Skope B550-2, B660-2, BME550-2 Operating And Service Manual

Operating and Service Manual
MAN0515 Rev. 4.0 Jan. 2006 edition
B550/660-2 BME550-2
SKOPE Gen2: Single Door Chiller
Vertical Display and Storage
SKOPE Gen2: Single Door Chiller
Designed and Manufactured by
New Zealand
SKOPE INDUSTRIES LIMITED PO Box 1091, Christchurch New Zealand Freephone: 0800 947 5673 Fax: (03) 983 3896 E-mail: enquiry@skope.co.nz Website: www.skope.co.nz
Australia
SKOPE AUSTRALIA PTY LTD A.C.N. 000 384 270 PO Box 7543, Baulkham Hills B.C. NSW 2153, Australia Freephone: 1800 121 535 Fax: 1800 121 533 E-mail: enquiry@skope.com.au Website: www.skope.com.au
CONTACT ADDRESSES
i
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
B550/660-2, BME550-2 SKOPE Gen2: Single Door Chiller Operating and Service Manual
MAN0515 Rev. 4.0 Jan. 2006 edition.
Copyright © 2005 SKOPE Industries Limited. All rights reserved.
SKOPE Industries Limited reserve the right to alter specifications without notice.
is a registered trade
mark of SKOPE Industries Limited.
ii
TRADE MARK INFRINGEMENT
The SKOPE trade mark on this product is infringed if the owner, for the time being, does any of the following:
•Applies the trade mark to the product after their state, condition, get-up or packaging has been altered in any manner
•Alters, removes (including part removal) or obliterates (including part obliteration) the trade mark on the product
•Applies any other trade mark to the product
•Adds to the product any written material that is likely to damage the reputation of the trade mark
Notice of the above contractual obligations passes to:
•Successors or assigns of the buyer
•Future owners of the product
SKOPE Gen2: Single Door Chiller
1SPECIFICATIONS
1.1Cabinet and Refrigeration Unit . . . . . . . . . . . . . . . . . . . . . . .7
2OPERATION
2.1Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.2Operation of Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Refrigeration Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Electronic Controller. . . . . . . . . . . . . . . . . . . . . . . . . . .9
Cabinet Lighting. . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Mains Isolating Switch . . . . . . . . . . . . . . . . . . . . . . . .10
2.3Shelving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Loading Product. . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.4Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
3ELECTRONIC CONTROLLER
3.1Controller Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Meaning of LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.2Controller Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.3Programming Controller . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.4Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.5Alarm Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Alarm Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.6Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Controller NTC Probe Resistance . . . . . . . . . . . . . . .20
Controller Removal . . . . . . . . . . . . . . . . . . . . . . . . . .21
Replacement Controller. . . . . . . . . . . . . . . . . . . . . . .22
Dixell Controller Wiring. . . . . . . . . . . . . . . . . . . . . . . .23
4SERVICE INSTRUCTIONS
4.1Interior Side Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.2Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.3Sign Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
TABLE OF CONTENTS
iii
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
4.4Refrigeration Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
To Remove the Refrigeration Unit . . . . . . . . . . . . . . 34
To Re-Install the Refrigeration Unit. . . . . . . . . . . . . . 36
Refrigeration Unit Junction Box . . . . . . . . . . . . . . . . 37
Evaporator Fan Motor Assembly . . . . . . . . . . . . . . . 38
Condenser Fan Motor Assembly . . . . . . . . . . . . . . . 39
Cleaning the Condenser Coil . . . . . . . . . . . . . . . . . . 40
Recommended Service Procedures. . . . . . . . . . . . . 41
For a Suspected Refrigerant Problem . . . . . . . . . . . 41
Short of Refrigerant. . . . . . . . . . . . . . . . . . . . . . . . . . 41
Compressor Not Pumping Efficiently . . . . . . . . . . . . 42
Capillary Restriction . . . . . . . . . . . . . . . . . . . . . . . . . 42
Refrigerant R134a Handling Precautions. . . . . . . . . 43
4.5Cabinet Wiring Junction Box . . . . . . . . . . . . . . . . . . . . . . . 44
4.6Mains Isolating Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.7Pressure Temperature Chart . . . . . . . . . . . . . . . . . . . . . . . 47
4.8Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5WIRING DIAGRAM
5.1Model: B550/660-2, BME550-2 . . . . . . . . . . . . . . . . . . . . . 52
6SPARES
6.1Cabinet Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.2Interior Side Light. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.3Cabinet Wiring Junction Box . . . . . . . . . . . . . . . . . . . . . . . 56
6.4Mains Isolating Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.5Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.6Sign Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.7Refrigeration Unit: UB40AAC. . . . . . . . . . . . . . . . . . . . . . . 60
6.8Refrigeration Unit: UB30AAC. . . . . . . . . . . . . . . . . . . . . . . 61
TABLE OF CONTENTS
iv
7
SKOPE Gen2: Single Door Chiller
1.1Cabinet and Refrigeration Unit
Table 1: Specifications
Cabinet Construction
Exterior / Interior: White powdercoat on galvanised steel Insulation:
50mm thick, polyurethane foam Cyclo-iso Pentane blowing agent: C5H10/C5H
12
Dimensions
Model: B550-2 B660-2 BME550-2
Height: 2195mm 2195mm 1995mm Width: 740mm 800mm 740mm Depth: 750mm 800mm 750mm
Floor area:
0.56m
2
0.6m
2
0.56m
2
Internal volume: 558 litres 658 litres 558 litres
Refrigeration
Electronic controlled, bottom mounted SKOPE refrigeration unit
Model: UB40AAC UB30AAC
Nominal capacity: 581 Watts 581 Watts Compressor: Electrolux GLY90RA Electrolux GLY90RA Refrigerant: R134a / 465 grams R134A / 465 grams
Electrical
230-240 Volts a.c. 50 Hz, single phase power supply Run Amps: 2.15 A 2.36 A 1.96 A
Interior Lighting
Either 1 or 2 vertical 28 Watt T5 fluorescent tubes (Ø16mm x 1150mm)
Illuminated Sign
1 x 14 W T5 fluorescent tube (Ø16mm x 550mm) No sign fitted
Door
Self-closing, aluminium framed, double glazed, toughened safety glass
Shelves
5 adjustable shelves 4 adjustable shelves
SPECIFICATIONS
1
8
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
2.1Safety Information
When using any electrical appliance, safety precautions should always be observed. Read these instructions carefully, and retain for future reference.
•When used by, or near, young children or infirm persons, close
supervision is necessary. Young children should be supervised to ensure that they do not play with the appliance.
•Do NOT use this appliance for other than its intended use.
•Do NOT cover the grilles or block the entry or exhaust of airflow
by placing objects up against the refrigeration units.
•Do NOT probe any opening.
•Only use this appliance with voltage specified on the rating label.
•Ensure adequate ventilation of the SKOPE refrigeration units.
•Be careful not to touch moving parts and hot surfaces.
•Regulations require that all electrical work be carried out by
authorised persons. For your own safety, and that of others, ensure this is done.
•If the supply cord becomes damaged, it must be replaced by a
SKOPE authorised service agent, or similarly qualified person, in order to avoid a hazard.
•If the refrigeration units are required to be installed or removed
from the cabinet, ensure all necessary safety precautions are observed.
Warning: Do NOT overload the power supply.
Caution:
Disconnect the cabinet from the mains power supply before attempting any electrical servicing, cleaning or maintenance.
OPERATION
2
9
SKOPE Gen2: Single Door Chiller
2.2Operation of Machine
Plug in the machine and check operation of the refrigeration unit, electronic controller and cabinet lighting.
Refrigeration Unit
On initial startup the evaporator and condenser fans and the compressor will operate. This may be verified by listening for compressor switch on and checking air movement out of the slots in the front kick panel. The internal cabinet air will continue to circulate at all times, as the evaporator fans operate continuously.
The compressor should switch off when the cabinet internal temperature reaches approximately +2°C. and switch on again at approximately +4°C.
A fan reversing device reverses the condenser fan motor for a period of time during the compressor ‘off-cycle’. This rotation change is to assist with self-cleaning of the condenser coil. Otherwise, the condenser fan operates continuously in a clockwise (LE) direction.
The two evaporator fans, located inside the evaporator box, operate continuously. Both evaporator fans operate in contra rotation, hence there are dedicated left and right hand blades and different wiring for the fan motors. Correct airflow, as viewed from the rear, of the unit left hand fan is clockwise and the right hand fan is anti-clockwise.
Electronic Controller
On initial startup, the electronic controller will either display the internal cabinet temperature or the controller set point. The compressor ‘on’ LED will indicate when the compressor is operating. The controller is located in the front kick panel (see page 14 for further controller operation).
OPERATION
2
10
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
Cabinet Lighting
On initial startup, the lights which illuminate the cabinet interior and top sign (when fitted) will come on and stay on permanently. The lights will require a period of time to stabilise following initial start up.
Mains Isolating Switch
This cabinet is fitted with a mains isolating switch and IEC (appliance) socket, located in the refrigeration unit compartment (see Figure 1 below). The isolating switch and socket can be used to isolate all cabinet and unit electrics, without unplugging the cabinet from the wall. Ensure the mains isolating switch is turned back on after servicing.
Figure 1: Isolating Switch
Isolating Switch
IEC Socket
Refrigeration Unit
Mains Flex
OPERATION
2
11
SKOPE Gen2: Single Door Chiller
2.3Shelving
The chiller is supplied with either four or five cabinet shelves, which may be positioned at different heights to suit various products. Each shelf is held in place with four shelf clips, which engage in each of the four shelf support strips. The support strips are marked with a ‘+’ for easy location of shelf clips (see Figure 2 below).
Loading Product
When loading the cabinet shelves with product:
•For even cooling and efficient operation, allow air space around packages etc.
•Do not allow products to overhang the front of the shelf as this could prevent the door from shutting or cause glass breakage.
• Leave an airspace of at least 75mm (3") above packages etc. on the top shelf.
Figure 2: Shelf Clip
Shelf Support Strip
Shelf Clip
‘+’ Mark
Shelf
OPERATION
2
12
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
2.4Cleaning
When necessary, wipe both the interior and exterior of the cabinet with a damp cloth. The exterior of the cabinet may be also be waxed with automobile polish for extra protection. Ensure the cabinet is disconnected from the mains power supply before cleaning.
Periodic cleaning of the condenser coil is also recommended (see page 40 for cleaning instructions).
Caution:
Disconnect the cabinet from the mains power supply before cleaning.
OPERATION
2
13
SKOPE Gen2: Single Door Chiller
3.1Controller Display
Table 2: Controller Operation
Item KeyFunction
1
SET: Press to display target set point. In programming mode it selects
a parameter or confirms an operation
2
DEFROST: Press to start a manual defrost
3
UP: Press to see maximum stored temperature. In programming mode
it browses the parameter codes, or increases the displayed value
4
DOWN: Press to see the minimum stored temp. In programming mode
it browses the parameter codes, or decreases displayed value
5
Compressor on LED indicator
6
Defrost cycle on LED indicator
7
Set Point displayed LED indicator
8
Decimal point LED indicator
Key Combinations:
Press both keys simultaneously, to lock and unlock the keypad
Press both keys simultaneously, to enter the programming mode
Press both keys simultaneously, to return to room temperature display
1
35
2
4
6
7
8
Figure 3: Controller Display
+ + +
ELECTRONIC CONTROLLER
3
14
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
Meaning of LEDs
Table 3: LED Functions
3.2Controller Operation
The SKOPE electronic controller controls and displays the cabinet temperature. The preset temperature setting controls the product temperature between 2°C and 4°C.
The electronic controller also signals system and temperature alarms (see Table 5 on page 19).
To ensure efficient operation, the electronic controller has a built in minimum off cycle time of 3 minutes and features regular timed defrost cycles. During the defrost cycle, the compressor switches off and the evaporator fan stays on.
The controller has two temperature probes; one is used for the cabinet temperature control and display, while the other probe is used for the condenser over-temperature alarms.
LEDModeFunction
ONCompressor enabled
FlashingAnti-short cycle delay enabled ONDefrost enabled FlashingDrip time in progress FlashingProgramming mode (see page 16) ONTemperature alarm (see page 19)
+
ELECTRONIC CONTROLLER
3
15
SKOPE Gen2: Single Door Chiller
3.3Programming Controller
The controller keypad must always be locked, to prevent unauthorised modification.
To Unlock the Keypad (to modify parameters)
Press both the UP and DOWN keys simultaneously until ‘Pon’ is displayed.
To Lock the Keypad
1.Press and hold both the UP and DOWN keys together for more than 3 seconds.
2. The ‘PoF’ message will be displayed and the keypad will be locked. At this point it will be possible only to see the Set Point or maximum or minimum temperature stored.
3.If a key is pressed for more than 3 seconds, the ‘PoF’ message will be displayed.
To Display the Set Point
Press and immediately release the SET key. The display will show the Set Point value and the Set Point LED will be highlighted.
To Change the Set Point
1. Push and hold the SET key for more than 2 seconds.
2. The value of the Set Point will be
displayed, and the LED will start blinking.
3.To change the Set value, push the UP or DOWN keys.
4.To memorise the new Set Point value, push the SET key again or wait 15 seconds.
ELECTRONIC CONTROLLER
3
16
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
To Start a Manual Defrost
Push and hold the DEFROST key for more than 2 seconds.
To Change a Parameter Value
1. Enter the programming mode by pressing and holding both the SET and DOWN keys for 3 sec.
(and start flashing).
2.Select the required parameter.
3.Press the SET key to display the Set value (now only the LED is flashing).
4.Press the UP or DOWN keys to change the Set value.
5.Press the SET key to store the new value and move to the following parameter.
6.To exit: Press both the SET and UP keys, or wait 15 seconds without pressing any keys.
7.To lock in new parameter value: after one minute operation, disconnect and reconnect cabinet into the mains power supply.
Notes:
1.The Set value is stored even when the procedure is exited, by waiting for the time-out to expire.
2.Dependent on customer requirements, the SKOPE electronic controller may have different parameter configurations (see ‘Controller Parameters’ in Table 4 on pages 18). To ensure the controller is programmed with the correct SKOPE program, check the program number printed on the controller box (parameter configuration 160 = Beverage, and 170 = Food).
ELECTRONIC CONTROLLER
3
17
SKOPE Gen2: Single Door Chiller
To See the Minimum Temperature
1.Press and release the DOWN key.
2.The ‘Lt’ message will be displayed, followed by the minimum temperature.
3.Press the DOWN key again, or wait 5 seconds, to restore the normal display.
To See the Maximum Temperature
1.Press and release the UP key.
2.The ‘Ht’ message will be displayed, followed by the maximum temperature recorded.
3.Press the UP key again, or wait 5 seconds, to restore the normal display.
To Reset the Maximum and Minimum Temperature
1.Press and hold the SET key for more than 3 seconds, while the maximum or minimum temperature is displayed. The ‘rSt’ message will be displayed.
2.To confirm the operation, the ‘rSt’ message starts flashing and the normal temperature will be displayed.
ELECTRONIC CONTROLLER
3
18
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
3.4Parameters
Table 4: Controller Parameters
Parameters
Display Beverage
160
Food
170
Range Description of Parameter
SET POINT PARAMETERS
Set 2 1 LS to US Set Point Hy 2 2 0.1°C to 25.5°C Differential LS 1 -1 -50°C to Set Minimum Set Point US 15 5 Set to 150°C Maximum Set Point
PROBE PARAMETERS
Ot -0.7 0 -12°C to 12°C Thermostat probe calibration OE 0 0 -12°C to 12°C Condenser probe calibration
CONTROL PARAMETERS
OdS 0 0 0 to 255 minutes Outputs delay at start up AC 3 3 0 to 50 minutes Anti-short cycle delay
DISPLAY PARAMETERS
CF °C °C °C / °F Temperature measurement unit rES dE in in / dE Resolution LoD P1 P1 P1 / P2 or SP Local display
DEFROST PARAMETERS
IdF 6 6 1 to 120 hours Interval between defrost cycles MdF 12 12 0 to 255 minutes Maximum length for defrost dFd dEF dEF rt / it / Set / DEF Displaying during defrost dAd 20 20 0 to 255 minutes Maximum display delay after defrost
ALARM PARAMETERS
ALc Ab Ab rE / Ab Temperature alarms configuration ALU 12 7 up to 150°C Maximum temperature alarm ALL -2 -2 -50°C to ALU Minimum temperature alarm AtH 1 1 0.1°C to 25.5°C Differential for temperature alarm in cabinet ALd 240 120 0 to 255 minutes Temperature alarm delay dAO 24 24 0 to 23.5 hours Delay of temperature alarm at start up tbA n n n = no / y = yes Alarm relay silencing PA2 58 58 -40°C to AU2 Condenser over temperature AU2 65 65 -40°C to 110°C AUE Condenser alarm temperature ACH 5 5 0.1°C to 25.5°C Differential for condenser alarm temp recovery dL2 2 2 0 to 255 minutes Condenser alarm delay dA2 0 0 0 to 23.5 hours Condenser alarm temperature delay at start up AOP CL CL OP / CL Alarm relay polarity
OTHER PARAMETERS
dP1 - - - Thermostat probe read out dP2 - - - Condenser probe read out rEL - - - Software release Ptb - - - Map code
ELECTRONIC CONTROLLER
3
19
SKOPE Gen2: Single Door Chiller
ELECTRONIC CONTROLLER
3
3.5Alarm Displays
Table 5: Controller Alarm Displays
Note: The refrigeration system and cabinet lighting shut down with ‘P1, P2 and CSd’ alarms.
Alarm Recovery
•Condenser Stage ONE over-temperature alarm (COH) recovers when the condenser is either cleaned or cools down.
•Condenser Stage TWO over-temperature alarm (CSd) recovers by disconnecting and reconnecting the cabinet mains power supply (or isolation switch), which will reset all the alarms.
•Cabinet temperature alarms (LO and HI) automactically stop at temperature recovery.
AlarmDescription
Stage ONE - Maintenance required: Immediately attend condenser (for auto alarm reset).
Stage TWO - Refrigeration Shut-Down: Condenser over-temperature has shut-down system and cabinet lighting. Attend condenser. To reset alarm, cabinet must be replugged into power supply. For repeat alarms, contact an authorised service agent.
Faulty Ambient probe (internal cabinet - return air). Refrigeration system and cabinet lighting shut down.
Faulty High Temperature probe (condenser). Refrigeration system and cabinet lighting shut down.
Internal cabinet - LOW temperature alarm. Alarm will stop at temperature recovery.
Internal cabinet - HIGH temperature alarm. Alarm will stop at temperature recovery.