49
B550/660-2, BME550-2
SKOPE Gen2: Single Door Chiller
4.8Troubleshooting
Table 8: Troubleshooting - continued on next page
Complaint Possible Cause Repair
9. Compressor
starts, but
does not
switch off
- start
winding.
Improperly wired. Check wiring against diagram.
Low voltage to unit. Determine reason and correct.
Relay failing to open, due to welded
contacts or relay incorrectly
mounted.
Determine reason and correct.
Replace if necessary.
Run capacitor defective on CSR
motor.
Determine reason and replace.
Excessively high discharge pressure.
Clean condenser. Check power
input. Possible overcharge,
insufficient condenser cooling,
or non-condensible gasses.
Compressor motor has winding open
or shorted. Check continuity and
resistance.
Replace compressor if faulty.
Internal mechanical trouble in compressor (tight). May be lubrication.
Replace compressor.
10. Compressor
starts and
runs, but
short cycles
on overload
protector
(relay may
chatter on
RSIR, CSIR
and CSR
motors).
Additional current passing through
overload protector.
Check wiring diagram. Check
for added fan motors etc.,
connected to wrong side of
protector.
Low voltage to unit. Determine reason and correct.
Overload protector defective. Check current, replace
protector.
Run capacitor defective on CSR
motor.
Determine reason and replace.
Excessive discharge pressure. Check condenser, check
ventilation, check for restrictions
in refrigeration system.
Suction pressure too high. Check for possibility of
misapplication.
Compressor too hot - insufficient
suction gas cooling.
Check refrigerant charge (fix
leak), add if necessary. Check
return vapour temperature and
suction superheat.
Comp’r motor has a winding shorted. Replace compressor.
SERVICE INSTRUCTIONS
4