Sixth Sense AI-200 Operating Manual

Page 1
User's ManualUser's Manual
DIN EN ISO 9001
Certificate: 01 100 98505
R
C21 / C91
Auto-Tune Fuzzy / PID
Auto-Tune Process
Process / Temperature Controller
Fuzzy / PID
/ Temperature Controller
R
UM0C911C
BRAINCHILD
Page 2
Warning SymbolWarning Symbol
The Symbol calls attention to an operating procedure, practice, or the like, which, if not correctly performed or adhered to, could result in personal injury or damage to or destruction of part or all of the product and system. Do not proceed beyond a warning symbol until the indicated conditions are fully understood and met.
Use the ManualUse the Manual
Installers
System Designer
Expert User
NOTE:
It is strongly recommended that a process should incorporate a
It is strongly recommended that a process should incorporate a
CONTROL like L91 which will shut down the equipment at
LIMIT
LIMIT CONTROL like L91 which will shut down the equipment at
preset process condition in order to preclude possible
a
a preset process condition in order to preclude possible
damage
damage to products or system.
Information in this user's manual is subject to change without notice.
This manual is applicable for the products with software version
This manual is applicable for the products with software version
23 and later version.
23
Copyright April 2003, The Brainchild Corporation, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of the Brainchild Corporation.
to products or system.
and later version.
a
Read Chapter 1, 2
Read All Chapters
Read Page 12
UM0C911C2
Page 3
Contents
Chapter 1 OverviewChapter 1 Overview 1-1 General -------------------------5
1-2 Ordering Code ---------------8 1-3 Programming Port ------------9 1-4 Keys and Displays ---------10 1-5 Menu Overview -------------12 1-6 Parameter Descriptions ---13
Chapter 2 Installation
Chapter 2 Installation
2-1 Unpaking ----------------------20 2-2 Mounting ----------------------20 2-3 Wiring precautions ----------22 2-4 Power Wiring -----------------25 2-5 Sensor Installation ----------
Guidlines----------------------25 2-6 Sensor Input Wiring --------26 2-7 Control Output Wiring -----26 2-8 Alarm Wiring -----------------30 2-9 Data Communication ------31
Chapter 3 Programming
Chapter 3 Programming 3-1 Lockout ------------------------33
3-2 Signal Input -------------------33 3-3 Control Outputs --------------34 3-4 Alarm ---------------------------39 3-5 Configure Display -----------40 3-6 Ramp ---------------------------41 3-7 Dwell Timer -------------------42 3-8 PV Shift ------------------------43 3-9 Digital Filter -------------------44 3-10 Failure Transfer -------------45 3-11 Auto-tuning ------------------46 3-12 Manual tuning --------------47 3-13 Manual Control -------------48 3-14 Data Communication -----50 3-15 PV Retransmission --------50
Page No
Chapter 4 Applications
Chapter 4 Applications
4-1 Heat Only Control with --
Dwell Timer ------------------51 4-2 Cool Only Control -----------52 4-3 Heat-Cool Control -----------53
Chapter 5 Calibration --------55Chapter 5 Calibration
Chapter 6 Specifications ----60Chapter 6 Specifications
Chapter 7
Chapter 7
Modbus Communications---66
Modbus
7-1 Functions Supported -------66 7-2 Exception Responses -----68 7-3 Parameter Table -------------69 7-4 Data Conversion ------------73 7-5 Communication Examples-73
Appendix A-1 Error Codes ------------------76
A-2 Warranty ----------------------77
Communications
Page No
UM0C911A 3
Page 4
Figures & TablesFigures & Tables
Figure 1.1 Fuzzy Control Advantage ----------------------------------------------------------------6 Figure 1.2 Programming Port Overview ------------------------------------------------------------9 Figure 1.3 Front Panel Description -----------------------------------------------------------------11 Figure 1.4 Display of Initial Stage -------------------------------------------------------------------11 Figure 2.1 Mounting Dimensions -------------------------------------------------------------------21 Figure 2.2 Lead Termination for C91 -------------------------------------------------------------23 Figure 2.3 Lead Termination for C21---------------------------------------------------------------23 Figure 2.4 Rear Terminal Connection for C21--------------------------------------------------23 Figure 2.5 Rear Terminal Connection for C91----- --------------------------------------------24 Figure 2.7 Power Supply Connections ------------------------------------------------------------25 Figure 2.8 Sensor Input Wiring ----------------------------------------------------------------------26 Figure 2.9 Output 1 Relay or Triac (SSR) to Drive Load ---------------------------------------26 Figure 2.10 Output 1 Relay or Triac (SSR) to Drive Contactor -------------------------------27 Figure 2.11 Output 1 Pulsed Voltage to Drive SSR ---------------------------------------------27 Figure 2.12 Output 1 Linear Current ---------------------------------------------------------------28 Figure 2.13 Output 1 Linear Voltage ---------------------------------------------------------------28 Figure 2.14 Output 2 Relay or Triac (SSR) to Drive Load -------------------------------------28 Figure 2.15 Output 2 Relay or Triac (SSR) to Drive Contactor -------------------------------29 Figure 2.16 Output 2 Pulsed Voltage to Drive SSR ---------------------------------------------29 Figure 2.17 Output 2 Linear Current ---------------------------------------------------------------29 Figure 2.18 Output 2 Linear Voltage --------------------------------------------------------------30 Figure 2.19 Alarm Output to Drive Load ----------------------------------------------------------30 Figure 2.20 Alarm Output to Drive Contactor ----------------------------------------------------30 Figure 2.21 RS-485 Wiring ---------------------------------------------------------------------------31 Figure 2.22 RS-232 Wiring ---------------------------------------------------------------------------32 Figure 2.23 Configuration of RS-232 Cable ------------------------------------------------------32 Figure 3.1 Conversion Curve for Linear Type Process Value ---------------------------------34 Figure 3.2 Heat Only ON-OFF Control ------------------------------------------------------------35 Figure 3.3 Output 2 Deviation High Alarm --------------------------------------------------------38 Figure 3.4 Output 2 Process Low Alarm ----------------------------------------------------------38 Figure 3.5 RAMP Function ---------------------------------------------------------------------------41 Figure 3.6 Dwell Timer Function --------------------------------------------------------------------42 Figure 3.7 PV Shift Application ----------------------------------------------------------------------43 Figure 3.8 Filter Characteristics ---------------------------------------------------------------------44 Figure 3.9 Effects of PID Adjustment -------------------------------------------------------------49 Figure 4.1 Heat Control Example -------------------------------------------------------------------51 Figure 4.2 Cooling Control Example ---------------------------------------------------------------52 Figure 4.3 Heat-Cool Control Example ------------------------------------------------------------53 Figure 5.1 RTD Calibration ---------------------------------------------------------------------------57 Figure 5.2 Cold Junction Calibration Setup ------------------------------------------------------58
Table 1.1 Display Form of Characters -------------------------------------------------------------11 Table 3.1 Heat-Cool Control Setup Value ---------------------------------------------------------34 Table 3.2 PID Adjustment Guide --------------------------------------------------------------------48 Table A.1 Error Codes and Corrective Actions --------------------------------------------------66
Page No
UM0C911B4
Page 5
Chapter 1 OverviewChapter 1 Overview
1-1 General1-1 General
The Fuzzy Logic plus PID microprocessor-based controller series, incorporate a bright, easy to read 4-digit LED display, indicating process value or set point value. The Fuzzy Logic technology enables a process to reach a predetermined set point in the shortest time, with the minimum of overshoot during power-up or external load disturbance.
C21 is a 1/32 DIN size panel mount controller. C91 is a 1/16 DIN size panel mount controller. These units are powered by 11-26 or 90-250
VDC/VAC supply, incorporatinga2amp.controlrelayoutput as standard. The second output can be used as cooling control, an alarm or dwell timer. Both outputs can select triac, 5V logic output, linear current or linear voltage to drive external device. There are six types of alarm plus a dwell timer can be configured for the second output.The units are fully programmable for PT100 and thermocouple types J,K, T, E, B, R, S, N, L with no need to modify the unit. The input signal is digitized by using a 18-bit A to D converter. Its fast sampling rate allows the unit to control fast processes.
Digital communications RS-485 or RS-232 ( for C21, C91) are available as an additional option. These options allow the units to be integrated with supervisory control system and software.
A programming port is available for automatic configuration, calibration and testing without the need to access the keys on front panel.
By using proprietary Fuzzy modified PID technology, the control loop will minimize the overshoot and undershoot in a shortest time. The following diagram is a comparison of results with and without Fuzzy technology.
UM0C911B 5
Page 6
Temperature
Set point
PID control with properly tuned PID + Fuzzy control
Figure 1.1
Figure 1.1
Fuzzy Control
Fuzzy
Advantage
Advantage
Control
Warm Up
High AccuracyHigh Accuracy
Load Disturbance
Time
The series are manufactured with custom designed ASIC(Application Specific Integrated Circuit ) technology which contains a 18-bit A to D converter for high resolution measurement ( true 0.1 F resolution
B
for thermocouple and PT100 ) and a 15-bit D to A converter for linear current or voltage control output. The ASIC technology provides improved operating performance, low cost, enhanced reliability and higher density.
Fast Sampling Rate
Fast Sampling Rate The sampling rate of the input A to D converter reaches 5 times/second.
The fast sampling rate allows this series to control fast processes.
Fuzzy ControlFuzzy Control
The function of Fuzzy control is to adjust PID parameters from time to time in order to make manipulation output value more flexible and adaptive to various processes. The results is to enable a process to reach a predetermined set point in the shortest time, with the minimum of overshoot and undershoot during power-up or external load disturbance.
Digital Communication
Digital Communication
The units are equipped with RS-485 or RS-232 interface card to provide digital communication. By using the twisted pair wires there are at most 247 units can be connected together via RS-485 interface to a host computer.
UM0C911A6
Page 7
Programming PortProgramming Port
A programming port is used to connect the unit to a hand-held programmer or a PC for quick configuration, also can be connected to an ATE system for automatic testing & calibration.
Auto-tune
The auto-tune function allows the user to simplify initial setup for a new system. A clever algorithm is provided to obtain an optimal set of control parameters for the process, and it can be applied either as the process is warming up ( cold start ) or as the process has been in steady state ( warm start ).
Lockout Protection
Lockout Protection
According to actual security requirement, one of four lockout levels can be selected to prevent the unit from being changed abnormally.
Bumpless Transfer
Bumpless Transfer
Bumpless transfer allows the controller to continue to control by using its previous value as the sensor breaks. Hence, the process can be well controlled temporarily as if the sensor is normal.
Soft-start Ramp
Soft-start Ramp
The ramping function is performed during power up as well as any time the set point is changed. It can be ramping up or ramping down. The process value will reach the set point with a predetermined constant rate.
Digital FilterDigital Filter
A first order low pass filter with a programmable time constant is used to improve the stability of process value. This is particularly useful in certain application where the process value is too unstable to be read.
UM0C911A 7
Page 8
1-2 Ordering Code1-2 Ordering Code
C21-
C21-
C91-
C91-
Power InputPower Input
4: 90 - 250 VAC,
4: 90 - 250 VAC,
50/60 HZ
50/60
5: 11 - 26 VAC or VDC
5:
11 - 26 VAC or VDC
9: Special Order
9:
Special Order
Signal InputSignal Input
1: Standard Input
1: Standard Input
Thermocouple: J, K, T, E, B,
Thermocouple:
RTD:
RTD: PT100 DIN, PT100 JIS
2:
0 - 60 mA
2: 0 - 60 mA
0 - 1V
3:
3: 0 - 1V
4:
0 - 5V
4: 0 - 5V
5:
1 - 5V
5: 1 - 5V
6:
4 - 20 mA
6: 4 - 20 mA
0 - 20 mA
7:
7: 0 - 20 mA
8:
0 - 10 V
8: 0 - 10 V
9:
Special Order
9: Special Order
Output 1Output 1
0: None
0: None
1:
Relay rated 2A/240VAC
1: Relay rated 2A/240VAC
Pulsed voltage to drive SSR,
2:
2: Pulsed voltage to drive SSR,
3:
Isolated 4 - 20mA / 0 - 20mA
3: Isolated 4 - 20mA / 0 - 20mA
4:
Isolated 1 - 5V / 0 - 5V
4: Isolated 1 - 5V / 0 - 5V
Isolated 0 - 10V
5:
5: Isolated 0 - 10V
6:
Triac output 1A / 240VAC,SSR
6: Triac output 1A / 240VAC,SSR
C:
C: Pulsed voltage to drive SSR,
Special order
9:
9: Special order
HZ
J, K, T, E, B,
R,
S, N, L
PT100 DIN, PT100 JIS
5V/30mA
5V/30mA
Pulsed voltage to drive SSR,
14V/40mA
14V/40mA
R, S, N, L
Display ColorDisplay Color
0: Red color
0: Red color
1: Green color
1:
Green color
Communications
0: None
0: None
1: RS-485 interface (for C21)
1:
RS-485 interface (for C21)
2: RS-232 interface (for C21)
2:
RS-232 interface (for C21) Retransmit 4-20 mA / 0-20
3: Retransmit 4-20 mA / 0-20
3:
4:
Retransmit 1-5V /0-5V
4: Retransmit 1-5V /0-5V
Retransmit 0-10V (for C21)
5:
5: Retransmit 0-10V (for C21)
9:
Special order
9: Special order
Output 2Output 2
0: None
0: None
1: Form A relay 2A/240VAC
1:
Form A relay 2A/240VAC
2: Pulsed voltage to
2:
Pulsed voltage to
SSR, 5V / 30mA
drive SSR, 5V / 30mA
drive
3:
Isolated 4 - 20mA / 0 - 20mA
3: Isolated 4 - 20mA / 0 - 20mA
4:
Isolated 1 - 5V / 0 - 5V
4: Isolated 1 - 5V / 0 - 5V
5:
Isolated 0 - 10V
5: Isolated 0 - 10V
Triac output, 1A / 240VAC, SSR
6:
6: Triac output, 1A / 240VAC, SSR
7:
Isolated 20V/25mA transducer
7: Isolated 20V/25mA transducer
power
supply
power supply
8:
Isolated 12V/40mA transducer
8: Isolated 12V/40mA transducer
supply
power
power supply
9:
Isolated 5V/80mA transducer
9: Isolated 5V/80mA transducer
power
supply
power supply
A:
RS-485 interface (for C91)
A: RS-485 interface (for C91)
Pulsed voltage to drive SSR,
C:
C: Pulsed voltage to drive SSR,
14V/40mA
14V/40mA
B:
Special order
B: Special order
mA
(for C21)
mA (for C21)
(for
C21)
(for C21)
8
UM0C911C
Page 9
Accessories
OM94-6 = Isolated 1A / 240VAC Triac Output Module ( SSR )
OM94-6 = Isolated 1A / 240VAC Triac Output Module ( SSR )
= 14V / 40 mA SSR Drive Module
OM94-7 = 14V / 40 mA SSR Drive Module
OM94-7
= Isolated 4 - 20 mA / 0 - 20 mA Analog Output Module
OM96-3
OM96-3 = Isolated 4 - 20 mA /0-20mAAnalog Output Module
= Isolated 1 - 5V / 0 - 5V Analog Output Module
OM96-4
OM96-4 = Isolated1-5V/0-5VAnalog Output Module
= Isolated 0 -10V Analog Output Module
OM96-5
OM96-5 = Isolated 0 -10V Analog Output Module
= Isolated RS-485 Interface Module for C21
CM94-1
CM94-1 = Isolated RS-485 Interface Module for C21
= Isolated RS-232 Interface Module for C21
CM94-2
CM94-2 = Isolated RS-232 Interface Module for C21
= Isolated 4 - 20 mA / 0 - 20 mA Retrans Module for C21
CM94-3
CM94-3 = Isolated 4 - 20 mA /0-20mARetrans Module for C21
= Isolated 1 - 5V / 0 - 5V Retrans Module for C21
CM94-4
CM94-4 = Isolated1-5V/0-5VRetrans Module for C21
= Isolated 0 -10V Retrans Module for C21
CM94-5
CM94-5 = Isolated 0 -10V Retrans Module for C21
= Isolated RS-485 Interface Module for C91
CM96-1
CM96-1 = Isolated RS-485 Interface Module for C91
= Isolated 20V/25mA DC Output Power Supply
DC94-1
DC94-1 = Isolated 20V/25mA DC Output Power Supply
= Isolated 12V/40mA DC Output Power Supply
DC94-2
DC94-2 = Isolated 12V/40mA DC Output Power Supply
= Isolated 5V/80mA DC Output Power Supply
DC94-3
DC94-3 = Isolated 5V/80mA DC Output Power Supply
= RS-232 Interface Cable ( 2M )
CC94-1
CC94-1 = RS-232 Interface Cable ( 2M )
= Programming port cable for C21
CC91-1
CC91-1 = Programming port cable for C21
= Programming port cable for C91
CC91-2
CC91-2 = Programming port cable for C91
Related ProductsRelated Products
SNA10A = Smart Network Adaptor for third party software, which
SNA10A = Smart Network Adaptor for third party software, which
SNA10B = Smart Network Adaptor for BC-Net software, which
SNA10B = Smart Network Adaptor for BC-Net software, which
SNA12A = Smart Network Adaptor for programming port to RS-232
SNA12A = Smart Network Adaptor for programming port to RS-232
converts 255 channels of RS-485 or RS-422 to RS-232
converts
255 channels of RS-485 or RS-422 to RS-232
Network.
Network.
converts 255 channels of RS-485 or RS-422 to RS-232
converts
255 channels of RS-485 or RS-422 to RS-232
network.
network.
interface
interface
BC-Set = Configuration SoftwareBC-Set = Configuration Software
UM0C911C 8-1
Page 10
1-3 Programming Port1-3 Programming Port
Front Panel
Access Hole
1
2
3
46
5
Rear Terminal
C21
control board
Programming Port
pin 1
Power board
Open the housing TopviewofC91
Figure 1.2 Programming Port OverviewFigure 1.2 Programming Port Overview
A special connector can be used to touch the programming port which is connected to a PC for automatic configuration, also can be connected to an ATE system for automatic calibration and testing.
The programming port is used for off-line automatic setup and testing procedures only. Don't attempt to make any connection to these pins when the unit is used for a normal control purpose.
9
UM0C911B
Page 11
1- 4 Keys and Displays1- 4 Keys and Displays
KEYPADOPERATIONKEYPADOPERATION
SCROLL KEY :
SCROLL KEY :
This key is used to select a parameter to be viewed or adjusted.
KEY :
UP KEY :
UP
This key is used to increase the value of selected parameter.
KEY :
DOWN
DOWN KEY : This key is used to decrease the value of selected parameter.
R
press for C91 and C92, press for C21press for C91 and C92, press for C21
KEY :
RESET
RESET KEY : This key is used to:
1. Revert the display to display the process value or set point value (if DISP is set with SP1 for C21).
2. Reset the latching alarm, once the alarm condition is removed.
3. Stop the manual control mode , auto-tuning mode and calibration mode.
4. Clear the message of communication error and auto-tuning error.
5. Restart the dwell timer when the dwell timer has been time out.
6. Enter the manual control menu during failure mode occurs.
KEY :
ENTER
ENTER KEY :
Press for 5 seconds to:
1. Ener setup menu. The display shows .
2. Enter manual control mode during manual control mode or is selected.
3. Enter auto-tuning mode during auto-tuning mode AT(for C91) or (for C21) is selected.
4. Perform calibration to a selected parameter during the calibration procedure. Press for 4.2 seconds to select calibration mode.
Press for 5 seconds or longer .
UM0C911C
10
Page 12
OP1
OP2
Deviation Indicator
Output 2 Indicator
C
F
Output 1 Indicator
Process Unit Indicator
O1
O2
Output 2
Output 2
Indicator
Indicator
Output 1
Output 1 Indicator
Indicator
SP2SP1
PV
MAN
AT
Auto-tuning Indicator Manual Mode Indicator
R
4 Buttons for ease of control setup and
C91
set point adjustment.
Figure 1.3 Front Panel DescriptionFigure 1.3 Front Panel Description
Table 1.1 Display Form of CharactersTable 1.1 Display Form of Characters
A
E
I
N
B
F
C
G H
c Dh
O
J
P
K
Q
L
R
M
W
: Confused Character: Confused Character
OP1
PV
OP2
C
SP2SP1
MAN
Display program code of the product for 2.5 seconds.
F
The left diagram shows program no. 34 for C91 with version 24. The program no. for C21 is 33.
AT
R
Figure 1.4
Figure 1.4
C91
Display of Initial Stage
Display
11
UM0C911C
3 Silicone Rubber Buttons
3 Silicone Rubber Buttons
and set point adjustment.
and
S
X
T
Y
U
Z ?
V
=
of Initial Stage
C21
for ease of control setup
for
ease of control setup
set point adjustment.
C
Page 13
1- 5 Menu Overview1- 5 Menu Overview
User menu *1User menu *1
PV
SP1
SP2
H
C
PV
INPT UNIT
DP PB
TD CYC1 ADDR
5sec.
Manual
Manual
5 sec.
Mode
Mode
Manual
Manual
5 sec.
Mode
Mode
Auto-tuning
Auto-tuning
5 sec.
Mode
Mode
Valu e
TI
Valu e
C91
PV
SP1
SP2
MAN
MAN
AT
User Menu *1User Menu *1
(DISP=PV) (DISP=SP1)
C21
SP1
PV
or
SP1
PV
or
SP2
5 sec.
H
5 sec.
C
5 sec.
A-T
INPT UNIT
DP
PB
TI
TD CYC1 ADDR
Valu e
Manual
Manual
Mode
Mode
Manual
Manual
Mode
Mode
Auto-tuning
Auto-tuning
Mode
Mode
Valu e
Valu e
Valu e
Setup menu*1Setup menu*1
LOCK
INPT UNIT
DP INLO INHI
SP1L SP1H
SHIF FILT DISP
PB
TI
TD
OUT1 O1TY O1FT O1HY CYC1 OFST RAMP
RR
OUT2 O2TY O2FT O2HY CYC2
CPB
DB
ALMD
COMM
ADDR BAUD DATA
PARI
STOP RELO REHI SEL1 SEL2 SEL3 SEL4 SEL5 SEL6 SEL7 SEL8
Calibration ModeCalibration Mode
6.2 sec.
Valu e
Press for 5 seconds to perform calibration.
Apply these modes will break the control loop and change some of the previous setting data. Make sure that if the system is allowable to apply these modes.
*1:
The flow chart shows a complete listing of all parameters. For actual application the number of available parameters depends on setup conditions, and should be less than that shown in the flow chart.
*2:
Release , press again for 2 seconds or longer (but not longer than 3 seconds), then release to enter the calibration menu.
Valu e
ADLO
ADHI RTDL RTDH CJLO
CJHI
*2
7.4 sec.
2 sec.
Valu e
Valu e
UM0C911C
12
Page 14
1-6 Parameter Descriptions1-6 Parameter Descriptions
Parameter Notation
LOCK
13
Parameter Description
Set point for output 1
SP1
Set point for output 2 when output 2 performs
SP2
alarm function or dwell timer
Select parameters to be locked
Input sensor selection
INPT
UM0C911A
Range
Low: SP1L High :SP1H
Low: -19999 High :45536
0 : No parameter
1 : Setup data are
2 : Setup data and
3 : All data are locked
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
is locked
locked
User data except Set point are locked
J type thermocouple
:
K type thermocouple
:
T type thermocouple
:
E type thermocouple
:
B type thermocouple
: :
R type thermocouple
S type thermocouple
:
N type thermocouple
:
L type thermocouple
: :
PT 100 ohms DIN curve
:
PT 100 ohms JIS curve
:
4 - 20 mA linear current input
:
0 - 20 mA linear current input
:
0 - 60 mV linear millivolt input
:
0 - 1V linear voltage input
:
0 - 5V linear voltage
input
:
1 - 5V linear voltage
input
:
0 - 10V linear voltage
input
Default Value
25.0 C (77.0 F)BB
10.0 C (18.0 F)BB
0
1
(0)
Page 15
Parameter Notation
UNIT
DP
INLO
INHI
SP1L
SP1H
SHIF
FILT
Parameter Description
Input unit selection
Decimal point selection
Input low sale value
Input high scale value
Low limit of set point value
High limit of set point value
PV shift (offset) value
Filter damping time constant of PV
0
1
2
0
1
2
3
Low:
Low:
Low:
Low:
Low:
0
1
2
3
4
5
6
7
8
9
UM0C911A
-19999
INLO+50
-19999
SP1L
-200.0 C
(-360.0 F)LL
:
:
:
:
:
:
:
:
:
:
Range
Degree C unit
:
Degree F unit
:
:
Process unit
No decimal
:
point
1 decimal digit
:
2 decimal digits
:
3 decimal digits
:
High:
High:
High:
High:
200.0 C
High:
( 360.0 F)LL
0 second time
constant
0.2 second time constant
0.5 second time
constant 1 second time
constant 2 seconds time
constant 5 seconds time
constant 10 seconds time
constant 20 seconds time
constant 30 seconds time
constant 60 seconds time
constant
45486
45536
45536
45536
Default Value
0
(1)
1
-17.8 C
L
L
(0F)
93.3 C
L
(200.0 F)
-17.8 C (0 F)
L
537.8 C
(1000 F)
L
0.0
2
14
L
L
L
Page 16
Parameter Notation
DISP
OUT1
O1TY
O1FT
O1HY
CYC1
Parameter Description
Normal display selection
Proportional band value
PB
Integral time value
TI
Derivative time value
TD
Output 1 function
Output 1 signal type
Output 1 failure transfer mode
Output 1 ON-OFF control hysteresis
Output 1 cycle time
OFST Offset value for P control
Range
0
1
Low: 0
Low:
Low:
0
1
0
1
2
3
4
5
6
7
8
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0 % to continue output 1 control function as the unit fails, or select OFF (0) or ON (1) for ON-OFF control.
: Display process
value normally
: Display set point 1
value normally
High:
High:
0
High:
0
Reverse (heating )
:
control action
:
Direct (cooling) control action
: Relay output
: Solid state relay
drive output
: Solid state relay
output
: 4-20 mA current
module
:
0 - 20 mA current
module
:
0 - 1V voltage module
:
0 - 5V voltage module
:
1 - 5V voltage module
:
0 - 10V voltage module
500.0 C
(900.0 F)LL
1000 sec
360.0 sec
(18.0 F)LL
Low: 0.1 High: 50.0 C(90.0 F)BB
Low: 0.1 High: 90.0 sec.
High: 100.0 %
Low: 0
Default Value
0
10.0 C
100
25.0
0
0
0
0.1 C
(0.2 F)LL
18.0
25.0
15
UM0C911A
Page 17
Parameter Notation
RAMP
RR
OUT2
O2TY
O2FT
Parameter Description
Ramp function selection
Ramp rate
Output 2 function
Output 2 signal type
Output 2 failure transfer mode
Range
0 : No Ramp Function
1 : Use unit/minute as
2 : Use unit/hour as
Low: 0
0 : Output 2 No Function
1 : Dwell timer action
2 : Deviation High Alarm
3 : Deviation Low Alarm
4 : Deviation band out of
5 : Deviation band in
6 : Process High Alarm
7 : Process Low Alarm
8 : Cooling PID Function
0
1
2
3
4
5
6
7
8
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0 % to continue output 2 control function as the unit fails, or select ON (0) or OFF (1) for alarm and dwell timer function.
UM0C911A
Ramp Rate
Ramp Rate
500.0 C
High:
(900.0 F)LL
band Alarm
band Alarm
:
Relay output
:
Solid state relay drive output
:
Solid state relay output
:
4 - 20 mA current module
:
0 - 20 mA current module
0 - 1V voltage
:
module 0 - 5V voltage
:
module
:
1 - 5V voltage module
:
0 - 10V voltage module
Default Value
0
0.0
2
0
0
16
Page 18
Parameter Notation
O2HY
CYC2
CPB
DB
ALMD
COMM
ADDR
BAUD
Parameter Description
Output 2 hysteresis value when output 2 performs alarm function
Output 2 cycle time
Cooling proportional band value
Heating-cooling dead band (negative value= overlap)
Alarm operation mode
Communication
function
Address assignment of digital communication
Baud rate of digital communication
Range
50.0 C
Low: 0.1
Low: 0.1
Low: 50
Low: -36.0
0
1
2 3
0 : No communication
1 : Modbus RTU mode
2
3
4
5
6
Low: 1 High: 255
0
1
2
3
4
5
6
High:
(90.0 F)LL
High: 90.0 sec.
High: 300 %
High: 36.0 %
: Normal alarm action
: Latching alarm action : Hold alarm action
: Latching & actionHold
protocol
:4-20mA retransmission
output
:0-20mA retransmission
output
:0-5V retransmission
output
:1-5V retransmission
output
:0-10V retransmission
output
:
2.4 Kbits/s baud rate
:
4.8 Kbits/s baud rate
:
9.6 Kbits/s baud rate
:
14.4 Kbits/s baud rate
:
19.2 Kbits/s baud rate
:
28.8 Kbits/s baud rate
:
38.4 Kbits/s baud rate
Default Value
0.1 C
(0.2 F)LL
18.0
100
0
0
1
2
17
UM0C911C
Page 19
Parameter Notation
DATA
PARI
STOP
RELO
REHI
SEL1
Parameter Description
Data bit count of digital communication
Parity bit of digital communication
Stop bit count of digital communication
Retransmission low scale value
Retransmission high scale value
Select 1'st parameter for user menu
Range
0 : 7 data bits
1 : 8 data bits
0 : Even parity
1 : Odd parity
2 : No parity bit
0 : One stop bit
1 : Two stop bits
Low: -19999
Low: -19999
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
High: 45536
High: 45536
:No parameter selected
:LOCK is put ahead
:INPT is put ahead
:UNIT is put ahead
:DP is put ahead
:SHIF is put ahead
:PB is put ahead
:TI is put ahead
:TD is put ahead
:O1HY is put ahead
:CYC1 is put ahead
:OFST is put ahead
:RR is put ahead
:O2HY is put ahead
:CYC2 is put ahead
:CPB is put ahead
:DB is put ahead
:ADDR is put ahead
Default Value
1
0
0
0.0 C
(32.0 F)LL
100.0 C
(212.0 F)LL
2
UM0C911C
18
Page 20
Parameter Notation
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8
Parameter Description
Select 2'nd parameter for user menu
Select 3'rd parameter for user menu
Select 4'th parameter for user menu
Select 5'th parameter for user menu
Select 6'th parameter for user menu
Select 7'th parameter for user menu
Select 8'th parameter for user menu
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Range
Default Value
3
4
6
7
8
10
17
19
UM0C911A
Page 21
Chapter 2 InstallationChapter 2 Installation
Dangerous voltages capable of causing death are sometimes
Dangerous voltages capable of causing death are sometimes
present in this instrument. Before installation or beginning any
present
in this instrument. Before installation or beginning any
cleaning or troubleshooting procedures the power to all equipment
cleaning
or troubleshooting procedures the power to all equipment
must be switched off and isolated. Units suspected of being faulty
must
be switched off and isolated. Units suspected of being faulty
must be disconnected and removed to a properly equipped
must
be disconnected and removed to a properly equipped
workshop for testing and repair. Component replacement and
workshop
internal adjustments must be made by a qualified maintenance
internal
person only.
person
for testing and repair. Component replacement and
adjustments must be made by a qualified maintenance
only.
This instrument is protected throughout by -- .
To minimize the possibility of fire or shock hazards, do not expose
To
minimize the possibility of fire or shock hazards, do not expose
this instrument to rain or excessive moisture.
this
instrument to rain or excessive moisture.
Do not use this instrument in areas under hazardous
Do not use this instrument in areas under hazardous
conditions such as excessive shock, vibration, dirt, moisture,
conditions
corrosive gases or oil. The ambient temperature of the areas should
corrosive
not exceed the maximum rating specified in Chapter 6.
not
Don't use harsh chemicals, volatile solvent such as thinner or strong
Don't
detergents to clean the instrument in order to avoid deformation or
detergents
discoloration.
discoloration.
such as excessive shock, vibration, dirt, moisture,
gases or oil. The ambient temperature of the areas should
exceed the maximum rating specified in Chapter 6.
Remove stains from this instrument using a soft, dry cloth.
Remove stains from this instrument using a soft, dry cloth.
use harsh chemicals, volatile solvent such as thinner or strong
to clean the instrument in order to avoid deformation or
Double InsulationThis instrument is protected throughout by -- .
Insulation
Double
2-1 Unpacking2-1 Unpacking
Upon receipt of the shipment remove the unit from the carton and
Upon receipt of the shipment remove the unit from the carton and
inspect the unit for shipping damage.
inspect
the unit for shipping damage.
If any damage due to transit , report and claim with the carrier.
If
any damage due to transit , report and claim with the carrier.
Write down the model number, serial number, and date code for
Write
down the model number, serial number, and date code for
future reference when corresponding with our service center. The
future
reference when corresponding with our service center. The
serial number (S/N) and date code (D/C) are labeled on the box and
serial
number (S/N) and date code (D/C) are labeled on the box and
the housing of control.
the
housing of control.
2-2 Mounting2-2 Mounting
Make panel cutout to dimension shown in Figure 2.1.Make panel cutout to dimension shown in Figure 2.1. Take the mounting clamp away and insert the controller into
Ta ke the mounting clamp away and insert the controller into
cutout. Install the mounting clamp back.
panel cutout. Install the mounting clamp back.
panel
UM0C911B
20
Page 22
Figure 2.1 Mounting DimensionsFigure 2.1 Mounting Dimensions
+0.5
_
45
0
+0.3
22.2
_
0
Panel
Panel
98.0mm
86 mm
94 mm
12.5mm
45 mm
45 mm
10.0mm
MOUNTING CLAMP
C21
SCREW
C91
21
UM0C911B
Page 23
2 - 3 Wiring Precautions2 - 3 Wiring Precautions
Before wiring, verify the label for correct model number and
Before wiring, verify the label for correct model number and
*
options. Switch off the power while checking.
options.
Switch off the power while checking.
Care must be taken to ensure that maximum voltage rating
must be taken to ensure that maximum voltage rating
Care
*
specified on the label are not exceeded.
specified
It is recommended that power of these units to be protected by
It
*
fuses or circuit breakers rated at the minimum value possible.
fuses
All units should be installed inside a suitably grounded metal
All
*
enclosure to prevent live parts being accessible from human
enclosure
hands and metal tools.
hands
All wiring must conform to appropriate standards of good practice
All
*
and local codes and regulations. Wiring must be suitable for
and
voltage, current, and temperature rating of the system.
voltage,
Beware not to over-tighten the terminal screws. The torque should
Beware
*
not exceed 1 N-m ( 8.9 Lb-in or 10.2 KgF-cm )
not exceed
Unused control terminals should not be used as jumper points as
Unused
*
they may be internally connected, causing damage to the unit.
they
Verify that the ratings of the output devices and the inputs as
Verify
*
specified in Chapter 6 are not exceeded.
specified
Except the thermocouple wiring, all wiring should use stranded
Except
*
copper conductor with maximum gauge 18 AWG.
copper
on the label are not exceeded.
is recommended that power of these units to be protected by
or circuit breakers rated at the minimum value possible.
units should be installed inside a suitably grounded metal
to prevent live parts being accessible from human
and metal tools.
wiring must conform to appropriate standards of good practice
local codes and regulations. Wiring must be suitable for
current, and temperature rating of the system.
not to over-tighten the terminal screws. The torque should
1 N-m ( 8.9 Lb-in or 10.2 KgF-cm )
control terminals should not be used as jumper points as
may be internally connected, causing damage to the unit.
that the ratings of the output devices and the inputs as
in Chapter 6 are not exceeded.
the thermocouple wiring, all wiring should use stranded
conductor with maximum gauge 18 AWG.
UM0C911B
22
Page 24
3.2mm min.
2.0mm
0.08" max.
7.0mm max.
4.5 ~7.0 mm
0.18" ~0.27"
Figure 2.2
Figure 2.2
Termination for C91
Lead Termination for C91
Lead
Figure 2.3
Figure 2.3
Termination for C21
Lead Termination for C21
Lead
OP2
+
3
2
1
N
L
90-250 VAC
47-63 Hz,10VA
V+,mA+
PTA
8 9
RTD
A
CAT.II
23
2A/240 VAC 2A/240 VAC
__
V,mA
_
TC
TC+
PTB
PTB
10
_
+
B
B
_
+
V
I
Figure 2.4
Figure 2.4
Terminal Connection
Rear Terminal Connection
Rear
C21
for
for C21
UM0C911B
OP1
__
+
5
L
RE+ RE
TX1 TX2
TXD RXD
RS-232
6
12 13 14
RS-485 or
RETRANSMISSION
4
COM
11
50 C max. Air ambient Use copper conductors (except on T/C input )
7
Page 25
TX2
1
OP2
RS-485
TX1
2
A
RTD
I
50 C max. air ambient
L
Use copper conductors ( except on T/C input )
Figure 2.5
Figure 2.5
Rear Terminal Connection
Rear
C91
for
for C91
3
B
+
+
4
V
B
5
Terminal Connection
+
PTA
TC+
TC
L
6
N
7
NC
8
NO
OP1
9
+
C
10
CAT.II
UM0C911B
24
Page 26
2 - 4 Power Wiring2 - 4 Power Wiring
The controller is supplied to operate at 11-26 VAC / VDC or 90-250
The controller is supplied to operate at 11-26 VAC / VDC or 90-250
VAC. Check that the installation voltage corresponds with the power
VAC.
Check that the installation voltage corresponds with the power
rating indicated on the product label before connecting power to
rating
indicated on the product label before connecting power to
the controller. Near the controller a fuse and a switch rated at
the
controller. Near the controller a fuse and a switch rated at
2A/250VAC should be equiped as shown in the following diagram.
2A/250VAC
which provides adequate protection against electric shock. The
which
enclosure must be connected to earth ground.
enclosure
Local requirements regarding electrical installation should be rigidly
Local
observed. Consideration should be given to prevent from
observed.
unauthorized person access to the power terminals.
unauthorized
should be equiped as shown in the following diagram.
C21
C91
L
1
N
2
This equipment is designed for installation in an enclosure
This equipment is designed for installation in an enclosure
Fuse
6
2A/250VAC
7
Figure 2.7 Power Supply ConnectionsFigure 2.7 Power Supply Connections
~
90 250 VAC or
~
11 26 VAC / VDC
provides adequate protection against electric shock. The
must be connected to earth ground.
requirements regarding electrical installation should be rigidly
Consideration should be given to prevent from
person access to the power terminals.
2-5 Sensor Installation Guidelines2-5 Sensor Installation Guidelines
Proper sensor installation can eliminate many problems in a control
Proper sensor installation can eliminate many problems in a control
The probe should be placed so that it can detect any
system. The probe should be placed so that it can detect any
system. temperature
temperature change with minimal thermal lag. In a process that
requires
requires fairly constant heat output, the probe should be placed
closed
closed to the heater. In a process where the heat demand is variable,
the
the probe should be closed to the work area. Some experiments with
probe
probe location are often required to find this optimum position.
change with minimal thermal lag. In a process that
fairly constant heat output, the probe should be placed
to the heater. In a process where the heat demand is variable,
probe should be closed to the work area. Some experiments with
location are often required to find this optimum position.
a liquid process, addition of a stirrer will help to eliminate thermal
In
In a liquid process, addition of a stirrer will help to eliminate thermal
Since the thermocouple is basically a point measuring device,
lag.
lag. Since the thermocouple is basically a point measuring device,
more than one thermocouple in parallel can provide an
placing
placing more than one thermocouple in parallel can provide an
temperature readout and produce better results in most
average
average temperature readout and produce better results in most
air
heated processes.
air heated processes.
25
UM0C911B
Page 27
Proper sensor type is also a very important factor to obtain precise
Proper sensor type is also a very important factor to obtain precise
measurements. The sensor must have the correct temperature range
measurements. to
to meet the process requirements. In special processes the sensor
meet the process requirements. In special processes the sensor
might need to have different requirements such as leak-proof, anti-
might
need to have different requirements such as leak-proof, anti-
vibration, antiseptic, etc.
vibration,
Standard
Standard sensor limits of error are 4 degrees F ( 2 degrees C )
or
or 0.75% of sensed temperature (half that for special ) plus drift
0.75% of sensed temperature (half that for special ) plus drift
caused by improper protection or an over-temperature occurrence.
caused
This error is far greater than controller error and cannot be corrected
This
error is far greater than controller error and cannot be corrected
on the sensor except by proper selection and replacement.
on
the sensor except by proper selection and replacement.
The sensor must have the correct temperature range
antiseptic, etc.
sensor limits of error are 4 degrees F (2degrees C )
AA
AA
by improper protection or an over-temperature occurrence.
2-6 Sensor Input Wiring2-6 Sensor Input Wiring
C21 C91
PTA
TC+, V+
TC+, V+
PTB, mA+
mA+
PTB,
TC-, V-
TC-, V-
mA-
PTB, mA-
PTB,
83 94
10 5
+
+
_
_
TC V mA RTD
Figure 2.8 Sensor Input WiringFigure 2.8 Sensor Input Wiring
2-7 Control Output Wiring2-7 Control Output Wiring
C21 C91
+
5610
_
Figure 2.9
Figure 2.9
Output 1 Relay or Triac (SSR) to Drive Load
Output
9
1 Relay or Tri ac (SSR) to Drive Load
UM0C911B 26
A
RTD
+
B
V
_
B
LOAD
120V/240VAC
120V/240VAC
Mains Supply
Mains Supply
Page 28
C21 C91
+
5
10
6
9
_
Three Phase
Three Phase
Delta
Delta
Heater
Heater
Load
Load
Figure 2.10
Figure 2.10
Output 1 Relay or Triac (SSR) to Drive Contactor
Output
1 Relay or Tri ac (SSR) to Drive Contactor
Contactor
No Fuse
No Fuse
Breaker
Breaker
120V /240V
120V /240V
Mains Supply
Mains
Supply
Three
Three
Phase
Phase
Heater
Heater
Power
Power
C21 C91
5 6
+
10
9
_
30mA /5V
30mA / 5V
Pulsed
Pulsed
Voltage
Voltage
SSR
+
_
Internal CircuitInternal Circuit
5V
0V
Figure 2.11 Output 1 Pulsed Voltage to Drive SSRFigure 2.11 Output 1 Pulsed Voltage to Drive SSR
27
UM0C911B
33
33
Load
120V /240V
120V /240V
Supply
Mains Supply
Mains
+
Page 29
C21 C91
5
10
6
9
0-20mA,
0 - 20mA,
- 20mA
4-20mA
4
+
Load
_
Figure 2.12 Output 1 Linear CurrentFigure 2.12 Output 1 Linear Current
Maximum Load
Maximum Load
500 ohms
500
ohms
C21 C91
5
10
6
9
0-1V, 0-5V
0 - 1V, 0 - 5V
- 5V, 0 - 10V
1-5V,0-10V
1
+
Minimum Load
Minimum Load
Load
10Kohms
10
_
Figure 2.13 Output 1 Linear VoltageFigure 2.13 Output 1 Linear Voltage
C21 C91
+
3 4
_
Figure 2.14
Figure 2.14
Output 2 Relay or Triac (SSR) to Drive Load
Output
2 Relay or Tri ac (SSR) to Drive Load
LOAD
2
1
UM0C911B 28
120V/240VAC
120V/240VAC
Mains Supply
Mains Supply
K ohms
Page 30
C21 C91
+
3
2
4
1
_
No Fuse
Three Phase
Three Phase
Delta
Delta
Heater
Heater
Load
Figure 2.15
Figure 2.15
Output 2 Relay or Triac (SSR) to Drive Contactor
Output
Load
2 Relay or Tri ac (SSR) to Drive Contactor
Contactor
No Fuse
Breaker
Breaker
120V /240V
120V /240V
Mains Supply
Mains
Supply
Three
Three
Phase
Phase
Heater
Heater
Power
Power
C21 C91
+
_
3 4
+
2
1
_
30mA /5V
30mA / 5V
Pulsed
Pulsed
Voltage
Voltage
SSR
+
_
Internal CircuitInternal Circuit
5V
0V
Figure 2.16 Output 2 Pulsed Voltage to Drive SSRFigure 2.16 Output 2 Pulsed Voltage to Drive SSR
C21 C91
+
3
2
0-20mA,
0 - 20mA,
- 20mA
4-20mA
4
_
4
1
Figure 2.17 Output 2 Linear CurrentFigure 2.17 Output 2 Linear Current
29
UM0C911B
33
33
Load
120V /240V
120V /240V
Mains Supply
Mains
+
+
Maximum Load
Maximum Load
Load
500 ohms
500
_
Supply
ohms
Page 31
C21 C91
3 4
Figure 2.18 Output 2 Linear VoltageFigure 2.18 Output 2 Linear Voltage
2-8 Alarm Wiring2-8 Alarm Wiring
Figure 2.19 Alarm Output to Drive LoadFigure 2.19 Alarm Output to Drive Load
C21 C91
3 4
Figure 2.20 Alarm Output to Drive ContactorFigure 2.20 Alarm Output to Drive Contactor
2 1
C21 C91
3
2
4
1
2 1
0-1V, 0-5V
0 - 1V, 0 - 5V
- 5V, 0 - 10V
1-5V,0-10V
1
LOAD
Three Phase
Three Phase
Delta
Delta
Heater
Heater
Load
Load
+
Load
_
120V/240VAC
120V/240VAC
Mains Supply
Mains
Supply
Contactor
Relay Output to
Relay Output to
Contactor
Drive Contactor
Drive
Minimum Load
Minimum Load
10Kohms
10
K ohms
120V /240V
120V /240V
Supply
Mains Supply
Mains
Three
Three
Phase
Phase
Heater
Heater
Power
No Fuse
No Fuse
Breaker
Breaker
Power
UM0C911B 30
Page 32
2-9 Data Communication2-9 Data Communication
C21 C91
TX1
TX2
C21 C91
TX1
TX2
TX1
12
2
TX2
13
1
Twisted-Pair WireTwisted-Pair Wire
12
2
13
1
TX1
TX2
RS-485 to RS-232
RS-485 to RS-232
adaptor
network adaptor
network
SNA10A or
SNA10A or
SNA10B
SNA10B
TX1
TX2
Max. 247 units can be linkedMax. 247 units can be linked
RS-232
PC
TX1
TX2
C21 C91
12 13
TX1
2
TX2
1
Terminator
Terminator
ohms / 0.5W
220 ohms / 0.5W
220
Figure 2.21 RS-485 WiringFigure 2.21 RS-485 Wiring
31
UM0C911B
Page 33
RS-232
C21
TXD
12
RXD
13
COM
11
Figure 2.22
Figure 2.22
RS-232 Wiring
RS-232
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
must be modified according to the following circuit diagram.
must
be modified according to the following circuit diagram.
C21
TX1 RD
TXD
12
TX2 TD
RXD
13
COM
COM
11
Figure 2.23
Figure 2.23
Configuration of RS-232 Cable
Configuration of RS-232 Cable
9-pin
9-pin
RS-232
RS-232
port
port
CC94-1
Wiring
To DTE ( PC) RS-232 PortTo DTE ( PC ) RS-232 Port
GND
1
2
3
4
5
Female DB-9Female DB-9
PC
1 DCD
1 DCD
6
RD
2RD
2
TD
3
3TD
7
DTR
4
4DTR
8
GND
5
5 GND
DSR
6
6DSR
9
RTS
7
7RTS
CTS
8
8CTS
RI
9
9RI
UM0C911B 32
Page 34
Chapter 3 ProgrammingChapter 3 Programming
Press for 5 seconds and release to enter setup menu. Press to select the desired parameter. The display indicates the parameter symbol. Press or to view or adjust the value of the selected parameter.
3-1 Lockout3-1 Lockout
There are four security levels can be selected by using LOCK parameter.
NONE
If is selected for LOCK, then no parameter is locked.
NONE
SET
If is selected for LOCK, then all setup data are locked.
SET
USER
If is selected for LOCK, then all setup data as well as user data
USER
section
(refer to ) except set point are locked to prevent from being changed.
ALL
If is selected for LOCK, then all parameters are locked to prevent
ALL
from being changed.
3-2 Signal Input3-2 Signal Input
INPT:
Selects the sensor type or signal type for signal input.
INPT:
Range:
Range:
UNIT:
Selects the process unit
UNIT:
Range:
Range:
DP:
Selects the resolution of process value.
DP:
Range:
Range:
INLO:
Selects the low scale value for the linear type input.
INLO:
INHI : Selects the high scale value for the linear type input.
INHI
:
How to use INLO and INHI :How to use INLO and INHI :
If4-20mAisselected for INPT,let SL specifies the input signal low ( ie. 4 mA ), SH specifies the input signal high ( ie. 20 mA ), S specifies the current input signal value, the conversion curve of the process value is shown as follows :
1-5
section 1-5
( thermocouple ) J_TC, K_TC, T_TC, E_TC, B_TC, R_TC
S_TC, N_TC, L_TC ( RTD ) PT.DN, PT.JS (linear ) 4-20, 0-20, 0-60, 0-1V, 0-5V, 1-5V, 0-10
C, F, PU( process unit ). If the unit is neither C nor F,
LL L L
then selects PU.
( for T/C and RTD ) NO.DP, 1-DP (for linear ) NO.DP, 1-DP, 2-DP, 3-DP
33
UM0C911C
Page 35
process value
INHI
PV
INLO
SL SHS
input signal
Formula : PV = INLO + ( INHI INLO )Formula : PV = INLO + ( INHI INLO )
Example : A 4-20 mA current loop pressure transducer with range
Example : A 4-20 mA current loop pressure transducer with range
0 - 15 kg/cm is connected to input, then perform the
0
- 15 kg/cm is connected to input, then perform the
following setup :
following
INPT=4-20 INLO=0.00
INPT = 4 - 20 INLO = 0.00
INHI = 15.00 DP = 2-DP
INHI
course, you may select other value for DP to alter the
Of
Of course, you may select other value for DP to alter the
resolution.
resolution.
2
setup :
= 15.00 DP = 2-DP
Figure 3.1
Figure 3.1
Conversion Curve for
Conversion
Linear Type Process Value
Linear
Curve for
Ty pe Process Value
SSLS SL
SH SLSH SL
3-3 Control Outputs3-3 Control Outputs
There are 4 kinds of control modes can be configured as shown in Table 3.1
Table 3.1
Table 3.1 Heat-Cool Control Setup ValueTable 3.1 Heat-Cool Control Setup Value
Control Modes
Heat only
Cool only
Heat: PID Cool: ON-OFF
Heat: PID Cool: PID
: Don't care
:Adjust to met process
requirements
OUT1 OUT2 O1HY O2HY CPB
REVR
DIRT
REVR
REVR
DE.HI
COOL
:Required if ON-OFF control
is configured
UM0C911A 34
DB
Page 36
Heat Only ON-OFF Control : Select REVR for OUT1, Set PB to 0,
Heat Only ON-OFF Control : Select REVR for OUT1, Set PB to 0,
is used to adjust dead band for ON-OFF control, The output 1
O1HY is used to adjust dead band for ON-OFF control, The output 1
O1HY hysteresis
hysteresis ( O1HY ) is enabled in case of PB=0.Theheat only
on-off
on-off control function is shown in the following diagram :
SP1 O1HY
( O1HY ) is enabled in case of PB = 0 . The heat only
control function is shown in the following diagram :
PV
SP1
Dead band = O1HY
OUT1 Action
ON
OFF
Figure 3.2 Heat Only
Figure 3.2 Heat Only
ON-OFF Control
ON-OFF
The ON-OFF control may introduce excessive process oscillation even
The ON-OFF control may introduce excessive process oscillation even
hysteresis is minimized to the smallest. If ON-OFF control is set ( ie.
if hysteresis is minimized to the smallest. If ON-OFF control is set ( ie.
if
= 0 ), TI, TD, CYC1, OFST, CYC2, CPB, DB will be hidden and have
PB
PB=0),TI,TD,CYC1,OFST, CYC2, CPB, DB will be hidden and have
function to the system. The auto-tuning mode and bumpless
no
no function to the system. The auto-tuning mode and bumpless
will be disabled too.
transfer
transfer will be disabled too.
Heat
only P ( or PD ) control :
Heat onlyP(orPD)control :
is used to adjust the control offset ( manual reset ).
OFST
OFST is used to adjust the control offset ( manual reset ).
hidden OFST
hidden OFST Function :
stabilized
stabilized ) if the process value is lower than the set point a definite
value,
value, say 5 C, while 20 C is used for PB, that is lower 25 %,
PB is not equal to 0. OFST is measured by
if
if PB is not equal to 0. OFST is measured by
with range 0 - 100.0 %. In the steady state ( ie. process has been
%
% with range 0 - 100.0 %. In the steady state ( ie. process has been
) if the process value is lower than the set point a definite
say 5C,while 20 C is used for PB, that is lower 25 %,
LL
LL
35
Control
REVR for OUT1, set TI to 0,
Select
Select REVR for OUT1, set TI to 0,
Function :
UM0C911A
Time
Time
O1HY
O1HY is
is
Page 37
then increase OFST 25 %, and vice versa. After adjusting OFST value,
then increase OFST 25 %, and vice versa. After adjusting OFST value,
process value will be varied and eventually, coincide with set point.
the process value will be varied and eventually, coincide with set point.
the
the P control ( TI set to 0 ), the auto-tuning is disabled.
Using
Using the P control ( TI set to 0 ), the auto-tuning is disabled.
to section 3-12 " manual tuning " for the adjustment of PB and
Refer
Refer to section 3-12 " manual tuning " for the adjustment of PB and
Manual reset ( adjust OFST ) is not practical because the load may
TD.
TD. Manual reset ( adjust OFST ) is not practical because the load may
from time to time and often need to adjust OFST repeatedly.
change
change from time to time and often need to adjust OFST repeatedly.
PID control can avoid this situation.
The
The PID control can avoid this situation.
Heat only PID control :
Heat only PID control :
be zero. Operate auto-tuning for the new process, or set PB, TI
not be zero. Operate auto-tuning for the new process, or set PB, TI
not
TD with historical values. See section 3-11 for auto-tuning
and
and TD with historical values. See section 3-11 for auto-tuning
operation.
operation. If the control result is still unsatisfactory, then use manual
tuning
tuning to improve the control . See section 3-12 for manual tuning. The
unit
unit contains a algorithm to achieve a
small
small overshoot and very quick response
tuned.
tuned.
Coolonlycontrol:ON-OFFcontrol,P(PD)control andPID
Cool only control:ON-OFF control, P ( PD ) control and PID
control can be used for cool control. Set OUT1 to DIRT ( direct
control
action ). The other functions for control,
action
onlyP(PD) cool only PID
only
descriptions for heat only control except that the output variable
descriptions
( and action ) for the cool control is inverse to the heat control.
(
NOTE :
NOTE :
undershoot problems in the process. TheP(orPD)control will result
undershoot in
in a deviation process value from the set point. It is recommended to
use
use PID control for the Heat-Cool control to produce a stable and zero
offset
offset process value.
If the control result is still unsatisfactory, then use manual
to improve the control . See section 3-12 for manual tuning. The
contains a algorithm to achieve a
overshoot and very quick response
can be used for cool control. Set OUT1 to DIRT ( direct
). The other functions for control,
control and control are same as
control
P ( PD ) cool only PID
and action ) for the cool control is inverse to the heat control.
The
The ON-OFF control may result excessive overshoot and
ON-OFF control may result excessive overshoot and
problems in the process. The P ( or PD ) control will result
a deviation process value from the set point. It is recommended to
PID control for the Heat-Cool control to produce a stable and zero
process value.
Selecting
Selecting REVR for OUT1, PB and TI should
clever PID and Fuzzy very
very clever PID and Fuzzy very
very
REVR for OUT1, PB and TI should
the process if it is properly
to
to the process if it is properly
cool only ON-OFF cool
only ON-OFF cool
cool
and control are same as
for heat only control except that the output variable
Setup Required :
Other Setup Required :
Other
& O2TY are set in accordance with the types of OUT1 & OUT2
O1TY
O1TY & O2TY are set in accordance with the types of OUT1 & OUT2
installed.
installed. CYC1 & CYC2 are selected according to the output 1 type (
O1TY
O1TY ) & output 2 type ( O2TY ). Generally, selects 0.5 ~ 2 sec. for
CYC1,
CYC1, if SSRD or SSR is used for O1TY; 10 ~ 20 sec. if relay is used
for
for O1TY, and CYC1 is ignored if linear output is used. Similar condition
is
is applied for CYC2 selection.
CYC1 & CYC2 are selected according to the output 1 type (
) & output 2 type ( O2TY ). Generally, selects 0.5 ~ 2 sec. for
if SSRD or SSR is used for O1TY; 10 ~ 20 sec. if relay is used
O1TY, and CYC1 is ignored if linear output is used. Similar condition
applied for CYC2 selection.
CYC1, O2TY, CYC2, O1FT, O2FT
O1TY,
O1TY, CYC1, O2TY, CYC2, O1FT, O2FT
UM0C911A 36
Page 38
You can use the program for the new process or directly
auto-tuning
auto-tuning
set the appropriate values for PB, TI & TD according to the historical records for the repeated systems. If the control behavior is still inadequate, then use to improve the control. See
3-12
section
section 3-12
CPB Programming : The cooling proportional band is measured by %
CPB Programming :
for manual tuning.
tuning
manual tuning
manual
of PB with range 50~300. Initially set 100% for CPB and examine the cooling effect. If cooling action should be enhanced then decrease CPB, if cooling action is too strong then increase CPB. The value of CPB is related to PB and its value remains unchanged throughout the auto-tuning procedures.
Adjustment of CPB is related to the cooling media used. For air is used as cooling media, adjust CPB at 100(%).For oil is used as cooling media, adjust CPB at 125(%). For water is used as cooling media, adjust CPB at 250(%).
DB Programming:
DB Programming: Adjustment of DB is dependent on the system requirements. If more positive value of DB ( greater dead band ) is used, an unwanted cooling action can be avoided but an excessive overshoot over the set point will occur. If more negative value of DB ( greater overlap ) is used, an excessive overshoot over the set point can be minimized but an unwanted cooling action will occur. It is adjustable in the range -36.0% to 36.0 % of PB. A negative DB value shows an overlap area over which both outputs are active. A positive DB value shows a dead band area over which neither output is active.
Output 2 ON-OFF Control ( Alarm function ):
Output 2 ON-OFF Control ( Alarm function ):
The output 2 can also be configured as alarm function. There are 6 kinds of alarm functions can be selected for output 2, these are: (deviation high alarm ), DE.LO DB.HI
(deviation low alarm ), (deviation band out of band alarm
DE.LO DB.HI
DB.LO PV.HI
), (deviation band in band alarm), (process high alarm )
DB.LO PV.HI
PV.LO Figure 3.3 Figure 3.4
and ( process low alarm ). Refer to and for
PV.LO Figure
DE.HI
DE.HI
3.3 Figure 3.4
the description of deviation alarm and process alarm with normal alarm mode ( NORM is set for ALMD ).
37
UM0C911A
Page 39
SV+SP2
SV+SP2-O2HY
PV
OUT2=DE.HI
OUT2 Action
ON
OFF
Figure 3.3 Output 2 Deviation
Figure 3.3 Output 2 Deviation
Alarm
High Alarm
High
PV
SP2+O2HY
SP2
OUT2 Action
ON
OFF
Figure 3.4 Output 2 Process
Figure 3.4 Output 2 Process
Alarm
Low Alarm
Low
UM0C911A 38
Time
Time
Time
Time
Page 40
3-4 Alarm3-4 Alarm
The output 2 can be selected as alarm output. There are 6 types of alarm functions and one dwell timer can be selected, and four kinds of alarm modes ( ALMD ) are available for each alarm function.
process
A sets two absolute trigger levels. When the process is
A sets two absolute trigger levels. When the process is
higher
higher than SP2, a process high alarm occurs, and the alarm
is
is off as the process is lower than SP2-O2HY. When the process is
lower
lower than SP2, a process low alarm occurs and the alarm is
off
off as the process is higher than SP2+O2HY. A process alarm is
independent
independent of set point.
A alerts the user when the process deviates too far
A alerts the user when the process deviates too far
from set point. When the process is higher than SV+SP2, a deviation
from high
high alarm occurs and the alarm is off as the process is lower
than
than SV+SP2-O2HY. When the process is lower than SV+SP2, a
deviation
deviation low alarm occurs and the alarm is off as the process
is
is higher than SV+SP2+O2HY. Trigger level of deviation alarm is
moving
moving with set point.
A presets two trigger levels relative to set point.
A presets two trigger levels relative to set point.
The two trigger levels are and for alarm. When the
The process
process is higher than ( SV+SP2 ) or lower than ( SV - SP2 ), a
deviation
deviation band high alarm occurs. When the process is within
the
the trigger levels, a deviation band low alarm occurs.
In the above descriptions denotes the current set point value for control which is different from SP1 as the ramp function is performed.
control
There are four types of alarm modes available for each alarm function,
There are four types of alarm modes available for each alarm function,
these are: Normal alarm, Latching alarm, Holding alarm and Latching/
these Holding
Holding alarm. They are described as follows:
Normal Alarm : ALMD = NORM
Normal Alarm : ALMD = NORM
When a normal alarm is selected, the alarm output is de-energized in the non-alarm condition and energized in an alarm condition.
Latching Alarm : ALMD = LTCH
Latching Alarm : ALMD = LTC H
If a latching alarm is selected, once the alarm output is energized, it will remain unchanged even if the alarm condition is cleared. The latching alarm is reset when the RESET key is pressed, once the alarm condition is removed.
alarm
process alarm
than SP2, a process high alarm occurs, and the alarm
PV.HI )
(
( PV.HI )
off as the process is lower than SP2-O2HY. When the process is
than SP2, a process low alarm occurs and the alarm is
PV.LO )
(
(PV.LO)
as the process is higher than SP2+O2HY. A process alarm is
of set point.
deviation
deviation alarm
alarm
set point. When the process is higher than SV+SP2, a deviation
alarm occurs and the alarm is off as the process is lower
(DE.HI)
(DE.HI)
SV+SP2-O2HY. When the process is lower than SV+SP2, a
low alarm occurs and the alarm is off as the process
(DE.LO)
(DE.LO)
higher than SV+SP2+O2HY. Trigger level of deviation alarm is
with set point.
deviation
deviation band alarm
band alarm
two trigger levels are and for alarm. When the
SV+SP2 SV - SP2
SV+SP2 SV
- SP2
is higher than ( SV+SP2 ) or lower than ( SV - SP2 ), a
band high alarm occurs. When the process is within
trigger levels, a deviation band low alarm occurs.
DB.HI )
(
( DB.HI )
SV
SVIn the above descriptions denotes the current set point value for
(DB.LO)
(DB.LO)
which is different from SP1 as the ramp function is performed.
are: Normal alarm, Latching alarm, Holding alarm and Latching/
alarm. They are described as follows:
39
UM0C911A
Page 41
Holding Alarm : ALMD = HOLD
Holding Alarm : ALMD = HOLD
A holding alarm prevents an alarm from power up. The alarm is enabled only when the process reaches the set point value. Afterwards , the alarm performs same function as normal alarm.
Latching / Holding Alarm : ALMD = LT.HO
Latching / Holding Alarm : ALMD = LT.HO
A latching / holding alarm performs both holding and latching function. The latching alarm is reset when the RESET key is pressed, once the alarm condition is removed.
Alarm Failure Transfer failure mode
Alarm Failure Transfer failure mode
Alarm will go on if is set for and go off if is
O2FT
set for . The unit will enter failure mode when sensor break
O2FT
is activated as the unit enters .
ON O2FT OFF
ON O2FT OFF
occurs or if the A-D converter of the unit fails.
3-5 Configure Display3-5 Configure Display
C21 can be configured to display the process value by selecting PV for DISP or to display the set point value by selecting SP1 for DISP in the normal condition.
Examples:
If LOCK is set with NONE, OUT2 is set with DEHI, DISP is set with PV, set SEL1=SHIF, SEL2=ADDR. SEL3=PB, SEL4~SEL8=NONE, then the display scrolling for C21 becomes:
PV
If LOCK is set with NONE, OUT1 is set with REVR,nonzero value is set for PB and TI, OUT2 is set with COOL, DISP is set with SP1, set SEL1=INPT, SEL2=PB, SEL3=TI, SEL4~SEL8=NONE, then the display scrolling for C21 becomes:
SP1
UM0C911A
40
Page 42
Example for C91:Example for C91:
Set OUT2=PVLO, LOCK=NONE, SEL1=INPT, SEL2=UNIT, SEL3=DP, SEL4~SEL8=NONE, then the display scrolling for C91 becomes
PV
PV
SP1 SP2
SP1 SP2
ATMAN
PV
3-6 Ramp3 - 6 Ramp
The ramping function is performed during power up as well as any
The ramping function is performed during power up as well as any
the set point is changed. Choose MINR or HRR for RAMP, the
time the set point is changed. Choose MINR or HRR for RAMP, the
time
will perform the ramping function. The ramp rate is programmed
unit
unit will perform the ramping function. The ramp rate is programmed
adjusting RR. The ramping function is disabled as soon as the
by
by adjusting RR. The ramping function is disabled as soon as the
mode, the manual control mode, the auto-tuning mode or the
failure
failure mode, the manual control mode, the auto-tuning mode or the
calibration
calibration mode occurs.
Example without Dwell TimerExample without Dwell Timer
Select MINR for RAMP, selects C for UNIT, selects 1-DP for DP, Set
Select MINR for RAMP, selects C for UNIT, selects 1-DP for DP, Set
RR= 10.0. SV is set to 200 C initially, and changed to 100 C after 30
RR= minutes
minutes since power up. The starting temperature is 30 C. After
power
power up the process is running like the curve shown below:
Note: When the ramp function is used, the display will show the
Note: When the ramp function is used, the display will show the
current ramping value. However it will revert to show the set point
current value
value as soon as the up or down key is touched for adjustment. The
ramping
ramping value is initiated to process value either as power up or RR
and
and /or set point are changed. Setting RR to zero means no ramp
function
function at all.
41
mode occurs.
L
L
10.0. SV is set to 200 C initially, and changed to 100 C after 30 since power up. The starting temperature is 30 C. After
LL
LL
L
L
up the process is running like the curve shown below:
PV
200C200
C
100C100
C
30C30
C
0
30 40
17
Figure 3.5 RAMP FunctionFigure 3.5 RAMP Function
Time
Time
(minutes)
(minutes)
ramping value. However it will revert to show the set point
as soon as the up or down key is touched for adjustment. The
value is initiated to process value either as power up or RR
/or set point are changed. Setting RR to zero means no ramp
at all.
UM0C911B
Page 43
3-7 Dwell Timer3-7 Dwell Timer
Output 2 can be configured as dwell timer by selecting TIMR for OUT2. As the dwell timer is configured, the parameter SP2 is used for dwell time adjustment. The dwell time is measured in minute ranging from 0.1 to 4553.6 minutes. Once the process reaches the set point the dwell timer starts to count down until zero ( time out ). The timer relay will remain unchanged until time out. The dwell timer operation is shown as following diagram.
After time out the dwell timer will be restarted by pressing the RESET key.
The timer stops to count during the manual control mode, failure mode, calibration period and auto-tuning period.
PV
SP
ALM
SP3
power off or touch RESET key
Time
ON
OFF
Time
Timer starts
Figure 3.6 Dwell Timer FunctionFigure 3.6 Dwell Timer Function
If output 2 is configured as dwell timer, ALMD will be hidden.If output 2 is configured as dwell timer, ALMD will be hidden.
UM0C911A 42
Page 44
3-8 PVShift3 - 8 PV Shift
In certain applications it is desirable to shift the controller display
In certain applications it is desirable to shift the controller display
from its actual value. This can be easily accomplished by using
value from its actual value. This can be easily accomplished by using
value
PV shift function.
the
the PV shift function.
The SHIF function will .alter PV onlyThe SHIF function will .alter PV only
Here is an example. A process is equipped with a heater, a sensor
Here is an example. A process is equipped with a heater, a sensor
a subject to be warmed up. Due to the design and position of the
and a subject to be warmed up. Due to the design and position of the
and components
components in the system, the sensor could not be placed any closer
the part. Thermal gradient ( different temperature ) is common and
to
to the part. Thermal gradient ( different temperature ) is common and
necessary
necessary to an extent in any thermal system for heat to be
transferred
transferred from one point to another. If the difference between the
sensor
sensor and the subject is 35 C, and the desired temperature at the
subject
subject to be heated is 200 C, the controlling value or the
temperature
temperature at the sensor should be 235 C. You should input -35 C
to subtract 35 C from the actual process display. This in turn will
as
as to subtract 35 C from the actual process display. This in turn will
cause
cause the controller to energize the load and bring the process
display
display up to the set point value.
Subject
165 C
in the system, the sensor could not be placed any closer
to an extent in any thermal system for heat to be
from one point to another. If the difference between the
and the subject is 35 C, and the desired temperature at the
to be heated is 200 C, the controlling value or the
at the sensor should be 235 C. Yo u should input -35 C
L
L
L
L
L
L
LL
LL
the controller to energize the load and bring the process
up to the set point value.
Sensor
Heat Transfer
200 C
C
Heater
Subject
165 C
Sensor
Heat Transfer
200 C
C
Heater
Subject
200 C
235 C
Sensor
Heat Transfer
C
Heater
35 C temperature difference isobserved SHIF= 0
43
Adjust SHIF SHIF= -35 C Supply more heat
Figure 3.7
Figure 3.7
PV Shift Application
Shift Application
PV
UM0C911A
Display is stable SHIF= -35 C PV=SV
Page 45
3- 9 Digital Filter3- 9 Digital Filter
In certain application the process value is too unstable to be read. To improve this a programmable low pass filter incorporated in the controller can be used. This is a first order filter with time constant specified by parameter . The default value of FILT is 0.5 sec. before shipping. Adjust FILT to change the time constant from 0 to 60 seconds. 0 second represents no filter is applied to the input signal. The filter is characterized by the following diagram.
PV
FILT
1 sec1 sec
FILT=0
FILT=1
FILT=30
Note
The Filter is available only for PV, and is performed for the displayed
The Filter is available only for PV, and is performed for the displayed
only. The controller is designed to use unfiltered signal for
value only. The controller is designed to use unfiltered signal for
value
even if Filter is applied. A lagged ( filtered ) signal, if used for
control
control even if Filter is applied. A lagged ( filtered ) signal, if used for
may produce an unstable process.
control,
control, may produce an unstable process.
1 sec1 sec
Figure 3.8
Figure 3.8
Characteristics
Filter Characteristics
Filter
UM0C911A 44
Time
Page 46
3 -10 Failure Transfer3 -10 Failure Transfer
The controller will enter as one of the following conditions occurs:
SBER
1. occurs due to the input sensor break or input current below
SBER 1mA if 4-20 mA is selected or input voltage below 0.25V if 1-5 V is selected .
ADER
2. occurs due to the A-D converter of the controller fails.
ADER
failure mode
failure mode
The output 1 and output 2 will perform the function as
failure transferfailure transfer
the controller enters failure mode.
Output 1 Failure Transfer, if activated, will perform :
Output 1 Failure Transfer
1. If output 1 is configured as proportional control ( PB=0 ), and BPLS is selected for O1FT, then output 1 will perform bumpless transfer. Thereafter the previous averaging value of MV1 will be used for controlling output 1.
2. If output 1 is configured as proportional control ( PB=0 ), and a value of 0 to 100.0 % is set for O1FT, then output 1 will perform failure transfer. Thereafter the value of O1FT will be used for controlling output 1.
3. If output 1 is configured as ON-OFF control ( PB=0 ), then output 1 will transfer to off state if OFF is set for O1FT and transfer to on state if ON is set for O1FT.
Output 2 Failure Transfer, if activated, will perform :
Output 2 Failure Transfer, if activated, will perform :
1. If OUT2 is configured as COOL, and BPLS is selected for O2FT,
1.
If OUT2 is configured as COOL, and BPLS is selected for O2FT,
then output 2 will perform bumpless transfer. Thereafter the previous
then
output 2 will perform bumpless transfer. Thereafter the previous
averaging value of MV2 will be used for controlling output 2.
averaging
2. If OUT2 is configured as COOL, and a value of 0 to 100.0 % is set
2.
If OUT2 is configured as COOL, and a value of 0 to 100.0 % is set
for O2FT, then output 2 will perform failure transfer. Thereafter the
for
value of O2FT will be used for controlling output 2.
value
3. If OUT2 is configured as alarm function, and OFF is set for O2FT,
3.
If OUT2 is configured as alarm function, and OFF is set for O2FT,
then output 2 will transfer to off state, otherwise, output 2 will transfer
then
to on state if ON is set for O2FT.
to
45
value of MV2 will be used for controlling output 2.
O2FT, then output 2 will perform failure transfer. Thereafter the
of O2FT will be used for controlling output 2.
output 2 will transfer to off state, otherwise, output 2 will transfer
on state if ON is set for O2FT.
UM0C911A
Page 47
3 -11 Auto-tuning3 -11 Auto-tuning
The auto-tuning process is performed at set point.
The auto-tuning process is performed at set point.
process will oscillate around the set point during tuning
The process will oscillate around the set point during tuning
The process.
process. Set a set point to a lower value if overshooting beyond
the
the normal process value is likely to cause damage.
The auto-tuning is applied in cases of :
The auto-tuning is applied in cases of :
Initial setup for a new process
Initial
*
The
The set point is changed substantially from the previous auto-
*
tuning
tuning value
The
The control result is unsatisfactory
*
1. The system has been installed normally.
2. Set the correct values for the setup menu of the unit.
3. Set the set point to a normal operating value or a lower value if
4. Press several times until appears on the
5. Press for at least 5 seconds. The AT indicator ( for C91 )
NOTE :NOTE :
The ramping function, if used, will be disabled once auto-tuning is proceeding.
The auto-tuning mode is disabled as soon as either failure mode
Set a set point to a lower value if overshooting beyond
normal process value is likely to cause damage.
setup for a new process
set point is changed substantially from the previous auto-
value
control result is unsatisfactory
Operation :Operation :
But don't use a zero value for PB and TI , otherwise, the auto-tuning program will be disabled. The LOCK parameter should be set at NONE.
overshooting beyond the normal process value is likely to cause damage.
display.( for C21) or AT indicator is lit (for C91).
or the display ( for C21 )will begin to flash and the auto-tuning procedure is beginning.
or manual control mode occurs.
UM0C911C 46
Page 48
Procedures:
The auto-tuning can be applied either as the process is warming
up ( Cold Start ) or as the process has been in steady state ( Warm Start ).
After the auto-tuning procedures are completed, the AT indicator will cease to flash and the unit revert to PID control by using its new PID values. The PID values obtained are stored in the nonvolatile memory.
Auto-Tuning ErrorAuto-Tuning Error
If auto-tuning fails an ATER message will appear on the display in
If auto-tuning fails an ATER message will appear on the display in
cases of :
cases
of :
If PB exceeds 9000 ( 9000 PU, 900.0 F or 500.0 C ). or if TI exceeds 1000 seconds.
or
if TI exceeds 1000 seconds.
or if set point is changed during auto-tuning procedure.
or
if set point is changed during auto-tuning procedure.
LLIf PB exceeds 9000 ( 9000 PU, 900.0 F or 500.0 C ).
LL
Solutions toSolutions to
1. Try auto-tuning once again.
1. Tr y auto-tuning once again.
2. Don't change set point value during auto-tuning procedure.
2.
Don't change set point value during auto-tuning procedure.
3. Don't set zero value for PB and TI.
3.
Don't set zero value for PB and TI.
4. Use manual tuning instead of auto-tuning. ( See section 3-12 ).
4.
Use manual tuning instead of auto-tuning. ( See section 3-12 ).
5. Touch RESET key to reset message.
5.
Touch RESET key to reset message.
3 - 12 Manual Tuning3 - 12 Manual Tuning
In certain applications ( very few ) using auto-tuning to tune a process may be inadequate for the control requirement, then you can try manual tuning.
If the control performance by using auto- tuning is still unsatisfactory, the following rules can be applied for further adjustment of PID values :
47
UM0C911A
Page 49
ADJUSTMENT SEQUENCEADJUSTMENT SEQUENCE
(1) Proportional Band ( PB )
(1) Proportional Band ( PB )
(2) Integral Time ( TI )(2) Integral Time ( TI )
(3) Derivative Time ( TD )(3) Derivative Time ( TD )
SYMPTOM SOLUTION
Slow ResponseSlow Response
High overshoot or
High overshoot or
Oscillations
Oscillations
Slow ResponseSlow Response
Instability or
Instability or
Oscillations
Oscillations
Slow Response or
Slow Response or
Oscillations
Oscillations
High OvershootHigh Overshoot
Decrease PBDecrease PB
Increase PBIncrease PB
Decrease TIDecrease TI
Increase TIIncrease TI
Decrease TDDecrease TD
Increase TDIncrease TD
Table 3.2 PID Adjustment GuideTable 3.2 PID Adjustment Guide
Figure 3.9 shows the effects of PID adjustment on process response.Figure 3.9 shows the effects of PID adjustment on process response.
3 -13 Manual Control3 -13 Manual Control
Operation:
To enable manual control the LOCK parameter should be set with
To enable manual control the LOCK parameter should be set with
NONE, then press for several times then (Heating output)
then press for several times then (Heating output)
NONE,
or (Cooling output) will appear on the display.Press for 5
or seconds
seconds then the MAN indicator (for C91) or the display (for C21) will
begin
begin to flash. The controller now enters the manual control mode.
down
down key to adjust the percentage values for the heating or cooling
output.
output.
The
The controller performs open loop control as long as it stays in manual
control
control mode.
Exit Manual ControlExit Manual Control
To press key the controller will revert to its normal display mode.To press key the controller will revert to its normal display mode.
(Cooling output) will appear on the display. Press for 5
then the MAN indicator (for C91) or the display (for C21) will
to flash. The controller now enters the manual control mode.
indicates
indicates output control variable for output 1, and
indicates
indicates control variable for output 2. Now you can use up-
output control variable for output 1, and control variable for output 2. Now you can use up-
key to adjust the percentage values for the heating or cooling
controller performs open loop control as long as it stays in manual
mode.
UM0C911C 48
Page 50
PV
Set pointSet point
PV
Perfect
PB too high
PB too high
PB too lowPB too low
P actionP action
Time
TI too highTI too high
Set pointSet point
Set pointSet point
49
TI too low
TI too low
PV
TD too lowTD too low
Perfect
TD too high
TD too high
Figure 3.9 Effects of PID AdjustmentFigure 3.9 Effects of PID Adjustment
UM0C911A
I actionI action
Perfect
Time
D actionD action
Time
Page 51
3 -14 Data Communication3 -14 Data Communication
The controllers support mode of protocol for the data communication. Other protocols are not available for the series.
Two types of interface are available for Data Communication. These are
Tw o types of interface are available for Data Communication. These are
and interface. Since RS-485 uses a differential architecture to
and interface.
485 RS-232
485 RS-232
and sense signal instead of a single ended architecture which is used
drive
drive and sense signal instead of a single ended architecture which is used
RS-232, RS-485 is less sensitive to the noise and suitable for a longer
for
for RS-232, RS-485 is less sensitive to the noise and suitable for a longer
communication. RS-485 can communicate without error over 1 km
distance
distance communication. RS-485 can communicate without error over 1 km
while RS-232 is not recommended for a distance over 20 meters.
distance
distance while RS-232 is not recommended for a distance over 20 meters.
Using a PC for data communication is the most economic way. The signal
Using a PC for data communication is the most economic way. The signal
transmitted and received through the PC communication Port ( generally
is transmitted and received through the PC communication Port ( generally
is
). Since a standard PC can't support RS-485 port, a network
RS-232
RS-232 ). Since a standard PC can't support RS-485 port, a network
( such as ) has to be used to convert RS-485 to
adaptor
adaptor(suchas )hastobeusedtoconvertRS-485to
for a PC if RS-485 is required for the data communication. But there
RS-232
RS-232 for a PC if RS-485 is required for the data communication. But there
no need to be sad. Many RS-485 units ( up to 247 units ) can be
is
is no need to be sad. Many RS-485 units ( up to 247 units ) can be
connected
connected to one RS-232 port, therefore a PC with 4 comm ports can
communicate
communicate with 988 units. It is quite economic.
Setup
Enters the setup menu.
Enters the setup menu.
Select RTU for COMM . Set individual address as for those units which are
Select
connected to the same port.
connected
Set the Baud Rate ( ), Data Bit ( ), Parity Bit ( ) and Stop
Set
Bit ( ) such that these values are accordant with PC setup conditions.
Bit
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
should be modified for proper operation of RS-232 communication
should according
according to Section 2-9.
to one RS-232 port, therefore a PC with 4 comm ports can
with 988 units. It is quite economic.
RTU for COMM . Set individual address as for those units which are
to the same port.
the Baud Rate (),Data Bit ( ), Parity Bit ()and Stop
STOP
()such that these values are accordant with PC setup conditions.
STOP
be modified for proper operation of RS-232 communication
to
RTU Modbus
Since RS-485 uses a differential architecture to
SNA10A SNA10B,
SNA10A SNA10B,
BAUD DATA PARI
BAUD DATA PARI
RS-
RS-
3 -15 PV Retransmission3 -15 PV Retransmission
C21 can output (retransmit) process value via its retransmission terminals RE+ and RE- provided that the retransmission option is ordered. A correct signal type should be selected for COMM parameter to meet the retransmission option installed. RELO and REHI are adjusted to specify the low scale and high scale values of retransmission.
UM0C911A 50
Page 52
Chapter 4 ApplicationsChapter 4 Applications
4 - 1 Heat Only Control with Dwell Timer4 - 1 Heat Only Control with Dwell Timer
An oven is designed to dry the products at 150 C for 30 minutes and then stay unpowered for another batch. A C91 equipped with
timer
is used for this purpose. The system diagram is shown as
timer follows :
Set
SP1=150.0
SP1=150.0
=30.0
SP2
SP2 =30.0
To achieve this function set the following parameters in the setup
To achieve this function set the following parameters in the setup
menu.
menu.
4 5
OP1
OP2
C
F
C
SP2SP1
PV
INPT=K_TC UNIT= C DP=1_DP
INPT=K_TC UNIT= C DP=1_DP
OUT1=REVR O1TY=RELY CYC1=18.0
OUT1=REVR
O1FT=BPLS OUT2=TIMR O2FT=ON
O1FT=BPLS
MAN
12
10
OUT1
Timer ( ALM )
Timer ( ALM )
AT
R
C91
9
T/C
Heater
OFF
L
L
O1TY=RELY CYC1=18.0
OUT2=TIMR O2FT=ON
Auto-Tuning is performed at 150 C for a new oven.LAuto-Tuning is performed at 150 C for a new oven.L
Oven
B
Figure 4.1
Figure 4.1
Heat Control
Heat Example
Example
dwell
dwell
Control
Mains
Mains
Supply
Supply
ON
51
UM0C911A
Page 53
4 - 2 Cool Only Control4 - 2 Cool Only Control
A C91 is used to control a refrigerator at temperature below 0 C. The temperature is lower than the ambient, a cooling action is required. Hence select DIRT for OUT1. Since output 1 is used to drive a magnetic contactor, O1TY selects RELY. A small temperature oscillation is tolerable, hence use ON-OFF control to reduce the over­all cost. To achieve ON-OFF control, PB is set with zero and O1HY is set at 0.1 C.BB
Setup Summary:
Setup Summary:
INPT=PT.DN
INPT=PT.DN
L
L
UNIT= C
UNIT= C
DP=1-DP
DP=1-DP
OUT1=DIRT
OUT1=DIRT
O1TY=RELY
O1TY=RELY
User Menu:User Menu:
PB =0( C)
PB = 0 (C)
O1HY=0.1 ( C )LL
O1HY=0.1
(C)LL
Refrigerator
RTD
4
9
5
3
OP1
OP2
C
F
SP2SP1
PV
Figure 4.2
Figure 4.2
Cooling Control Example
Cooling
MAN
AT
R
C91
Control Example
Mains
Mains
Supply
Supply
10
UM0C911A 52
Page 54
4 - 3 Heat-Cool Control4 - 3 Heat-Cool Control
An injection mold required to be controlled at 120 C to ensure a
An injection mold required to be controlled at 120 C to ensure a
consistent quality for the parts. An oil pipe is buried in the mold. Since
consistent plastics
plastics is injected at higher temperature ( e.g. 250 C ), the
circulation
circulation oil needs to be cooled as its temperature rises. Here is an
example:
example:
quality for the parts. An oil pipe is buried in the mold. Since
is injected at higher temperature ( e.g. 250 C ), the
oil needs to be cooled as its temperature rises. Here is an
L
L
L
L
53
Plastics
Freezer
OP1
PV
4-20 mA
OUT2
OP2
1,2 9
SP2SP1
MAN
Injection Mold
Oil Tank
OUT1
C
F
AT
R
C91
120 C
Oil Pump
RTD
10
INPT
5 4 3
Figure 4.3
Figure 4.3
Heat-Cool Control Example
Heat-Cool
UM0C911A
Heater Supply
Control Example
Page 55
The PID Heat-Cool is used for the above example. To achieve this set the following parameters in the Setup Menu:
INPT=PT.DN
INPT=PT.DN
UNIT= C
L
UNIT= C
L
DP= 1-DP
DP=
1-DP
OUT1=REVR
OUT1=REVR
O1TY=RELY
O1TY=RELY
CYC1=18.0 (sec.)
CYC1=18.0
O1FT=BPLS
O1FT=BPLS
OUT2=COOL
OUT2=COOL
O2TY=4-20
O2TY=4-20
O2FT=BPLS
O2FT=BPLS
(sec.)
Adjust SV at 120.0 C , CPB at 125(%)andDBat-4.0 (%).LAdjust SV at 120.0 C , CPB at 125 ( % ) and DB at -4.0 (%).L
Apply at 120 C for a new system to get an optimal PID
Apply at 120 C for a new system to get an optimal PID
values.
values.
Adjustment of CPB is related to the cooling media used. If water is
Adjustment of CPB is related to the cooling media used. If water is
used
used as cooling media instead of oil, the CPB is set at 250 (%). If air is
used
used as cooling media instead of oil, the CPB is set at 100 (%).
Adjustment
Adjustment of DB is dependent on the system requirements. More
positive
positive value of DB will prevent unwanted cooling action, but will
increase
increase the temperature overshoot, while more negative value of DB
will
will achieve less temperature overshoot, but will increase unwanted
cooling
cooling action.
Section 3-11.
See Section 3-11.
See
as cooling media instead of oil, the CPB is set at 250 (%). If air is as cooling media instead of oil, the CPB is set at 100 (%).
of DB is dependent on the system requirements. More
value of DB will prevent unwanted cooling action, but will
the temperature overshoot, while more negative value of DB
achieve less temperature overshoot, but will increase unwanted
action.
LAuto-tuning
LAuto-tuning
UM0C911A 54
Page 56
Chapter 5 CalibrationChapter 5 Calibration
Do not proceed through this section unless there is a definite need to re-calibrate the controller. Otherwise, all previous calibration data will be lost. Do not attempt recalibration unless you have appropriate calibration equipment. If calibration data is
lost, you will need to return the controller to your supplier who may charge you a service fee to re-calibrate the controller.
Entering calibration mode will break the control loop. Make sure that if the system is allowable to apply calibration mode.
Equipments needed before calibration:
Equipments needed before calibration: (1) A high accuracy calibrator ( Fluke 5520A Calibrator
recommended ) with following functions: 0 - 100 mV millivolt source with 0.005 % accuracy 0 - 10 V voltage source with 0.005 % accuracy 0 - 20 mA current source with 0.005 % accuracy 0 - 300 ohm resistant source with 0.005 % accuracy
(2) A test chamber providing 25 C - 50 C temperature range (3) A switching network ( SWU16K, optional for automatic
calibration )
(4) A calibration fixture equipped with programming units ( optional
for automatic calibration )
(5) A PC installed with calibration software BC-Net and Smart
Network Adaptor SNA10B ( optional for automatic calibration )
The calibration procedures described in the following section are a step by step manual procedures.
manual procedures.
Since it needs 30 minutes to warm up an unit before calibration, calibrating the unit one by one is quite inefficient. An
calibration
calibration system
system
for small quantity as well as for unlimited quantity is
available upon request.
A
A
A
A
BB
automatic
automatic
55
UM0C911A
Page 57
Manual Calibration ProceduresManual Calibration Procedures
Perform step 1 to enter calibration mode.
*
Set the Lock parameter to the unlocked condition ( LOCK=
Step 1.
Step 1.
NONE).
Press and hold the scroll key until appears on the display, then release the scroll key. Press the scroll key for 2 seconds then release,the display will show and the unit enters calibration mode .
Perform step 2 to calibrate Zero of A to D converter and
*
step 3 to calibrate gain of A to D converter.
Short the thermocouple inpt terminals , then press scroll key
Step 2.
Step 2.
for at least 5 seconds. The display will blink a moment and a new value is obtained. Otherwise, if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails.
Press scroll key until the display shows . Send a 60
Step 3.Step 3.
mV signal to the thermocouple input terminals in correct polarity . Press scroll key for at least 5 seconds . The display will blink a moment and a new value is obtained . Otherwise , if the display didn't blink or if the obtained value is equal to
-199.9 or 199.9, then the calibration fails.
Perform both steps 4 and 5 to calibrate RTD function ( if
*
required ) for input .
UM0C911C 56
Page 58
Step 4.Step 4.
Press scroll key until the display shows . Send a 100 ohms signal to the RTD input terminals according to the connection shown below:
100 ohms
C21
8 9
10
C91
3 4 5
Figure 5.1 RTD CalibrationFigure 5.1 RTD Calibration
Press scroll key for at least 5 seconds . The display will blink a moment, otherwise the calibration fails.
Press scroll key and the display will show . Change
Step 5.Step 5.
the ohm's value to 300 ohms .Press scroll key for at least 5 seconds. The display will blink a moment and two values are obtained for RTDH and RTDL ( step 4 ). Otherwise, if the display didn't blink or if any value obtained for RTDH and RTDL is equal to -199.9 or 199.9 , then the calibration fails.
Perform step 6 to calibrate offset of cold junction compensation
*
, if required.
Step 6.
Step 6.
Setup the equipments according to the following diagram
for calibrating the cold junction compensation. Note that a K
type thermocouple must be used.
57
UM0C911C
Page 59
5520A
5520A
Calibrator
Calibrator
K-TC
Figure 5.2
Figure 5.2
Junction Calibration Setup
Cold Junction Calibration Setup
Cold
The 5520A calibrator is configured as K type thermocouple output
The 5520A calibrator is configured as K type thermocouple output
with internal compensation. Send a 0.00 C signal to the unit under
internal compensation. Send a 0.00 C signal to the unit under
with
calibration.
calibration.
The unit under calibration is powered in a still-air room with temperature 25 3 C. Stay at least 20 minutes for warming up. Perform step 1 stated above, then press scroll key until the display shows . Press up/down key to obtain
40.00. Press scroll key for at least 5 seconds. The display will blink a moment and a new value is obtained . Otherwise , if the display didn't blink or if the obtained value is equal to -5.00 or
40.00, then the calibration fails.
Perform step 7 to calibrate of compensation
*
if required.
Setup the equipments same as step 6. The unit under
Step 7.Step 7.
calibration is powered in a still-air room with temperature
3C.
3C.
AB
AB
calibrator source is set at 0.00 C with internal compensation mode.
AB
Stay at least 20 minutes for warming up . The
C21
K+
K
Stay at least 20 minutes in still-
Stay at least 20 minutes in still-
air room
air room
room temperature 25 3 C
gain cold junctiongain cold junction
C91
9
4
10
5
room
temperature 25 3 CAL
L
L
B
AL
50
50
UM0C911C 58
Page 60
Perform step 1 stated above , then press scroll key until the display shows . Press scroll key for at least 5 seconds. The display will blink a moment and a new value is obtained. Otherwise , if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails.
This setup is performed in a hence
it is recommended to use a computer to perform the
procedures.
Input modification recalibration linear
Input modification recalibration linear
*
voltage linear current
or a input:
voltage linear
1. Remove R60(3.3K) and install two 1/4 W resistors RA and RB on the control board with the recommended values specified in the following table.
The low temperature coefficient resistors should be used for RA and RB.
and procedures for a
current
high temperature chamber,
high temperature chamber,
Input Function
T/C, RTD, 0~60mV
0~1V
0~5V,1~5V
0~10V
0~20mA, 4~20mA
2. Perform and to calibrate the linear input zero.
3. Perform but send a span signal to the input terminals
*
Step 8.Step 8.
59
Step 1 Step 2
Step 1 Step 2
Step 3
Step
instead of 60mV. The span signal is 1V for 0~1V input, 5V for 0~5V or 1~5V input, 10V for 0~10V input and 20mA for 0~20mA or 4~20mA input.
Final stepFinal step
Set the LOCK value to your desired function.Set the LOCK value to your desired function.
3
RA RB
XX
61.9K
324K
649K
39W
UM0C911C
3.92K
3.92K
3.92K
3.01W
R60
3.3K
X
X
X
X
Page 61
Chapter 6 SpecificationsChapter 6 Specifications
Power
90 250 VAC, 47 63 Hz, 10VA, 5W maximum
90 250 VAC, 47 63 Hz, 10VA, 5W maximum
11 26 VAC / VDC, 10VA, 5W maximum
11
26 VAC / VDC, 10VA, 5W maximum
Input
Resolution :
Resolution :
Sampling Rate :
Sampling Maximum
Maximum Rating :
Temperature
Temperature Effect :
Sensor
Sensor Lead Resistance Effect :
T/C:
T/C: 0.2uV/ohm
3-wire
3-wire RTD: 2.6 C/ohm of resistance difference of two
2-wire
2-wire RTD: 2.6 C/ohm of resistance sum of two leads Burn-out Current :Burn-out Current :
Common
Common Mode Rejection Ratio ( CMRR ): Normal Mode Rejection Ratio ( NMRR ): 55dBNormal Mode Rejection Ratio ( NMRR ): 55dB
Sensor Break Detection :Sensor Break Detection :
Sensor open for TC, RTD and mV inputs,
Sensor open for TC, RTD and mV inputs,
Sensor short for RTD input
Sensor
below 1 mA for 4-20 mA input,
below
below 0.25V for1-5Vinput,
below
unavailable for other inputs.
unavailable
Sensor Break Responding Time :Sensor Break Responding Time :
Within 4 seconds for TC, RTD and mV inputs,
Within 4 seconds for TC, RTD and mV inputs,
0.1 second for 4-20 mA and1-5Vinputs.
0.1
18
bits
18 bits
Rate :
times / second
5
5 times / second
Rating :
Lead Resistance Effect :
0.2uV/ohm RTD: 2.6 C/ohm of resistance difference of two
RTD: 2.6 C/ohm of resistance sum of two leads
Mode Rejection Ratio ( CMRR ):
short for RTD input
1 mA for 4-20 mA input,
0.25V for 1 - 5 V input,
second for 4-20 mA and 1 - 5 V inputs.
VDC minimum, 12 VDC maximum
-2
-2 VDC minimum, 12 VDC maximum
1 minute for mA input )
(
( 1 minute for mA input )
Effect :
1.5uV/ C
AB
1.5uV/ C for all inputs except
AB
A
3.0uV/ C
A
3.0uV/ C for mA inputB
L
L
leads
leads
L
L
200
200 nA
for other inputs.
input
mA
mA input
nA
for all inputs except
for mA inputB
120dB
120dB
UM0C911B 60
Page 62
Characteristics:
Type Range
-120 C 1000 C
-120 C 1000 C
J
-184 F 1832 F )
( -184 F 1832 F )
(
-200 C 1370 C
-200 C 1370 C
K
-328 F 2498 F )
( -328 F 2498 F )
(
-250 C 400 C
-250 C 400 C
T
-418 F 752 F )
( -418 F 752 F )
(
-100 C 900 C
-100 C 900 C
E
-148 F 1652 F )
( -148 F 1652 F )
(
0 C 1800 C
0 C 1800 C
B
32 F 3272 F )BB
( 32 F 3272 F )BB
(
0 C 1767.8 C
0 C 1767.8 C
R
32 F 3214 F )BB
( 32 F 3214 F )BB
(
0 C 1767.8 C
0 C 1767.8 C
S
32 F 3214 F )BB
( 32 F 3214 F )BB
(
-250 C 1300 C
-250 C 1300 C
N
-418 F 2372 F )
( -418 F 2372 F )
(
-200 C 900 C
-200 C 900 C
L
-328 F 1652 F )
( -328 F 1652 F )
(
PT100
PT100
-210 C 700 C
-210 C 700 C
DIN )
( DIN )
(
-346 F 1292 F )
( -346 F 1292 F )
(
PT100
PT100
-200 C 600 C
-200 C 600 C
JIS )
(
( JIS )
-328 F 1112 F )
( -328 F 1112 F )
(
-8mV 70mV-8mV 70mV
mV
V
-3mA 27mA-3mA 27mA
-1.3V 11.5V-1.3V 11.5V
mA
Accuracy
Accuracy
25 C
@25 C
@
AL2CAL2C
AL2CAL2C
AL2CAL2C
AL2CAL2C
AL2CAL2C
( 200 C
( 200 C
C )
1800 C )
1800
AL2CAL2C
AL2CAL2C
AL2CAL2C
AL2CAL2C
AL0.4 CAL0.4 C
AL0.4 CAL0.4 C
A0.05 %A0.05 %
A0.05 %A0.05 %
A0.05 %A0.05 %
Input
Input
Impedance
Impedance
2.2 M2.2 M
2.2 M2.2 M
2.2 M2.2 M
2.2 M2.2 M
2.2 M2.2 M
2.2 M2.2 M
2.2 M2.2 M
2.2 M2.2 M
2.2 M2.2 M
1.3 K1.3 K
1.3 K1.3 K
2.2 M2.2 M
70.5
650 K650 K
61
UM0C911A
Page 63
Output 1 / Output 2Output 1 / Output 2
Relay Rating :
Relay Rating :
Pulsed Voltage :
Pulsed
Linear Output CharacteristicsLinear Output Characteristics
Type
4~20 mA4~20 mA 3.6~4 mA3.6~4 mA 20~21 mA20~21 mA
0~20 mA0~20 mA 0mA0 mA
0~5V0 ~ 5 V
1~5V1 ~ 5 V
0~10V0 ~ 10 V
Linear OutputLinear Output
Resolution :Resolution :
Output Regulation :
Output Regulation :
Output Settling Time :
Output
Isolation Breakdown Voltage :
Isolation
Temperature Effect :
Temperature
Triac ( SSR ) OutputTriac ( SSR ) Output
Rating :
Rating :
Inrush Current :
Inrush
Min. Load Current :
Min.
Load Current :
Max. Off-state Leakage :
Max.
Off-state Leakage :
Max. On-state Voltage :
Max.
On-state Voltage :
Insulation Resistance :
Insulation
Dielectric Strength :
Dielectric
2A/240
2A/240 VAC, life cycles 200,000 for
VAC, life cycles 200,000 for
resistive load
resistive
load
Source Voltage 5V,
Voltage :
Source
Voltage 5V,
current limiting resistance 66 .
current
limiting resistance 66 .
Zero
Zero
Tolerance
Tolerance
0V0 V
0.9~1V0.9 ~ 1 V
0V0 V
15 bits15 bits
0.02 % for full load change
% for full load change
0.02
0.1 sec. ( stable to 99.9 % )
Settling Time :
Breakdown Voltage :
Effect :
1A / 240 VAC
/ 240 VAC
1A
Current :
Resistance :
Strength :
0.1
sec. ( stable to 99.9 % )
1000 VAC
1000
0.01 % of SPAN / C
0.01
AL
% of SPAN /CAL
20A for 1 cycle
20A
for 1 cycle
50 mA rms
50
mA rms
3mArms
3
mA rms
1.5 V rms
1.5
V rms
1000 Mohms min. at 500 VDC
1000
Mohms min. at 500 VDC
2500 VAC for 1 minute
2500
VAC for 1 minute
Tolerance
Tolerance
20~21 mA20~21 mA
5 ~ 5.25 V5 ~ 5.25 V
5 ~ 5.25 V5 ~ 5.25 V
10 ~10.5 V10 ~10.5 V
VAC
Span
Span
Load
Load
Capacity
Capacity
500 max.W500 max.W
500 max.W500 max.W
10 K min.W10 K min.W
10 K min.W10 K min.W
10 K min.W10 K min.W
UM0C911B
62
Page 64
DC Voltage Supply Characteristics ( Installed at Output 2 )DC Voltage Supply Characteristics ( Installed at Output 2 )
Type
Tolerance
Max. Output Current
Max. Output Current
20 V20 V A1 VA1 V 25 mA25 mA
A0.6 VA0.6 V 40 mA40 mA
12 V12 V
5V5 V A0.25 VA0.25 V 80 mA80 mA
Output 2 Functions :
Output
2 Functions :
Alarm Mode :
Alarm
Mode :
Dwell Timer :
Dwell
Timer :
Dwell timer, Deviation High / Low Alarm,
Dwell timer, Deviation High / Low Alarm,
Deviation Band High / Low Alarm,
Deviation
PV High / Low Alarm, PID cooling control
PV
Normal, Latching, Hold, Latching / Hold.
Normal,
0.1 - 4553.6 minutes
0.1
High / Low Alarm, PID cooling control
Latching, Hold, Latching / Hold.
- 4553.6 minutes
Ripple VoltageRipple Voltage
0.2 Vp-p0.2 Vp-p
0.1 Vp-p0.1 Vp-p
0.05 Vp-p0.05 Vp-p
Band High / Low Alarm,
Data CommunicationData Communication
Interface :
Interface :
Protocol :
Protocol
Address :
Address
Baud Rate :
Baud
Data Bits :
Data
Parity Bit :
Parity
Stop Bit :
Stop
Communication Buffer :
Communication
RS-232 ( 1 unit ), RS-485 ( up to 247 units )
( 1 unit ), RS-485 ( up to 247 units )
RS-232
Modbus Protocol RTU mode
Modbus
:
:
Rate :
Bits :
Bit :
Bit :
Protocol RTU mode
1 - 247
1
- 247
2.4 ~ 38.4 Kbits/sec
2.4
~ 38.4 Kbits/sec
7 or 8 bits
7
or 8 bits
None, Even or Odd
None,
Even or Odd
1 or 2 bits
1
or 2 bits
Buffer :
160 bytes
160
bytes
Analog RetransmissionAnalog Retransmission
Output
Output Signal : 4-20 mA, 0-20 mA, 0 - 5V,
Resolution : 15 bits
Resolution : 15 bits Accuracy
Accuracy :
Load
Load Resistance :
Output
Output Regulation :
4-20 mA, 0-20 mA, 0 - 5V,
Signal :
- 5V, 0 - 10V
1-5V,0-10V
1
AAL
% of span 0.0025 %/ C
:
0.05 % of span 0.0025 %/ C
AAL
0.05
Resistance :
- 500 ohms ( for current output )
0
0 - 500 ohms ( for current output )
K ohms minimum ( for voltage output )
10
10 K ohms minimum ( for voltage output )
Regulation :
% for full load change
0.01
0.01 % for full load change
Isolation BarrierIsolation Barrier
500 VAC500 VAC
500 VAC500 VAC
500 VAC500 VAC
63
UM0C911C
Page 65
Output Settling Time : 0.1 sec. (stable to 99.9 % )
Output Settling Time : 0.1 sec. (stable to 99.9 % ) Isolation
Breakdown Voltage :
Isolation Breakdown Voltage :
Linearity Error :
Integral
Integral Linearity Error :
Temperature
Temperature Effect :
Saturation
Saturation Low :
Saturation
Saturation High :
Linear
Linear Output Range :
Low : High :
Output Range :
AL
Effect :
AL
mA ( or 0V )
0
0mA(or0V)
22.2
22.2 mA ( or 5.55V, 11.1V min. )
User InterfaceUser Interface
Single 4-digit LED Display
Single 4-digit LED Display
Keypad :
Keypad
Programming Port :
Programming
Communication Port :
Communication
4 keys for C91, 3 keys for C21
4
:
keys for C91, 3 keys for C21
For automatic setup, calibration and testing
For
Port :
Port :
A
0.005
0.005 % of span
A
0.0025
0.0025 % of span/ C
mA ( or 5.55V, 11.1V min. )
0-22.2mA(0-20mA
0-22.2mA(0-20mA or 4-20mA)
0-5.55V
0-5.55V(0-5V,1-5V)
- 11.1 V ( 0 - 10V )
0
0-11.1V(0-10V)
automatic setup, calibration and testing
Connection to PC for supervisory control
Connection
VAC min.
1000 VAC min.
1000
% of span
% of span/ C
( 0 - 5V, 1 - 5V )
to PC for supervisory control
Control ModeControl Mode
Output 1 :
Output 1 :
Output 2 :
Output
ON-OFF :
ON-OFF
PorPD:
P
PID :
PID
Cycle Time :
Cycle
Manual Control :
Manual
Auto-tuning :
Auto-tuning
Failure Mode :
Failure
Ramping Control :
Ramping
Reverse ( heating ) or direct ( cooling ) action
( heating ) or direct ( cooling ) action
Reverse
PID cooling control, cooling P band 50~300%
PID
2 :
cooling control, cooling P band 50~300%
of PB, dead band -36.0 ~ 36.0 % of PB
of
PB, dead band -36.0 ~ 36.0 % of PB
0.1 - 90.0 ( F ) hysteresis control ( P band = 0 )
0.1
:
0 - 100.0 % offset adjustment
0
or PD :
- 100.0 % offset adjustment
Fuzzy logic modified
Fuzzy
:
logic modified
Proportional band 0.1 ~ 900.0 F.
Proportional
Integral time 0 - 1000 seconds
Integral
Derivative time 0 - 360.0 seconds
Derivative
0.1 - 90.0 seconds
0.1
Time :
Control :
:
Mode :
sensor break or A-D converter damage
sensor
Control :
L
- 90.0 (F) hysteresis control ( P band = 0 )
L
band 0.1 ~ 900.0 F.
time 0 - 1000 seconds
time 0 - 360.0 seconds
- 90.0 seconds
Heat (MV1) and Cool (MV2)
Heat
(MV1) and Cool (MV2)
Cold start and warm start
Cold
start and warm start
Auto-transfer to manual mode while
Auto-transfer
break or A-D converter damage
0 - 900.0 F/minute or
0
- 900.0 F/minute or
0 - 900.0 F/hour ramp rate
0
- 900.0 F/hour ramp rate
L
L
to manual mode while
L
L
L
L
Digital FilterDigital Filter
Function :
Function : Time
Constant :
Time Constant :
order
First
First order
0,
0.2, 0.5, 1, 2, 5, 10, 20, 30, 60
0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60
seconds
programmable
seconds programmable
or 4-20mA)
UM0C911B 64
Page 66
Environmental & PhysicalEnvironmental & Physical
Operating Temperature :
Operating Temperature :
Storage Temperature :
Storage
Temperature :
Humidity :
Humidity
Altitude:
Altitude:
Pollution:
Pollution:
Insulation Resistance :
Insulation
Dielectric Strength :
Dielectric
Vibration Resistance :
Vibration
Shock Resistance :
Shock
Moldings :
Moldings
Dimensions :
Dimensions
C21-----50mm(W) X 26.5mm(H) X 110.5mm(D),
C21-----50mm(W)
C91-----48mm(W) X 48mm(H) X 94mm(D),
C91-----48mm(W)
Weight :
Weight
0 to 90 % RH ( non-condensing )
0
:
to 90 % RH ( non-condensing )
2000m maximum
2000m
Degree 2
Degree
Resistance :
Strength :
Resistance :
Resistance :
Flame retardant polycarbonate
Flame
:
:
98 mm depth behind panel
98
86 mm depth behind panel
86
C21----- 120 grams
C21-----
:
C91----- 140 grams
C91-----
-10 Cto50 C
BB
to 50 C
BB
-10 C
-40 Cto60 C
-40 C
to 60 C
BB
BB
maximum
2
20 Mohms min. ( at 500 VDC )
20
Mohms min. ( at 500 VDC )
2000 VAC, 50/60 Hz for 1 minute
2000
VAC, 50/60 Hz for 1 minute
10 - 55 Hz, 10 m/s for 2 hours
10
- 55 Hz, 10 m/s for 2 hours
2
200 m/s ( 20 g )
200
m/s ( 20 g )
retardant polycarbonate
X 26.5mm(H) X 110.5mm(D),
mm depth behind panel
X 48mm(H) X 94mm(D),
mm depth behind panel
120 grams
140 grams
Approval StandardsApproval Standards
Safety : UL61010C-1
Safety : UL61010C-1
CSA C22.2 No.24-93
CSA
C22.2 No.24-93
EN61010-1 ( IEC1010-1 )
Protective Class :
Protective Class :
EMC:
EMC:
EN61010-1
IP65 front panel for C21.
IP65
IP30 front panel for C91.
IP30
IP20 for terminals and housing with protective
IP20
cover.
cover.
All indoor use.
All
indoor use.
EN61326
EN61326
( IEC1010-1 )
front panel for C21. front panel for C91. for terminals and housing with protective
2
65
UM0C911C
Page 67
Chapter 7 Modbus CommunicationsChapter 7 Modbus Communications
This chapter specifies the Modbus Communications protocol as RS-232 or RS-485 interface module is installed. Only RTU mode is supported. Data is transmitted as eight-bit binary bytes with 1 start bit, 1 stop bit and optional parity checking (None, Even or Odd). Baud rate may be set to 2400, 4800, 9600, 14400, 19200, 28800 and 38400.
7-1 Functions Supported7-1 Functions Supported
Only function 03, 06 and 16 are available for this series of controllers. The message formats for each function are described as follows:
Function 03: Read Holding RegistersFunction 03: Read Holding Registers
Query ( from master )
Query
Slave address (0-255) Function code (3) Starting address of register Hi (0) Starting address of register Lo (0-79,
No. of words Hi (0) No. of words Lo (1-79) CRC16 Hi CRC16 Lo
Function 06: Preset single RegisterFunction 06: Preset single Register
Query ( from master )Query
Slave address (0-255) Function code (6) Register address Hi (0) Register address Lo (0-79, 128-131) Data Hi Data Lo CRC16 Hi CRC16 Lo
128-131)
Response ( from slave )Response
Byte count Data 1 Hi Data 1 Lo Data 2 Hi Data 2 Lo
CRC16 Hi CRC16 Lo
Response ( from slave )Response
UM0C911B
66
Page 68
Function 16: Preset Multiple RegistersFunction 16: Preset Multiple Registers
Query ( from master )Query
Slave address (0-255) Function code (16) Starting address of register Hi (0) Starting address of register Lo (0-79,
128-131) No. of words Hi (0) No. of words Lo (1-79) Byte count (2-158) Data 1 Hi Data 1 Lo Data 2 Hi Data 2 Lo
CRC16 Hi CRC16 Lo
Response ( from slave )Response
CRC16 Hi CRC16 Lo
67
UM0C911B
Page 69
7-2 Exception Responses7-2 Exception Responses
If the controller receives a message which contains a corrupted character (parity check error, framing error etc.), or if the CRC16 check fails, the controller ignores the message. However, if the controller receives a syntactically correct message which contains an illegal value, it will send an exception response, consisting of five bytes as follows:
slave address +offset function code + exception code + CRC16 Hi + CRC16 Lo
Where the offset function code is obtained by adding the function code with 128 (ie. function 3 becomes H'83), and the exception code is equal to the value contained in the following table:
Exception Code
1
2
3
Name
Bad function code
Illegal data address
Illegal data value
UM0C911A
Cause
Function code is not supported by the controller
Register address out of range
Data value out of range or attempt to write a read-only or protected data
68
Page 70
7-3 Parameter Table7-3 Parameter Table
Register
Parameter
Address
Notation
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Set point 1
SP1
Set point 2
SP2
Set point 3
SP3
Lock code
LOCK
Input sensor selection
INPT
Measuring unit
UNIT
Decimal point position
DP
Low scale value for linear input
INLO
High scale value for linear input
INHI
Low limit of SP1
SP1L
High limit of SP1
SP1H
PV shift value
SHIF
Filter time constant
FILT
Display form ( for C21 )
DISP
P ( proportional ) band
PB
Integral time
TI
Derivative time
TD
Output 1 function
OUT1
Output 1 signal type
O1TY
Output 1 failure transfer
O1FT
Output 1 ON-OFF hysteresis
O1HY
Output 1 cycle time
CYC1
Offset value for P control
OFST
Ramp function
RAMP
Ramp rate
RR
Output 2 function
OUT2
Retransmission low scale value
RELO
Output 2 signal type
O2TY
Output 2 failure transfer
O2FT
Output 2 ON-OFF hysteresis
O2HY
Parameter
Scale Low
*4
*7
*6
0
0
0
0
*4
*4
*4
*4
*4
0
0
*5
0
0.0
0
0
-1999.9
*5
0.0
0.0
0
*5
0
*4 *4
0
-1999.9
*5
Scale High
*4
*7
*6
65535
65535
65535
65535
*4
*4
*4
*4
*4
65535
65535
*5
65535
6553.5
65535
65535
4553.6
*5
6553.5
6553.5
65535
*5
65535
65535
4553.6
*5
Notes
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
69
UM0C911C
Page 71
Register Address
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Parameter Notation
CYC2
CPB
DB
ALFN
REHI *4 *4
ALMD
ALHY
ALFT
COMM
ADDR
BAUD
DATA
PARI
STOP
SEL1
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8
ADLO
ADHI
RTDL
RTDH
CJLO
CJHI
DATE
SRNO
HOUR
Parameter
Output 2 cycle time
Cooling P band
Heating-cooling dead band
Alarm function
Retransmission high scale value
Alarm opertion mode
Alarm hysteresis
Alarm failure transfer
Communication function
Address
Baud rate
Data bit count
Parity bit
Stop bit count
Selection 1
Selection 2
Selection 3
Selection 4
Selection 5
Selection 6
Selection 7
Selection 8
mV calibration low coefficient
mV calibration high coefficient
RTD calibration low coefficient
RTD calibration high coefficient
Cold junction calibration low coefficient
Cold junction calibration high coefficient
Date Code
Serial Number
Working hours of the controller
Scale Low
0.0
0
-1999.9
0
0
*5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-1999.9
-1999.9
-1999.9
-1999.9
-199.99
-1999.9
0
0
0
Scale High
6553.5
65535
4553.6
65535
65535
*5
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
65535
4553.6
4553.6
4553.6
4553.6
455.36
4553.6
65535
65535
65535
Notes
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
UM0C911C
70
Page 72
Register Address
61
62
63
64, 128
65, 129
66
130
67
131
68
69
70
71,140
72
73
74
75
76
77
78
79
Parameter Notation
BPL1
BPL2
CJCL
PV
SV
MV1
MV2
TIMER
EROR
MODE
PROG
CMND
JOB1
JOB2
JOB3
CJCT
Parameter
Bumpless transfer of OP1
Bumpless transfer of OP2
Cold junction signal low
Process value
Current set point value
OP1 control output value
OP2 control output value
Remaining time of dwell timer
Error code *1
Operation mode & alarm status *2
Program code *3
Command code
Job code
Job code
Job code
Cold Junction Temperature
Reserved
Reserved
Reserved
Scale Low
0.00
0.00
0.000
*4
*4
0.00
0.00
-1999.9
0
0
0.00
0
0
0
0
-199.99
0
0
0
Scale High
655.35
655.35
65.535
655.35
655.35
4553.6
65535
65535
655.35
65535
65535
65535
65535
455.36
65535
65535
65535
*1: The error code is show in the first column of Table A.1.
*2: Definition for the value of MODE register
H'000X = Normal mode H'010X = Calibration mode
H'0X00 = Alarm status is off
H'0x01 = Alarm status is on H'020X = Auto-tuning mode H'030X = Manual control mode H'040X = Failure mode
The alarm status is shown in
MV2 instead of MODE for
models C21 and C91.
*4
*4
Notes
R
R
R
R
R
Read only, unless in manual control
Read only, unless in manual control
R
R
R
R
R/W
R/W
R/W
R/W
R
R
R
R
71
UM0C911C
Page 73
*3: The PROG Code is defined in the following table:
Model No.
PROG Code
BTC-9100 BTC-8100 BTC-4100 BTC-7100
6.XX
11.XX 12.XX
13.XX
C21
33.XX
C91
34.XX
Where XX denotes the software version number. For example: PROG=34.18 means that the controller is C91 with software version
18.
*4: The scale high/low values are defined in the following table for SP1,
INLO, INHI, SP1L, SP1H, SHIF, PV, SV, RELO and REHI:
Conditions
Scale low
Scale high
Non-linear
input
-1999.9 -19999 -1999.9 -199.99 -19.999
4553.6
Linear input
DP = 0
Linear input
DP = 1
Linear input
DP = 2
Linear input
DP = 3
45536 4553.6 455.36 45.536
*5: The scale high/low values are defined in the following table for PB,
O1HY, RR, O2HY and ALHY:
Conditions
Scale low
Scale high
Non-linear
input
6553.5
Linear input
DP = 0
Linear input
DP = 1
Linear input
DP = 2
Linear input
DP = 3
0.0 0 0.0 0.00 0.000
65535 6553.5 655.35 65.535
*6: The scale high/low values are defined in the following table for SP3:
Conditions
Scale low
Scale high
ALFN=1
(TIMR)
-1999.9
4553.6
Linear input
input
-1999.9 -19999 -1999.9 -199.99 -19.999
4553.6
Linear input
DP = 0
DP = 1
Linear input
DP = 2
Linear input
DP = 3
45536 4553.6 455.36 45.536
Non-linear
*7: The scale high/low values are defined in the following table for SP2:
For C21and C91
Non-linear
Conditions
Scale low
Scale high
OUT2=1
(TIMR)
-1999.9
4553.6
Linear input
input
-1999.9 -19999 -1999.9 -199.99 -19.999
4553.6
Linear input
DP = 0
DP = 1
Linear input
DP = 2
Linear input
DP = 3
45536 4553.6 455.36 45.536
UM0C911C
72
Page 74
For BTC-9100, BTC-8100, BTC-7100 and BTC-4100
Conditions
Scale low
Scale high
Non-linear
input
-1999.9 -19999 -1999.9 -199.99 -19.999
4553.6
Linear input
DP = 0
45536 4553.6 455.36 45.536
Linear input
DP = 1
Linear input
DP = 2
Linear input
DP = 3
7-4 Data Conversion7-4 Data Conversion
The word data are regarded as unsigned ( positive ) data in the Modbus message. However, the actual value of the parameter may be negative value with decimal point. The high/low scale values for each parameter are used for the purpose of such conversion.
Let M = Value of Modbus message
A = Actual value of the parameter SL = Scale low value of the parameter SH = Scale high value of the parameter
The conversion formulas are as follows:
M=
A=
65535 SH-SL
SH-SL 65535
( A SL)
M+SL
7-5 Communication Examples :7-5 Communication Examples :
Example 1: Down load the default values via the programming portExample 1: Down load the default values via the programming port
The programming port can perform Modbus communications regardless of the incorrect setup values of address, baud, parity, stop bit etc. It is especially useful during the first time configuration for the controller. The host must be set with 9600 baud rate, 8 data bits, even parity and 1 stop bit.
The Modbus message frame with hexadecimal values is shown as follows:
73
UM0C911A
Page 75
01 10 00 00 00 34
Addr. Func.
Starting Addr.
No. of words
68
Bytes
19
4F
4E
83
4E
SP1=25.0 SP2=10.0 SP3=10.0
00 00 00 01 00 00 00 01 4D 6D 51 C4
LOCK=0 INPT=1 UNIT=0 DP=1 INLO=-17.8 INHI=93.3
4D 6D 63 21 4E 1F 00 02 00 00 00 64
SP1L=-17.8 SP1H=537.8
SHIF=0.0
FILT=2 DISP=0 PB=10.0
00 64 00 FA 00 00 00 00 4E 1F 00 01
TI=100 TD=25.0 OUT1=0 O1TY=0 O1FT=0 O1HY=0.1
83
00 B4 00 FA 00 00 00 00 00 02 4E
CYC1=18.0 OFST=25.0 RAMP=0 RR=0.0 OUT2=2
RELO=0.0
00 00 4E 1F 00 01 00 B4 00 64 4E
O2TY=0 O2FT=0 O2HY=0.1 CYC2=18.0 CPB=100
DB=0
00 02 52 07 00 00 00 01 00 00 00 01
ALFN=2 ALMD=0 ALHY=0.1 ALFT=0
REHI=100.0
COMM=1
00 01 00 02 00 01 00 00 00 00 00 02
ADDR=1 DATA=1 PARI=0 STOP=0
00 03 00 04 00
SEL2=3 SEL4=6 SEL5=7 SEL6=8
00
SEL8=17
11
BAUD=2
SEL3=4
Hi Lo
CRC16
00 07 00 08 00
06
UM0C911C
SEL1=2
SEL7=10
1F
1F
0A
74
Page 76
Example 2: Read PV, SV, MV1 and MV2.Example 2: Read PV, SV, MV1 and MV2. Send the following message to the controller via the COMM port or
programming port:
03 00
H'40 H'80
00
04 Hi Lo
Addr. Func. Starting Addr. No. of words CRC16
Example 3: Perform Reset Function (same effect as pressing key)Example 3: Perform Reset Function (same effect as pressing key)
R
Query
06 00 H'48
H'68
H'25 Hi Lo
Addr. Func. Register Addr. Data Hi/Lo CRC16
Example 4: Enter Auto-tuning ModeExample 4: Enter Auto-tuning Mode
Query
06 00 H'48
H'68
H'28 Hi Lo
Addr. Func. Register Addr. Data Hi/Lo CRC16
Example 5: Enter Manual Control Mode
Example 5: Enter Manual Control Mode
Query
06 00 H'48
H'68
H'27 Hi Lo
Addr. Func. Register Addr. Data Hi/Lo CRC16
Example 6: Read All Parameters
Example 6: Read All Parameters
Query
03 00 00
00
H'50 Hi Lo
Addr. Func. Starting Addr. No. of words CRC16
Example 7: Modify the Calibration Coefficient
Example 7: Modify the Calibration Coefficient
Preset the CMND register with 26669 before attempting to change the calibration coefficient.
06 00 H'48
H'68
H'2D Hi Lo
Addr. Func. Register Addr. Data Hi / Lo CRC16
75
UM0C911C
Page 77
Table A.1 Error Codes and Corrective ActionsTable A.1 Error Codes and Corrective Actions
Display
Error Code
4
10
11
14
15
26
29
30
39
40
Symbol
Error Description
Illegal setup values been used: Before COOL is used for OUT2, DIRT ( cooling action ) has already been used for OUT1, or PID mode is not used for OUT1 ( that is PB =0,and/orTI=0)
Communication error: bad function code
Communication error: register address out of range
Communication error: attempt to write a read-only data or a protected data
Communication error: write a value which is out of range to a register
Fail to perform auto-tuning function
EEPROM can't be written correctly
Cold junction compensation for thermocouple malfunction
Input sensor break, or input current below 1 mA if 4-20 mA is selected, or input voltage below
0.25V if 1 - 5V is selected A to D converter or related
component(s) malfunction
Corrective Action
Check and correct setup values of OUT2, PB, TI and OUT1. IF OUT2 is required for cooling control, the control should use PID mode ( PB = 0, TI = 0 ) and OUT1 should use reverse mode (heating action) , otherwise, don't use OUT2 for cooling control.
Correct the communication software to meet the protocol requirements.
Don't issue an over-range
address to the slave.register
Don't write a read-only data or a protected data to the slave.
Don't write an over-range data to the slave register.
1.The PID values obtained after
1.The PID values obtained after
auto-tuning procedure are out
auto-tuning procedure are out
of range. Retry auto-tuning.
of range. Retry auto-tuning.
2.Don't change set point value
2.Don't change set point value
during auto-tuning procedure.
during auto-tuning procedure.
3.Use manual tuning instead of
3.Use manual tuning instead of
auto-tuning.
auto-tuning.
4. Don't set a zero value for PB.4. Don't set a zero value for PB.
5. Don't set a zero value for TI.5. Don't set a zero value for TI.
6. Touch RESET key6. Touch RESET key
Return to factory for repair.
Return to factory for repair.
Return to factory for repair.Return to factory for repair.
Replace input sensor.
Return to factory for repair.
UM0C911A
76
Page 78
WARRANTY
Brainchild Electronic Co. is pleased to offer suggestions on the use of its various products. However, Brainchild makes no warranties or representations of any sort regarding the fitness for use, or the application of its products by the Purchaser. The selection, application or useof Brainchildproducts isthe Purchaser's responsibility. No claims will be allowed for any damages or losses, whether direct, indirect, incidental, special or consequential. Specifications are subject to change without notice. In addition,Brainchild reserves the right to make changes-without notification to Purchaser-to materials or processing that do not affect compliance with any applicable specification. Brainchild products are warranted tobe free from defects inmaterial and workmanship for two years afterdelivery tothe first purchaser for use. An extended period is available with extra cost upon request. Brainchild's sole responsibilityunder thiswarranty,at Brainchild'soption, islimited to replacement or repair, free of charge, or refund of purchase price within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuseor abuse.
RETURNS
No products return can be accepted without a completed Return Material Authorization ( RMA ) form.
77
UM0C911A
Page 79
BRAINCHILD Electronic Co., Ltd.BRAINCHILD Electronic Co., Ltd.
No.209, Chung Yang Rd., Nan Kang Dist.,
No.209, Chung Ya n g Rd., Nan Kang Dist.,
Ta iw a n, R.O.C. 115
Taipei, Taiwan, R.O.C. 115
Taipei,
886-2-27861299
Te l:
Tel: 886-2-27861299
886-2-27861395
Fax:
Fax: 886-2-27861395
site: http://www.brainchild.com.tw
web
web site: http://www.brainchild.com.tw
Loading...