SKOPE Open Deck Chiller
User Manual
MAN11106 Rev. 2.0 Nov. 2018
Page 2
Page 3
SKOPE OD460
User Manual
CONTENTS
1 Installation
Safety First . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Positioning the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Climate Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chiller Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Air Movement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Shelves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installing the Shelves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Optional Gravity Shelf System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Operation
Automatic Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Lights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Night Blind . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Loading Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Electronic Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Day and Night Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Continuous Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Temperature Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Controller Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Controller Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3 Maintenance
Isolating Electrics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Page 4
4
Installation
User Manual
SKOPE OD460
1 Installation
Safety First Always observe safety precautions when using any electrical appliance.
Read these instructions carefully and retain them for future reference.
When the appliance is used by or near young children or infirm persons,
close supervision is necessary, especially to ensure children do not play with it.
Do not use this appliance for other than its intended use.
Do not cover the grilles or block the entry or exhaust of airflow by
placing objects up against the refrigeration unit.
Do not probe any opening.
Only use this appliance with the voltage specified on the cabinet rating
label.
Ensure the chiller has adequate ventilation as this is essential to
economical, high performance.
Be careful not to touch moving parts and hot surfaces.
For your own safety and that of others, ensure that all electrical work is
done by authorised personnel.
If the power supply flexible cord becomes damaged, it must be replaced
by an authorised service agent or similarly qualified person in order to avoid a hazard.
Ensure all necessary safety precautions are observed during installation
or removal of the refrigeration unit.
The chiller is not designed to be stable while in motion. Use extreme
caution when moving or transporting it.
Do not store explosive substances such as aerosol cans with a
flammable propellant in this appliance.
Please contact SKOPE Customer Services for advice regarding
disposal of this appliance.
WARNING
Disconnect the cabinet from the mains power supply before
attempting any cleaning or maintenance.
CAUTION
Never overload the power supply, which could damage the
chiller and product. See the rating label inside the cabinet for
the safe power supply and current draw.
CAUTION
Do NOT allow liquids or any other materials to drain into the
bottom of the cabinet, as this could lead to refrigeration
system failure.
Page 5
5
SKOPE OD460
Installation
User Manual
Positioning the Cabinet
Climate Class The OD460 chiller is designed to operate within a climate class 3
environment (25°C @ 60% RH). We recommend that you put the chiller in the coolest place possible because it will use less power and last longer.
Chiller
Location
The location of the chiller may be the single most important decision that will extend its life and ensure economical, high performance. Ensure the cabinet is placed where it is not exposed to drafts or direct sunlight. The cabinet must sit on a level surface to prevent the condensate tray from overflowing.
Air Movement The cabinet must NOT be situated where it is affected by air-conditioning air
outlets, ventilation fans or air re-circulation fans, as this will compromise the airflow and thus product temperature in the open cabinet zone.
There must be NO air movement directly into the cabinet opening. Air movement will cause failure of the air curtain over the product, resulting in excessive temperature rise. Detectable air draft will adversely effect the cabinet operation. Maximum air movement across the cabinet opening must not exceed 0.2 m/s.
Power Cord The cabinet has a flexible power cord fitted with a 3-pin plug, which exits the
rear of the cabinet at floor level. Locate the power cord before the cabinet is moved into position so that it is not trapped behind the cabinet.
The cabinet must have its own dedicated power supply. Multi-plug connecting boxes and extension cords must not be used. Check the cabinet does not overload the power supply (see the rating label inside the cabinet for current draw).
Ventilation Adequate ventilation must be provided around the refrigeration unit and
cabinet at all times. Refrigeration exhaust air must not be restricted, and must be able to easily flow out and away from the cabinet.
Ensure there is unimpeded clearance in front of the kick panel at all times. Never store cardboard cartons or other items in the front or rear of the refrigeration unit.
Determine if the installation is free-standing or enclosed, and ensure the installation meets the ventilation requirements detailed below.
Free-standing installations
Free-standing cabinets must be installed with the following minumum clearances:
30mm behind (provided by the rear spacers on the back of the cabinet).
60mm on either side of the cabinet.
200mm above the cabinet.
If these clearances can’t be met, the installation should be treated as an enclosed installation.
IMPORTANT
There must be NO air movement directly into the cabinet
opening.
CAUTION
Ensure adequate ventilation clearance around the refrigeration
unit and cabinet.
Page 6
6
Installation
User Manual
SKOPE OD460
Enclosed installations
Enclosed installations must have the following minimum clearances around the cabinet, and include the following features:
75mm behind the cabinet.
An air guide must be used to ensure all refrigeration exhaust air is
directed up and away from the cabinet.
The air guide must also ensure the air exhaust outlet cannot be blocked
by product or other items above the cabinet.
Refrigeration exhaust air must NOT be allowed to run horizontally across the top of the cabinet, as it may be pulled down into the cabinet interior.
30mm
(rear spacer)
60mm
(min)
60mm
(min)
200mm
(min)
Free-standing installation ventilation requirements
Air
intake
Front
Back wall
Exhaust air
Exhaust air
Air guide
Enclosure ceiling
Air intake
Front
Enclosed installation ventilation
Exhaust air
Exhaust air must
NOT run across
top of cabinet
Enclosure
back wall
75mm
(min)
Exhaust air
Exhaust air
Air
intake
Front
Enclosure ceiling
Air guide
Enclosure back wall
Exhaust air
must NOT run across
top of
cabinet
Enclosed installation ventilation requirements
Page 7
7
SKOPE OD460
Installation
User Manual
Shelves
Installing the
Shelves
The chiller is supplied with three metal shelves. The shelves are different depths, with the top shelf being the shallowest and the bottom shelf the deepest. The bottom shelf is fixed in position, and the two top shelves are height and angle adjustable, and removable.
The two top shelves are each held in place by two cantilevered shelf brackets which clip into cut-outs in the cabinet back duct. Further 6mm interval height adjustments can be made by separating the shelf bracket into two parts and re-slotting together using the alternative slots (see image below).
To fit the shelves
Alternative height
adjustable slots
Position for
level shelves
Position for
angled shelves
1. Clip the cantilevered shelf brackets into the slots in the cabinet back duct.
Use the different positions on the bracket to set the shelf angled or level (see image above).
2. Sit the corresponding metal shelf on the cantilevered brackets ensuring the back of the shelf clips over the rear of the brackets.
3. Push the cantilevered brackets outwards until they clip into the edge locating slots on the side of the shelf.
Locating slot
Shelf
Shelf brackets
Page 8
8
Installation
User Manual
SKOPE OD460
Optional
Gravity Shelf
System
When the chiller is ordered with the optional gravity feed matting, each shelf is supplied with corresponding gravity feed matting and shelf dividers. The gravity shelf system comes in three sizes to suit the three different size shelves.
To fit the gravity feed matting and shelf dividers
1. Match up the shelf dividers with the corresponding mats.
2. Starting from the LH or RH side of the mat, fit the LH or RH end divider into the end row of slots.
3. Work across the matting and fit the centre dividers at required intervals, then fit the opposite end divider.
4. Slide the ticket strip across the front of the mat.
5. Place the mat and dividers onto the corresponding shelf inside the chiller.
6. Repeat for the remaining shelves.
Page 9
9
SKOPE OD460
Operation
User Manual
2 Operation
Automatic Start-Up
After the cabinet has been positioned in a suitable place, plug it in a nd c h e c k the following activity.
Lights
The chiller is fitted with interior LED lights. The lights turn off and on automatically when the chiller is switched between Night and Day mode (via night blind or electronic controller button, see “Day and Night Modes” on page 11). The lights can also be switched on and off manually without changing the chiller between night and day mode by pressing the light button on the electronic controller faceplate (see “Faceplate” on page 12).
Lighting components must not be tampered with in any way. If a unit is suspected of being faulty, a service call should be arranged so that a replacement component can be fitted.
Night Blind
The chiller is fitted with a manual night blind which should be pulled down into the closed position during store closing hours to save power. The night blind has a switch which automatically tells the electronic controller to run the chiller in Night mode (with the lights OFF) when the blind is in the closed position or Day mode (with the lights ON) when in the open position.
The night blind is located at the top of the cabinet opening and is not visible when in the open position.
To close the night blind, use the handle to pull the blind down and hook it under the night blind retaining brackets at the bottom of the chiller opening. To open, use the handle to release the blind from the retaining brackets and control the blind as it opens.
Item Activity
Electronic controller
An electronic controller runs the chiller and is visible behind the front panel. The display panel first flashes start-up messages before stabilising on the cabinet temperature.
Lighting
If the night blind is up, the lights that illuminate the cabinet interior will come on a few seconds after the chiller is turned on.
The lights are off when the night blind is down.
Refrigeration unit
The refrigeration unit evaporator and condenser fans should all operate continuously from the time the cabinet is plugged in. This may be verified by checking for air movement inside the cabinet. The internal cabinet air will continue to circulate at all times.
The compressor will start after approximately one minute, will switch off when the cabinet internal temperature reaches approximately +1.5°C and on again at approximately +4°C.
Page 10
10
Operation
User Manual
SKOPE OD460
Loading Product
Let the chiller run for 30 minutes before loading it with product for the first time. When loading the cabinet shelves with product:
Allow adequate air space around each item to ensure even cooling and
efficient operation of the chiller.
Remove some product if the shelves are flexing.
Do not exceed maximum shelf loadings:
Shelf Maximum weight
Top shelf 27.5 kg
Middle shelf 35.0 kg
Bottom shelf 40.0 kg
Page 11
11
SKOPE OD460
Operation
User Manual
Electronic Controller
Introduction The OD460 chiller is fitted with a Carel ir33 electronic controller which is
visible through a cut-out in the cabinet front panel.
The electronic controller switches the chiller between Day and Night modes depending on the night blind position, and uses temperature probes to control and display the chiller temperature, collect data, signal temperature alarms and force a defrost cycle when required.
The electronic controller is pre-programmed and requires no initial setup or additional programming. SKOPE does not recommend that the settings be changed unless it is absolutely necessary.
Day and Night
Modes
The electronic controller will automatically switch the chiller between Day and Night modes depending on the night blind position. When the blind is in the open (up) position, the chiller runs in Day mode. When the blind is in the closed (down) position, the chiller runs in Night mode.
During Day mode, the lights are ON and the chiller keeps product at required (cool) temperature for serving, and the chiller temperature is displayed on the controller display.
During Night mode, nHt is displayed on the controller display, the lights are OFF and the chiller slightly elevates the product temperature to achieve higher energy efficiency during store closing hours.
Note: The chiller is suitable for storage of perishable products in either Day or Night modes (all shelves maintain temperatures below 5°C).
CAUTION
The electronic controller must only be adjusted by an
authorised service agent.
Page 12
12
Operation
User Manual
SKOPE OD460
Faceplate Because the electronic controller plays such an important role, it’s helpful to
know the parts of the faceplate you may use.
910
11
12
43
15
14
1312
8
7
6
5
No. Item Description
1
Mute (program): Button. Mutes the audible controller alarm. Also used
for controller programming.
2
Aux (up): Button. Press and hold to switch the lights on and off. Also
used for controller programming.
3
Set: Button. Service use only. Used for controller programming
4
Defrost (down): Button. Press and hold to initiate a manual defrost
cycle. Also used for controller programming.
5
Compressor: Indicator. On when the compressor and condenser fan
are running. Flashes when activation of the compressor is temporarily delayed.
6 Fan: Indicator. On when the fans are operational.
7
Defrost: Indicator. On when a defrost cycle is activated. Flashes when
the activation of the defrost is temporarily delayed due to procedures in progress.
8 Aux: n.a.
9 Alarm: Indicator. Flashes in the event of alarms.
10 Clock: Indicator. On when real time clock is enabled.
11 Light: Indicator. On when the cabinet lighting is activated.
12 Service: Indicator. Flashes in the event of malfunctions.
13
Display: Indicator. Digital display of cabinet temperature or alarms.
Displays nHt during night mode. The temperature is what the sensor inside the chiller detects, and not necessarily the product temperature. However, they may be very close depending on how the controller is set to sense temperature.
14 HACCP: n.a.
15 Continuous Cycle: Continuous cycle in progress (see page 13).
Page 13
13
SKOPE OD460
Operation
User Manual
Defrost To ensure efficient operation, the electronic controller forces a defrost cycle
when required. During a defrost cycle, the compressor stops, DEF and the
will display on the electronic controller faceplate. The cabinet will resume normal operation once the defrost cycle has finished. A manual defrost can also be initiated by pressing and holding the
button.
Continuous
Cycle
The continuous cycle can be used to pull down the temperature of product inside the cabinet quickly. During a continuous cool down the compressor runs continuously for a set time.
To start a continuous cycle
To stop a continuous cycle
1. While the cabinet is switched on and running, press and hold the and
buttons for five seconds.
The symbol will display during a continuous cycle.
1. The electronic controller will automatically stop the continuous cycle after a period of time.
The continuous cycle can be stopped by pressing and holding the and
buttons for five seconds.
Page 14
14
Operation
User Manual
SKOPE OD460
Temperature
Setpoint
The chiller is manufactured with a pre-set control temperature set point which can be adjusted if required. SKOPE do not recommend that the set point be changed unless absolutely necessary.
To view and adjust the temperature setpoint
Controller
Reset
To delete program modifications and reset the controller to SKOPE default program or when a replacement controller is being fitted, a ‘Controller Reset’ must be performed.
To reset the controller
1. To view the setpoint: press and hold the
key for 2 seconds, until the
setpoint value flashes
2. To adjust the setpoint: press either the
and keys to display the
required setpoint value.
3. Press the key again to memorise the new setpoint value. If this is not done within 60 seconds, changes will be lost and you will need to repeat the above procedure.
1. Disconnect the cabinet from the power supply.
2. Press and hold the key while plugging the cabinet into the power supply (may require two people). After a few seconds the program mode ‘bn0’ is displayed. The controller must never be left in program mode ‘bn0’ as failure will occur.
3. Press the or keys to select bn1 (SKOPE default program).
4. Immediately press the key to confirm the preferred program. If not confirmed within 60 seconds the cabinet will remain in program mode ‘bn0’ (and cause failure). If this occurs, repeat the above procedure.
Page 15
15
SKOPE OD460
Operation
User Manual
Controller Alarms
Code Display Buzzer Alarm Description Action
Flashing
on
Product HIGH temperature alarm (auto reset)
1. Check the cabinet product loading to ensure ventilation slots are not blocked and that product does not overhang the shelves.
2. Ensure the cabinet is installed with good refrigeration unit ventilation.
3. If immediate alarm recovery is required ­unplug the cabinet from the power supply for 1 minute, then reconnect to power supply.
If alarm persists, contact SKOPE.
Flashing
on
Product LOW temperature alarm (auto reset)
Flashing
off
Refrigeration system high temperature
pre-warning (auto reset)
1. Check refrigeration ventilation. Ensure clear airpath at the top and front of the cabinet (to extract hot air). A minimum of 200mm clear space is required above and in front of the refrigeration unit.
2. Ensure the cabinet is installed in a suitable environment.
3. To reset the ‘CHt’ alarm - unplug the cabinet from the power supply for 1 minute, then reconnect to power supply.
If alarm persists, contact SKOPE.
Flashing
on
Refrigeration system high temperature shut­down (manual reset)
Flashing
off
Ambient probe fault (also flashes ‘rE’)
To reset alarm - unplug the cabinet from the power supply for 1 minute, then reconnect to power supply.
If alarm persists, contact SKOPE.
Flashing
off Evaporator probe fault
Flashing
off Condenser probe fault
None
off Defrost over-time limit
Flashing
off Real-time clock fault
Flashing
off
Controller E prom error
Flashing
off
Controller E prom error
None
- Start defrost request
None
None
- End defrost request
Page 16
16
Maintenance
User Manual
SKOPE OD460
3 Maintenance
Isolating Electrics
The chiller cabinet should be isolated from the power supply before attempting any maintenance.
Use the isolating switch and plug, located in the refrigeration unit compartment, to turn off the electrics to the cabinet and refrigeration unit without unplugging the cabinet from the wall.
To isolate the electrics
1. Remove the front panel from the cabinet by undoing the fixing screws near the bottom of the panel and lifting it up and off the cabinet.
2. Swit ch off ( O) t he po wer at the mains isolation switch and unplug the mains IEC plug on the LH side of the refrigeration unit compartment.
Front Panel
Switch
Plug
Page 17
17
SKOPE OD460
Maintenance
User Manual
Maintenance
To ensure the chiller continues to run efficiently and reliably, the following maintenance should be carried out:
To clean the condenser coil
Cleaning Cabinet Keep the interior and exterior of the cabinet
clean by regular wiping with a damp cloth.
The bottom shelf can be removed to assist with cleaning by undoing the two side fixing screws. Ensure the bottom shelf is refitted before reconnecting the chiller to the power supply.
Be careful not to wash any liquid down into the refrigeration system, as this could lead to refrigeration failure.
Cleaning Condenser Coil The condenser coil must be cleaned at least
monthly with a soft brush to remove dust and fluff (see instructions below).
Regular Servicing A thorough service clean must be
completed by qualified service personnel every six months.
Time Frames Time frames specified above are indicative
only. More regular cleaning and servicing may be required depending on chiller placement and operating environment.
1. Remove the front panel and isolate the chiller from the power supply (see page 16).
2. Brush the condenser coil with a soft brush
3. Refit the front panel and reconnect to the power supply.
WARNING
Disconnect the chiller from the power supply before cleaning
the condenser coil.
Condenser coil
Page 18
18
Maintenance
User Manual
SKOPE OD460
Troubleshooting
For questions about the electronic controller, see page 11. For problems with the cabinet and refrigeration cassette, use the following table.
Problem Possible Cause Suggestions
• Chiller not operating
• No controller display
• Loss of power supply
• Isolating switch turned off
• Check mains power supply.
• Check isolating switch (see page 16).
• Lights not on • Night blind is down • Raise the night blind.
• Light switched off • Switch light on at electronic controller faceplate (see page 12).
• Lighting fault • Arrange a service call.
• Blown cabinet fuse • Arrange a service call.
• Power consumption is higher than expected
• Refrigeration unit operating too hot
• Clean the condenser coil (see page 17).
• Ensure the cabinet has good ventilation around the refrigeration unit (see page 5).
• Ensure the cabinet is installed in a cool location within operating specifications (see page 5).
• Product is too warm • Restricted airflow to cabinet
• Ensure product is not blocking airflow slots.
• Ensure there is space around individual product pieces.
• Warm cabinet temperatures
• Compressor operating for long periods (more than 1 hour)
• Blocked condenser • Clean the condenser coil (see page 17).
• Poor ventilation around
refrigeration cassette
• Ensure the cabinet is installed in a cool location within operating specifications (see page 5).
Page 19
SKOPE Contacts
SKOPE Industries Limited
NEW ZEALAND CONTACT
Head Office PO Box 1091, Christchurch New Zealand Freephone: 0800 947 5673 Fax: (03) 983 3896 E-mail: enquiry@skope.co.nz Website: www.skope.co.nz
AUSTRALIAN CONTACT
A.B.N. 73 374 418 306 PO Box 7543, Baulkham Hills B.C. NSW 2153, Australia Freephone: 1800 121 535 Fax: 1800 121 533 E-mail: enquiry@skope.com.au Website: www.skope.com.au
OD460 SKOPE Open Deck Chiller User Manual MA N11106 Rev. 2.0 Nov. 2018
© 2015 SKOPE Industries Limited. All rights reserved. SKOPE Industries Limited reserve the right to alter specifications without notice.
is a registered trademark of SKOPE Industries Limited.
Loading...