Main menu Submenu/Option Range Default Note:
Target value
Setting of desired temperature; this menu is not accessible in the slave
mode.
-10 to +60 +10,0°C p. 7
Function Operated
Slave unit mode. The module is controlled by an external voltage 010V.
Operated p. 8
Reg. P
Autonomous pressure (evaporation temperature) control mode p. 9
Reg. T*
Autonomous temperature control mode for cooling p. 10
Reg. T+
Autonomous temperature control mode for heating
Defrost Mode Off
Defrosting of indoor unit evaporator is not in use Off p. 11
External
Defrosting with external support (heating cable etc.)
Reverse
Defrosting by switching from cooling to heating
mode.
Period
Setting the minimum time period between defrosting
cycles
0.1 to 99.9 1 hour p. 12
Length
Setting the maximum duration of defrosting 1.0 to 60.0 10 min
Start
Setting the temperature to start defrosting -20 to +5,0 -5,0°C p. 13
Stop
Setting the temperature to stop defrosting +3 to +25.0 +7,0°C
Outputs Relay 1 Function ON/OFF
Relay is controlled by On/Off input. On/Off p. 14
Compres.
Relay is controlled according to the
compressor
Defrost
Relay is controlled according to the
operation (Heat/Cool)
Error
Relay is controlled according to the
error state
Heat/Cool
Relay is controlled according to the
operation (Heat/Cool)
Limiting
Relay to limit the long lasting
compressor load.
Logic Direct
Relay switches with direct logic Direct
Inverse
Relay switches with inverse logic
Relay 2 Function
This setting is the same as setting the Relay 1 Compres.
Logic
This setting is the same as setting the Relay 1 Direct
Relay 3 Function
This setting is the same as setting the Relay 1 Error
Logic
This setting is the same as setting the Relay 1 Direct
DC Vent Fixed
Setting the speed and mode (Co, Fa, On) of the
indoor fan
Off p. 15
Auto 1
Fan speed according to compressor speed 1:1
Auto 2
Fan speed of 60-200% of compressor speed
Off
Output not used
Reg.cons Time con
Setting the time constant of the module. 10 to 999 30 sec. p. 16
Prop.con
Setting the proportional constant of the module. 0 to 999 35
Int.cons
Setting the integral constant of the module. 0 to 999 0
Der.cons
Setting the derivative constant of the module. 0 to 999 60
Display Backlight
Setting the LCD backlight. 1 to 16 8 p. 17
Contrast
Setting the LCD contrast. 1 to 16 8
Time gap
Setting the time period of the operator inactivity 10 to 999 60
Language
Setting the language version CZ / EN EN p. 18
Password
Enter the password before setting the module. After logging in, you can perform
setting for about 30 minutes. Without knowing the password, you can only adjust the
contrast and backlight brightness of the display.
201201 p. 6
Tab 1: Summary of the module settings
After setting is done, click on “Write” button to save all parameters in module memory.
All saved parameters can be displayed by clicking “Read” button.