Under DRY mode, the range of temperature setting is 16°C~30°C and the initial value is 24°C.
2.1.3 Heating Mode
After setting to heating mode, the outdoor unit will st
art to calculate the system load demand. If
the load is “0”, all the other loads will not be put into operation. If the load is over “0”, the electronic
expansion valve will be firstly opened and then the outdoor fan is started. After 30 seconds, the
compressor is started, the 4-way valve is energized and the indoor fan runs under anti cold air
mode.
Under DRY mode, the range of temperature setting is 16°C~30°C and the ini
tial value is 20°C.
2.1.4 Fan Mode
When the indoor unit is set to fan mode, all the loads of the out
door unit will be stopped and the
indoor fan will run at preset speed. Under this mode, the fault is detected but will not be treated.
The temperature is not adjustable, displayed at 26°
C.
2.1.5 Auto Mode
Under this mode, the run mode will vary with the ambient temper
ature according to the following
conditions:
When T
amb.
˚26°C, the unit will run under cooling mode and the preset temperature is 26°C;
When 20°CT
amb.
26°C, the unit will run under DRY mode and the preset temperature is 24°C;
When T
amb.
˘20°C, the unit will run under heating mode and the preset temperature is 20°C.
When T
amb.
24°C, the unit will exit the heating mode. For cooling-only unit, when T
amb.
˘20°C,
the unit will run under fan mode and the preset temperature is 20. When T
amb.
24°C, the unit will
exit the fan mode.
Once the mode is activated, the unit will run
30 seconds the shortest before it switch the run
status under auto mode according to the ambient temperature.
2.2 Special Control Functions
2.2.1 Energy-saving Func
tion
Set a upper and lower limit of temperature by using manual controlle
r, so that the temperature of
air conditioner is set to an energy-saving range, thus to save the power consumption of the air
conditioner. For example, the temperature under cooling mode is defaulted 1630°C, but the
user may customize it to 2630°C by using manual controller. In this range, the lowest setting is
26°C other 16°C.
2.2.2 Memory Function
Upon re-energization after power shutdown or failure, the air conditioner can
memorize the last
work mode, temperature setting, fan speed and other parameters, so that it is not necessary to
repeat setting of those parameters. The user may also inactivate this function by using manual
controller.
2.2.3 Timer Function
For easy control of the air conditioner, the user may set the air conditione
r to timer on or timer off
by using the manual controller. The timer is available with two modes for user’s option, i.e.
countdown and 7-day time section.