limited
”button,can set minute.
◆
After finish setting minute, press “clock” button, to confirm clock setting, and back to
main interface.
◆
At clock setting interface, if there is not operation within 30seconds, system will
confirm clock setting and back to main interface automatically.
◆
At clock setting interface, press “power” button, can confirm current clock setting and
back to main interface.
②②②②
Timer setting and cancelling (ON/OFF timer)
◆
At main interface, press “clock” button, enter timer group setting.
Now press “+”or“-”button, can switch timer groups, there are 4 groups ON/OFF timer.
◆
When group 1 ON timer flashing, press “clock” button, enter group 1 ON timer “hour”
setting interface, “hour” flash, then press “+”or“-”button,then can set “hour” for group 1
ON timer.
◆
After finish setting “hour”, press “clock” button, then “minute” flash, then press “+”or“-
”button,can set “minute” for group 1 timer.
◆
After finish setting group 1 ON timer “minute”, press “clock” button, enter group 1 OFF
timer setting, same way like ON timer setting..
◆
After finish setting group 1 ON/OFF timer, press “clock” button, confirm group 1
setting, and enter group 2 ON/OFF timer setting, same way like group 1 setting.
◆
At timer interface, if there is not operation within 30seconds, then confirm current timer
setting, and back to main interface (this setting can be remembered if electricity is cut off)
◆
At timer interface, press “clock” button, confirm current timer setting, and back to main
interface.
◆
Other groups ON/OFF timer setting are same way like group1.
◆
Remarks: 1 and 2 timers are heat pump ON/OFF timer, 3 timer is for return water, 4
timer is for compensating cool water.
◆
How to cancel timer?
At timer interface, press “clock” button for 5seconds, when the ON and OFF signal
disappear, then press “power” button to confirm, can cancel current group ON/OFF timer.
③③③③
Lock keys and unlock keys
◆
At locking state, press “power” button for 3seconds, buzzer will give a voice of “Di”,
keys will be locked.
◆
If there is not operation within 60seconds constantly, will lock keys automatically.
④④④④
Forced defrosting
◆
At ON status, press “-”for 3seconds, enter forced defrost.
◆
To quit forced defrost, there are two ways.
a. Automatic quitting: when defrost time reach H5 setting, can quit forced defrost.
b. Forced quitting: Press “power”button,after power off, 3minutes later, will quit forced
defrost completely.
⑤⑤⑤⑤Remove history error code
At the interface of query history error code, press “power” and “M” button together for
5seconds, can remove all the history error code.
⑥⑥⑥⑥One-click restore function
Under power off status, press “power” and “-“ button together for 5seconds, can restore
factory setting.
Part 2. Working modes:
1. Heating mode
◆
Water tank temp ≤ Water tank preset temp L3-Compressor restart temp drop setting L2, start
to heat.
◆
Water tank temp ≥ water tank preset temp L3, stop heating.
2. Defrost mode
2.1 Conditions of entering defrost when heating
◆
Ambient temp≤H8 value,and air heat exchanger lowest tube temp≤H4 value, and lasts for
≥ 3min;
◆
Compressor total working time≥H2 value,and lasts for≥5min
◆
(Ambient temp - Air heat exchanger lowest tube temp)≥preset temp H7,and lasts for
more than 30sec.
When heating, when all of above conditions are met, system will enter defrost.
2.2 Conditions of quitting defrost when heating
When air heat exchanger lowest tube temp>H6 value, or defrosting time reach H5, system
quit defrost.
::::
::::
::::
2.3 Defrost running
①When defrost entering conditions are met, will work as below:
◆
Compressor and fan motor stop working.
◆
At 30sec, four way valve get electricity, electric heater start.
◆
At 60sec, compressor starts.
②When defrost quitting conditions are met, will work as below:
◆
Compressor stop working
::::
◆
At 55sec, four way valve losses electricity, electric heater stop working (according to
electric heater controlling logistic to judge if electric heater continues to work)
◆
At 60sec, fan motor starts.
◆
At 65sec, compressor start, recover normal heating mode.
◆
Compressor total working time will be reset, and re-timing.
2.4 Quit defrost abnormally
◆
Turn off heat pump when defrosting, system will quit defrost at once first, then heat
pump stop working.
◆
There are error happen and heat pump stop working to protect when defrosting, system
will quit defrost at once, and stop working.
◆
When defrosting, system doesn’t detect low pressure protection.
::::
Part 3. Each electrical component controlling
1. Compressor
◆
Compressor start / stop according to hot water tank real temperature and preset temp.
◆
After compressor stops, should need at least 3min, then it can restart again.
◆
After compressor start, should work at least 2min first, then can stop. (Except turned off or
there is error).
◆
There is not 3min protection for the first time starting.
2. Four - way valve
◆
When heating, 4-way valve lose electricity.
◆
Four way valve delay 2min to change direction after compressor stop.
◆
When defrosting and forced defrosting, 4-way valve get electricity, refer to defrosting
process.
3. Circulating water pump
◆
When system request power on, water pump start at once;
◆
When system request power off,water pump delay 30s to stop after compressor stop;
◆
When defrost, water pump doesn’t stop.
4. Fan motor
◆
after water pump worked for 30s, fan motor start;When heat pump powers off, fan motor and
compressor stop at the same time.
◆
When defrosting, fan motor doesn’t work, refer to defrosting process.
5. Auxiliary electric heater
5.1 Starting conditions:
◆
At heating mode
◆
Ambient temperature ≤ L5 setting.
◆
Water tank temperature < water tank preset temperature - L2.
◆
Low level switch connects.
When all of above conditions are met, electric heater starts.
5.2 Stopping conditions:
◆
Water tank temp ≥ water tank preset temp when heating.
◆
Water tank temp sensor damaged and controller show error code.
◆
Ambient temp ≥ parameter L5+2℃;
◆
Water level switch has error
◆
Low level switch disconnects
Any of above condition is met, electric heater stops.
5.3 When defrosting, forced defrosting, secondary anti-freeze, electric heater is forced to start.
5.4 Except there is water level error, hot water tank temp sensor error, when there is other temp
error, high and low pressure error protection, electric heater will start.
6. Return water vale (When L6=20℃℃℃℃, return water function is invalid)
6.1 Condition of return water valve open (should met at the same time):
◆
Low water level switch connects
◆
Water tank temp ≥ preset return water temp L6 + 5
◆
Return water temp ≤ L6 – 5
6.2 Condition of return water valve close (meet any below condition):
◆
Low water level switch disconnects
◆
Water tank temp < preset return water temp L6 + 5
◆
Return water temp > L6
7. Cool water compensating valve
7.1 After compensate cool water manually, before high water level switch connects, the cool
water compensating valve opens all the time, until high water level switch connects, this valve
will recover normal controlling function.
7.2 When select there is not cool water compensating timer, system can compensate cool water at
any time.
7.3 When select there is cool water compensating timer, system can compensate cool water only
in cool water compensating timer period.
7.4 Cool water compensating controlling as below:
①When low water level switch is disconnecting, cool water compensating valve open.
②When low water level switch connects, and high level switch disconnects, according to
below work.
◆
Water tank temp ≥ preset cool water compensating temp L7, cool water compensating
valve open to compensate.
◆
When water tank temp ≤ preset cool water compensating temp L7-5,cool water
compensating valve close.
③When high water level switch connects, cool water compensating valve closes.
④When heat pump is under off state, cool water compensating valve is not allowed to pen,
⑤When defrost, cool water compensating valve is forced to close.
8. Electric expansion valve
Because of electric expansion valve working is very complicated, here will not descript how it
working.
Part 4. Error and protections
1. Communication error and protection
◆
Within 20seconds at the first time power on heat pump, if PC board can’t get signal from
operating panel all the time, operating panel can’t exit from whole show. PCB will not conduct,
system will work according to “the last time working status parameters that operating panel
input” only.
◆
In the process of power on, if operating panel can’t get signal from PC board constantly for
10seconds, system will judge this communication error, and display Er:09, heat pump work
according to former preset temperature, when communication recover, Er:09 will disappear.
2.Three phase protection
When power on, system will check the three phase live line, if there is wrong phase or lack of
phase, system will enter phase protection, and turn off all output and display error code, only
after remove error and re-supply electricity, system will back to normal work.
3. Ambient air temperature sensor error
◆
After heat pump power on, if detect ambient temperature sensor is short circuit or open circuit,
system will judge ambient temperature sensor error, heat pump continue to work.
◆
When this error happens, relative anti-freeze condition will be invalid.
◆
This error can recover automatically.
((((
only valid for 3phase heat pump
))))
◆
When this error happen, operating panel will alarm, and display Er:21.
4. Water tank temperature sensor error
◆
After heat pump power on, if detect hot water tank temperature sensor is short circuit or open
circuit, system will judge hot water tank temperature sensor error, heat pump will stop working.
◆
This error can recover automatically.
◆
When this error happen, operating panel will alarm, and display Er:15.
5. Outlet water temperature sensor error
◆
After heat pump power on, if detect outlet water temperature sensor is short circuit or open
circuit, system will judge outlet water temperature sensor error, heat pump will stop working.
◆
When this error happens, relative anti-freeze condition will be invalid.
◆
This error can recover automatically.
◆
When this error happen, operating panel will alarm, and display Er:27.
6. Return water temperature sensor error
◆
After heat pump power on, if detect return water temperature sensor is short circuit or open
circuit, system will judge return water temperature sensor error, heat pump will continue to work.
◆
When this error happens, return water function will be invalid.
◆
This error can recover automatically.
◆
When this error happen, operating panel will alarm, and display Er:22.
Remarks:
Return water temp sensor is water tank return water temp sensor from hot water system.
7. Air heat exchanger lowest tube temperature sensor error
◆
After heat pump power on, if detect air heat exchanger lowest tube temperature sensor of is
short circuit or open circuit, system will judge air heat exchanger lowest tube temperature sensor
error, heat pump will continue to work.
◆
When this error happens, electric expansion valve controlling will be changed to by manual.
◆
This error can recover automatically. Defrost will be only according to time (defrost period
according to H3)
◆
When this error happen, operating panel will alarm, system 1 display Er:16, system 2 display
Er:17.
8. Inlet gas temperature sensor error
◆
After heat pump power on, if detect inlet gas temperature sensor is short circuit or open
circuit, system will judge inlet gas temperature sensor error, heat pump will continue to work.
◆
When this error happens, electric expansion valve controlling will be changed to by manual.
◆
This error can recover automatically.
◆
When this error happen, operating panel will alarm, system 1 display Er:29, system 2 display
Er:30.
9. Outlet gas temperature sensor error
◆
After heat pump power on, if detect outlet gas temperature sensor is short circuit or open
circuit, system will judge outlet gas temperature sensor error, heat pump will stop working.
◆
This error can recover automatically.
◆
When this error happen, operating panel will alarm, system 1 display Er:18, system 2 display
Er:19.
10. Outlet gas pressure is too high protection
◆
When standby, detect outlet gas pressure switch, if disconnects, system will enter high
pressure protection, and heat pump stop working to protect.
◆
When working, if detect outlet gas pressure switch disconnects for 10seconds, system will
enter high pressure protection, and heat pump stop working.
◆
If this problem happen 3times within 30minutes, system will not recover normal working
unless cut off electricity (the first two times can recover automatically)
◆
When this error happen, operating panel will alarm, and system 1 display Er:05, system 2
display Er:07
11. Inlet gas pressure is too low protection
◆
When standby, detect inlet gas pressure switch, if disconnects, system will enter low pressure
protection, and heat pump stop working to protect.
◆
After compressor has started for 3min, if detect inlet gas pressure switch disconnects for
10seconds, system will enter low pressure protection, and heat pump stop working.
◆
If this problem happen 3times within 30minutes, system will not recover normal working
unless cut off electricity (the first two times can recover automatically)
◆
When this error happen, operating panel will alarm, and system 1 display Er:06, system 2
display Er:08.
12. Outlet gas temperature is too high protection
◆
1 minute after compressor start, detect outlet gas temperature, if the temperature ≥115℃
constantly for 10sec, then system will stop working to protect.
◆
When detect outlet gas temperature ≤ L10-30℃, then system quit the protection.
◆
If this error happen 3times within 30minutes, system will not recover normal working unless
cut off electricity (the first two times can recover automatically)
◆
When this error happen, operating panel will alarm, and system 1 display Er:12, system 2
display Er:13.
13. Outlet water temperature too high protection at heating mode
◆
At heating mode, after compressor has running for 5min, when detect outlet water temperature
≥62℃ (F11), then system will enter too heat protection, compressor and fan motor stop working,
water pump continue to work.
◆
When detect outlet water temperature ≤F11-5℃, then system quit the protection.
◆
When this error happen, operating panel will alarm, and display Er:45.
14 Water flow protection
◆
1 minute after circulating water pump start, detect water flow switch, if the water flow switch
disconnect constantly for 10sec, then system will stop working to protect.
◆
After this error happen, if error doesn’t recover, system will start circulating water pump to
detect water flow per 5min, when this error happen 3times constantly, system will not start
circulating water pump, until detect water flow switch connects, then will start circulating water
pump again,
◆
This error can recover automatically.
◆
When this error happen, operating panel will alarm, and display Er:03.
15. Compressor current is too small or too large protection
◆
6 seconds after compressor start, detect compressor current, if current ≤1A and lasts for 6sec,
or current ≥L8 and lasts for 6sec, system will stop working to protect.
◆
When this error happen, operating panel will alarm, and display Er:35.
16. Ambient temperature too low protection
◆
When ambient temperature <H2, compressor and fan motor will stop working. Hot water tank
electric heater will start.
◆
When this error happen, operating panel will alarm, and display Er:44.
◆
When ambient temperature >H2+2, quit the protection, compressor and fan motor start, hot
water tank electric heater will work according to normal condition.
17. Anti-freeze protection in winter
◆
Under standby or power off state, when ambient temperature <2℃, enter 1st step anti-freeze
protection, circulating water pump will start to work for 5minutes per 40min. When outlet water
temperature ≤ 4℃, circulating water pump needn’t wait for 40min, can start water pump at once.
◆
Under standby or power off state, When ambient temperature <2℃ and hot water tank
temperature ≤4℃, enter 2nd step anti-freeze protection, heat pump will start to heat. When hot
water tank temperature ≥15℃, stop heating, or when ambient temperature ≥8℃, system will quit
the 2nd step anti-freeze.
◆
At the process of anti-freeze, if detect outlet water temperature≤2℃, LCD show error code
Er:04, when detect outlet water temperature≥4℃, quit the error, this error only display, no other
function.
◆
If there is hot water tank temp sensor error, entering 1st step anti-freeze will be only according
to ambient temperature, and only 1st step anti-freeze is valid.
◆
If there is ambient temperature sensor error, enter 1st step anti-freeze protection, when hot
nd
water tank temperature ≤4℃, enter 2
step anti-freeze protection.
◆
If both ambient temperature and outlet water temperature have error, system will only enter 1st
step anti-freeze, start water pump automatically.
18. Water level switch error
◆
Under standby or power off state, if detect high water level switch connects, but low water
level switch disconnects, then judge water level switch has error, heat pump will stop working to
protect.
◆
This error can recover automatically.
◆
When this error happen, operating panel will alarm, and display Er:25.
Part 5. Other functions
1. Power-off memory function.
◆
System will memory the preset working mode and all parameters when power off.
◆
When power on again, can resume the working status and parameters setting automatically.
2. Power on / off at fixed time
◆
Fixed power on time and fixed power off time can be set.
◆
Detailed information can be consulted wired panel operating part.
3. Forced defrosting function
◆
Forced defrosting condition can be entered by operating wired panel.
◆
Detailed information can be consulted operating panel introduction.
4. Error query and memory function
◆
At query interface, when show “Er”, press “+”button or “-”button, can check history error.
◆
Error code is recorded according to time sequence.
◆
At least 6 history error codes can be recorded, and these history error codes can be
remembered even power supply is cut off.
5. Time limit setting by password
◆
Installer can set limited running time, when heat pump total running time reach preset time,
heat pump will be locked, can’t start to work anymore.
◆
Time limit setting can be removed, details can be consulted operating panel introduction.
6. Water tank temperature display correction function
◆
If F3 setting is 0, water tank temperature display correction function is invalid.
◆
If F3 setting is not 0, water tank temperature display temp = water tank real temp + F3
7. When electric heater working only, circulating water pump can be forced to start.
If F2 setting is 1, when electric heater start, circulating water pump will start 3sec in advance.
When electric heater stops, circulating water pump will delay 3sec to stop. Factory setting of F2
is 1.
8. Reserved ports on PC board
Programming port: convenient to download the site program.
Rs485 port: Open type RS485-RTU protocol port, convenient to extend system function. Such
as, add remote telephone controlling module, heat pump can be controlled by telephone. If
connect RS485 port to computer, heat pump can be controlled by controlling centre of computer.
Part 6. Details of PC board
1. DIP switch
Switch code 1 2 3 4
Off (figure side) 3phase Heating + cooling Air source Hot water
ON 1phase
Only heating Water source Swim pool
Other DIP switch
Heat pump No Switch 5 Switch 6 Switch 7 Switch 8
#1 0FF 0FF 0FF 0FF
#2 0FF 0FF 0FF 0N
#3 0FF 0FF 0N 0FF
#4 0FF 0FF 0N 0N
#5 0FF 0N 0FF 0FF
#6 0FF 0N 0FF 0N
#7 0FF 0N 0N 0FF
#8 0FF 0N 0N 0N
#9 0N 0FF 0FF 0FF
#10 0N 0FF 0FF 0N
#11 0N 0FF 0N 0FF
#12 0N 0FF 0N 0N
#13 0N 0N 0FF 0FF
#14 0N 0N 0FF 0N
#15 0N 0N 0N 0FF
#16 0N 0N 0N 0N
2. Output and input port
No Digital input Digital output Analog input Analog output
1 Water flow
switch
Water tan temperature sensor
Electric
expansion valve 1
2 High pressure
switch 1
3 High pressure
switch 2
Compressor 2 Outlet water temperature sensor
Compressor 1
air heat exchanger lowest tube
temperature sensor 2
Electric
expansion valve 2
4 Low pressure
switch 1
Electric heater
air heat exchanger lowest tube
temperature sensor 1
5 Low pressure
switch 2
6 Linkage switch Cool water
7 3phase A Inlet gas temperature sensor 1
8 3phase B Inlet gas temperature sensor 2
9 3phase C Four way valve Ambient temp sensor
10 Water pump Return water temp sensor
11 Compressor 1 current
12 Compressor2 current
Return water valve Outlet gas temperature sensor 1
compensating valve*
Outlet gas temperature sensor 2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.