Sinclair ROCKY SERIES ASH-09AIR, ROCKY SERIES ASH-12AIR, ROCKY SERIES YX1F Service Manual

Page 1
SERVICE MANUAL
ASH-09AIR, ASH-12AIR
ROCKY SERIES
3
Page 2
4
Page 3
Service Manual
Table of Contents
Part
: Technical Information
.......................................................................1
1. Summary
......................................................................................................................1
2. Specications
..........................................................................................................2
2.1 Specication Sheet ...........................................................................................................2
2.2 Operation Characteristic Curve ........................................................................................4
2.3 Capacity Variation Ratio According to Temperature .........................................................4
2.4 Cooling and Heating Data Sheet in Rated Frequency .....................................................5
2.5 Noise Curve ......................................................................................................................5
3. Outline Dimension Diagram
........................................................................6
3.1 Indoor Unit ........................................................................................................................6
3.2 Outdoor Unit .....................................................................................................................7
4. Refrigerant System Diagram
......................................................................8
5. Electrical Part
...........................................................................................................9
5.1 Wiring Diagram .................................................................................................................9
5.2 PCB Printed Diagram .....................................................................................................11
6. Function and Control
......................................................................................13
6.1 Remote Controller Introduction of YB1FA ......................................................................13
6.2 Brief Description of Modes and Functions ......................................................................16
Part
: Installation and Maintenance
.................................................21
7. Notes for Installation and Maintenance
..........................................21
8. Installation
................................................................................................................23
8.1 Installation Dimension Diagram ......................................................................................23
8.2 Installation Parts-checking ............................................................................................25
8.3 Selection of Installation Location ....................................................................................25
8.4 Electric Connection Requirement ...................................................................................25
8.5 Installation of Indoor Unit ................................................................................................25
8.6 Installation of Outdoor Unit .............................................................................................28
8.7 Vacuum Pumping and Leak Detection ...........................................................................29
8.8 Check after Installation and Test Operation ...................................................................29
5
Page 4
Service Manual
9. Maintenance
............................................................................................................30
9.1 Malfunction Analysis .......................................................................................................30
9.2 Flashing LED of Indoor/Outdoor Unit and Primary Judgement ......................................34
9.3 How to Check Simply the Main Part ...............................................................................43
10. Exploded View and Parts List
..............................................................55
10.1 Indoor Unit ....................................................................................................................55
10.2 Outdoor Unit .................................................................................................................57
11. Removal Procedure
.......................................................................................61
11.1 Removal Procedure of Indoor Unit ...............................................................................61
11.2 Removal Procedure of Outdoor Unit ............................................................................66
Appendix:
........................................................................................................................75
Appendix 1: Reference Sheet of Celsius and Fahrenheit ....................................................75
Appendix 2: Conguration of Connection Pipe .....................................................................75
Appendix 3: Pipe Expanding Method ...................................................................................76
Appendix 4: List of Resistance for Temperature Sensor ......................................................77
6
Page 5
Service Manual
1. Summary
Part
: Technical Information
Indoor Unit:
ASH-09AIR ASH-12AIR
Outdoor Unit:
ASH-09AIR
ASH-12AIR
Remote Controller:
YX1F
ON/OFF MODE
FAN SWING
SLEEP TIMER
+
-
AUTO COOL DRY FAN HEAT
T-ON T-OFF
SWING SLEEP LOCK SPEED
7
Page 6
Service Manual
2. Specications
2.1 Specication Sheet
Model ASH-09AIR ASH-12AIR
Power
Supply
Rated Voltage V~ 220-240 220-240
Rated Frequency Hz 50 50
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity(Min~Max) W 2500(600~2800) 3200(600~3500)
Heating Capacity(Min~Max) W 2750(600~3000) 3400(600~3800)
Cooling Power Input(Min~Max) W 800(120~1300) 1020(120~1400)
Heating Power Input(Min~Max) W 780(120~1400) 995(120~1500)
Cooling Current Input A 3.6 4.5
Heating Current Input A 3.5 4.4
Rated Input W 1400 1500
Rated Current A 6.7 7.2
Air Flow Volume(SH/H/M/L/SL) m3/h 500/400/300/250/- 500/400/300/250/-
Dehumidifying Volume L/h 0.8 1.4
EER W/W 3.13 3.14
COP W/W 3.53 3.42
SEER 5.8 6.1
HSPF / /
Application Area m
2
12-18 15-22
Indoor
Unit
Fan Type Cross-ow Cross-ow
Fan Diameter Length(DXL) mm Φ85X596 Φ85X596
Cooling Speed(SH/H/M/L/SL) r/min 1320/1100/920/730/- 1320/1100/920/730/-
Heating Speed(SH/H/M/L/SL) r/min 1350/1200/1100/1000/- 1350/1200/1100/1000/-
Fan Motor Power Output W 10 10
Fan Motor RLA A 0.15 0.15
Fan Motor Capacitor μF 1 1
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm Φ7 Φ7
Evaporator Row-n Gap mm 2-1.4 2-1.4
Evaporator Coil Length(LXDXW) mm 592X25.4X266.7 592X25.4X266.7
Swing Motor Model MP24AA MP24AA
Swing Motor Power Output W 1.5 1.5
Fuse Current A 3.15 3.15
Sound Pressure Level(SH/H/M/L/SL) dB (A) 38/34/31/28/- 39/34/31/28/-
Sound Power Level(SH/H/M/L/SL) dB (A) 50/46/43/40/- 53/47/43/40/-
Dimension(WXHXD) mm 790X265X174 790X265X174
Dimension of Carton Box(LXWXH) mm 870X248X355 870X248X355
Dimension of Package(LXWXH) mm 873X251X370 873X251X370
Net Weight kg 9 9
Gross Weight kg 10.5 10.5
8
Page 7
Service Manual
Outdoor
Unit
Model of Outdoor Unit ASH-09AIR ASH-12AIR
Compressor Manufacturer/Trademark
ZHUHAI LANDA COMPRESSOR
CO., LTD
ZHUHAI GREE DAIKIN DEVICE
CO., LTD
Compressor Model QXA-A091zE190A 1GDY23AXD
Compressor Oil 68EP FVC50K
Compressor Type Rotary Rotary
L.R.A. A 16.5 16.5
Compressor RLA A 4.5 4
Compressor Power Input W 942 845
Overload Protector 1NT11L-6233 1GDY23AXD-05
Throttling Method Capillary Capillary
Operation temp
o
C 16~30 16~30
Ambient temp (cooling)
o
C -15~48 -15~48
Ambient temp (heating)
o
C -15~24 -15~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Φ7 Φ7.94
Rows-n Gap mm 1-1.4 1-1.4
Coil Length (LXDXW) mm 692X19.05X506 731X19.05X550
Fan Motor Speed rpm 900/600 900/600
Output of Fan Motor W 30 30
Fan Motor RLA A 0.4 0.4
Fan Motor Capacitor μF / /
Air Flow Volume of Outdoor Unit m3/h 1600 2200
Fan Type Axial-ow Axial-ow
Fan Diameter mm Φ400 Φ438
Defrosting Method Automatic Defrosting Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IP24 IP24 Permissible Excessive Operating
Pressure for the Discharge Side
MPa 4.3 4.3
Permissible Excessive Operating
Pressure for the Suction Side
MPa 2.5 2.5
Sound Pressure Level (H/M/L) dB (A) 50/-/- 51/-/-
Sound Power Level (H/M/L) dB (A) 60/-/- 63/-/-
Dimension (WXHXD) mm 776X540X320 842X596X320
Dimension of Carton Box (LXWXH) mm 820X355X580 878X360X630
Dimension of Package (LXWXH) mm 823X358X595 881X363X645
Net Weight kg 27 31 Gross Weight kg 29.5 34 Refrigerant R410A R410A Refrigerant Charge kg 0.7 0.85
Connection
Pipe
Length m 5 5 Gas Additional Charge g/m 20 20 Outer Diameter Liquid Pipe mm Φ6 Φ6 Outer Diameter Gas Pipe mm Φ9.52 Φ12 Max Distance Height m 10 10 Max Distance Length m 15 20 Note: The connection pipe applies metric diameter.
The above data is subject to change without notice; please refer to the nameplate of the unit.
9
Page 8
Service Manual
2.2 Operation Characteristic Curve
2.3 Capacity Variation Ratio According to Temperature
Cooling Heating
0 10 20 30 40 50 60 70 90 0 10 20 30 40 50 60 70 80 90 100 120110
80
11
10
9 8 7 6 5 4 3 2 1 0
11
10
9 8 7 6 5 4 3 2 1 0
220V
230V
240V
220V
230V
240V
Current (A)
Current (A)
Conditions Indoor:DB27°C/WB19°C Outdoor:DB35°C/WB24°C Indoor air flow:Super High Pipe length:5m
Conditions Indoor:DB20°C/WB15°C Outdoor:DB7°C/WB6°C Indoor air flow:Super High Pipe length:5m
Compressor speed (rps) Compressor speed (rps)
Cooling Heating
32 33 34 35 36 37 38 39 43
40 41 42
100
105
95 90 85 80 75 70 65 60 55 50
Conditions Indoor:DB27°C/WB19°C Indoor air flow:Super High Pipe length:5m
Outdoor temp.(°C)
Capacity ratio (%)
–15 –10 –5
110
100
90 80 70 60 50 40
0 5 7 10
Conditions Indoor:DB20°C/WB15°C Indoor air flow:Super High Pipe length:5m
Outdoor temp.(°C)
Capacity ratio (%)
10
Page 9
Service Manual
2.4 Cooling and Heating Data Sheet in Rated Frequency
Instruction:
T1: Inlet and outlet pipe temperature of evaporator T2: Inlet and outlet pipe temperature of condenser P: Pressure at the side of big valve Connection pipe length: 5 m.
Cooling:
Heating:
Rated cooling
condition(oC) (DB/WB)
Model
Pressure of gas pipe
connecting indoor
and outdoor unit
Inlet and outlet pipe temperature of heat
exchanger
Fan speed
of indoor
unit
Fan speed
of outdoor
unit
Compressor
revolution (rps)
Indoor Outdoor P (MPa) T1 (oC) T2 (oC)
27/19 35/24 09/12K 0.8 ~ 1.1 11 to 14 38 to 41 Super High High 60
Rated heating
condition(oC) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe temperature of heat
exchanger
Fan speed
of indoor
unit
Fan speed of outdoor
unit
Compressor
revolution (rps)
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/15 7/6 09/12K 2.8 ~ 3.2 38 to 41 2 to 5 Super High High 66
2.5 Noise Curve
Indoor side noise
Outdoor side noise
Indoor fan motor rotating speed
Compressor frequency/Hz
Low Middle High Supper High
Noise/dB(A)
Noise/dB(A)
70
60
40
30
35
25
50
40
30
0 20 40 60 80 100
20
09K 12K
11
Page 10
Service Manual
3. Outline Dimension Diagram
3.1 Indoor Unit
Unit:mm
174
790
71
40
76
40
605
37
148
Φ55
Φ55
265
265
12
Page 11
Service Manual
714 257
776
510
540
286
540
297
842
320
596
257
763
3.2 Outdoor Unit
(2) ASH-12AIR
(1) ASH-09AIR
Unit:mm
Unit:mm
13
Page 12
Service Manual
4. Refrigerant System Diagram
Indoor unit
Outdoor unit
COOLING
HEATING
4-Way valve
Discharge
Suction
Heat exchanger (evaporator)
Heat exchanger (condenser)
Valve
Valve
Liquid pipe side
Gas pipe side
Strainer Capillary Strainer
Accumlator
Compressor
Connection pipe specication: Liquid pipe:1/4" (6mm) Gas pipe:3/8" (9.52mm)09K Gas pipe:1/2" (12mm)12K
Cooling and heating model
14
Page 13
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Indoor Unit
●Instruction
Symbol Symbol Color Symbol Symbol Color Symbol Name
WH White GN Green CAP Jumper cap
YE Yellow BN Brown COMP Compressor
RD Red BU Blue Grounding wire
YEGN Yellow/Green BK Black / /
VT Violet OG Orange / /
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
SWING-UD
M2
AC-L
BN
BK
BU
EVAPORATOR
CAP
PE
YEGN
JUMP
DISP2
SWING
N
COM-OUT
BK BN
3
XT
2
N(1)
BU
YEGN
DISP1
DISPLAY BOARD
TERMINAL
RECEIVER AND
MOTOR
BLOCK
M1
PGPGF
FAN
MOTOR
OUTDOOR UNIT
θ
RT1
RT2
TUBE TEMP.
SENSOR
T-SENSOR
θ
SENSOR
ROOM TEMP.
AP2
PRINTED CIRCUIT BOARD
AP1
CONNECTING
CABLE
15
Page 14
Service Manual
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
● Outdoor Unit
BN
BK
BU
L4
L1
L4
L3
L3
RING
MAGNETIC
PE
L3
BU
V
RD
YE
LX1-1
LX1-2
TERMINAL
N
L
N(1)
2 3
L
N
CN2
OFAN
W
V
U
AP:Main Board
N
AC-L
COMU
PE
L2
L2
REACTOR
L
BU
BN
TEMP.
SENSOR
TEMP.
SENSOR
TEMP.
RT3
RT2
RT1
SENSOR
θ
4YV
4-WAY
4WAY
MAGNETIC
RING
(20k)
(15k)
(50k)
MAGNETIC
RING
X1
MID.ISOLATION SHEET
YEGN
PE
PE
YEGN
YEGN
YEGN
YEGN(GN)
VALVE
OUTTUBE
OUTROOM
EXHAUST
BLOCK
BU BK
BN
BU(WH) BN(BK)
VT
VT
the risk of electric shock!
Please don't touch any terminal when the machine
is running ,stopping or has
been powered off for less than 30 minutes to prevent
WARNING
BU
YE
RD
θ
θ
YEGN
RD
W
U
COMP.
COMP
WIRE
XT
POWER
FAN
M
PE
PE
OVC-COMP
NOTE:
Motor
only applies to the
iron shell motor.
ground
ELECTRICAL BOX
YEGN
MOTOR
INDOOR UNIT
16
Page 15
Service Manual
5.2 PCB Printed Diagram
No. Name
1 Live wire interface 2 Fuse 3 Fan capacitor 4 Neutral wire interface 5 Fan motor interface of PG 6 Communication interface 7 Auto button 8 up&down swing interface
9
Interface of PG feedback
interface
10 Jumper cap
11
Interface of temperature
sensor 12 display interface 13 High Frequency Transformer
● Top view
● Bottom view
Indoor Unit
1
2
3
4 5 6 7 8
9
10
11
12
13
17
Page 16
Service Manual
Outdoor Unit
● Top view
● Bottom view
1
2
3 4 11
5
6
7
8
9
10
No. Name
1 Reactor wiring terminal 2 Compressor wiring terminal
3
Terminal of outdoor unit temperature sensor
4
Compressor overload protection terminal
5
Terminal with indoor unit communication wire
6
Terminal of power supply live wire
terminal 7 Terminal of power supply neutral wire 8 Interface of earthing wire 9 Terminal of outdoor fan
10 Interface of 4-way valve 11 Terminal of electronic expansion valve
18
Page 17
Service Manual
6. Function and Control
6.1 Remote Controller Introduction
AUTO COOL DRY FAN HEAT
T-ON T-OFF
SWING SLEEP LOCK
SPEED
+
_
ON/OFF
FAN SWING
SLEEP
TIMER
MODE
ON/OFF button
MODE button
+/- botton
FAN button
SWING button
SLEEP button
TIMER button
Icon Display on Remote Controller
Operation introduction of remote controller
For auto operation
Timer on Timer off
Sending signal
For air swing For sleeping For locking For setting fan speed
Set temperature
Set time
For cooling
For drying
For fan only
For heating
AUTO COOL DRY FAN HEAT
T-ON T-OFF
SWING SLEEP
LOCK SPEED
Buttons on Remote Controller
Note:
When power is connected(stand by condition), you can operate the air conditioner through the remote controller. When unit is on, each time you press the button on remote controller, the sending signal icon on the display of remote controller
will blink once. If the air conditioner gives out a beep sound, it means the signal has been sent.
When unit is off, set temperature will be displayed on the remote controller(If the light of indoor unit display is turned on, the
corresponding icon will be displayed); When unit is on, it will display the icon of the on-going function.
1. ON/OFF Button
Press this button to turn unit on/off.
2. MODE Button
Pressing this button once can select your required mode circularly as below(the corresponding icon
will be lit up after the mode is
selected):
AUTO COOL DRY FAN HEAT
19
Page 18
Service Manual
When selecting auto mode, air conditioner will operate automatically according to ex-factory setting. Set temperature can't be
adjusted and won't be displayed either. Press FAN button to adjust fan speed. (This function is not available in this air conditioner.)
When selecting cool mode, air conditioner will operate under cool mode. Then press + or -- button to adjust set temperature. Press
FAN button to adjust fan speed.
When selecting dry mode, air conditioner will operate at low fan speed under dry mode. In dry mode, fan speed can't be adjusted. When selecting fan mode, air conditioner will operate in fan mode only. Then press FAN button to adjust fan speed. When selecting heat mode, air conditioner will operate under heat mode. Then press + or -- button to adjust set temperature. Press
FAN button to adjust fan speed.
3. +/- button
Pressing + or - button once will increase or decrease set temperature by 1 °F(°C). Hold + or -- button for 2s, set temperature on
remote controller will change quickly. Release the button after your required set temperature is reached.
When setting Timer On, Timer Off or Clock, press + or -- button to adjust the time (See TIMER Button for setting details).
4. FAN Button
Pressing this button can select fan speed circularly as: AUTO, SPEED 1(
), SPEED 2( ), SPEED 3( ), SPEED 4( ) (unavailable
in this air conditioner. Speed 4 is the same with speed 3).
Note:
Under Auto mode, air conditioner will select proper fan speed automatically according to ex-factory setting. Fan speed can't be adjusted under Dry mode.
5. SWING Button
Press this button to turn on up&down air swing.
6. SLEEP Button
Under Cool, Heat, Dry mode, press this button to turn on Sleep function. Press this button to cancel Sleep function. Under Fan and Auto mode, this function is unavailable.
Simple operationfi rst
1.After putting through power “
” button on remote controller to turn on the air conditioner.
2.Press “
” button to select your required operation mode: AUTO, COOL, DRY, FAN.
3.Press “+” or “-” button to set your required temperature.(temperature can’t adjusted under AUTO mode)
4.Press “
” button to select your required fan speed: auto, fi rst notch, second notch, third notch, fourth notch (fourthnotch is same
as third notch for this air conditioner.)
SPEED 2 (equals to medium fan speed)SPEED 1 (equals to low fan speed)
SPEED 3 (equals to high fan speed) SPEED 4
AUTO
7. TIMER Button
When unit is on, press this button to set Timer Off. T-OFF and H icon will be blinking. Within 5s, press + or - button to adjust the
When unit is off, press this button to set Timer On. T-ON and H icon will be blinking. Within 5s, press + or - button to adjust the
time for Timer On. Pressing + or - button once will increase or decrease the time by 0.5h. Hold + or - button for 2s, time will change quickly. Release the button after your required set time is reached. Then press TIMER button to confirm it. T-ON and H icon will stop blinking.
Cancel Timer On/Off: If Timer function is set up, press TIMER button once to review the remaining time. Within 5s, press TIMER
Note:
Range of time setting is: 0.5~24h
button again to cancel this function.
The interval between two motions can't exceed 5s, otherwise the remote controller will exit setting status.
time for Timer Off. Pressing + or - button once will increase or decrease the time by 0.5h. Hold + or - button for 2s, time will change quickly. Release the button after your required set time is reached. Then press TIMER button to confirm it. T-OFF and H icon will stop blinking.
20
Page 19
Service Manual
1. Press the back side of remote controller on the spot marked with , and then push out the cover of battery box along the arrow direction.
2. Replace two No.7 (AAA 1.5V) dry batteries and make sure the positions of + and -­polar are correct.
3. Reinstall the cover of battery box.
Note:
During operation, point the signal sender of the remote controller at the receiving
window of the indoor unit;
The distance between signal sender and receiving window should be within 8m.
There should be no obstacle between them.
Signal may be interfered easily in the room where there is fl uorescent lamp or wireless telephone; Remote controller should be close to indoor unit during operation.
Replace new batteries of the same model when replacement is required.
If you don't use remote controller for a long time, please take out the batteries.
If the display on remote controller is fuzzy or if there's no display, please replace batteries.
battery
cover of battery box
remove
reinstall
Replacement of Batteries in Remote Controller
21
Page 20
Service Manual
6.2 Brief Description of Modes and Functions
1. Temperature Parameters
Indoor preset temperature (Tpreset)
Indoor ambient temperature (Tamb.)
2. Basic Functions
Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory function
is available, for the rst energization, if the compressor is at stop before de-energization, the compressor will be started without a
3-minute lag; if the compressor is in operation before de-energization, the compressor will be started with a 3-minute lag; and once
started, the compressor will not be stopped within 6 minutes regardless of changes in room temperature;
(1) Cooling Mode
Working conditions and process of cooling
Cooling conditions and process(09k)
a. When Tamb.≥Tpreset the unit starts cooling. In this case, the IDU fan motor, ODU fan motor and compressor run, and the IDU fan
motor runs at set speed;
b. When Tamb.=Tpreset-3℃, the compressor continuously operates below the frequency of 15Hz (not including 15Hz) for 15mins. If
Tamb.=Tset-3℃ still keeps the same, the compressor stops operation;
c. When Tamb.≤Tpreset-4℃, the compressor stops operation; ODU fan motor stops operation with a delay of 30s and IDU fan motor
operates at set speed;
d. When Tpreset-2℃<Tamb.<Tset, the unit will maintain its previous running status.
Cooling conditions and process(12k)
a.When Tamb.+Tindoor supplementary≥Tpreset, the unit starts cooling. In this case, the IDU fan motor, ODU fan motor and
compressor run, and the IDU fan motor runs at set speed;
b. When Tamb.+Tindoor supplementary≤Tpreset-2℃, the compressor stops operation; ODU fan motor stops operation with a delay
of 30s and IDU fan motor operates at set speed;
c.When Tpreset-2
℃<
Tindoor amb.+Tindoor supplementary<Tpreset, the unit will maintain its previous running status.
Under this mode, the four-way valve will be de-energized and temperature can be set within a range from 16 to 30oC.
If the compressor is shut down for some reason, the indoor fan and the swing device will operate at original state.
Protection
Antifreeze protection
Under cooling and dehumidifying mode, 6 minutes after the compressor is started:
If T evap≤2oC, the compressor will operate at reduced frequency.
If T evap≤-1oCis detected for durative 3 minutes, the compressor will stop, and after 30 seconds, the outdoor fan will stop; and under
cooling mode, the indoor fan and the swing motor will remain at the original state.
If T evap. ≥10oCand the compressor has remained at OFF for at least 3 minutes, the compressor will resume its original operation
state.
Total current up and frequency down protection
If I
total
≤6, frequency rise will be allowed; if I
total
≥7, frequency rise will not be allowed; if I
total
≥8, the compressor will run at reduced
frequency; and if I
total
≥9, the compressor will stop and the outdoor fan will stop with a time lag of 30s.
(2) Dehumidifying Mode
Working conditions and process of dehumidifying
If Tamb>Tpreset, the unit will enter cooling and dehumidifying mode, in which case the compressor and the outdoor fan will operate
and the indoor fan will run at low speed.
If Tpreset -2oC≤Tamb≤Tpreset, the compressor remains at its original operation state.
If Tamb.< Tpreset -2oC, the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will operate at
low speed.
Protection
Protection is the same as that under the cooling mode.
(3) Heating Mode
22
Page 21
Service Manual
Working conditions and process of heating
If Tamb.≤Tpreset +2oC, the unit enters heating mode, in which case the four-way valve, the compressor and the outdoor fan will
operate simultaneously, and the indoor fan will run at preset speed in the condition of preset cold air prevention.
If T amb.≥Tpreset +5oC, the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will stop after
60-second blow at low speed
If Tpreset +2oC<T amb.< Tpreset +5oC, the unit will maintain its original operating status.
Under this mode, the four-way valve is energized and temperature can be set within a range of 16 - 30oC. The operating symbol, the
heating symbol and preset temperature are revealed on the display.
Condition and process of defrost
When duration of successive heating operation is more than 45 minutes, or accumulated heating time more than 90 minutes, and
one of the following conditions is reached, the unit will enter the defrost mode after 3 minutes.
(1)T outdoor ambient>5oC, T outdoor tube≤-2oC;
(2) -2oC≤T outdoor ambient<5oC, T outdoor tube≤-6oC;
(3) -5oC≤T outdoor ambient<-2oC, T outdoor tube≤-8oC;
(4)-10oC≤Toutdoor ambient<-5oC, Toutdoortube-T compensatory≤(T outdoor ambient-3oC)
(5)T outdoor ambient<-10oC, T outdoortube-T compensatory≤(T outdoor ambient-3oC)
(after energizing, T compensatory=0oC during the rst defrosting; if it is not the rst defrosting, T compensatory is conrmed by T
outdoortube of quitting last defrosting: a. whenT outdoor tube>2oC, T compensatory=0oC; b. whenT outdoor tube≤2oC, T compensatory=3oC)
At that time, the indoor fan stops and the compressor stops, and after 30 seconds the outer fan will stop, and then after 30 seconds,
the four-way valve will stop. After 30 seconds, the compressor is initiated for raising the frequency to defrost frequency.
When the compressor has operated under defrost mode for 7.5 minutes, or T outdoor ambient≥10oC, the compressor will be
converted to 46Hz operation. After 30 seconds, the compressor will stop. And after another 30 seconds, the four-way valve will
be opened, and after 60 seconds, the compressor and the outer fan will be started, the indoor fan will run under preset cold air
prevention conditions, and H1 will be displayed at temperature display area on the display panel. Defrost frequency is 85Hz.
Protection
Cold air prevention
The unit is started under heating mode (the compressor is ON):
In the case of T indoor amb. <24oC: if T tube≤40oC and the indoor fan is at stop state, the indoor fan will begin to run at low speed
with a time lag of 2 minutes. Within 2 minutes, if T tube>40oC, the indoor fan also will run at low speed; and after 1-minute operation
at low speed, the indoor fan will be converted to operation at preset speed. Within 1-minute low speed operation or 2-minute non-
operation, if T tube>42oC, the fan will run at present speed.
In the case of T indoor amb. ≥24oC: if T tube≤42oC, the indoor fan will run at low speed, and after one minute, the indoor fan will be
converted to preset speed. Within one-minute low speed operation, if T tube>42oC, the indoor fan will be converted to preset speed.
Note: T indoor amb. indicated in
and
refers to, under initially heating mode, the indoor ambient temperature before the
command to start the compressor is performed according to the program, or after the unit is withdrawn from defrost, the indoor
ambient temperature before the defrost symbol is cleared.
Total current up and frequency down protection
If the total current I
total
≤6, frequency rise will be allowed; if I
total
≥7, frequency rise will not be allowed; if I
total
≥8, the compressor will run
at reduced frequency; and if I
total
≥9, the compressor will stop and the outdoor fan will stop with a time lag of 30s.
(4) Fan Mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the four-way valve and the electric
heater will stop.
Under the mode, temperature can be set within a range of 16 - 30oC .
(5) AUTO Mode
Working conditions and process of AUTO mode
a. When T ambient ≥26oC, the unit will operate in Cool mode. The set temperature is 25oC.
b. When T ambient ≤22oC, the heat pump unit will operate in Heat mode., set temperature be 20oC; the cooling only unit will operate
in Fan mode, set temperature be 25oC.
c. When 23oC≤T ambient ≤25oC, the unit will operate in the previous state. If it is energized for the rst time, it will operate in Fan
mode.
d. Under auto mode, if its cooling mode, operation frequency is same as that under cooling mode; if its heating mode, operation
frequency is same as that under heating mode.
23
Page 22
Service Manual
Protection
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor will
remain unchanged for at least 6 minutes.
(6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
Overload protection
T tube: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat exchanger
under heating mode.
1) Cooling overload
a.If T tube≤52oC, the unit will return to its original operation state.
b.If T tube≥55oC, frequency rise is not allowed.
c.If T tube≥58oC, the compressor will run at reduced frequency.
d.If T tube≥62oC, the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a.If T tube≤50oC, the unit will return to its original operation state.
b.If T tube≥53oC, frequency rise is not allowed.
c.If T tube≥56oC, the compressor will run at reduced frequency.
d.If T tube≥60oC, the compressor will stop and the indoor fan will blow residue heat and then stop.
Exhaust temperature protection of compressor
a.If exhaust temperature ≥98oC, frequency is not allowed to rise.
b.If exhaust temperature ≥103oC, the compressor will run at reduced frequency.
c.If exhaust temperature ≥110oC, the compressor will stop.
d.If exhaust temperature ≤90oCand the compressor has stayed at stop for at least 3 minutes, the compressor will resume its operation.
Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justied and the whole system will stop.
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the compressor will
resume its operation. If module protection occurs six times in succession, the compressor will not be started again.
Overload protection
If temperature sensed by the overload sensor is over 115oC, the compressor will stop and the outdoor fan will stop with a time lag of 30
seconds. If temperature is below 95oC, the overload protection will be relievedoC.
DC bus voltage protection
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds.
When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least 3 minutes, the compressor will
resume its operation.
Faults of temperature sensors
Designation of sensors Faults
Indoor ambient temperature
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds
Indoor tube temperature
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds
Outdoor ambient temperature
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds
Outdoor tube temperature
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds, and no detection is performed within 10 minutes after defrost begins.
Exhaust
After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or short-circuited for successive 30 seconds.
Overload
After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or short-circuited for successive 30 seconds.
Zero-crossing inspection circuit malfunction of the IDU fan motor
Zero-crossing signal is not detected for continuously 3s; Or the interval between the zero-crossing signals in 3s>25ms (power frequency: 50Hz)
24
Page 23
Service Manual
Indoor Units
(1) ON/OFF
Press the remote button ON/OFF: the on-off state will be changed once each time you press the button.
(2) Mode Selection
Press the remote button MODE, then select and show in the following ways: AUTO, COOL, DRY, FAN, HEAT, AUTO.
(3) Temperature Setting Option Button
Each time you press the remote button TEMP+ or TEMP-, the setting temperature will be up or down by 1oC. Regulating
Range: 16~30oC, the button is useless under the AUTO mode.
(4) Time Switch
You should start and stop the machine according to the setting time by remote control.
(5) SLEEP State Control
a. When the air conditioner is under the mode of COOL, DRY, and the SLEEP mode has been set well, after the SLEEP state keeps about
1 hour, the pre-setting T will raise 1oC, and it will raise 1oC again after 2 hours, so it raise 2oC in 2 hours, then it will run on at the setting
temperature and wind speed.
b. When the air conditioner is under the mode of HEAT, and the Timer has been set well, after the SLEEP state keeps about 1 hour, the pre-
setting T will reduce 1oC, and it will reduce 1oC again after 2 hours, so it reduce 2oC in 2 hours, then it will run on at the setting temperature
and wind speed.
c. The setting temperature keeps the same under the FAN mode and AUTO mode.
(6) Buzzer Control
a. Cooling only model:The buzzer will send a “Di Di” sound when the air conditioner is powered up or received the information sent by the
remote control or there is a button input, the single tube cooler doesnt receive the remote control ON signal under the mode of heating
mode.
b. Cooling and heating model:The buzzer will send a “Di” sound when the air conditioner is powered up or received the information sent by
the remote control or there is a button input, the single tube cooler doesnt receive the remote control ON signal under the mode of heating
mode.
(7) Auto button
If the controller is on, it will stop by pressing the button, and if the controller is off, it will be automatic running state by pressing the button,
swing on and light on, and the main unit will run based on the remote control if there is remote control order.
(8) Up-and-Down Swinging Control
When power on, the up-and-down motor will firstly move the air deflector to counter-clockwise, close the air outlet. After starting the
machine, if you dont set the swinging function, heating mode and auto-heating mode, the up-and-down air deflector will move to D
clockwise; under other modes, the up-and-down air deector will move to L1. If you set the swinging function when you start the
machine, then the wind blade will swing between L and D. The air deector has 7 swinging states: Location L, Location A, Location B,
Location C, Location D, Location L to Location D, stop at any location between L-D (the included angle between L~D is the same). The
air deector will be closed at 0 Location, and the swinging is effectual only on condition that setting the swinging order and the inner fan is
running. The indoor fan and compressor may get the power when air deector is on the default location.
(9) Display
Operation pattern and mode pattern display
All the display patterns will display for a time when the power on, the operation indication pattern will display in red under standby status.
When the machine is start by remote control, the indication pattern will light and display the current operation mode (the mode light includes:
L1 A1 B1 C1 D1
L A B C D
Heating angle
Cooling angle
O(0°)
O(0°)
25
Page 24
Service Manual
Cooling, heating and dehumidify). If you close the light key, all the display patterns will close.
Double-8 display
According to the different setting of remote control, the nixie light may display the current temperature (the temperature scope is
from 16oC to 30oC) and indoor ambient temperature. The set temperature displayed in auto cooling and fan mode is 25
℃ ,
The set
temperature displayed in auto heating mode is 20℃and the temperature will display H1 under the defrosting mode.(If you set the
fahrenheit temperature display, the nixie light will display according to fahrenheit temperature)
(10) Protection function and failure display
E2: Freeze-proong protection E4: Exhausting protection E5: Overcurrent protection
E6: Communication failure H4: Overload protection
F1: Indoor ambient sensor start and short circuit (continuously measured failure in 30S)
F2: Indoor evaporator sensor start and short circuit (continuously measured failure in 30S)
F3: Outdoor ambient sensor start and short circuit (continuously measured failure in 30S)
F4: Outdoor condenser sensor start and short circuit (continuously measured failure in 30S, and dont measure within 10 minutes
after defrosted)
F5: Outdoor exhausting sensor start and short circuit (continuously measured failure in 30S after the compressor operated 3 minutes)
H3: Overload protection of compressor H5: Module protection
PH: High-voltage protection PL: Low-voltage protection
P1: Nominal cooling and heating P2: Maximum cooling and heating
P3: Medium cooling and heating P0: Minimum cooling and heating
(11) Drying Function
You may start or stop the drying function under the modes of cooling and dehumidify at the starting status (The modes of automatism,
heating and air supply do not have drying function). When you start the drying function, after stop the machine by pressing the switch
button, you should keep running the inner fans for 10 minutes under low air damper (The swing will operate as the former status
within 10 minutes, and other load is stopped), then stop the entire machine; When you stop the drying function, press the switch
button will stop the machine directly. When you start the drying function, operating the drying button will stop the inner fans and close
the guide louver.
(12) Memory function when interrupting the power supply
Memory content: mode, swing function, light, set temperature and wind speed. After interrupted the power supply, the machine will
start when recovering the power according to the memory content automatically. If the last remote control command has not set
the timed function, the system will remember the last remote control command and operate according it. If the last remote control
command has set timed function and the power supply is interrupted before the timed time, the system will remember the timed
function of the last remote control command, the timed time will recounted form power on. If the last remote control command has
set timed function, the time is out and the system is start or stop according to the set time when the power supply is interrupted, the
system will remember the operation status before the power supply was interrupted, and do not carry out timed action; The timed
clock will not remembered.
(13) Sleep function
In this mode, the system will select proper sleep curve to operate according to different set temperature.
If start up sleep function under cooling or drying mode, the system will increase set temperature automatically within a certain
range to operate.
If start up sleep function under heating mode, the system will decrease set temperature automatically within a certain range to
operate.
26
Page 25
Service Manual
Part
: Installation and Maintenance
1. Select the installation location according to the require­ment of this manual.(See the requirements in installation part)
2. Handle unit transportation with care; the unit should not be carried by only one person if it is more than 20kg.
3. When installing the indoor unit and outdoor unit, a suf­cient xing bolt must be installed; make sure the installation support is rm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components dur­ing installation.
6. Make sure no foreign objects are left in the unit after n­ishing installation.
Electrical Safety Precautions:
7. Notes for Installation and Maintenance
Safety Precautions: Important!
Please read the safety precautions carefully before installation and maintenance. The following contents are very important for installation and maintenance.
Please follow the instructions below.
●The installation or maintenance must accord with the instructions.
●Comply with all national electrical codes and local electrical codes.
●Pay attention to the warnings and cautions in this manual.
●All installation and maintenance shall be performed by distributor or qualied person.
●All electric work must be performed by a licensed technician according to local regulations and the instructions given in this manual.
●Be caution during installation and maintenance. Prohibit incorrect operation to prevent electric shock, casualty and other accidents.
1. Cut off the power supply of air conditioner before checking and maintenance.
2. The air condition must apply specialized circuit and prohibit share the same circuit with other appliances.
3. The air conditioner should be installed in suitable location and ensure the power plug is touchable.
4. Make sure each wiring terminal is connected firmly during installation and maintenance.
5. Have the unit adequately grounded. The grounding wire can’t be used for other purposes.
6. Must apply protective accessories such as protective boards, cable-cross loop and wire clip.
7. The l ive wire , neutra l wire and ground ing wire of power supply must be corresponding to the live wire, neutral wire and grounding wire of the air conditioner.
8. The power cord and power connection wires can’t be pressed by hard objects.
9. If power cord or connection wire is broken, it must be replaced by a qualied person.
1. Avoid contact between refrigerant and re as it generates poisonous gas; Prohibit prolong the connection pipe by welding.
2. Apply specied refrigerant only. Never have it mixed with any other refrigerant. Never have air remain in the refrigerant line as it may lead to rupture or other hazards.
3. Ma k e su r e n o r ef r ig er a nt ga s is leaki n g ou t wh en installation is completed.
4. If th ere is refr iger ant lea kage, plea se t ake s uff icie nt measure to minimize the density of refrigerant.
5. Never touch the refrigerant piping or compressor without wearing glove to avoid scald or frostbite.
Warnings
Refrigerant Safety Precautions:
Improper installation may lead to re hazard, explosion, electric shock or injury.
Installation Safety Precautions:
10. If the power cord or connection wire is not long enough, please get the specialized power cord or connection wire from the manufacture or distributor. Prohibit prolong the wire by yourself.
11. For the air conditioner without plug, an air switch must be installed in the circuit. The air switch should be all-pole parting and the contact parting distance should be more than 3mm.
12. Make sure all wires and pipes are connected properly and the valves are opened before energizing.
13. Check if there is electric leakage on the unit body. If yes, please eliminate the electric leakage.
14. Replace the fuse with a new one of the same specication if it is burnt down; don’t replace it with a cooper wire or conducting wire.
15. If the unit is to be installed in a humid place, the circuit breaker must be installed.
27
Page 26
Service Manual
Main Tools for Installation and Maintenance
1. Level meter, measuring tape
4. Electroprobe
7. Electronic leakage detector
10. Pipe pliers, pipe cutter
2. Screw driver
5. Universal meter
8. Vacuum pump
11. Pipe expander, pipe bender
3. Impact drill, drill head, electric drill
6. To r q u e wrench , open-end w r e n ch, in n e r hexagon spanner
9. Pressure meter
12. Soldering appliance, refrigerant container
28
Page 27
Service Manual
8. Installation
8.1 Installation Dimension Diagram
Drainage pipe
At least 250cm
At least 15cm
At least 50cm
At least 50cm
At least
30cm
At least 300cm
At least 200cm
Space to the oor
Space to the obstruction
Space to the
obstruction
Space to the
obstruction
Space to the ceiling
Space to the obstruction
Space to the obstruction
At least 30cm
At least 15cm
At least 15cm
Space to the wall
Space to the wall
Space to the wall
29
Page 28
Service Manual
Installation procedures
Preparation before installation
Prepare tools
Read the requirements for electric connection
select installation location
Select indoor unit installation location
Install wall-mounting frame, drill wall holes
Connect pipes of indoor unit and drainage pipe
Connect wires of indoor unit
Connect wires of outdoor unit
Bind up pipes and hang the indoor unit
Make the bound pipes pass through the wall hole and then connect outdoor unit
Neaten the pipes
Vacuum pumping and leakage detection
Check after installation and test operation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
Select outdoor unit installation location
Install the support of outdoor unit (select it according to the actual situation)
Install drainage joint of outdoor unit (only for cooling and heating unit)
Connect pipes of outdoor unit
Start installation
Fix outdoor unit
30
Page 29
Service Manual
No. Name No. Name
1 Indoor unit 8 Sealing gum 2 Outdoor unit 9 Wrapping tape
3 Connection pipe 10
Support of outdoor unit
4 Drainage pipe 11 Fixing screw
5
Wall-mounting frame
12
Drainage plug(cooling and heating unit)
6
Connecting cable(power cord)
13
Owner’s manual, remote controller
7 Wall pipe
1. Safety Precaution
(1) Must follow the electric safety regulations when installing the unit. (2) According to the local safety regulations, use qualified power supply circuit and air switch. (3) Make sure the power supply matches with the requirement of air conditioner. Unstable power supply or incorrect wiring may result in electric shock,re hazard or malfunction. Please insta ll proper powe r supply cables befo re usi ng the air conditioner.
(4) Properly connect the live wire, neutral wire and grounding wire of power socket. (5) Be sure to cut off the power supply before proceeding any work related to electricity and safety. (6) Do not put through the power before nishing installation. (7) For appliances with type Y attachment,the instructions shall contain the substance of thefollowing.If the supply cord is damaged,it must be replaced by the manufacturer,its service agent or similarly qualied persons in order to avoid a hazard. (8) The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
8.2 Installation Parts-checking
8.3 Selection of Installation Location
8.4 Electric Connection Requirement
8.5 Installation of Indoor Unit
Air-conditioner Air switch capacity
09/12K 10A
1.Please contact the local agent for installation.
2.Don't use unqualied power cord.
1. Basic Requirement:
Installing the unit in the following places may cause malfunction. If it is unavoidable, please consult the local dealer: (1) The place with strong heat sources, vapors, ammable or explosive gas, or volatile objects spread in the air. (2) The place with high-frequency devices (such as welding machine, medical equipment). (3) The place near coast area. (4) The place with oil or fumes in the air. (5) The place with sulfureted gas. (6) Other places with special circumstances.
2. Grounding Requirement:
(1) The air conditioner is rst class electric appliance. It must be prope rly grounding with special ized grounding device by a professional. Please make sure it is always grounded effectively, otherwise it may cause electric shock. (2) The yellow-green wire in air conditioner is grounding wire, which can't be used for other purposes. (3) The grounding resistance should comply with national electric safety regulations. (4) The app liance must be positioned so that the plug is accessible. (5) An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in xed wiring. (6) Including an air switch with suitable capacity, please note the following table. Air switch should be included magnet buckle and heating buckle function, it can protect the circuit­short and overload. (Caution: please do not use the fuse only for protect the circuit)
1. Choosing Installation Iocation
Recommend the installation location to the client and then conrm it with the client.
2. Install Wall-mounting Frame
(1) Hang the wall-mounting frame on the wall; adjust it in horizontal position with the level meter and then point out the screw xing holes on the wall. (2) Drill the screw xing holes on the wall with impact drill (the specification of drill head should be the same as the plastic
2. Indoor Unit:
(1) There should be no obstruction near air inlet and air outlet. (2) Select a location where the condensation water can be dispersed easily and won't affect other people. (3) Select a loc ation w hich is conve nient to connect the outdoor unit and near the power socket. (4) Select a location which is out of reach for children. (5) The location should be able to withstand the weight of indoor unit and won't increase noise and vibration. (6) The appliance must be installed 2.5m above oor. (7 ) D on't inst all the indo or uni t r ight abov e the electr ic appliance. (8) The appliance shall not be installed in the laundry.
3. Outdoor Unit:
(1) Select a location where the noise and outow air emitted by the outdoor unit will not affect neighborhood. (2) The location should be well ventilated and dry, in which the outdoor unit won't be exposed directly to sunlight or strong wind. (3) The location should be able to withstand the weight of outdoor unit. (4) Make sure that the installation follows the requirement of installation dimension diagram. (5) Select a location which is out of reach for children and far away from animals or plants.If it is unavoidable, please add fence for safety purpose.
Note:
31
Page 30
Service Manual
Outlet
pipe
Drain hose
Drain hose
Tape
Outlet pipe
Insulating pipe
Torque wrench
Open-end wrench
Indoor pipe
Pipe
Union nut
Union nutPipe joint
Pipe
Refer to the following table for wrench moment of force
:
Left
Rear left
Right
Rear right
Cut off the hole
Left Right
Drain hose
Insulating pipe
5-10
°
Φ55mm
Indoor
Outdoor
(1) Pay attention to dust prevention and take relevant safety measures when opening the hole. (2) The plastic expansion particles are not provided and should be bought locally.
(1) Add insulating pipe in the indoor drain hose in order to prevent condensation. (2) The plastic expansion particles are not provided. (As show in Fig.10)
Fig.1
Fig.2
Fig.5 Fig.6
Fig.7
Fig.8
Fig.9
Fig.10
Fig.3
Fig.4
in the holes. (3) Fix the wall-mounting frame on the wall with tapping screws (ST4.2X25TA) and then check if the frame is rmly installed by pulling the frame. If the plastic expansion particle is loose, please drill another xing hole nearby.
3. Install Wall-mounting Frame
(1) Choose the position of piping hole according to the direction of outlet pipe. The position of piping hole should be a little lower than the wall-mounted frame.(As show in Fig.1)
5. Connect the Pipe of Indoor Unit
(1) Aim the pipe joint at the corresponding bellmouth.(As show in Fig.5) (2) Pretightening the union nut with hand. (3) Adjust the torque force by referring to the following sheet. Place the open-end wrench on the pipe joint and place the torque wrench on the union nut. Tighten the union nut with torque wrench.(As show in Fig.6) (4) Wrap the indoor pipe and joint of connection pipe with insulating pipe, and then wrap it with tape.(As show in Fig.7)
6. Install Drain Hose
(1) Connect the drain hose to the outlet pipe of indoor unit.(As show in Fig.8) (2) Bind the joint with tape.(As show in Fig.9)
4. Outlet Pipe
(1) The pipe can be led out in the direction of right, rear right, left or rear left.(As show in Fig.3) (2) When selecting leading out the pipe from left or right, please cut off the corresponding hole on the bottom case.(As show in Fig.4)
(2) Open a piping hole with the diameter of Φ55mm on the selected outlet pipe position.In order to drain smoothly, slant the piping hole on the wall slightly downward to the outdoor side with the gradient of 5-10°.(As show in Fig.2)
Note:
Note:
Left
Wall
Φ55mm
Right
Mark in the middle of it
Level meter
Rear piping hole
Wall
Space
to the
wall
above
150mm
Space
to the
wall
above
150mm
Φ55mm
Rear piping hole
Hex nut diameter(mm) Tightening torque(N.m)
Φ6 15~20
Φ9.52 30~40
Φ12 45~55 Φ16 60~65 Φ19 70~75
32
Page 31
Service Manual
(4) Put wiring cover back and then tighten the screw. (5) Close the panel.
Indoor unit
Gas pipe
Indoor and
outdoor power cord
Liquid pipe
Drain hose
Band
Drain hose
Band
Connection pipe
Indoor power cord
Wiring cover
Screw
Panel
(1 ) A ll w i res of indoo r un it and outdo or unit shoul d be connected by a professional. (2) If the length of power connection wire is insufcient, please contact the supplier for a new one. Avoid extending the wire by yourself. (3) For the air conditioner with p lug, the plug s hould be reachable after nishing installation. (4) For the air conditioner without plug, an air switch must be installed in the line. The air switch should be all-pole parting and the contact parting distance should be more than 3mm.
(1) The power cor d and control wir e can't be cros sed or winding. (2) The drain hose should be bound at the bottom.
Do not bend the drain hose too excessively in order to prevent blocking.
7. Connect Wire of Indoor Unit
(1) Open the panel, remove the screw on the wiring cover and then take down the cover.(As show in Fig.11)
8. Bind up Pipe
(1) Bind up the connection pipe, power cord and drain hose with the band.(As show in Fig.14) (2) Reserve a certain length of drain hose and power cord for installation when binding them. When binding to a certain degree, separate the indoor power and then separate the drain hose.(As show in Fig.15) (3) Bind them evenly. (4) The liquid pipe and gas pipe should be bound separately at the end.
9. Hang the Indoor Unit
(1) Put the bound pipes in the wall pipe and then make them pass through the wall hole. (2) Hang the indoor unit on the wall-mounting frame. (3) Stuff the gap between pipes and wall hole with sealing gum. (4) Fix the wall pipe.(As show in Fig.16) (5) Check if the indoor unit is installed rmly and closed to the wall.(As show in Fig.17)
(2) Make the power connection wire go through the cable-cross hole at the back of indoor unit and then pull it out from the front side.(As show in Fig.12)
(3) Remove the wire clip; connect the power connection wire to the wiring terminal according to the color; tighten the screw and then x the power connection wire with wire clip.(As show in Fig.13)
Note:
Note:
Note:
Indoor
Outdoor
Wall pipe
Sealing gum
Upper hook
Lower hook of wall-mounting frame
Fig.11
Fig.12
Fig.13
Fig.14
Fig.15
Fig.16
Fig.17
Note:This step only applicable for N.American models.
Power connection
wire
Cable-cross
hole
N(1) 2 3
blue brownblack
yellow­green
Outdoor unit connection
33
Page 32
Service Manual
(1) Take sufficient protective measures when installing the outdoor unit. (2) Make sure the support can withstand at least four times the unit weight. (3) The outdoor unit should be installed at least 3cm above the oor in order to install drain joint.(As show in Fig.18) (4) For the unit with cooling capacity of 2300W~5000W, 6 expansion screws are needed; for the unit with cooling capacity of 6000W~8000W, 8 expansion screws are needed; for the unit with cooling capacity of 10000W~16000W, 10 expansion screws are needed.
(1) After tightening the screw, pull the power cord slightly to check if it is rm. (2) Never cut the power connection wire to prolong or shorten the distance.
(1) The through-wall height of drain hose shouldn't be higher than the outlet pipe hole of indoor unit.(As show in Fig.25) (2) Slant the drain hose slightly downwards. The drain hose can't be curved, raised and uctuant, etc.(As show in Fig.26)
Note:
Note:
Note:
The drain hos can't raise upwards
gas pipe
Liquid pipe
Liquid valve
gas valve
Union nut
Pipe joint
Foot holes
Foot holes
Chassis
Outdoor drain joint
Drain hose
Drain vent
8.6 Installation of Outdoor Unit
1. Fix the Support of Outdoor Unit(Select it According to the Actual Installation Situation)
(1) Select installation location according to the house structure. (2) Fix the support of outdoor unit on the selected location with expansion screws.
5. Connect Outdoor Electric Wire
(1) Remove the wire clip; connect the power connection wire to the wiring terminal according to the color; x them with screws. (As show in Fig.23)
6. Neaten the Pipes
(1) The pipes should be placed along the wall, bent reasonably and hidden possibly. Min. semidiameter of bending the pipe is 10cm. (2) If the outdoor unit is higher than the wall hole, you must set a U-shaped curve in the pipe before pipe goes into the room, in order to prevent rain from getting into the room.(As show in Fig.24)
(2) Fix the power connection wire with wire clip.
2. Install Drain Joint(Only for cooling and heating unit)
(1) Connect the outdoor drain joint into the hole on the chassis. (2) Connect the drain hose into the drain vent. (As show in Fig.19)
3. Fix Outdoor Unit
(1) Place the outdoor unit on the support. (2) Fix the foot holes of outdoor unit with bolts. (As show in Fig.20)
4. Connect Indoor and Outdoor Pipes
(1) Remove the screw on the right handle of outdoor unit and then remove the handle.(As show in Fig.21) (2) Remove the screw cap of valve and aim the pipe joint at the bellmouth of pipe.(As show in Fig.22)
(3) Pretightening the union nut with hand. (4) Tighten the union nut with torque wrench.
Refer to the following table for wrench moment of force
:
Fig.18 Fig.19
Fig.20
Fig.22
Fig.23
Fig.24
Fig.25
At least 3cm above the floor
Handle
Screw
Fig.21
U-shaped curve
Wall
Hex nut diameter(mm) Tightening torque(N.m)
Φ6 15~20
Φ9.52 30~40
Φ12 45~55 Φ16 60~65 Φ19 70~75
Handle
Indoor unit connection
yellow green
N(1)
N
N
L
L
32
blue black brown
34
Page 33
Service Manual
(3) The water outlet can't be placed in water in order to drain smoothly.(As show in Fig.27)
Liquid valve
Gas valve
Refrigerant charging vent
Nut of refrigerant
Charging vent
Vacuum pump
Piezometer
Valve cap
Lo Hi
Inner hexagon spanner
Open
Close
The drain hose can't be fluctuant
The drain hose can't be fluctuant
The water outlet can't be fluctuant
No. Items to be checked Possible malfunction
1
Has the unit been installed rmly?
The unit may drop, shake or emit noise.
2
Have you done the refrigerant leakage test?
It may cause insufcient cooling (heating) capacity.
3
Is heat insulation of pipeline sufcient?
It may cause condensation and water dripping.
4 Is water drained well?
It may cause condensation and water dripping.
5
Is the voltage of power supply according to the voltage marked on the nameplate?
It may cause malfunction or damage the parts.
6
Is electric wiring and pipeline installed correctly?
It may cause malfunction or damage the parts.
7
Is the unit grounded securely?
It may cause electric leakage.
8
Does the power cord follow the specication?
It may cause malfunction or damage the parts.
9
Is there any obstruction in air inlet and air outlet?
It may cause insufcient cooling (heating).
10
The dust and sundries caused during installation are removed?
It may cause malfunction or damaging the parts.
11
The gas valve and liquid valve of connection pipe are open completely?
It may cause insufcient cooling (heating) capacity.
The water outlet can't be placed in water
1. Use Vacuum Pump
(1) Remove the valve caps on the liquid valve and gas valve and the nut of refrigerant charging vent. (2) Connect the charging hose of piezometer to the refrigerant charging vent of gas valve and then connect the other charging hose to the vacuum pump. (3) Open the piezometer completely and operate for 10-15min to check if the pressure of piezometer remains in -0.1MPa. (4) Close the vacuum pump and maintain this status for 1-2min to check if the pressure of piezometer remains in -0.1MPa. If the pressure decreases, there may be leakage. (5) Remove the piezometer, open the valve core of liquid valve and gas valve completely with inner hexagon spanner. (6) Tighten the screw caps of valves and refrigerant charging vent.(As show in Fig.28)
1. Check after Installation
Check according to the following requirement after finishing installation.
2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client. (2) Method of test operation
● Put through the power, press ON/OFF button on the remote controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16℃, the air conditioner can’t start cooling.
2. Leakage Detection
(1) With leakage detector: Check if there is leakage with leakage detector. (2) With soap water: If leakage detector is not available, please use soap water for leakage detection. Apply soap water at the suspected position and keep the soap water for more than 3min. If there are air bubbles coming out of this position, there's a leakage.
8.7 Vacuum Pumping and Leak Detection
8.8 Check after Installation and Test Operation
Fig.26
Fig.27
Fig.28
35
Page 34
Service Manual
9. Maintenance
Note: When replacing the controller, be sure to insert the wire jumper into the new controller, otherwise the unit will display C5
9.1 Malfunction Analysis
The remote controller does not receive signals (after it is powered, the buzzer will sound, unless it has malfunction)
Trip of breaker or blow of fuse
Air conditioner can not
start up
Measure insulation resistance to ground to see if there is any leakage.
The circuit or the part of the air conditioner has malfunction. They heat and break the insula­tion and lead to short circuit or creepage. Measure the insula­tion resistance or eliminate the malfunction one by one. If the breaker itself has malfunction, then replace the breaker.
The transformer connection is loose or has bad contact or the transformer has malfunction.
Fasten the wiring; measure the output voltage of the trans­former , if it is incorrect, change the transformer.
No power
Check power supply circuit.
Power plug is not well plugged in and poor connection.
Check if the plug is properly plugged in and make the loose contact firm.
Fuse of controller burnt out
The air condi­tioner does not react after it is powered ( after the plug is inserted, the buzzer does not sound and the remote startup has no response)
Remote controller malfunction
Receiver loose or poor connection
Receiver is broken
Change controller fuse
Controller is broken
Check remote controller
Remote controller is short of power
Change batteries
First, press the manual switch button AUTO,if there is no response,check based on the above methods. If it runs nor­mally after pressing the button, check again whether the instal­lation position and the connec­tion wire of the reception head is correct. If it is correct,then re­place the receiver or the remote controller.
Power voltage is too low
Check the voltage. If it is lower than 10% of the rated voltage, check the cause, improve the power supply condition and add the sta-
bilized voltage power supply.
The breaker trips at once when it is set to “ON”.
The breaker trips in few minutes when it is set to “ON”.
36
Page 35
Service Manual
Improper set of temperature
Adjust set temperature
If cooling (heating) load is proper
Check the forecasted load of cooling (heating)
The refrigerant has leakage or is insufficient
Check and fill the leakage, then vacuumize it and supplement the re­frigerant as required
Leakage between the high pres­sure and the low pressure in­side the compressor
Replace the compressor
Malfunction of four-way valve Replace the four-way valve
Local block of capillary Replace the capillary
Blockage of cooling system
Judge whether the system is blocked by observing the condensation of evapora­tor and the pressure value of the high pressure manometer and take measures to deal with the system.
Malfunction of refri g e r a nt flow
Heat insulation for the connection pipes of the indoor unit and the out­door unit is bad.
Make sure that heat insulation for the thick and thin pipes is good. Heat insulation must also be provided for the joint andthe exposed part of the copper pipe .
Block of outdoor heat ex­changer
Clean the dust accumulated on the surface of the heat exchanger.
Air filter were blocked
Clean the filter
Fan speed was set too slow
To set the fan speed to high or middle speed
Air circulation is insufficient
Fan rotation speed becomes low
Capacitor damage
Motor damage
Replace the capaci­tor
Replace the motor
The installation position of the outdoor unit is not appropriate.
Good ventilation must be provided for the installation position of the outdoor unit.
The outdoor temperature is too high.
Properly install the rainproof plate or the sunproof plate. If the maximum cool air still can not meet the requirement, it is sug­gested to replace the air conditioner.
Keep certain air tightness indoors, try not to use electricalappliance with large quantity of heat
The air tightness is not enough. People come in and out too frequently. There are heating devices indoors.
Poor COOL(HEAT) operation
37
Page 36
Service Manual
Improper set of temperature
Adjust set temperature
If cooling (heating) load is proper
Check the forecasted load of cooling (heating)
The refrigerant has leakage or is insufficient
Check and fill the leakage, then vacuumize it and supplement the re­frigerant as required
Leakage between the high pres­sure and the low pressure in­side the compressor
Replace the compressor
Malfunction of four-way valve Replace the four-way valve
Local block of capillary Replace the capillary
Blockage of cooling system
Judge whether the system is blocked by observing the condensation of evapora­tor and the pressure value of the high pressure manometer and take measures to deal with the system.
Malfunction of refrig e r a n t flow
Heat insulation for the connection pipes of the indoor unit and the out­door unit is bad.
Make sure that heat insulation for the thick and thin pipes is good. Heat insulation must also be provided for the joint andthe exposed part of the copper pipe .
Block of outdoor heat ex­changer
Clean the dust accumulated on the
surface of
the heat exchanger.
Air filter were blocked
Clean the filter
Fan speed was set too slow
To set the fan speed to high or middle speed
Air circulation is insufficient
Fan rotation speed becomes low
Capacitor damage
Motor damage
Replace the capaci­tor
Replace the motor
The installation position of the outdoor unit is not appropriate.
Good ventilation must be provided for the installation position of the outdoor unit.
The outdoor temperature is too high.
Properly install the rainproof plate or the sunproof plate. If the maximum cool air still can not meet the requirement, it is sug­gested to replace the air conditioner.
Keep certain air tightness indoors, try not to use electricalappliance with large quantity of heat
The air tightness is not enough. People come in and out too frequently. There are heating devices indoors.
Poor COOL(HEAT) operation
38
Page 37
Service Manual
Adjust fan location
Fan of indoor unit contacts other parts
Foreign object in indoor unit
Take out the foreign object
Adjust support washer of compressor, and tighten loosen screws
Touch of pipeline of outdoor unit Separate the touching pipeline.
Abnormal sound and shake
Touch of inner plates
1. Tighten connect screw.
2. Stick absorbing clay between plates.
Louver of outdoor unit touched outer case.
Adjust location of louver.
Abnormal sound inside compressor
Change compressor
Drainage pipe blocked or broken Change drainage pipe
Re-wrap and make it tight.
Wrap of refrigerant pipe joint is not close enough.
Water leakage
Change controller
Wire loose or wrong connection
In cool, heat mode, the outdoor unit and compres­sor will not run.
Correctly wire according to the drawing
Improper setting of temperature
Adjust setting temp.
Controller malfunction (IC2003 broken, creepage of parallel capaci­tor of relay loop, relay is broken etc.)
First, check whether the connection is wrong. If no, replace the parts
The swing fan does not run.
The torque of the swing motor is not enough
Wrong connection
The controller is damaged(IC2003 is damaged, the swing relay can not close, etc)
Compressor shakes too much
39
Page 38
Service Manual
9.2 Flashing LED of Indoor/Outdoor Unit and Primary Judgement
NO.
Malfunction Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of display status and during blinking, ON 0.5s and OFF
0.5s
Operation Indicator
Cool Indicator
Heating Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
1
High pressure protection of system
E1
OFF 3s and blink once
During cooling and drying operation, except indoor fan operates, all loads stop operation. During heating operation, the complete unit stops.
Possible reasons:
1. Refrigerant was superabundant;
2. Poor heat exchange (including
and bad radiating environment ); Ambient temperature is too high.
2
Antifreezing protection
E2
OFF 3S and blink twice
OFF 3S and blink 3 times
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates.
1. Poor air-return in indoor unit;
2. Fan speed is abnormal;
3. Evaporator is dirty.
3
System block or refrigerant leakage
E3
OFF 3S
and blink
3 times
OFF 3S
and
blink
9 times
The Dual-8 Code Display will show E3 until the low pressure switch stop operation.
1.Low-pressure protection
2.Low-pressure protection of system
3.Low-pressure protection of compressor
4
High discharge temperature protection of compressor
E4
OFF 3S and blink 4 times
OFF 3S
and blink
7 times
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation, all loads stop.
Please refer to the malfunction analysis (discharge protection, overload).
5
Overcurrent protection
E5
OFF 3S and blink 5 times
OFF 3S
and blink
5 times
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation, all loads stop.
1. Supply voltage is unstable;
2. Supply voltage is too low and load is too high;
3. Evaporator is dirty.
6
Communi­cation Malfunction
E6
OFF 3S and blink 6 times
OFF
During cooling operation, compressor stops while indoor fan motor operates. During heating operation, the complete unit stops.
Refer to the corresponding malfunction analysis.
7
High temperature
resistant protection
E8
OFF 3S and blink 8 times
OFF 3S
and blink
6 times
During cooling operation: compressor will stop while indoor fan will operate. During heating operation, the complete unit stops.
Refer to the malfunction analysis (overload, high temperature resistant).
8
EEPROM malfunction
EE
OFF 3S
and blink
15 times
OFF 3S
and blink
11 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
Replace outdoor control panel AP1
9
Limit/ decrease frequency due to high temperature of module
EU
OFF 3S
and blink
6 times
OFF 3S
and blink
6 times
All loads operate normally, while operation frequency for compressor is decreased
Discharging after the complete unit is de-energized for 20mins, check whether the thermal grease on IPM Module of outdoor control
the radiator is inserted tightly. If its no use, please replace control panel AP1.
10
Malfunction protection of jumper cap
C5
OFF 3S
and blink
15 times
Wireless remote receiver and button are effective, but can not dispose the related command
1. No jumper cap insert on mainboard.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of mainboard.
40
Page 39
Service Manual
NO.
Malfunction Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of display status and during blinking, ON 0.5s and OFF
0.5s
Operation Indicator
Cool Indicator
Heating Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
11
Gathering refrigerant
F0
OFF 3S
and blink
1 times
OFF 3S
and blink
1 times
When the outdoor unit receive signal of Gathering refrigerant ,the system will be forced to run under cooling mode for gathering refrigerant
Nominal cooling mode
12
Indoor ambient temperature sensor is open/short circuited
F1
OFF 3S
and blink
once
During cooling and drying operation, indoor unit operates while other loads will stop; during heating operation, the complete unit will stop operation.
1. Loosening or bad contact of indoor ambient temp. sensor and mainboard terminal.
2. Components in mainboard fell down leads short circuit.
3. Indoor ambient temp. sensor damaged.(check with sensor resistance value chart)
4. Mainboard damaged.
13
Indoor evaporator temperature sensor is open/short circuited
F2
OFF 3S
and blink
twice
AC stops operation once reaches the setting temperature. Cooling, drying: internal fan motor stops operation while other loads stop operation; heating: AC stop operation
1. Loosening or bad contact of Indoor evaporator temp. sensor and mainboard terminal.
2. Components on the mainboard fall down leads short circuit.
3. Indoor evaporator temp. sensor damaged.(check temp. sensor value chart for testing)
4. Mainboard damaged.
14
Outdoor ambient temperature sensor is open/short circuited
F3
OFF 3S
and blink
3 times
OFF 3S
and
blink
6 times
During cooling and drying operating, compressor stops while indoor fan operates; During heating operation, the complete unit will stop operation
Outdoor temperature sensor hasnt been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor)
15
Outdoor condenser temperature sensor is open/short circuited
F4
OFF 3S
and blink
4 times
OFF 3S
and
blink
5 times
During cooling and drying operation, compressor stops while indoor fan will operate; During heating operation, the complete unit will stop operation.
Outdoor temperature sensor hasnt been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor)
16
Outdoor discharge temperature sensor is open/short circuited
F5
OFF 3S
and blink
5 times
OFF 3S
and
blink
7 times
During cooling and drying operation, compressor will sop after operating for about 3 mins, while indoor fan will operate; During heating operation, the complete unit will stop after operating for about 3 mins.
1.Outdoor temperature sensor hasnt been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor)
2.The head of temperature sensor hasnt been inserted into the copper tube
17
Limit/ decrease frequency due to overload
F6
OFF 3S
and blink
for 6
times
OFF 3S
and
blink
3 times
All loads operate normally, while operation frequency for compressor is decreased
Refer to the malfunction analysis (overload, high temperature resistant)
18
Decrease frequency due to overcurrent
F8
OFF 3S
and blink
8 times
OFF 3S
and blink once
All loads operate normally, while operation frequency for compressor is decreased
The input supply voltage is too low; System pressure is too high and overload
41
Page 40
Service Manual
NO.
Malfunction Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of display status and during blinking, ON 0.5s and OFF
0.5s
Operation Indicator
Cool Indicator
Heating Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
19
Decrease frequency due to high air discharge
F9
OFF 3S
and blink
9 times
OFF 3S
and
blink
twice
All loads operate normally, while operation frequency for compressor is decreased
Overload or temperature is too high;
Malfunction of electric expansion valve (EKV)
20
Limit/ decrease frequency due to antifreezing
FH
OFF 3S
and blink
2 times
OFF 3S
and blink
2 times
OFF 3S
and
blink
4 times
All loads operate normally, while operation frequency for compressor is decreased
Poor air-return in indoor unit or fan speed is too low
21
Voltage for DC bus-bar is too high
PH
OFF 3S
and blink
11 times
OFF 3S
and
blink
13 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 265VAC, turn on the unit after the supply voltage is increased to the normal range.
2.If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel (AP1)
22
Voltage of DC bus-bar is too low
PL
OFF 3S
and blink
21 times
OFF 3S
and
blink
12 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 150VAC, turn on the unit after the supply voltage is increased to the normal range.
2.If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel (AP1)
23
Compressor Min frequence in test state
P0
(during
blinking,
ON
0.25s
and OFF
0.25s)
(during
blinking,
ON
0.25s
and OFF
0.25s)
Showing during min. cooling or min. heating test
24
Compressor rated frequence in test state
P1
(during
blinking,
ON
0.25s
and OFF
0.25s)
(during
blinking,
ON
0.25s
and OFF
0.25s)
Showing during nominal cooling or nominal heating test
25
Compressor maximum frequence in test state
P2
(during
blinking,
ON
0.25s
and OFF
0.25s)
(during
blinking,
ON
0.25s
and OFF
0.25s)
Showing during max. cooling or max. heating test
42
Page 41
Service Manual
NO.
Malfunction Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of display status and during blinking, ON 0.5s and OFF
0.5s
Operation Indicator
Cool Indicator
Heating Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
26
Compressor intermediate frequence in test state
P3
(during
blinking,
ON
0.25s
and OFF
0.25s)
(during
blinking,
ON
0.25s
and OFF
0.25s)
Showing during middle cooling or middle heating test
27
Overcurrent protection of phase current for compressor
P5
OFF 3S
and blink
15 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor.
28
Charging malfunction
of capacitor
PU
OFF 3S
and blink
17 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
Refer to the part three—charging malfunction analysis of capacitor
29
Malfunction of module temperature sensor circuit
P7
OFF 3S
and blink
18 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
Replace outdoor control panel AP1
30
Module high temperature protection
P8
OFF 3S
and blink
19 times
During cooling operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
After the complete unit is de­energized for 20mins, check whether the thermal grease on IPM Module of outdoor control panel
radiator is inserted tightly. If its no use, please replace control panel AP1.
31
Decrease frequency due to high temperature resistant during heating operation
H0
OFF 3S
and blink
10 times
All loads operate normally, while operation frequency for compressor is decreased
Refer to the malfunction analysis (overload, high temperature resistant)
32
Static dedusting protection
H2
OFF 3S
and blink
twice
33
Overload protection for compressor
H3
OFF 3S
and blink
3 times
OFF 3S
and blink
8 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
1. Wiring terminal OVC-COMP is loosened. In normal state, the resistance for this terminal should be less than 1ohm.
2.Refer to the malfunction analysis (
discharge protection, overload)
43
Page 42
Service Manual
NO.
Malfunction Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of display status and during blinking, ON 0.5s and OFF
0.5s
Operation Indicator
Cool Indicator
Heating Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
34
System is abnormal
H4
OFF 3S
and blink
4 times
OFF 3S
and blink
6 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis (overload, high temperature resistant)
35
IPM protection
H5
OFF 3S
and blink
5 times
OFF 3S
and blink
4 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor.
36
Module temperature is too high
H5
OFF 3S
and blink
5 times
OFF 3S
and blink
10 times
37
Internal motor (fan motor) do not operate
H6
OFF 3S
and blink
11 times
Internal fan motor, external fan motor, compressor and electric heater stop operation,guide louver stops at present location.
1. Bad contact of DC motor feedback terminal.
2. Bad contact of DC motor control end.
3. Fan motor is stalling.
4. Motor malfunction.
5. Malfunction of mainboard rev detecting circuit.
38
Desynchro­nizing of compressor
H7
OFF 3S
and blink
7 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor.
39
PFC protection
HC
OFF 3S
and blink
6 times
OFF 3S
and blink
14 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis
40
Outdoor DC fan motor malfunction
L3
OFF 3S
and blink
23 times
OFF 3S
and
blink
14 times
Outdoor DC fan motor malfunction lead to compressor stop operation,
DC fan motor malfunction or system blocked or the connector loosed
41
power protection
L9
OFF 3S
and blink
20 times
OFF 3S
and blink
9 times
compressor stop operation and Outdoor fan motor will stop 30s latter , 3 minutes latter fan motor and compressor will restart
To protect the electronical components when detect high power
42
Indoor unit and outdoor unit doesn't match
LP
OFF 3S
and blink
19 times
OFF 3S
and blink
16 times
compressor and Outdoor fan motor can’t work
Indoor unit and outdoor unit doesn't
match
43
Failure start­up
LC
OFF 3S
and blink
11 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation.
Refer to the malfunction analysis
44
Page 43
Service Manual
NO.
Malfunction Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of display status and during blinking, ON 0.5s and OFF
0.5s
Operation Indicator
Cool Indicator
Heating Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
44
Malfunction of phase current detection circuit for compressor
U1
OFF 3S
and blink
13 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
Replace outdoor control panel AP1
45
Malfunction of voltage dropping for DC bus-bar
U3
OFF 3S
and blink
20 times
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
Supply voltage is unstable
46
Malfunction of complete units current detection
U5
OFF 3S
and blink
13 times
During cooling and drying operation, the compressor will stop while indoor fan will operate; During heating operating, the complete unit will stop operation.
Theres circuit malfunction on outdoor units control panel AP1, please replace the outdoor units control panel AP1.
47
The four-way valve is abnormal
U7
OFF 3S
and blink
20 times
If this malfunction occurs during heating operation, the complete unit will stop operation.
1.Supply voltage is lower than AC175V;
2.Wiring terminal 4V is loosened or broken;
3.4V is damaged, please replace 4V.
48
Zero­crossing malfunction of outdoor unit
U9
OFF 3S and blink 18 times
During cooling operation, compressor will stop while indoor fan will operate; during heating,the complete unit will stop operation.
Replace outdoor control panel AP1
49
Frequency limiting (power)
OFF 3S and blink 13 times
50
Compressor is open­circuited
OFF 3S
and blink
once
51
The temperature for turning on the unit is reached
OFF 3S and blink
8 times
52
Frequency limiting (module temperature)
OFF 3S and blink
11 times
45
Page 44
Service Manual
NO.
Malfunction Name
Display Method of Indoor Unit Display Method of Outdoor Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of display status and during blinking, ON
0.5s and OFF 0.5s
Operation Indicator
Cool Indicator
Heating Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
53
Normal communica­tion
continously
5455Defrosting
OFF 3S
and blink
once
(during blinking, ON 10s
and OFF
0.5s)
OFF 3S
and blink
twice
Defrosting will occur in heating mode. Compressor will operate while indoor fan will stop operation.
Its the normal state
U8
Flash 17
times
every 3s
Operation
of remote
controller or
control
panel is
available,
but the unit
won’t act.
1. Discharging speed of capacitor is slow, which lead to wrong judgement of controller.
Zero-crossing detection circuit of main board is abnormal
Refer to maintenance flowchart
Zero-crossing inspection circuit malfun­ction of the IDU fan motor
46
Page 45
Service Manual
47
Page 46
Service Manual
Analysis or processing of some of the malfunction display:
1. Compressor discharge protection
Possible causes: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short pass for condenser; the system has
noncondensing gas (such as air, water etc.); blockage of capillary assy (including lter); leakage inside four-way valve causes incorrect
operation; malfunction of compressor; malfunction of protection relay; malfunction of discharge sensor; outdoor temperature too high.
Processing method: refer to the malfunction analysis in the above section.
2. Low voltage overcurrent protection
Possi ble cause: Sudden drop of supply voltage.
3. Communication malfunction
Processing method: Check if communication signal cable is connected reliably.
4. Sensor open or short circuit
Processing method: Check whether sensor is normal, connected with the corre sponding position on the controller and if damage of lead
wire is found.
5. Compressor over load protection
Possible causes: insufcient or too much refrigrant; blockage of capillary and increase of suction temp.; improper running of compressor,
burning in or stuck of bearing, damage of discharge valve; malfunction of protector.
Processing method: adjust refrigerant amount; replace the capillary; replace the compressor; use universal meter to check if the
contactor of compress or is ne when it is not overheated, if not replace the protector.
6. System malfunction
i.e.overload protection.When tube temperature(Check the temperature of outdoor heat exchanger when cooling and check the
temperatur e of indoor heat exchanger when heating) is too high, protectionwill beactivated.
Possi ble causes: Outdoor temperature is too high when cooling; insufcient outdoor air circulation; refrigerant ow malfunction.
please refer to the malfunction analysis in the previous section for handling method .
7. IPM module protection
Processing method:Once the module malfunction happens,if it persists for a long time and can not be selfcanceled, cut off the power and
turn off the unit,and then re-energize the unit again after about 10 min.After repeating the procedure for sever times, if the malfunction
still exists,replace the module.
48
Page 47
Service Manual
9.3 How to Check Simply the Main Part
(1) Malfunction of Temperature Sensor F1, F2
Troubleshooting for F1,F2 malfunction
Is
the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
Insert the temperature
sensor tightly
yes
Is malfunction
eliminated
Is there short circuit due to trip-over of
the parts?
Make the parts upright
yes
Is malfunction
eliminated
Replace the mainboard with the same model.
End
no
no
Is the
temperature sensor normal according
to the Resistance
Table?
no
Replace it with a
temperature sensor
with the same model
no
yes
yes
Is malfunction
removed
no
yes
yes
no
Main detection points:
Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
Is there short circuit due to trip-over of the parts?
Is the temperature sensor broken?
Is mainboard broken?
Malfunction diagnosis process:
Indoor Unit
49
Page 48
Service Manual
(2) Malfunction of Blocked Protection of IDU Fan Motor H6
Main detection points:
Is the control terminal of PG motor connected tightly?
Is the feedback interface of PG motor connected tightly?
The fan motor can't operate
The motor is broken?
Detectioncircuit of the mainboard is dened abnormal?
Malfunction diagnosis process:
Measure the voltage of this foot to neutral wire on the mainboard
Start
off stir the blade with a tool
While power is
smoothly
Replace PG motor
End
yes
no
Is malfunction
eliminated
yes
no
Insert the control
terminal of PG
motor tightly
no
no
Reinstall the blade and
motor correctly
Is malfunction
eliminated
no
no
yes
yes
Turn on the
unit again; measure whether the output
voltage on control terminal for PG motor
is more than 50V within 1 min after the
louvers are opened
no
yes
yes
Is the motor
started up
no
Is malfunction
eliminated
yes
yes
yesno
yes
Is malfunction
eliminated
Tighten the screw; reassemble the blade, motor and shaft bearing rubber base sub-assy to make sure there is no foreign object between them
Replace the mainboard with the same model.
Check if the connection of PG motor feedback terminal is firm.
Check if the connection of PG motor control terminal is firm.
to see whether the blade rotates
2.
Malfunction of Blocked Protection of IDU Fan Motor H6
Main.detection.points:
ƽ
SmoothlyIs.the.control.terminal.of.PG.motor.connected.tightly?
ƽ
SmoothlyIs.the.feedback.interface.of.PG.motor.connected.tightly?
ƽ
The.fan.motor.can't.operate.
˛
ƽ
The.motor.is.broken?
ƽ
Detectioncircuit.of.the.mainboard.is.
.abnormal?
Malfunction.diagnosis.process:
50
Page 49
Service Manual
Appearance of the jumper cap
Troubleshooting for C5
malfunction
Is there jumper cap on the
mainboard
?
Is
the jumper cap inserted
correctly and
tightly
?
Replace the jumper cap
with the same model
End
yes
yes
Assemble the jumper cap with the same model
no
Is malfunction
eliminated
no
yes
Insert the
jumper cap
tightly
Is malfunction
eliminated
no
no
yes
Is malfunction
eliminated
no
yes
Replace the mainboard with the same model.
(3) Malfunction of Protection of Jumper Cap C5
Main detection points:
Is there jumper cap on the mainboard?
Is the jumper cap inserted correctly and tightly?
The jumper is broken?
Detectioncircuit of the mainboard isdened abnormal?
Malfunction diagnosis process:
51
Page 50
Service Manual
(4) Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8
Main detection points:
ƽ
Instant energization afte de-energization while the capacitordischarges slowly?
ƽ
Malfunction diagnosis process:
Troubleshooting for U8 malfunction
Turn power off for 1minute,the turn back on
U8 is still displayed
The unit returns to normal. Conclusion:U8 is displayed due to power off/on while the capacitor discharges slowly.
The zero-cross detection circuit of the mainboard is defined abnormal.Replace the mainboard with the same model
End
No
Yes
52
Page 51
Service Manual
(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged?
Fault diagnosis process:
Troubleshooting for F1,F2 malfunction
Is
the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
Insert the temperature
sensor tightly
yes
Is malfunction
eliminated
Is there short circuit due to trip-over of
the parts?
Make the parts upright
yes
Is malfunction
eliminated
Replace the mainboard with the same model.
End
no
no
Is the
temperature sensor normal according
to the Resistance
Table?
no
Replace it with a
temperature sensor
with the same model
no
yes
yes
Is malfunction
removed
no
yes
yes
no
Outdoor Unit
53
Page 52
Service Manual
(2) IPM Protection, Out-of-step Fault, Compressor Phase Overcurrent (AP1 below refers to the outdoor control panel)
Main check points:
●Is the connection between control panel AP1 and compressor COMP secure? Loose? Is the connection in correct order?
●Is the voltage input of the machine within normal range? (Use AC voltmeter to measure the voltage between terminal L and N on the
wiring board XT)
●Is the compressor coil resistance normal? Is the insulation of compressor coil against the copper tube in good condition?
●Is the working load of the machine too high? Is the radiation good?
I●s the charge volume of refrigerant correct?
Fault diagnosis process:
Energize and
switch on
IPM protection
occurs after the machine has run for a
p
eriod of time?
Use AC voltmeter to measure the voltage between terminal L and N on the wiring board XT)
If the voltage between terminal L and N on wiring board XT is within 210VAC~250VAC?
Check the supply voltage and restore it to
210VAC~250VAC
Voltage between
the two ends of celectrolytic
capacitor is
Restart the unit. Before
protection occurs,
use DC voltmeter to
measure the voltage
between the two
ends of electrolytic
capacitor on control
panel AP1
If the unit can
work
normally?
Please confirm:
1. If the indoor and outdoor heat exchangers are dirty? If they are
obstructed by other
objects which affect
the heat exchange of indoor and outdoor unit.
2. If the indoor and outdoor fans are working normally?
3. If the environment temperature is too high, resulting in that the system
pressure is too high
and exceeds the
permissible range?
4. If the charge volume of refrigerant is too much, resulting in that the system pressure is too high?
5. Other conditions resulting in that the
system pressure
becomes too high.
The connection of capacitor C2
is loose.
Reconnect the capacitor C2 according to Electrical Wiring Diagram. Then, Restart the unit.
Stop the unit and disconnect the power supply. Wait 20 minutes, or use DC voltmeter to measure the voltage
between the two ends of
capacitor C2, until the
voltage is lower than 20V
Replace the capacitor C2. Then, energize and start the unit.
Replace the
control panel AP1
Take corrective actions according to Technical Service Manual, and
then energize and start
the unit.
If there is any
abnormality
described above?
Replace the
control panel AP1
If the connection between AP1 and COMP is unsecure or the connection order is wrong?
Connect the control panel
A
P1 and compressor COMP correctly according to the Electrical Wiring Diagram. Then, energize and start the unit.
Use ohmmeter to measure the resistance between the three terminals on compressor COMP, and compare the measurements with the
compressor resistance on
Service Manual.
If the
resistance is
normal?
Use ohmmeter to measure the resistance between the two
terminals of compressor
COMP and copper tube.
Replace the compressor
COMP
Resistance higher
than 500MΩ?
Replace the control panel
AP1
END
Y N
Y
N
Y
If the unit can
work normallv?
Y
If the unit can
work normally?
Y
N
Y
N
If the unit can
work normally?
Y
Y
N
N
If the unit can
work
normally?
Y
Y
N
N
N
Y
higher than 250V
Remove the wires on the two ends of capacitor C2. Then, use capacitance meter to measure the capacitor C2. Verify as per the Parameters Sheet.
Stop the unit and disconnect the power supply. Then, check the connection of capacitor C2 according to Electrical Wiring Diagram.
If capacitor C2 is failed?
Refer to the Electrical Wiring Diagram and check if the connection between AP1 and COMP is loose and if the connection order is correct.
54
Page 53
Service Manual
(3)High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Is outdoor ambient temperature in normal range?
●Are the outdoor and indoor fans operating normally?
●Is the heat dissipation environment inside and outside the unit good?
Fault diagnosis process:
End
Y
N
Y
N
Y
N
Overheat and high
temperature protection
Is outdoor ambient temperature higher than 53?
20 minutes after the complete
unit is powered off.
Is heat dissipation of the indoor unit
and outdoor unit abnormal?
Normal protection, please operate it after the outdoor ambient temp­erature is normalized.
Improve the heat dissipation environ­ment of the unit
Does the outdoor fan work normally?
1. Check if the fan terminal OFAN is connected correctly
2. Resistance between any two terminals is measure by an ohm gauge and should be less than 1K Ohm.
Replace the control panel
AP1
Replace the fan
capacitor C1
Replace the outdoor fan
55
Page 54
Service Manual
(4) Start-up failure (following AP1 for outdoor unit control board)
Mainly detect:
●Whether the compressor wiring is connected correct?
●Is compressor broken?
●Is time for compressor stopping enough?
Fault diagnosis process:
Y
N
Y
N
N
Y
Y
N
Power on the unit
Is stop time of the compressor
longer than 3 minutes?
Restart it up after 3 minutes
Does startup fail?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Connect the wires as per the connection diagram
Replace the control panel AP1
If the fault is eliminated?
Replace the
compressor
End
56
Page 55
Service Manual
(5) Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Is the system pressure too high?
●Is the input voltage too low?
Fault diagnosis process:
Out of step occurs once the
unit is powered on.
Is stop time of the
compressor longer than
3 minutes?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Is the connection made in clockwise
direction?
Connect the
wires correctly
Replace the control
panel AP1
If the fault is eliminated?
Replace the compressor
End
Out of step occurs in
operation
Is the outdoor fan working
normally?
Is the outdoor unit blocked
by foreign objects?
Replace the
control panel AP1
If the fault is eliminated?
Replace the compressor
End
Check if the fan terminal
OFAN is connected correctly
Remove foreign objects
Replace the fan
capacitor C1
Replace the outdoor fan
57
Page 56
Service Manual
(6)Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:
20 minutes after the
complete unit is
powered off
Is the terminal FA for the
electronic expansion valve
connected correctly?
Connect the
wires correctly
Resistances between the first four pins close to the terminal hole and the fifth pin are almost the same, less than 100 ohm.
Replace the electronic
expansion valve
If the fault is eliminated?
If the fault is eliminated?
Replace the
control panel
AP1
Coolant leakage, refilling
the coolant
End
58
Page 57
Service Manual
(7) Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken
Fault diagnosis process:
Y
Y
N
N
N
N
N
N
Y
Y
Y
Start
Check wiring of the reactor (L) of the outdoor unit and the PFC capacitor
Whether there is any
damage or
short-circuit?
Replace it as per the
wiring diagram and
reconnect the wires
If the fault is eliminated?
Remove the PFC capacitor
and measure resistance
between the two terminals.
Is the resistance around zero?
The capacitor is
short circuited and
the capacitor should be repla­ced
Restart the unit
If the fault is eliminated?
Disconnect the terminals for the reactor and measure the resistance between the two terminals of the
reactor by an ohm gauge
Whether there is any damage
or short-circuit?
Replace the reactor
Restart the unit
If the fault is eliminated?
Replace the control
panel AP1
End
Y
59
Page 58
Service Manual
(8) Communication malfunction: (following AP1 for outdoor unit control board)
Mainly detect:
●Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
●Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is there any
damage?
Fault diagnosis process:
Y
N
Y
N
N
Y
N
N
Y
N
Y
N
Y
Y
Start
Did the equipment operate normally before the failure
occurs?
The AP1 voltage detection circuit is at fault
Check wiring inside of the indoor and outdoor
units
Are wires broken?
Check the communication
circuit of the outdoor unit
If the fault is eliminated?
The communication
circuit is abnormal
Replace the main board of
the indoor unit
End
If the fault is eliminated?
Replace the main board AP1 of the outdoor unit
If the fault is eliminated?
Is the connection right?
Check the wiring of the indoor and outdoor units with reference to the
wiring diagram
Correctly connect the
corresponding wires for
the indoor and outdoor
units with reference to
the wiring diagram
60
Page 59
Service Manual
(9) Malfunction of Overcurrent Protection E5
Main detection points:
Is the supply voltage unstable with big uctuation?
Is the supply voltage too low with overload?
Hardware trouble?
Malfunction diagnosis process:
5. Malfunction of Overcurrent Protection
Main detection points:
Is the supply voltage too low with overload?
Hardware trouble? Malfunction diagnosis process:
no
no
no
no
yes
no
no
End
yes
Malfunction is eliminated
Is the supply voltage unstable with big fluctuation?
Start
Is the supply voltage too low with overload?
The fan is abnormal? Fan speed is too low or fan doesn’t rotate
Measure the
current of live wire on the main
board with a clamp ampere meter. Is the current higher than the value of the overcurrent protection?
Is there blockage inside the system? (Filth blockage, ice plug,
greasy blockage, the cut off valve hasn’t been
opened completely)
Is the compressor running abnormally? Is there abnormal sound or oil leakage; is the temperature of the shell too high, etc.?
Is the indoor / outdoor
heat exchanger dirty,or are the air inlet
and outlet blocked?
Normal fluctuation should be within 10 % of the rated voltage on the nameplate
Malfunction is eliminated
no
yes
no
yes
no
yes
no
no
no
yes
no
yes
no
yes
yes
yes
yes
yes
yes
yes
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Adjust the supply voltage to maintain it within normal range
Clean the indoor and outdoor heat exchangers and remove the blockage of air inlet and outlet
Check the motor and reinstall the motor to have the fan run normally
Replace the mainboard with the same model
Replace the compressor
Flush the heat exchangers with high pressure nitrogen
Replace the mainboard with the same model
61
Page 60
Service Manual
10. Exploded View and Parts List
10.1 Indoor Unit
43
42
45
46
44
15
14
13
12
16
17
18
19
20
21
22
23
24
38
37
36
35
34
33
32
31
30
29
28
27
11
10
9
8
7
6
5
4
3
2
1
25
39
40
26
41
ON/OFF MODE
FAN SWING
SLEEP TIMER
+
-
AUTO COOL DRY FAN HEAT
T-ONT-OFF
SWING SLEEP LOCK SPEED
62
Page 61
Service Manual
Above data is subject to change without notice.
No.
Description
Part Code
QtyASH-09AIR ASH-12AIR
1 Front Panel Sub-Assy 20012241 20012241 1
2 Front Panel A2 20012121S 20012121S 1
3 Filter Sub-Assy 11122081 11122081 2
4 Screw Cover 24252016 24252016 3
5 Electric Box Cover2 20122075 20122075 1
6 Front Case 20012120C 20012120C 1
7 Axile Bush 10542036 10542036 1
8 Guide Louver 10512111 10512111 1
9 Air Louver 1 10512113 10512113 1
10 Air Louver 2 10512114 10512114 1
11 Helicoid Tongue 26112162 26112162 1
12 Axile Bush 10542036 10542036 1
13 Rear Case assy 2220210111 2220210111 1
14 Cross Flow Fan 10352043 10352043 1
15 Fan Bearing 7651221001 7651221001 1
16 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
17 O-Gasket of Cross Fan Bearing 76512203 76512203 1
18 Ring of Bearing 26152022 26152022 1
19 Remote Controller 30510065 30510065 1
20 Drainage Hose 0523001406 0523001406 1
21 Wall Mounting Frame 01252015 01252015 1
22 Evaporator Assy 01002762 0100276201 1
23 Evaporator Support 24212090 24212090 1
24 Connecting Cable 4002052317 4002052317 0
25 Connecting Cable 400205403 400205403 0
26 Decorative Strip / / /
27 Tube Sensor 3900031302 3900031302 1
28 Ambient Temperature Sensor / / /
29 Main Board 30138000723 30138000723 1
30 Terminal Board 42011233 42011233 1
31 Electric Box 2011208201 2011208201 1
32 Transformer / / /
33 Electric Box Assy 10000202063 10000202063 1
34 Display Board 30565056 30565056 1
35 Crank 10582070 10582070 1
36 Step Motor 1521212901 1521212901 1
37 Rubber Plug (Water Tray) 76712012 76712012 1
38 Motor Press Plate 26112160 26112160 1
39 Fan Motor 15012115 15012115 1
40 Pipe Clamp 26112164 26112164 1
41 Jumper 4202021902 4202021902 1
42 Capacitor CBB61 33010747 33010747 1
43 Shield Cover of Electric Box Sub-assy 0159207301 0159207301 1
44 Shield Cover of Electric Box 0141203601 0141203601 1
45 Electric Box Cover1 22242135 22242135 1
46 Power Cord / / /
indoor
indoor
63
Page 62
Service Manual
10.2 Outdoor Unit
ASH-09AIR
14
2
17
26
12
5
23 24
8
9
4
11
3
13
15
10
25
27
18
16
20
21
22
19
1
6
7
64
Page 63
Service Manual
Above data is subject to change without notice.
No.
Description
Part Code
Qty
ASH-09AIR outdoor
Product Code CB171W10400
1 Front Grill 22413043 1
2 Cabinet Sub-assy 0000030001510 1
3 Axial Flow Fan 10333004 1
4 Electrical Heater / /
5 Chassis Sub-assy 02803037P 1
6 Clapboard Sub-Assy 0123338502 1
7 Drainage Connecter 06123401 1
8 Compressor and Fittings 0010389601 1
9 4-Way Valve Assy 03073151 1
10 Valve Support 01713142P 1
11 Cut off Valve Assy 07133474 1
12 Valve 07130239 1
13 Valve Support Block 26113017 2
14 Right Side Plate Sub-Assy
01303178
1
15 Big Handle 2623343106 1
16 Magnet Coil 4300040050 1
17 Magnet Coil 4300040050 1
18 Rear Grill 01473009 1
19 Electric Box 20113032 1
20 Filter Board / /
21 Main Board 30138000744 1
22 Electric Box Assy 10000100354 1
23 Top Cover Sub-Assy 0125307002 1
24 Condenser Assy 01100200412 1
25 Motor Support 01703104 1
26 Fan Motor 1501308506 1
27 Small Handle 26233100 1
65
Page 64
Service Manual
ASH-12AIR
3
4 5 76
2
1
20 23
24
2221
18
17
15
16
19
8
10
9
12
11
14
13
66
Page 65
Service Manual
Above data is subject to change without notice.
No.
Description
Part Code
Qty
ASH-12AIR outdoor
1 Left Side Plate 01303200P 1
2 Fan Motor 15013085 1
3 Motor Support 01703136 1
4 Condenser Assy 01100200426 1
5 Top Cover Sub-Assy 01253081 1
6 Rear Grill 01475014 1
7 Clapboard Sub-Assy 01233180 1
8 Compressor and Fittings 0010389201 1
9 Compressor Gasket 76713027 3
10 4-Way Valve Assy 03073386 1
11 Big Handle 2623343106 1
12 Cut off Valve Assy 0713380601 1
13 Cut off Valve Assy 071302392 1
14 Valve Support
01713142P
1
15 Front Grill 22413044 1
16 Cabinet 01433033P 1
17 Axial Flow Fan 10333011 1
18 Chassis Sub-assy 01700000033P 1
19 Electric Box Assy 10000100353 1
20 Electric Box 20113032 1
21 Main Board 30138000745 1
22 Reactor 43130184 1
23 Wire Clamp 71010103 1
24 Terminal Board 42010313 1
67
Page 66
Service Manual
11. Removal Procedure
11.1 Removal Procedure of Indoor Unit
Caution: discharge the refrigerant
completely before removal.
ProcedureSteps
1. Remove fi lter
2. Remove horizontal louver
a
b
Panel
Clasp
left fi lter and right fi ler
Axile bush
Open the panel.
Loosen the clasp shown in the fig and then pull the left filter and right filer outwards to remove them.
Push out the axile bush on horizontal louver. Bend the horizontal louver with hand and then separate the horizontal louver from the crankshaft of step motor to remove it.
Horizontal louver Location of step motor
68
Page 67
Service Manual
a
b
Open the front panel; separate the panel rotation shaft from the groove fixing the front panel and then removes the front panel.
Note: The display of some models is fixed on the panel; unscrew the screws fi xing the display on the panel before removing the panel.
Remove the screws on the electric box cover to remove the electric box cover.
Electric box cover
Screws
Panel
Front panel
Panel rotation
Groove
3. Remove panel
4. Remove electric box cover
Front case sub-assy
Front case sub-assy
Left clasp
Middle clasp
Right clasp
Screw caps
Screws
Remove the screws fi xing front case.
Note:
1.Open the screw caps before removing the screws around the air outlet.
2.The quantity of screws fixing the front case sub-assy is different for different models.
Loosen the clasps at left, middle and right sides of front case. Life the front case sub-assy upwards to remove it.
5. Remove front case sub-assy
ProcedureSteps
69
Page 68
Service Manual
Vertical louver
Loosen the connection clasps between vertical louver and bottom case to remove vertical louver.
Clasps
6. Remove vertical louver
7. Remove electric box assy
Bottom case
a
b
Cut off the tieline which binding the temperature sensor and grounding wire on the evaporator, and then pull out the indoor tube temperature sensor from the evaporator. Remove the screws at the connection place between grounding wire and evaporator. Pull out the wiring terminal of motor and wiring terminal of step motor from the mainboard.
Note:
1.Location of tube temperature sensor and tieline on the evaporator is different for different models.
2.When pulling out the wiring terminal, pay attention to loose the clasp and don’t pull it so hard.
Loosen the connection clasps between shield cover of electric box sub-assy and electric box, and then remove the shield cover of electric box sub-assy.
Electric box
Clasps
Wiring terminal of motor
Temperature sensor
Grounding wire
Location of grounding
wire screw
Evaporator
Wiring terminal of step motor
Shield cover of electric box sub-assy
ProcedureSteps
70
Page 69
Service Manual
c
a
b
c
d
Remove two screws fi xing display.
Note: The display of some models is fixed on the panel; unscrew the screws fixing the display on the panel before removing the panel.
Remove the screw fi xing electric box assy and then remove the electric box assy.
Screws
Screws
Display
Screws
Connection pipe clamp
Evaporator assy
Screws
Connection pipe
8. Remove evaporator assy
At the back of the unit, remove the screw fixing connection pipe clamp and then remove the connection pipe clamp.
Remove 3 screws fi xing evaporator assy.
Adjust the position of connection pipe on evaporator slightly and then lift the evaporator upwards to remove it.
ProcedureSteps
71
Page 70
Service Manual
Motor clamp
10. Remove motor and cross fl ow blade
a
b
Remove the screws fixing motor clamp and then remove the motor clamp.
Remove the screws at the connection place of cross flow blade and motor; lift the motor and cross flow blade upwards to remove them.
Motor
Screws
Cross fl ow
c Remove the bearing holder sub-assy.
Holder sub-assy
Bottom case
Remove the screw fi xing step motor and then remove the step motor.
Step motor
9. Remove stepping motor
ProcedureSteps
Screws
72
Page 71
Service Manual
11.2 Removal Procedure of Outdoor Unit
Warning: Be sure to wait for a minimum of 20 minutes after
turning off all power supplies and discharge the refrigerant
completely before removal.
ASH-09AIR outdoor
Procedure Steps
1.Remove big handle
2. Remove top cover
top cover
big handle
Before disassamble
Remove 1 connection screw fixing big handleand then removethe big handle.
Remove 3 connection screws among top cover plate, front panel and right sideplate. Then remove top cover plate.
73
Page 72
Service Manual
3.Remove grille and front panel
4.Remove axial flow blade
5.Remove right side plate
Remove connection screws between the front grille and the front panel. Then remove the front grille. Remove connection screws connecting the front panel with the chassis and the motor support, and then remove the front panel.
Remove the nut fixing the blade and then remove the axial flow blade.
Remove connection screws connecting the right side plate with the valve support and the electric box. Then remove the right side plate.
Grille
Panel
Axial flow blade
Right side plate
Procedure Steps
74
Page 73
Service Manual
Remove the 2 screws fixing the cover of elec­tric box. Lift to remove the cover. Loosen the wire and disconnect the terminal. Lift to re­move the electric box assy.
6.Remove electric box assy
Electric box assy
Unscrew the fastening nut of the 4-way Valve Assy coil and remove the coil. Wrap the 4­way Valve Assy with wet cotton and unsolder the 4 weld spots connecting the 4-way Valve Assy to take it out.(Note: Refrigerant should be discharged firstly.) Welding process should be as quickly as possible and keep wrapping cotton wet all the time. Be sure not to burn out the lead-out wire of compressor.
7.Remove 4-way valve assy
8.Remove capillary sub-assy
Unsolder weld point of capillary Sub-assy, valve and outlet pipe of condensator. Then remove the capillary Sub-assy. Do not block the capillary when unsoldering it. (Note: be­fore unsoldering,discharge refrigerants completely)
4-way Valve Assy
Capillary Sub-assy
Procedure Steps
75
Page 74
Service Manual
Remove the 4 tapping screws fixing the motor. Pull out the lead-out wire and remove the motor. Remove the 2 tapping screws fixing the motor support. Lift motor support to re­move it.
9.Remove motor and motor support
Motor
Motor support
10.Remove clapboard sub-assy
Loosen the screws of the Clapboard Sub-Assy . The Clapboard Sub-Assy has a hook on the lower side. Lift and pull the Clapboard Sub-Assy to remove.
Clapboard Sub-Assy
Procedure Steps
76
Page 75
Service Manual
11.Remove Compressor
a Remove the 2 screws fixing the gas valve.
Unsolder the welding spot connecting gas valve and air return pipe and remove the gas valve. (Note: it is necessary to warp the gas valve when unsoldering the welding spot.) Remove the 2 screws fixing liquid valve. Unsolder the weld­ing spot connecting liquid valve and remove the liquid valve.
b Remove the 3 footing screws of the compressor
and remove the compressor.
Compressor
Gas valve
Liquid valve
Procedure Steps
77
Page 76
Service Manual
ASH-12AIR outdoor
Procedure
Steps
1. Before disassembly
3. Remove top cover
2. Remove big handle and valve cover
top cover
big handle
Remove the connection screw xing the big handle and then remove the valve cover.
Remove connection screws connecting the top panel with the front panel and the right side plate, and then remove the top panel.
valve cover
78
Page 77
Service Manual
Remove connection screws between the front grille and the front panel. Then remove the grille.
Remove connection screws connecting the front panel with the chassis and the motor support and then remove the front panel.
Remove connection screws connecting the right side plate with the valve support and the electric box. Then remove the right side plate.
Remove the nut on the blade and then remove the axial ow blade.
front panel
grille
ProcedureSteps
right side plate
axial ow blade
4. Remove grille
5. Remove front panel
6. Remove right side plate
7. Remove axial ow blade
79
Page 78
Service Manual
Remove the tapping screws xing the motor and disconnect the leading wire insert of the motor. Then remove the motor. Remove the tapping screws xing the motor support and lift the motor support to remove it.
Remove screws xing the electric box subassembly; loosen the wire bundle and unplug the wiring terminals. Then lift the
electric box to remove it.
Remove the screws xing the isolation sheet and then remove the isolation sheet.
Unsolder the welding joint connecting the capillary, valves and the outlet pipe of condenser to remove the capillary. Do not block the capillary with welding slag during unsoldering.
motor support
motor
Electric Box Assy
ProcedureSteps
isolation sheet
8. Remove motor and motor support
9. Remove Electric Box Assy
10. Remove isolation sheet
11. Remove compressor
liquid valve
gas valve
a
80
Page 79
Service Manual
ProcedureSteps
compressor
Remove the 2 screws xing the gas valve and unsolder the welding joint between the gas valve and the air-return pipe to remove the gas valve. (NOTE: Discharge the refrigerant completely before unsoldering; when unsoldering, wrap the gas valve with a wet cloth completely to avoid damage to the valve caused by high temperature). Remove the 2 screws xing the liquid valve and unsolder the welding joint connecting the liquid valve to the Y-type pipe to remove the liquid valve.
b
Unsolder pipes connecting with compressor.
c
Remove the 3 foot nuts on the compressor and then remove the compressor.
d
4-way valve
nuts
81
Page 80
Service Manual
Appendix:
1.Standard length of connection pipe
● 5m, 7.5m, 8m.
2.Min. length of connection pipe is 3m.
3.Max. length of connection pipe and max. high difference.
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each additional 5m of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Appendix 2: Conguration of Connection Pipe
Cooling capacity
Max length of
connection pipe
Max height
difference 5000 Btu/h(1465 W) 15 m 5 m 7000 Btu/h(2051 W) 15 m 5 m 9000 Btu/h(2637 W) 15 m 10 m
12000 Btu/h(3516 W) 20 m 10 m 18000 Btu/h(5274 W) 25 m 10 m 24000 Btu/h(7032 W) 25 m 10 m
28000 Btu/h(8204 W) 30 m 10 m 36000 Btu/h(10548 W) 30 m 20 m 42000 Btu/h(12306 W) 30 m 20 m 48000 Btu/h(14064 W) 30 m 20 m
Set temperature
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Ambient temperature
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
32/33 32 0 55/56 55.4 13 79/80 78.8 26 34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28 37/38 37.4 3 61/62 60.8 16 84/85 84.2 29 39/40 39.2 4 63 62.6 17 86/87 86 30 41/42 41 5 64/65 64.4 18 88/89 87.8 31 43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33 46/47 46.4 8 70/71 69.8 21 93/94 93.2 34 48/49 48.2 9 72 71.6 22 95/96 95 35 50/51 50 10 73/74 73.4 23 97/98 96.8 36 52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
61 60.8 16 69/70 69.8 21 78/79 78.8 26 62/63 62.6 17 71/72 71.6 22 80/81 80.6 27 64/65 64.4 18 73/74 73.4 23 82/83 82.4 28 66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(mm) Gas pipe(mm) Cooling only(g/m) Cooling and heating(g/m)
Ф6 Ф9.5 or Ф12 15 20
Ф6 or Ф9.5 Ф16 or Ф19 15 20
Ф12 Ф19 or Ф22.2 30 120 Ф16 Ф25.4 or Ф31.8 60 120 Ф19 / 250 250
Ф22.2 / 350 350
● When the length of connection pipe is above 5m, add refrigerant according to the prolonged length of liquid pipe. The additional refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter
82
Page 81
Service Manual
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the port again according to the steps above.
The length is equal
Improper expanding
leaning
damaged
surface
crack uneven
thickness
Smooth surface
Downwards
Pipe
Shaper
Union pipe
Pipe
Expander
Hard mold
Pipe
Pipe
Pipe cutter
Leaning Uneven Burr
Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps:
A:Cut the pip
● Conrm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
B:Remove the burrs
● Remove the burrs with shaper and prevent the burrs from getting into the pipe.
C:Put on suitable insulating pipe
D:Put on the union nut
● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe.
E:Expand the port
● Expand the port with expander.
● "A" is different according to the diameter, please refer to the sheet below:
Outer diameter(mm)
A(mm)
Max Min
Ф6 - 6.35 (1/4") 1.3 0.7
Ф9.52 (3/8”) 1.6 1.0 Ф12 - 12.70 (1/2”) 1.8 1.0 Ф16 - 15.88 (5/8”) 2.4 2.2
Appendix 3: Pipe Expanding Method
Note:
Note:
83
Page 82
Service Manual
Appendix 4: List of Resistance for Temperature Sensor
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units (15K)
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-19 138.1 20 18.75 59 3.848 98 1.071
-18 128.6 21 17.93 60 3.711 99 1.039
-17 121.6 22 17.14 61 3.579 100 1.009
-16 115 23 16.39 62 3.454 101 0.98
-15 108.7 24 15.68 63 3.333 102 0.952
-14 102.9 25 15 64 3.217 103 0.925
-13 97.4 26 14.36 65 3.105 104 0.898
-12 92.22 27 13.74 66 2.998 105 0.873
-11 87.35 28 13.16 67 2.896 106 0.848
-10 82.75 29 12.6 68 2.797 107 0.825
-9 78.43 30 12.07 69 2.702 108 0.802
-8 74.35 31 11.57 70 2.611 109 0.779
-7 70.5 32 11.09 71 2.523 110 0.758
-6 66.88 33 10.63 72 2.439 111 0.737
-5 63.46 34 10.2 73 2.358 112 0.717
-4 60.23 35 9.779 74 2.28 113 0.697
-3 57.18 36 9.382 75 2.206 114 0.678
-2 54.31 37 9.003 76 2.133 115 0.66
-1 51.59 38 8.642 77 2.064 116 0.642
0 49.02 39 8.297 78 1.997 117 0.625
1 46.6 40 7.967 79 1.933 118 0.608
2 44.31 41 7.653 80 1.871 119 0.592
3 42.14 42 7.352 81 1.811 120 0.577
4 40.09 43 7.065 82 1.754 121 0.561
5 38.15 44 6.791 83 1.699 122 0.547
6 36.32 45 6.529 84 1.645 123 0.532
7 34.58 46 6.278 85 1.594 124 0.519
8 32.94 47 6.038 86 1.544 125 0.505
9 31.38 48 5.809 87 1.497 126 0.492
10 29.9 49 5.589 88 1.451 127 0.48
11 28.51 50 5.379 89 1.408 128 0.467
12 27.18 51 5.197 90 1.363 129 0.456
13 25.92 52 4.986 91 1.322 130 0.444
14 24.73 53 4.802 92 1.282 131 0.433
15 23.6 54 4.625 93 1.244 132 0.422
16 22.53 55 4.456 94 1.207 133 0.412
17 21.51 56 4.294 95 1.171 134 0.401
18 20.54 57 4.139 96 1.136 135 0.391
19 19.63 58 3.99 97 1.103 136 0.382
84
Page 83
Service Manual
Resistance Table of Tube Temperature Sensors for Outdoor and Indoor (20K)
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-19 181.4 20 25.01 59 5.13 98 1.427
-18 171.4 21 23.9 60 4.948 99 1.386
-17 162.1 22 22.85 61 4.773 100 1.346
-16 153.3 23 21.85 62 4.605 101 1.307
-15 145 24 20.9 63 4.443 102 1.269
-14 137.2 25 20 64 4.289 103 1.233
-13 129.9 26 19.14 65 4.14 104 1.198
-12 123 27 18.13 66 3.998 105 1.164
-11 116.5 28 17.55 67 3.861 106 1.131
-10 110.3 29 16.8 68 3.729 107 1.099
-9 104.6 30 16.1 69 3.603 108 1.069
-8 99.13 31 15.43 70 3.481 109 1.039
-7 94 32 14.79 71 3.364 110 1.01
-6 89.17 33 14.18 72 3.252 111 0.983
-5 84.61 34 13.59 73 3.144 112 0.956
-4 80.31 35 13.04 74 3.04 113 0.93
-3 76.24 36 12.51 75 2.94 114 0.904
-2 72.41 37 12 76 2.844 115 0.88
-1 68.79 38 11.52 77 2.752 116 0.856
0 65.37 39 11.06 78 2.663 117 0.833
1 62.13 40 10.62 79 2.577 118 0.811
2 59.08 41 10.2 80 2.495 119 0.77
3 56.19 42 9.803 81 2.415 120 0.769
4 53.46 43 9.42 82 2.339 121 0.746
5 50.87 44 9.054 83 2.265 122 0.729
6 48.42 45 8.705 84 2.194 123 0.71
7 46.11 46 8.37 85 2.125 124 0.692
8 43.92 47 8.051 86 2.059 125 0.674
9 41.84 48 7.745 87 1.996 126 0.658
10 39.87 49 7.453 88 1.934 127 0.64
11 38.01 50 7.173 89 1.875 128 0.623
12 36.24 51 6.905 90 1.818 129 0.607
13 34.57 52 6.648 91 1.736 130 0.592
14 32.98 53 6.403 92 1.71 131 0.577
15 31.47 54 6.167 93 1.658 132 0.563
16 30.04 55 5.942 94 1.609 133 0.549
17 28.68 56 5.726 95 1.561 134 0.535
18 27.39 57 5.519 96 1.515 135 0.521
19 26.17 58 5.32 97 1.47 136 0.509
85
Page 84
Service Manual
Resistance Table of Discharge Temperature Sensor for Outdoor (50K)
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-29 853.5 10 98 49 18.34 88 4.75
-28 799.8 11 93.42 50 17.65 89 4.61
-27 750 12 89.07 51 16.99 90 4.47
-26 703.8 13 84.95 52 16.36 91 4.33
-25 660.8 14 81.05 53 15.75 92 4.20
-24 620.8 15 77.35 54 15.17 93 4.08
-23 580.6 16 73.83 55 14.62 94 3.96
-22 548.9 17 70.5 56 14.09 95 3.84
-21 516.6 18 67.34 57 13.58 96 3.73
-20 486.5 19 64.33 58 13.09 97 3.62
-19 458.3 20 61.48 59 12.62 98 3.51
-18 432 21 58.77 60 12.17 99 3.41
-17 407.4 22 56.19 61 11.74 100 3.32
-16 384.5 23 53.74 62 11.32 101 3.22
-15 362.9 24 51.41 63 10.93 102 3.13
-14 342.8 25 49.19 64 10.54 103 3.04
-13 323.9 26 47.08 65 10.18 104 2.96
-12 306.2 27 45.07 66 9.83 105 2.87
-11 289.6 28 43.16 67 9.49 106 2.79
-10 274 29 41.34 68 9.17 107 2.72
-9 259.3 30 39.61 69 8.85 108 2.64
-8 245.6 31 37.96 70 8.56 109 2.57
-7 232.6 32 36.38 71 8.27 110 2.50
-6 220.5 33 34.88 72 7.99 111 2.43
-5 209 34 33.45 73 7.73 112 2.37
-4 198.3 35 32.09 74 7.47 113 2.30
-3 199.1 36 30.79 75 7.22 114 2.24
-2 178.5 37 29.54 76 7.00 115 2.18
-1 169.5 38 28.36 77 6.76 116 2.12
0 161 39 27.23 78 6.54 117 2.07
1 153 40 26.15 79 6.33 118 2.02
2 145.4 41 25.11 80 6.13 119 1.96
3 138.3 42 24.13 81 5.93 120 1.91
4 131.5 43 23.19 82 5.75 121 1.86
5 125.1 44 22.29 83 5.57 122 1.82
6 119.1 45 21.43 84 5.39 123 1.77
7 113.4 46 20.6 85 5.22 124 1.73
8 108 47 19.81 86 5.06 125 1.68
9 102.8 48 19.06 87 4.90 126 1.64
86
Loading...