Sinclair SDV5-125DFA, SDV5 Series, SDV5-200DFA, SDV5-140DFA, SDV5-560DFA Service Manual

...
Page 1
INDOOR FRESH AIR PROCESSING DUCT UNITS SDV5-xxDFA
C O M M E R C I A L A I R C O N D I T I O N E R S S D V 5
Page 2
Original instructions
IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
Page 3
Fresh Air Processing Unit
1 Specifications ........................................................................................ 4
2 Dimensions ............................................................................................ 7
3 Unit Placement .................................................................................... 10
4 Piping Diagram .................................................................................... 11
5 Wiring Diagrams .................................................................................. 12
6 Fan Performance ................................................................................. 15
7 Capacity Tables .................................................................................... 17
8 Electrical Characteristics ...................................................................... 20
9 Sound Levels ........................................................................................ 21
201806 3
Page 4
1 Specifications
SDV5-125DFA / SDV5-140DFA
Table 1.1: SDV5-125D,140FA specifications
Model name SDV5-125DFA SDV5-125DFA
Power supply 1-phase, 220-240V, 50Hz
Cooling1
Heating2
Fan motor
Coil
Airflow rate (H/M/L) m3/h 2000/1917/1833/1750/1667/1583/1500
External static pressure3 Pa 180 (30~200)
Sound pressure level4 dB(A) 48/47/46/45/44/43/42
Sound power level dB(A) 66/65/64/63/62/61/60
Unit
Refrigerant type R410A
Throttle
Design pressure (H/L) MPa 4.4/2.6
Refrigerant
Drain piping mm OD Ф25
Operating temperature range °C Heating: -5 to 16; Cooling: 20 to 43; Fan only: 16 to 20
Notes:
1. Outdoor air temperature 33°C DB, 28°C WB; equivalent refrigerant piping length 8m with zero level difference.
2. Outdoor air temperature 0°C DB, -2.9°C WB; equivalent refrigerant piping length 8m with zero level difference.
3. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to
higher noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit’s installation manual.)
4. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
Capacity kW 12.5 14.0
Input W 480 480
Capacity kW 10.5 12.0
Input W 480 480
Model WZDK750-38GS-W
Type DC
Brand Panasonic/ Welling
Input (H/M/L) W 360
Number of rows 4
Tube pitch × row pitch mm 25.4×22
Fin spacing mm 1.6
Fin type Hydrophilic aluminum
Tube OD and type mm Ф9.53 Inner groove
Dimensions (L×H ×W) mm 996×355.6×88
Number of circuits 7
Net dimensions (W×H×D) mm 1322×423×691
Packed dimensions
Net/Gross weight kg 68/76
Liquid/Gas side mm Ф9.53/Ф15.9
mm 1436×450×768
Type Electronic expansion valve
Model BD24FKS(L)
4 201806
Page 5
SDV5-200DFA / SDV5-250DFA / SDV5-280DFA
Table 1.2:
Model name SDV5-200DFA SDV5-250DFA SDV5-280DFA
Power supply 1-phase, 220-240V, 50Hz
Cooling1
Heating2
Fan motor
Coil
Airflow rate (H/M/L) m3/h 3000/2833/2667/2500/2333/2167/2000
External static pressure3 Pa 200 (30~250)
Sound pressure level4 (H/M/L) dB(A) 50/49/48/47/46/44/43
Sound power level dB(A) 68/67/66/65/64/62/61
Unit
Refrigerant type R410A
Throttle
Design pressure (H/L) MPa 4.4/2.6
Refrigerant
Drain piping mm OD Ф32
Operating temperature range °C Heating: -5 to 16; Cooling: 20 to 43; Fan only: 16 to 20
Notes:
1. Outdoor air temperature 33°C DB, 28°C WB; equivalent refrigerant piping length 8m with zero level difference.
2. Outdoor air temperature 0°C DB, -2.9°C WB; equivalent refrigerant piping length 8m with zero level difference.
3. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to
higher noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit’s installation manual.)
4. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
SDV5-200,250,280DFA
Capacity kW 20.0 25.0 28.0
Input W 850 850 850
Capacity kW 12.8 16.0 18.0
Input W 850 850 850
Model WZDK750-38GS-W
Type DC
Brand Panasonic/ Welling
Input W 600 650
Number of rows 4
Tube pitch × row pitch mm 25.4×22
Fin spacing mm 1.8
Fin type Hydrophilic aluminum
Tube OD and type mm Ф9.53 Inner groove
Dimensions (L×H ×W) mm 1125×512×88
Number of circuits 20
Net dimensions (W×H×D) mm 1454×515×931
Packed dimensions
Net/Gross weight kg 130/142
Liquid/Gas side mm Ф12.7/Ф22.2
specifications
mm 1509×550×990
Type Electronic expansion valve
Model BD24FKS(L)
201806 5
Page 6
SDV5-560DFA
Table 1.3:
SDV5-560DFA specifications
Model name SDV5-560DFA
Power supply 1-phase, 220-240V, 50/60Hz
Cooling1
Heating2
Fan motor
Coil
Airflow rate (H/M/L) m3/h 7400/7000/6600/6200/5800/5400/5000
External static pressure3 Pa 300 (100~400)
Sound pressure level4 (H/M/L) dB(A) 59/58/57/56/54/53/51
Sound power level dB(A) 77/76/75/74/72/71/69
Unit
Refrigerant type R410A
Throttle
Design pressure (H/L) MPa 4.4/2.6
Refrigerant
Drain piping mm OD Ф32
Operating temperature range °C Heating: -5 to 16; Cooling: 20 to 43; Fan only: 16 to 20
Capacity kW 56
Input W 2272
Capacity kW 39.0
Input W 2272
Model ZKSN-920-8-12-1
Type DC
Brand Nidec/Yongan
Input W 920
Number of rows 5
Tube pitch × row
Fin spacing mm 1.5
Fin type Hydrophilic aluminum
Tube OD and type mm Ф7 Inner groove
Dimensions (L×H ×W) mm 1602×588×53.84
Number of circuits 28
Net dimensions
Packed dimensions
Net/Gross weight kg 218/248
Liquid/Gas side mm Ф15.9/Ф28.6
mm 21×13.37
mm 2010×680×905
mm 2105×800×929
Type Electronic expansion valve
Model DPF(TS2)4.5C-02
6 201806
Page 7
2 Dimensions
(W)
foeziS
Air
Inlet
(W)
)L(
Size of Air Outlet
(L)
Refrigerant piping
(liquid side)
Connect to water
piping
Position of
lifting bolt
Air
Inlet Flange
Fresh
Air
Inlet Flange
Connection
hole
Electric control
box assembly
Air Inlet
Air Outlet
Air
fresh
fre sh
Fresh
2.1 Unit Dimensions
SDV5-125DFA / SDV5-140DFA
Figure 2.1:
SDV5-125,140DFA dimensions (unit: mm)
201806 7
Page 8
Sizeof Fresh
Air Inlet
Positionof lifting bolt
SizeofAir Outlet
Refrigerant piping
(gasside)
Refrigerant piping
(liquid side)
Φ22 (OD)
Φ12.7(OD)
Conne ct to
water piping
F r e s h
Air InletFlange
AirOutlet Flange
Fresh Air Inlet
Air Outlet
Positions of 4-12 *25
lifting bolts
Electric control
box assem bly
Conne ction hole
(for the air duct)
(L)
(W)
(W)
(L)
56
81
10
5
68
.5
205
80
110
SDV5-200DFA / SDV5-250DFA / SDV5-280DFA
Figure 2.2:
SDV5-200,250,280DFA dimensions (unit: mm)
8 201806
Page 9
SDV5-560DFA
Air Outlet Flange
Repair hole
Electric control 
box assembly
Return Air Inlet
Air Outlet
Refrigerant piping
(gas side)
Refrigerant piping
(liquid side)
Φ28 (OD)
Φ15.9(OD)
Positions of 4-12*25 
lifting bolts
1937
1905
1940
2010
990
1600
626
316
333
680
905
905
750
500
590
316
Figure
2.3: SDV5-560DFA
dimensions (unit: mm)
201806 9
Page 10
3 Unit Placement
Maintenance roomage
Maintenance roomage
checking orifice
or more
600mmX600mm
500mm
or more
600mm
checkingorifice
Confirm the minimum drain tilt is 1/100 or more
3.1 Placement Considerations
Unit placement should take account of the following considerations:
Units should not be installed in the following locations:
Where exposure to direct radiation from a high-temperature heat source or to interference from a source of
electromagnetic radiation may occur.
Where dust or dirt may affect heat exchangers.Where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.Where exposure to salinity may occur, such as seaside locations.Where highly flammable materials are present.Where exposure to oily air may occur, such as a kitchen.Where exposure to very high humidity may occur, such as a laundry.
Units should be installed in positions where:
The ceiling is horizontal and is able to bear the unit’s weight.There are no obstructions that could impede the airflow into and out of the unit.The airflow out of the unit can reach throughout the room.There is sufficient space for access during installation, servicing and maintenance.The refrigerant piping and drain piping can be easily connected to the refrigerant piping and drain piping systems.Short-circuit ventilation (where outlet air returns quickly to a unit’s air inlet) will not occur.
3.2 Space Requirements
Figure 3.1: Fresh Air Processing Unit space requirements (unit: mm)
10 201806
Page 11
4 Piping Diagram
flare nut
flare nut
T2B
gas side
motor
heat exchanger
fan
EXV
liquid side
T2
T0
TA
SDV5-125DFA / SDV5-140DFA / SDV5-200DFA / SDV5-250DFA / SDV5-280DFA / SDV5-560DFA
Figure 4.1:
SDV5-125,140,200,250,280,560DFA
piping diagram
Legend
T0 Outdoor fresh air temperature sensor
Indoor heat exchanger mid-point temperature sensor
T2
T2B Indoor heat exchanger outlet temperature sensor
TA Air outlet temperature sensor
201806 11
Page 12
5 Wiring Diagrams
SDV5-125DFA / SDV5-140DFA
Figure 5.1:
SDV5-125,140DFA
wiring diagram
12 201806
Page 13
SDV5-200DFA / SDV5-250DFA / SDV5-280DFA
Figure 5.2:
SDV5-200,250,280DFA
wiring diagram
201806 13
Page 14
SDV5-560DFA
Figure 5.3:
SDV5-560DFA
wiring diagram
14 201806
Page 15
6 Fan Performance
250Pa
240Pa
230Pa
220Pa
210Pa
200Pa
190Pa
180Pa(default)
170Pa
160Pa
150Pa
140Pa
130Pa
120Pa
110Pa
100Pa
50
70
90
110
130
150
170
190
210
230
250
1450 1650 1850 2050
Static pressure (Pa)
Air flow (m3/h)
400Pa
380Pa
360Pa
340Pa
330Pa
320Pa
310Pa 300Pa 290Pa 280Pa 270Pa 260Pa
240Pa
220Pa
200Pa(default)
180Pa
160Pa
140Pa
120Pa
100Pa
40
60
80
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
1950 2150 2350 2550 2750 2950 3150
Static pressure (Pa)
Air flow (m3/h)
Figure 6.1:
SDV5-125,140DFA fan performance
SSH
SH
H
M
L
SL
SSL
201806 15
Figure 6.2:
SDV5-200,250,280DFA fan performance
L
SL
SSL
M
H
SH
SSH
Page 16
Figure 6.3: SDV5-560DFA fan performance
Air flow(m3/h)
16 201806
Page 17
7 Capacity Tables
7.1 Cooling Capacity Table
Table 7.1: Fresh Air Processing Unit cooling capacity
Outdoor air temperature (°C WB)
Capacity
(kW)
12.5
14.0
20.0
25.0
Abbreviations: TC: Total capacity
Notes:
1. Shaded cells indicate rating condition.
201806 17
Outdoor air temperature
(°C DB)
20.0 5.6 6.1
22.0 6.3 6.9 7.5
25.0 6.8 7.5 8.3 8.9
27.0 8.0 8.8 9.5
29.0 9.2 10.0 10.8
31.0 9.6 10.5 11.3 12.0
33.0 9.9 10.9 11.8 12.5 13.3
35.0 11.1 12.2 13.1 13.8 14.4
38.0 12.8 13.7 14.4 15.1
43.0 13.4 14.3 15.0 15.8
20.0 6.3 6.8
22.0 7.0 7.8 8.4
25.0 7.6 8.4 9.2 10.0
27.0 8.9 9.8 10.7
29.0 10.3 11.2 12.1
31.0 10.7 11.7 12.6 13.5
33.0 11.1 12.2 13.2 14.0 14.8
35.0 12.5 13.7 14.6 15.4 16.2
38.0 14.3 15.3 16.1 16.9
43.0 15.0 16.0 16.8 17.7
20.0 9.0 9.7
22.0 10.0 11.1 12.0
25.0 10.8 12.0 13.2 14.3
27.0 12.7 14.0 15.3
29.0 14.7 16.0 17.3
31.0 15.3 16.7 18.0 19.3
33.0 15.8 17.4 18.8 20.0 21.2
35.0 17.8 19.6 20.9 22.0 23.1
38.0 20.5 21.8 23.0 24.1
43.0 21.4 22.8 24.0 25.2
20.0 11.2 12.1
22.0 12.5 13.9 15.0
25.0 13.5 15.0 16.5 17.9
27.0 15.9 17.5 19.1
29.0 18.4 20.0 21.6
31.0 19.1 20.9 22.5 24.1
33.0 19.8 21.8 23.5 25.0 26.5
35.0 22.3 24.5 26.1 27.5 28.9
38.0 25.6 27.3 28.7 30.2
43.0 26.7 28.5 30.0 31.5
15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0 TC TC TC TC TC TC TC TC
kW kW kW kW kW kW kW kW
Table continued on next page …
Page 18
Table 7.1: Fresh Air Processing Unit cooling capacity (continued)
Capacity
(kW)
28.0
56.0
Outdoor air temperature
(°C DB)
20.0 12.5 13.6
22.0 14.0 15.5 16.8
25.0 15.1 16.8 18.5 20.0
27.0 17.8 19.6 21.4
29.0 20.6 22.4 24.2
31.0 21.4 23.4 25.2 27.0
33.0 22.1 24.4 26.3 28.0 29.7
35.0 24.9 27.4 29.3 30.8 32.3
38.0 28.6 30.6 32.2 33.8
43.0 29.9 32.0 33.6 35.3
20.0 25.0 27.2
22.0 28.0 31.0 33.6
25.0 30.2 33.6 37.0 40.0
27.0 35.6 39.2 42.8
29.0 41.2 44.8 48.4
31.0 42.8 46.8 50.4 54.0
33.0 44.2 48.8 52.6 56 59.4
35.0 49.8 54.8 58.6 61.6 64.6
38.0 57.2 61.2 64.4 67.6
43.0 59.8 64.0 67.2 70.6
15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0 TC TC TC TC TC TC TC TC
kW kW kW kW kW kW kW kW
Abbreviations: TC: Total capacity
Notes: Shaded cells indicate rating condition.
Outdoor air temperature (°C WB)
18 201806
Page 19
7.2 Heating Capacity Table
Table 7.2: Fresh Air Processing Unit heating capacity
Capacity
(kW)
12.5
14.0
20.0
25.0
28.0
56
Abbreviations: TC: Total capacity
Notes: Shaded cells indicate rating condition.
Outdoor air temperature
(°C DB)
-5.0 8.9 8.7
0.0 10.5
3.0 11.1 10.9 9.8
7.0 12.1 12.0 11.8
11.0 13.7 13.5 13.4
15.0 15.8 15.6 15.4
-5.0 10.2 10.0
0.0 12.0
3.0 12.7 12.5 11.2
7.0 13.8 13.7 13.5
11.0 15.6 15.4 15.3
15.0 18.0 17.8 17.6
-5.0 15.2 14.9
0.0 18.0
3.0 19.1 18.7 16.8
7.0 20.7 20.5 20.3
11.0 23.4 23.2 22.9
15.0 27.0 26.7 26.5
-5.0 16.9 16.6
0.0 20.0
3.0 21.2 20.8 18.7
7.0 23.0 22.8 22.5
11.0 26.0 25.7 25.5
15.0 30.0 29.7 29.4
-5.0 18.6 18.3
0.0 22.0
3.0 23.3 22.9 20.6
7.0 25.3 25.0 24.8
11.0 28.6 28.3 28.0
15.0 33.0 32.7 32.3
-5.0 33.0 32.4
0.0 39.0
3.0 41.3 40.6 36.5
7.0 44.9 44.3 44.0
11.0 50.7 50.2 49.6
15.0 58.5 58.0 57.3
-7.0 -5.2 -2.9 0.0 2.0 4.0 6.0 10.0 14.0
TC TC TC TC TC TC TC TC TC
kW kW kW kW kW kW kW kW kW
Outdoor air temperature (°C WB)
201806 19
Page 20
8 Electrical Characteristics
Table 8.1: Fresh Air Processing Unit electrical characteristics
Power supply Indoor fan motors
Model name
Hz Volts Min. volts Max. volts MCA MFA
SDV5-125DFA 50 220-240 198 264 3.5 15 0.31 2.8 SDV5-140DFA 50 220-240 198 264 3.5 15 0.34 2.8 SDV5-200DFA 50 220-240 198 264 5.2 15 0.80 4.1 SDV5-250DFA 50 220-240 198 264 5.2 15 0.96 4.1 SDV5-280DFA 50 220-240 198 264 5.2 15 0.96 4.1
SDV5-560DFA 50 220-240 198 264 14.5 30 1.84 11.6
Abbreviations:
MCA: Minimum Circuit Amps MFA: Maximum Fuse Amps FLA: Full Load Amps
Rated motor
output (kW)
FLA
20 201806
Page 21
9 Sound Levels
Suction
Discharge
Microphone
1.4m
Concealed Duct Type
Duct
9.1 Overall
Table 9.1: Fresh Air Processing Unit sound pressure levels1
Sound pressure levels dB(A)
Model name
SSH SH H M L SL SSL
SDV5-125DFA 48 47 46 45 44 43 42 SDV5-140DFA 48 47 46 45 44 43 42 SDV5-200DFA 50 49 48 47 46 44 43 SDV5-250DFA 50 49 48 47 46 44 43 SDV5-280DFA 50 49 48 47 46 44 43 SDV5-560DFA 59 58 57 56 55 53 51
Notes:
1. Sound pressure levels are measured 1.4m below the unit in a semi-
anechoic chamber. During in-situ operation, sound pressure levels may be higher as a result of ambient noise.
9.2 Octave Band Levels
Figure
9.2: SDV5-125,140DFA octave band levels Figure 9.3: SDV5-200,250,280DFA octave band levels
80
Figure 9.1: Fresh Air Processing Unit sound pressure level
measurement
80
70
60
SSH
SH
H
M
50
L
SL
SSL
40
30
20
10
0
Octave band sound pressure level dB(A)
63 125 250 500 1000 2000 4000 8000
NC65 NC60 NC55
NC50 NC45 NC40 NC35 NC30
NC25 NC20 NC15
70
SSH
60
SH
H
M
L
50
SL
SSL
40
30
20
10
0
Octave band sound pressure level dB(A)
63 125 250 500 1000 2000 4000 8000
NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
NC25
NC20 NC15
Octave band center frequency (Hz) Octave band center frequency (Hz)
201806 21
Page 22
80
70
60
50
40
30
20
10
Figure 9.3: SDV5-560DFA octave band levels
SSH
SH
H
M
L
SL
SSL
NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
NC25
NC20 NC15
Octave band sound pressure level dB(A)
0
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
22 201806
Page 23
FRESH AIR PROCESSING DUCT UNITS SDV5-125-280DHA
COMMERCIAL AIR CONDITIONERS SDV5
Page 24
SDV5-125DFA
Page 25
No Description Part Code Note Qty Price Code
MODEL: SDV5-125DFA FRESH AIR PROCESSING DUCT UNIT
1 E-Part box cover 12226000000009 1 2 E-part box assembly 17226000002660 1
2.1 Reactance 17400306000163 1
2.2 Radiator Components 17127000006656 1
2.2.1
Module board assembly 17127000006679 1
2.2.2 Radiator 11203803002876 1
2.2.3 rectifier bridge 11201418000014 1
2.3 Indoor unit main control board 17126000003346 1
2.4 Wire joint 17400401001516 1
2.5 Wire joint 17400401000156 1
2.6 Clip 12222200001925 1
2.7 Insulation plate 12122000006931 1 3 Side board ass’y 12226000003496 1 4 Front panel assembly 12223000000145 1 5 Centrifugal fan 12200102000023 1 6 Motor 11002015000348 1 7 Bearin supporting board 12226000000369 1 8 Fan motor ass'y 12226000000012 1 9 Top cover assembly 12226000000794 1 10 Centrifugal fan 12200102000006 1 11 Left clapboard ass'y 12223000001065 1 12 Pipe temperature sensor assemblies 11201007000030 1 13 Pipe temperature sensor 11201007000025 1 14 chassis ass'y 12226000003453 1 15 beam ass'y 12226000000440 1 16 Drain tray 12822500000131 1 17 Supporting board ass'y, evaporator 12226000000811 1 18 Evaporator ass'y 15826000000040 1
18.1 Pipe Temperature Sensor 11201007000113 1 19 air fresh filter 12100204A00159 1 20 Rear clapboard 12223000000160 1 21 Evaporator right support board subassembly 12223000000292 1 22 23 24
cover plate 12226000000292 1 Fixing board, pipes 12223000001708 1 Pipe fixing clamp 12223000001610 1
The data are subject to change without notice.
Page 26
SDV5-140DFA
Page 27
No Description Part Code Note Qty Price Code
MODEL: SDV5-140DFA FRESH AIR PROCESSING DUCT UNIT
1 E-Part box cover 12226000000009 1 2 E-part box assembly 17226000002660 1
2.1 Reactance 17400306000163 1
2.2 Radiator Components 17127000006656 1
2.2.1
Module board assembly 17127000006679 1
2.2.2 Radiator 11203803002876 1
2.2.3 rectifier bridge 11201418000014 1
2.3 Indoor unit main control board 17126000003346 1
2.4 Wire joint 17400401001516 1
2.5 Wire joint 17400401000156 1
2.6 Clip 12222200001925 1
2.7 Insulation plate 12122000006931 1 3 Side board ass’y 12226000003496 1 4 Front panel assembly 12223000000145 1 5 Centrifugal fan 12200102000023 1 6 Motor 11002015000348 1 7 Bearin supporting board 12226000000369 1 8 Fan motor ass'y 12226000000012 1 9 Top cover assembly 12226000000794 1 10 Centrifugal fan 12200102000006 1 11 Left clapboard ass'y 12223000001065 1 12 Pipe temperature sensor assemblies 11201007000030 1 13 Pipe temperature sensor 11201007000025 1 14 chassis ass'y 12226000003453 1 15 beam ass'y 12226000000440 1 16 Drain tray 12822500000131 1 17 Supporting board ass'y, evaporator 12226000000811 1 18 Evaporator ass'y 15826000000040 1
18.1 Pipe Temperature Sensor 11201007000113 1 19 air fresh filter 12100204A00159 1 20 Rear clapboard 12223000000160 1 21 Evaporator right support board subassembly 12223000000292 1 22 23 24
cover plate 12226000000292 1 Fixing board, pipes 12223000001708 1 Pipe fixing clamp 12223000001610 1
The data are subject to change without notice.
Page 28
SDV5-200DFA
Page 29
No Description Part Code Note Qty Price Code
MODEL: SDV5-200DFA FRESH AIR PROCESSING DUCT UNIT
1 Electric control box cover assembly 12223000010829 1 2 E-part box assembly 17226000002674 1
2.1 Indoor unit main control board 17126000003347 1
2.2 Radiator assembly 17127000006663 1
2.2.1
rectifier bridge 11201418000014 2
2.2.2 Module board assembly 17127000006676 1
2.3 Reactance 17400306000785 1
2.4 Capacitor 17400103000146 1
2.5 reactor 17400306000307 1 3 Side board ass’y 12226000003473 1 4 connecting board ass'y 12226000000224 1 5 Centrifugal fan 12200102000012 1 6 Chassis assembly 12223000010834 1 7 Below flange ass'y 12226000000301 1 8 Motor support 12226000003614 1 9 Fan-motor assembly 12226000003474 1 10 Flange assembly 12226000000004 1 11 Left clapboard ass'y 12226000000283 1 12 Volute shell ass'y 12200101000019 1 13 Brushless DC Motor 11002015007704 1 14 Beam ass'y 12226000000791 1 15 Top cover ass'y 12226000000792 1 16 Connecting board ass'y 12226000000231 1 17 Below flange ass'y 12226000000301 1 18 Fixing board ass'y, drain tray 12226000000249 1 19 Left clapboard ass'y 12226000000270 1 20 Drainage tray ass'y 12226000000243 1 21 Evaporator ass 15826000002132 1 22 Flange ass'y 12226000000005 1 23 Top cover ass'y 12226000000212 1 24 Air filter 12100204001739 1 25 Pipe clamp board assembly 12226000002154 1 26 27 28 29
Fixing board, pipes 12223000001708 1 Pipe fixing clamp 12223000001610 1 Pipe clamp board assembly 12226000002156 1 Side panel ass'y 12226000003497 1
The data are subject to change without notice.
Page 30
SDV5-250DFA
Page 31
No Description Part Code Note Qty Price Code
MODEL: SDV5-250DFA FRESH AIR PROCESSING DUCT UNIT
1 Electric control box cover assembly 12223000010829 1 2 E-part box assembly 17226000002674 1
2.1 Indoor unit main control board 17126000003347 1
2.2 Radiator assembly 17127000006663 1
2.2.1
rectifier bridge 11201418000014 2
2.2.2 Module board assembly 17127000006676 1
2.3 Reactance 17400306000785 1
2.4 Capacitor 17400103000146 1
2.5 reactor 17400306000307 1 3 Side board ass’y 12226000003473 1 4 connecting board ass'y 12226000000224 1 5 Centrifugal fan 12200102000012 1 6 Chassis assembly 12223000010834 1 7 Below flange ass'y 12226000000301 1 8 Motor support 12226000003614 1 9 Fan-motor assembly 12226000003474 1 10 Flange assembly 12226000000004 1 11 Left clapboard ass'y 12226000000283 1 12 Volute shell ass'y 12200101000019 1 13 Brushless DC Motor 11002015007704 1 14 Beam ass'y 12226000000791 1 15 Top cover ass'y 12226000000792 1 16 Connecting board ass'y 12226000000231 1 17 Below flange ass'y 12226000000301 1 18 Fixing board ass'y, drain tray 12226000000249 1 19 Left clapboard ass'y 12226000000270 1 20 Drainage tray ass'y 12226000000243 1 21 Evaporator ass 15826000002132 1 22 Flange ass'y 12226000000005 1 23 Top cover ass'y 12226000000212 1 24 Air filter 12100204001739 1 25 Pipe clamp board assembly 12226000002154 1 26 27 28 29
Fixing board, pipes 12223000001708 1 Pipe fixing clamp 12223000001610 1 Pipe clamp board assembly 12226000002156 1 Side panel ass'y 12226000003497 1
The data are subject to change without notice.
Page 32
SDV5-280DFA
Page 33
No Description Part Code Note Qty Price Code
MODEL: SDV5-280DFA FRESH AIR PROCESSING DUCT UNIT
1 Electric control box cover assembly 12223000010829 1 2 E-part box assembly 17226000002674 1
2.1 Indoor unit main control board 17126000003347 1
2.2 Radiator assembly 17127000006663 1
2.2.1
rectifier bridge 11201418000014 2
2.2.2 Module board assembly 17127000006676 1
2.3 Reactance 17400306000785 1
2.4 Capacitor 17400103000146 1
2.5 reactor 17400306000307 1 3 Side board ass’y 12226000003473 1 4 connecting board ass'y 12226000000224 1 5 Centrifugal fan 12200102000012 1 6 Chassis assembly 12223000010834 1 7 Below flange ass'y 12226000000301 1 8 Motor support 12226000003614 1 9 Fan-motor assembly 12226000003474 1 10 Flange assembly 12226000000004 1 11 Left clapboard ass'y 12226000000283 1 12 Volute shell ass'y 12200101000019 1 13 Brushless DC Motor 11002015007704 1 14 Beam ass'y 12226000000791 1 15 Top cover ass'y 12226000000792 1 16 Connecting board ass'y 12226000000231 1 17 Below flange ass'y 12226000000301 1 18 Fixing board ass'y, drain tray 12226000000249 1 19 Left clapboard ass'y 12226000000270 1 20 Drainage tray ass'y 12226000000243 1 21 Evaporator ass 15826000002132 1 22 Flange ass'y 12226000000005 1 23 Top cover ass'y 12226000000212 1 24 Air filter 12100204001739 1 25 Pipe clamp board assembly 12226000002154 1 26 27 28 29
Fixing board, pipes 12223000001708 1 Pipe fixing clamp 12223000001610 1 Pipe clamp board assembly 12226000002156 1 Side panel ass'y 12226000003497 1
The data are subject to change without notice.
Page 34
NOTE CONCERNING PROTECTION OF ENVIRONMENT
his product must not be disposed of via normal household waste after its service life, but must be
T taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal procedures. The materials are recyclable in accordance with their respective symbols. By means of re-use, material recycling or any other form of recycling old appliances you are making an important contribution to the protection of our environment. Please ask your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT MEDIUM
T
his unit is containing fluorinated gases included in the Kyoto protocol. The maintenance and the liquidation must be carried out by qualified personnel. Type of refrigerant: R410A The composition of the cooling medium R410A: (50% HFC-32, 50% HFC-125) The quantity of the refrigerant: please see the unit label. The value GWP: 2088 (1 kg R410A = 2,088 t CO2 eq) GWP = Global Warming Potential
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODU
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain
www.sinclair-world.com
This product was manufactured in China (Made in China).
CER
REPRESENTATIVE
SINCL
AIR Global Group s.r.o. Purkynova 45 612 00 Brno Czech Republic
TECHNICAL SUPPORT
AIR Global Group s.r.o.
SINCL Purkynova 45 612 00 Brno Czech Republic
Tel.: +420 800 100 285 Fax: +420 541 590 124
www.sinclair-solutions.com info@sinclair-solutions.com
Loading...