1. Introduction
www.sinclair-solutions.com
. USBC software can also display current setting of SCMI-01
module.
2. Preparation
Mini USB cable is needed for communication between computer and SCMI-01 module. This cable is not included in standard package.
Fig 1: Mini USB cable Fig 2: Front panel of module
Connect the SCMI-01 module with computer using mini USB cable (Fig 1). Display of module will turn on after successful connection.
3. SCMI-01 setting via USBCommunicator
Application bookmark
Here you can find the information about this software (“About”), select the language (“Language”) and you can also close whole application (“Close”).
Fig 3: „Application“ bookmark
Page 4
Device bookmark
This option shows „Supported devices” interface. To set SCMI-01 module, choose SCMI Sinclair driver option. USBC software will automatically detect SCMI-01 device after you connect it to computer.
Fig 4: „Device“ bookmark
Page 5
The setting options in USBC software are the same as options in SCMI-01 module itself. You can find detailed information about each feature in user manual for SCMI-01 module.
Fig 5: SCMI Sinclair driver interface
Page 6
Main menu Submenu/Option Range Default Note: Target value
Setting of desired temperature; this menu is not accessible in the slave mode.
-10 to +60 +10,0°C p. 7
Function Operated
Slave unit mode. The module is controlled by an external voltage 0­10V.
Operated p. 8
Reg. P
Autonomous pressure (evaporation temperature) control mode p. 9
Reg. T*
Autonomous temperature control mode for cooling p. 10
Reg. T+
Autonomous temperature control mode for heating
Defrost Mode Off
Defrosting of indoor unit evaporator is not in use Off p. 11
External
Defrosting with external support (heating cable etc.)
Reverse
Defrosting by switching from cooling to heating mode.
Period
Setting the minimum time period between defrosting cycles
0.1 to 99.9 1 hour p. 12
Length
Setting the maximum duration of defrosting 1.0 to 60.0 10 min
Start
Setting the temperature to start defrosting -20 to +5,0 -5,0°C p. 13
Stop
Setting the temperature to stop defrosting +3 to +25.0 +7,0°C
Outputs Relay 1 Function ON/OFF
Relay is controlled by On/Off input. On/Off p. 14
Compres.
Relay is controlled according to the compressor
Defrost
Relay is controlled according to the operation (Heat/Cool)
Error
Relay is controlled according to the error state
Heat/Cool
Relay is controlled according to the operation (Heat/Cool)
Limiting
Relay to limit the long lasting compressor load.
Logic Direct
Relay switches with direct logic Direct
Inverse
Relay switches with inverse logic
Relay 2 Function
This setting is the same as setting the Relay 1 Compres.
Logic
This setting is the same as setting the Relay 1 Direct
Relay 3 Function
This setting is the same as setting the Relay 1 Error
Logic
This setting is the same as setting the Relay 1 Direct
DC Vent Fixed
Setting the speed and mode (Co, Fa, On) of the indoor fan
Off p. 15
Auto 1
Fan speed according to compressor speed 1:1
Auto 2
Fan speed of 60-200% of compressor speed
Off
Output not used
Reg.cons Time con
Setting the time constant of the module. 10 to 999 30 sec. p. 16
Prop.con
Setting the proportional constant of the module. 0 to 999 35
Int.cons
Setting the integral constant of the module. 0 to 999 0
Der.cons
Setting the derivative constant of the module. 0 to 999 60
Display Backlight
Setting the LCD backlight. 1 to 16 8 p. 17
Contrast
Setting the LCD contrast. 1 to 16 8
Time gap
Setting the time period of the operator inactivity 10 to 999 60
Language
Setting the language version CZ / EN EN p. 18
Password
Enter the password before setting the module. After logging in, you can perform setting for about 30 minutes. Without knowing the password, you can only adjust the contrast and backlight brightness of the display.
201201 p. 6
Tab 1: Summary of the module settings
After setting is done, click on “Write” button to save all parameters in module memory.
All saved parameters can be displayed by clicking “Read” button.
Page 7
4. Language update of SCMI-01 module
Click on “globe” icon in SCMI Sinclair driver interface (as shown in fig 5). In the dialog window you need to open “languages” folder located in downloaded files/on mini CD and choose desired language set (XXX.RAW file). Each language set consists of two languages – English and the chosen one (DE, PL, CZ, HR, HU).
5. Password
You can change or deactivate password via USBC software.
Page 8
NOTE CONCERNING PROTECTION OF ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal procedures. The materials are recyclable in accordance with their respective symbols. By means of re-use, material recycling or any other form of recycling old appliances you are making an important contribution to the protection of our environment. Please ask your local council where your nearest disposal station is located.
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain
www.sinclair-world.com
This product was manufactured in Czech Republic (Made in Czech Republic).
REPRESENTATIVE
SINCLAIR EUROPE spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
TECHNICAL SUPPORT
NEPA spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
Tel.: +420
800 100 285
Fax: +420 541 590 124
www.sinclair-solutions.com info@sinclair-solutions.com
Loading...