Sinclair MV-H**BIF series, MV-H09BIF, MV-H12BIF, MV-H18BIF, MV-H24BIF Service Manual

Page 1
MULTI VARIABLE SERIES
WALL MOUNTED - FOCUS
MV-HxxBIF
SERVICE MANUAL
EN
Page 2
IMPO
RTANT N
OTE:
Read this manual ca
r
efully befo
r
e installing
or operating your new air conditioning unit. Make sure to save this manual for futu
re r
efe
r
ence.
Page 3
Service Manual
Table of Contents
Part
: Technical Information
.......................................................................1
1. Summary
......................................................................................................................1
2. Specications
..........................................................................................................2
2.1 Specication Sheet ...........................................................................................................2
2.2 Noise Criteria Curve Tables
...................................................................
3
3. Outline Dimension Diagram
........................................................................4
4. Refrigerant System Diagram
......................................................................5
5. Electrical Part
...........................................................................................................6
5.1 Wiring Diagram .................................................................................................................6
5.2 PCB Printed Diagram .......................................................................................................8
6. Function and Control
........................................................................................9
6.1 Remote Controller Introduction of YAN1F6(WiFi) ............................................................9
6.3 Ewpe Smart App Operation Manual
...............................................................................
15
6.4 Brief Description of Modes and Functions
......................................................................
16
Part
: Installation and Maintenance
.................................................
19
7. Notes for Installation and Maintenance
..........................................
19
8. Installation
................................................................................................................24
8.1 Installation Dimension Diagram
......................................................................................24
8.2 Installation Parts-checking
............................................................................................
26
8.3 Selection of Installation Location
....................................................................................
26
8.4 Requirements for electric connection
.............................................................................
26
8.5 Installation of Indoor Unit
................................................................................................
26
8.6 Check after Installation and Test operation
....................................................................
29
9. Maintenance
............................................................................................................
30
9.1 Error Code
......................................................................................................................
30
9.2 Maintenance Method for Normal Malfunction
.................................................................
39
10. Exploded View and Parts List
..............................................................41
11. Removal Procedure
.......................................................................................44
Appendix:
........................................................................................................................
49
Appendix 1: Reference Sheet of Celsius and Fahrenheit
....................................................
49
Appendix 2: Conguration of Connection Pipe
.....................................................................
49
Appendix 3: Pipe expanding method
....................................................................................
50
Appendix 4: List of Resistance for Temperature Sensor
......................................................
51
Page 4
1
Service Manual
1. Summary
Indoor Unit:
Part
: Technical Information
Remote Controller:
YAC1FB9(WiFi)
Page 5
3
Service Manual
2.2 Noise Criteria Curve Tables
Page 6
4
Service Manual
3. Outline Dimension Diagram
Unit:mm
Model W H D
09K 790 275 200 12K 845 289 209 18K 970 300 224 24K 1078 325 246
W
12K
09K
D
H
90
150
54
168.5 462 159.5
Φ55
Φ55
54
123.5542 179.5
83.2
124.7
35
Φ55
Φ55
35
18K
104 685 181
140
190
38
Φ55
Φ55
38
24K
79
154
43
206 685 187
Φ70
Φ70
43
Page 7
5
Service Manual
4. Refrigerant System Diagram
outdoor
indoor
D1
C
1
B1
A
1
filter
A heat exchanger
gas -liquid separator
inverter compressor
discharge silencer
discharge temperature sensor
SP
4-way valve
outdoor heat exchanger
fan
high pressure switch
B heat exchanger
C heat exchanger
D heat exchanger
filter
filter
filter
filter
C2
C3
D3
D2
B3
B2
A2
A3
A1:A
unit electronic expansion valve B1:B-unit electronic expansion valve C1:C-unit electronic expansion valve D1:D-unit electronic expansion valve A2:A-unit gas pipe temperature sensor B2:B-unit gas pipe temperature sensor C2:C-unit gas pipe temperature sensor D2:D-unit gas pipe temperature sensor A3:A
unit liquid pipe temperature sensor B3:B-unit liquid pipe temperature sensor C3:C-unit liquid pipe temperature sensor D3:D-unit liquid pipe temperature sensor
Page 8
6
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Indoor Unit
● Instruction
Symbol Symbol Color Symbol Symbol Color Symbol Name
WH White GN Green CAP Jumper cap
YE Yellow BN Brown COMP Compressor
RD Red BU Blue Grounding wire
YEGN Yellow/Green BK Black / /
VT Violet OG Orange / /
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
09K
Page 9
Service Manual
60000700068804
287'22581,7
76(1625
7(03
6(1625
7(03
6(1625
57
5220
78%(
57
:,),
:,),
5(&(,9(5$1'
',63/$<%2$5'
$3
',63 ',63
6:,1*8'
0
83'2:1
02725
67(33,1*
6:,1*/5
67(33,1*
02725
/()75,*+7
0
+($/7+/ +($/7+1
%8
5'
&2/'3/$60$
*(1(5$725
35,17('&,5&8,7%2$5'
$3
-803
&$3
%1
<(*1
;7
3(
(9$325$725
%/2&.
7(50,1$/
%.
%8
%.
%8
1
$&/
&20287
%1
&11(&7,1*
&$%/(
<(*1
/
0
)$102725
3* 3*)
1
/
5,1*
0$*1(7,&
$3
02'8/(
&200$18$/
$3
:,5('
&21752//(5
'5<&
'225&
237,21$/
'5<&217$&7
$3
12/18/24K
Page 10
8
Service Manual
5.2 PCB Printed Diagram
Top view
No Name
1
Interface of communication wire for
indoor unit and outdoor unit 2
3
Interface of live wire
Fuse
Interface of health function neutral
wir
e
4
Interface of neutral wire
5
Interface of fan
6
Interface of health function live wire
7 8
Auto butto
n
Interface of WIF
I
9
Up&down swing interface
Interface of PG feedbac
k
10
11
12
Needle stand for tube temperature
sensor
13
Display interface
14
Jum
p
15
15
17
16
11
12
18
14
13
45 6 8910
● Bottom view
1
2
3
7
Interface of left&right swing
16
Terminal of live wire used for
outdoor unit power supply
17
Terminal of gate control function
18
Terminal of Wired controller
Page 11
9
Service Manual
Set fan speed
Send signal
Turbo mode
8ć heating function Set temperature
Set time
X-FAN function
TIMER ON/TIMER OFF
Child lock Up & down swing Left & right swing
Light
Temp. display type
:Set temp.
:Outdoor ambient temp.
:Indoor ambient temp.
Sleep mode
Clock
Heat mode
Fan mode
Dry mode
Cool mode
Auto mode
Operation mode
I feel
Healthy mode Scavenging functions
Quiet
WiFi
This is a general remote controller.Some
models have this function while some do not. Please refer to the actual models.
{
6
3
7
9
11
13
15
12
14
16
10
8
5
4
2
1
1 ON/OFF button
2 MODE button
3 FAN button
4 TURBO button
6 button
7 button
9 I FEEL button
14 LIGHT button
15 button
16 TEMP button
11 CLOCK button
12 QUIET button
13
WiFi button
10 TIMER ON / TIMER OFF button
8 SLEEP button
5 ▲/ button
This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
After putting through the power, the air conditioner will give out a sound. Operation indicator " " is ON (red indicator,the colour is different for different models). After that, you can operate the air conditioner by using remote controller.
Under on status, pressing the button on the remote controller, the signal icon " " on the display of remote controller will blink once and the air conditioner will give out a “di” sound, which means the signal has been sent to the air conditioner.
●As for the models with functions of WiFi or wired controller, the indoor unit must has been controlled by standard remote controller under auto mode first,and then the function of adjustable temperature under auto mode can be realized by APP or the wired controller.
●This remote controller can adjust the temperature under auto mode. When matching with the unit which is without the function of adjustable temperature under auto mode, the set temperature under auto mode may be invalid, or the displayed set temperature on the unit is not same as that on the remote controller under auto mode.
6. Function and Control
6.1 Remote Controller Introduction
Page 12
10
Service Manual
Press this button to turn on the unit. Press this button again to turn off the unit.
It’s Low fan speed under Dry mode.
X-FAN function Hold fan speed button for 2s in COOL or DRY mode, the icon “ ” is displayed and the indoor fan will continue operation for a few minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is defaulted. X-FAN is not available in AUTO, FAN or HEAT mode.
This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould.
Having set X-FAN function on: After turning off the unit by pressing ON/OFF button indoor fan will continue running for a few minutes. at low speed. In this period, Hold fan speed button for 2s to stop indoor fan directly.
Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
(This indicator is not
(This indicator
Operation indicator is ON.
available for some models).
(This indicator is not
available for some models).
is not available for some models).
Fan speed: auto, low speed, low-medium speed,medium speed,
medium-high speed,high speed.
Under auto mode, temperature can be displayed;Under auto mode,set temperature can be adjusted.
This button is used for setting Fan Speed in the sequence that goes from AUTO,
,
to
,,
,
then back to Auto.
Low-Medium speed
Medium-High speed
Medium speed
High speed
Auto
Low speed
Page 13
11
Service Manual
When I FEEL function is turned on, the remote controller should be put within the area where indoor unit can receive the signal sent by the remote controller.
● The function is only available for some mode
● Press this button, can select Sleep 1 ( ), Sleep 2 ( ), Sleep 3 ( ) and cancel the Sleep, circulate between these, after electrified, Sleep Cancel is defaulted.Sleep 1 is Sleep mode 1, in Cool modes; sleep status after run for one hour, the main unit setting temperature will increase 1 , two hours, setting temperature increased 2 , then the unit will run at this setting temperature; In Heat mode: sleep status after run for one hour, the setting temperature will decrease 1 , two hours, setting temperature will decrease 2 , then the unit will run at this setting temperature.
● Sleep 2 is sleep mode 2, that is air conditioner will run according to the presetting a group of sleep temperature curve.
● Sleep 3-the sleep curve setting under Sleep mode by DIY; (1)Under Sleep 3 mode, press “Turbo” button for a long time, remote controller enters into user individuation sleep setting status, at this time, the time of remote controller will display “1hour”, the setting temperature “88” will display the corresponding temperature of last setting sleep curve and blink (The first entering will display according to the initial curve setting value of original factory); (2)Adjust "▲" and " "▲ button, could change the corresponding setting temperature, after adjusted, press “Turbo” button for confirmation; (3) At this time, 1hour will be automatically increased at the timer postion on the remote control, (that are "2hours" or "3hours" or "8hours"), the place of setting temperature "88"will display the corresponding temperature of last setting sleep curve and blink; (4) Repeat the above step (2)~(3) operation, until 8 hours temperature setting finished, sleep,curve setting finished, at this time, the remote controller will resume the original imer display; temperature display will resume to original setting temperature.
● Sleep3- the sleep curve setting under Sleep mode by DIY could be inquired: The user could accord to sleep curve setting method to inquire the presetting sleep curve, enter into user individuation sleep setting status, but do not change the temperature,press “Turbo” button directly fo
r
confirmation. Note: In the above presetting or enquiry procedure, if continuously within 10s, there is no button pressed, the sleep curve setting within 10s, there is no button pressed, the sleep curve setting status will be automatically quit and resume to display the original displaying. In the presetting or enquiry procedure, press "ON/OFF" button, "Mode" button, "Timer" button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
123
Page 14
12
Service Manual
13.WiFi button
This function is only available for some models.
This function is applicable to partial of models.
Press " WiFi " button to turn on or turn off WiFi function. When WiFi function is turned on, the " WiFi " icon will be displayed on remote controller; Under status of unit off, press "MODE" and " WiFi " buttons simultaneously for 1s, WiFi module will restore to factory default setting.
● The Quiet function can be set up in all modes; Under the Quiet mode,the fan speed is not available.
● The Quiet function is only available for some models.
● When quiet function is selected Under cooling mode: indoor fan operates at notch 4 speed. 10 minutes later or when indoor ambient temperature≤28
, indoor fan will operate
at notch 2 speed or quiet mode according to the comparison between indoor ambinet temperature and set temperature. Under heating mode: indoor fan operates at notch 3 speed or quiet mode according to the comparison between indoor ambient temp
erature and set temperature. Under dry
, fan mode: indoor fan operates at quiet mode.
Under auto mode: the indoor fan operates at the auto quiet mode according to actual cooling, heating or fan mode.
Page 15
13
Service Manual
13.WiFi button
This function is only available for some models.
This function is applicable to partial of models.
Press " WiFi " button to turn on or turn off WiFi function. When WiFi function is turned on, the " WiFi " icon will be displayed on remote controller; Under status of unit off, press "MODE" and " WiFi " buttons simultaneously for 1s, WiFi module will restore to factory default setting.
The Quiet function can be set up in all modes; Under the Quiet mode,the fan speed is not available.
The Quiet function is only available for some models.
● When quiet function is selected Under cooling mode: indoor fan operates at notch 4 speed. 10 minutes later or when indoor ambient temperature≤28, indoor fan will operate at notch 2 speed or quiet mode according to the comparison between indoor ambinet temperature and set temperature. Under heating mode: indoor fan operates at notch 3 speed or quiet mode according to the comparison between indoor ambient temperature and set temperature. Under dry, fan mode: indoor fan operates at quiet mode. Under auto mode: the indoor fan operates at the auto quiet mode according to actual cooling, heating or fan mode.
Page 16
14
Service Manual
Page 17
15
Service Manual
Control Flow Chart
Download and installation
Operating Systems
Requirement for Users smart phone:
Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed, register the account and add the device to achieve long-distance control and LAN control of smart home appliances. For more information, please refer to "Help" in App.
6.3 Ewpe Smart App Operation Manual
iOS system
Support iOS7.0 and above version
Android system
Support Android 4.4
and
above version
App Download Linkage
Internet
Cellular/
Other Wi-FI
Home Wi-Fi
Home wireless router
Home Wi-Fi
Cloud
APP
intelligent
home
appliances
Page 18
16
Service Manual
6.4 Brief Description of Modes and Functions
1.Basic function of system
(1)Cooling mode
(1) Under this mode, fan and swing operates at setting status. Temperature setting range is 16~30OC.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(2)Drying mode
(1) Under this mode, fan operates at low speed and swing operates at setting status. Temperature setting range is 16~30OC.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(3) Protection status is same as that under cooling mode.
(4) Sleep function is not available for drying mode.
(3)Heating mode
(1) Under this mode, Temperature setting range is 16~30OC.
(2) Working condition and process for heating mode:
When turn on the unit under heating mode, indoor unit enters into cold air prevention status. When the unit is stopped or at OFF status,
and indoor unit has been started up just now, the unit enters into residual heat-blowing status.
(4)Working method for AUTO mode:
1.Working condition and process for AUTO mode:
a.Under AUTO mode, standard heating Tpreset=20OC and standard cooling Tpreset=25OC. The unit will switch mode automatically
according to ambient temperature.
2.Protection function
a. During cooling operation, protection function is same as that under cooling mode.
b. During heating operation, protection function is same as that under heating mode.
3. Display: Set temperature is the set value under each condition. Ambient temperature is (Tamb.-Tcompensation) for heat pump unit
and Tamb. for cooling only unit.
4. If there’s I feel function, Tcompensation is 0. Others are same as above.
(5)Fan mode
Under this mode, indoor fan operates at set fan speed. Compressor, outdoor fan, 4-way valve and electric heating tube stop operation.
Indoor fan can select to operate at high, medium, low or auto fan speed. T
emperature setting range is 16~30OC.
2. Other control
(1) Buzzer
Upon energization or availably operating the unit or remote controller, the buzzer will give out a beep.
(2) Auto button
If press this auto button when turning off the unit, the complete unit will operate at auto mode. Indoor fan operates at auto fan speed
and swing function is turned on. Press this auto button at ON status to turn off the unit.
(3) Auto fan
Heating mode: During auto heating mode or normal heating ode, auto fan speed will adjust the fan speed automatically according to
ambient temperature and set temperature.
(4) Sleep
After setting sleep function for a period of time, system will adjust set temperature automatically.
(5) Timer function:
General timer and clock timer functions are compatible by equipping remote controller with different functions.
(6) Memory function
memorize compensation temperature, off-peak energization value.
Memory content: mode, up&down swing, light, set temperature, set fan speed, general timer (clock timer can’t be memorized).
After power recovery, the unit will be turned on automatically according to memory content.
(7) Health function
During operation of indoor fan, set health function by remote controller. Turn off the unit will also turn off health function.
Turn on the unit by pressing auto button, and the health is defaulted ON.
Page 19
17
Service Manual
(8)I feel control mode
After controller received I feel control signal and ambient temperature sent by remote controller, controller will work according to the ambient
temperature sent by remote controller.
(9)Compulsory defrosting function
(1) Start up compulsory defrosting function
Under ON status, set heating mode with remote controller and adjust the temperature to 16OC. Press “+, -, +, -, +,-” button successively
within 5s and the complete unit will enter into compulsory defrosting status. Meanwhile, heating indicator on indoor unit will ON 10s and OFF
0.5s successively. (Note: If complete unit has malfunction or stops operation due to protection, compulsory defrosting function can be started
up after malfunction or protection is resumed.
(2)Exit compulsory defrosting mode
After compulsory defrosting is started up, the complete unit will exit defrosting operation according to the actual defrosting result, and the
complete unit will resume normal heating operation.
(10)Refrigerant recovery function (applicable for moving the unit or maintaining the unit)
(1) Start up refrigerant recovery function
Set cooling mode with remote controller within 5min after energization, adjust temperature at 16OC and press light button on remote
controller for 3 times successively to any one indoor unit within 3s and then the complete unit will enter into refrigerant recovery status. All
indoor units display Fo. Maintenance person close all liquid valves. After 5min, withstand the thimble of all checking valves with tools one by
one. If there’s no refrigerant spraying out, close corresponding valve immediately, turn off the unit with remote controller and then remove the
connection pipe.
(2) Exit refrigerant recovery function
During refrigerant recovery process, if any one indoor unit receives any remote control signal or refrigerant recovery function has operates
for about 25min, refrigerant recovery function will be exited automatically. If the complete unit is at standby status before refrigerant recovery,
the complete unit will still at standby status after refrigerant recovery. If the complete unit is at ON status, the unit will operate according to
original operation mode.
(11)Ambient temperature display control mode
1. When user set the remote controller to display set temperature (corresponding remote control code: 01), current set temperature will be
displayed.
2. Only when remote control signal is switched to indoor ambient temperature display status (corresponding remote control code: 10) from
other display status (corresponding remote control code: 00, 01,11),controller will display indoor ambient temperature for 3s and then turn
back to display set temperature.
Under this mode, indoor fan operates at set fan speed. Compressor, outdoor fan, 4-way valve and electric heating tube stop operation.
Indoor fan can select to operate at high, medium, low or auto fan speed. T
emperature setting range is 16~30OC.
(12)Off-peak energization function
Adjust compressor’s minimum stop time. The original minimum stop time is 180s and then we change to:
The time interval between two start-ups of compressor can’t be less than 180+T s(0≤T≤15). T is the variable of controller. That’s to say
the minimum stop time of compressor is 180s~195s. Read-in T into memory chip when refurbish the memory chip each time. After power
recovery, compressor can only be started up after 180+T s at least.
(13) SE control mode
The unit operates at SE status.
(14) X-fan mode
When X-fan function is turned on, after turn off the unit, indoor fan will still operate at low speed for 2min and then the complete unit will be
turned off. When x-fan function is turned off, after turn off the unit, the complete unit will be turned off directly.
(15) 8º heating function
Under heating mode, you can set 8º heating function by remote controller. The system will operate at 8ºset temperature.
(16)Turbo function
Turbo function can be set under cooling and heating modes. Press Fan Speed button to cancel turbo setting. Turbo function is not available under auto, drying and fan modes.
(17)Mode shock
When there’s indoor unit under operation, if start up other indoor unit and the setting mode is inconsistent with that indoor unit, mode shock
will occur. The indoor with mode shock displays “E7” and indoor fan stops operation. Corresponding relationship for mode shock and
operation status after shock is as below:
Page 20
18
Service Manual
Mode relationship table for mode shock:
Mode Indoor unit with
mode shock
Operation status after mode shock
Indoor unit A Indoor unit B Indoor unit A Indoor unit B Cooling/drying heating Indoor unit B Cooling/drying Indoor fan stops operation
Heating Cooling, drying, fan Indoor unit B Heating Indoor fan stops operation Fan Heating Indoor unit A Indoor fan stops operation Heating
Note: (1) Indoor unit A: The indoor unit under operation currently
(2) Indoor unit B: The indoor unit is tuned on latter
(3) If set auto mode with remote controller, the complete unit will judge according to actual operation mode under auto mode.
Page 21
19
Service Manual
1. Select the installation location according to the require­ment of this manual.(See the requirements in installation part)
2. Handle unit transportation with care; the unit should not be carried by only one person if it is more than 20kg.
3. When installing the indoor unit and outdoor unit, a suf­cient xing bolt must be installed; make sure the installation support is rm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components dur­ing installation.
6. Make sure no foreign objects are left in the unit after n­ishing installation.
Electrical Safety Precautions:
7. Notes for Installation and Maintenance
Safety Precautions: Important!
Please read the safety precautions carefully before installation and maintenance. The following contents are very important for installation and maintenance.
Please follow the instructions below.
●The installation or maintenance must accord with the
instructions.
●Comply with all national electrical codes and local
electrical codes.
●Pay attention to the warnings and cautions in this
manual.
●All installation and maintenance shall be performed by distributor or qualied person.
●All electric work must be performed by a licensed
technician according to local regulations and the instructions given in this manual.
●Be caution during installation and maintenance. Prohibit
incorrect operation to prevent electric shock, casualty and other accidents.
1. Cut off the power supply of air conditioner before checking and maintenance.
2. The air condition must apply specialized circuit and prohibit share the same circuit with other appliances.
3. The air conditioner should be installed in suitable location and ensure the power plug is touchable.
4. Make sure each wiring terminal is connected firmly during installation and maintenance.
5. Have the unit adequately grounded. The grounding wire can’t be used for other purposes.
6. Must apply protective accessories such as protective boards, cable-cross loop and wire clip.
7. The live wire, neutral wire and grounding wire of power supply must be corresponding to the live wire, neutral wire and grounding wire of the air conditioner.
8. The power cord and power connection wires can’t be pressed by hard objects.
9. If power cord or connection wire is broken, it must be
replaced by a qualied person.
1. Avoid contact between refrigerant and re as it generates
poisonous gas; Prohibit prolong the connection pipe by welding.
2. Apply specied refrigerant only. Never have it mixed with
any other refrigerant. Never have air remain in the refrigerant line as it may lead to rupture or other hazards.
3. Make sure no refrigerant gas is leaking out when installation is completed.
4. If there is refrigerant leakage, please take sufficient measure to minimize the density of refrigerant.
5. Never touch the refrigerant piping or compressor without wearing glove to avoid scald or frostbite.
Warnings
Refrigerant Safety Precautions:
Improper installation may lead to re hazard, explosion,
electric shock or injury.
Installation Safety Precautions:
Part
: Installation and Maintenance
10. If the power cord or connection wire is not long enough, please get the specialized power cord or connection wire from the manufacture or distributor. Prohibit prolong the wire by yourself.
11. For the air conditioner without plug, an air switch must be installed in the circuit. The air switch should be all-pole parting and the contact parting distance should be more than 3mm.
12. Make sure all wires and pipes are connected properly and the valves are opened before energizing.
13. Check if there is electric leakage on the unit body. If yes, please eliminate the electric leakage.
14. Replace the fuse with a new one of the same specication
if it is burnt down; don’t replace it with a cooper wire or conducting wire.
15. If the unit is to be installed in a humid place, the circuit breaker must be installed.
Page 22
20
Service Manual
Safety Precautions for Installing and Relocating the Unit:
Warnings
To ensure safety, please be mindful of the following precautions.
1. When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the
specied refrigerant.
Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in injury.
2.When installing or moving this unit, do not charge the refrigerant which is not comply with that on the nameplate or
unqualied refrigerant.
Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even series safety accident.
3.When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling mode.Then, fully close the valve at high pressure side (liquid valve).About 30-40 seconds later, fully close the valve at low pressure side (gas valve), immediately stop the unit and disconnect power. Please note that the time for refrigerant recovery should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury.
4.During refrigerant recovery, make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection pipe.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury.
5.When installing the unit, make sure that connection pipe is securely connected before the compressor starts running.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury.
6.Prohibit installing the unit at the place where there may be leaked corrosive gas or ammable gas.
If there leaked gas around the unit, it may cause explosion and other accidents.
7.Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service center authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or re.
8.Use the specied types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so
that their terminals receive no external stresses.
Electric wires with insufcient capacity, wrong wire connections and insecure wire terminals may cause electric shock or re.
Safety Precautions for Refrigerant
●To realize the function of the air conditioner unit, a special refrigerant circulates in the system. The used refrigerant is the uoride R32,which is specially cleaned. The refrigerant is ammable and inodorous. Furthermore, it can leads to explosion under certain conditions. But the ammability of the refrigerant is very low. It can be ignited only by re.
●Compared to common refrigerants, R32 is a nonpolluting refrigerant with no harm to the ozonosphere. The inuence upon
the greenhouse effect is also lower. R32 has got very good thermodynamic features which lead to a really high energy
efciency. The units therefore need a less lling.
WARNING:
●Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture. Should repair be necessary,contact your nearest authorized Service Centre. Any repairs carried out by unqualied
personnel may be dangerous. The appliance shall be stored in a room without continuously operating ignition sources. (for
example:open ames , an operating gas appliance or an operating electric heater.)
●Do not pierce or burn.
●Appliance shall be installed, operated and stored in a room with a oor area larger than 4m (or 6m ).
●Appliance lled with ammable gas R32. For repairs, strictly follow manufacturer’
s instructions only.Be aware that
refrigrants not contain odour.
●Read specialist’s manual.
Page 23
21
Service Manual
Safety Operation of Flammable Refrigerant
Qualication requirement for installation and maintenance man
●All the work men who are engaging in the refrigeration system should bear the valid certication awarded by the authoritative organization and the qualication for dealing with the refrigeration system recognized by this industry. If it needs other technician to maintain and repair the appliance, they should be supervised by the person who bears the qualication for using the ammable refrigerant.
●It can only be repaired by the method suggested by the equipment’s manufacturer
.
Installation notes
●The air conditioner is not allowed to use in a room that has running re (such as re source,working coal gas ware,
operating heater).
●It is not allowed to drill hole or burn the connection pipe.
●The air conditioner must be installed in a room that is larger than the minimum room area.
The minimum room area is shown on the nameplate or following table a.
●Leak test is a must after installation.
table a - Minimum room area(m
2
)
Maintenance notes
●Check whether the maintenance area or the room area meet the requirement of the nameplate.
— It’s only allowed to be operated in the rooms that meet the requirement of the nameplate.
●Check whether the maintenance area is well-ventilated.
— The continuous ventilation status should be kept during the operation process.
●Check whether there is re source or potential re source in the maintenance area. — The naked ame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged.
●Check whether the appliance mark is in good condition.
— Replace the vague or damaged warning mark.
Welding
●If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below:
a. Shut down the unit and cut power supply b. Eliminate the refrigerant c. Vacuuming d. Clean it with N2 gas e. Cutting or welding f. Carry back to the service spot for welding
●Make sure that there isn’t any naked ame near the outlet of the vacuum pump and it’s well-ventilated.
●The refrigerant should be recycled into the specialized storage tank.
Filling the refrigerant
●Use the refrigerant lling appliances specialized for R32. Make sure that different kinds of refrigerant won’t contaminate with
each other.
●The refrigerant tank should be kept upright at the time of lling refrigerant.
●Stick the label on the system after lling is nished (or haven’t nished).
●Don’t overlling.
●After lling is nished, please do the leakage detection before test running; another time of leak detection should be done
when it’s removed.
Safety instructions for transportation and storage
●Please use the ammable gas detector to check before unload and open the container.
●No re source and smoking.
●According to the local rules and laws.
Page 24
22
Service Manual
●When installing or relocating the unit, be sure to keep the
refrigerant circuit free from air or substances other than the specied
refrigerant.
Any presence of air or other foreign substance in the refrigerant
circuit will cause system pressure rise or compressor rupture,
resulting in injury.
●When installing or moving this unit, do not charge the refrigerant
which is not comply with that on the nameplate or unqualified
refrigerant.Otherwise, it may cause abnormal operation, wrong
action, mechanical malfunction or even series safety accident.
●When refrigerant needs to be recovered during relocating or
repairing the unit, be sure that the unit is running in cooling mode.
Then, fully close the valve at high pressure side (liquid valve).About
30-40 seconds later, fully close the valve at low pressure side (gas
valve), immediately stop the unit and disconnect power. Please note
that the time for refrigerant recovery should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in and
cause pressure rise or compressor rupture, resulting in injury.
●During refrigerant recovery, make sure that liquid valve and gas
valve are fully closed and power is disconnected before detaching
the connection pipe.
If compressor starts running when stop valve is open and connection
pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
●When installing the unit, make sure that connection pipe is securely
connected before the compressor starts running.
If compressor starts running when stop valve is open and connection
pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
●Prohibit installing the unit at the place where there may be leaked
corrosive gas or ammable gas.
If there leaked gas around the unit, it may cause explosion and other
accidents.
●Do not use extension cords for electrical connections. If the electric
wire is not long enough, please contact a local service center
authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or re.
●Use the specied types of wires for electrical connections between
the indoor and outdoor units. Firmly clamp the wires so that their
terminals receive no external stresses.
Electric wires with insufcient capacity, wrong wire connections and
insecure wire terminals may cause electric shock or re.
To ensure safety, please be mindful of the following precautions.
Page 25
23
Service Manual
Main Tools for Installation and Maintenance
1. Level meter, measuring tape
4. Electroprobe
7. Electronic leakage detector
10. Pipe pliers, pipe cutter
2. Screw driver
5. Universal meter
8. Vacuum pump
11. Pipe expander, pipe bender
3. Impact drill, drill head, electric drill
6. Torque wrench, open-end wrench, inner hexagon spanner
9. Pressure meter
12. Soldering appliance, refrigerant container
Page 26
24
Service Manual
8. Installation
8.1 Installation Dimension Diagram
Drainagepipe
At least250cm
At least 15cm
At least 300cm
Spacetothe
Spacetothe ceiling
Space to the obstruction
At least15cm
At least 15cm
Spacetothe wall
Space to the wall
Page 27
25
Service Manual
Preparation before installation
Prepare tools
Read the requirements for electric connection
select installation location
Select indoor unit installation location
Install wall-mounting frame, drill wall holes
Connect pipes of indoor unit and drainage pipe
Connect wires of indoor unit
Connect wires of outdoor unit
Bind up pipes and hang the indoor unit
Make the bound pipes pass through the wall hole and then connect outdoor unit
Neaten the pipes
Vacuum pumping and leakage detection
Check after installation and test operation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
Select outdoor unit installation location
Install the support of outdoor unit (select it according to the actual situation)
Install drainage joint of outdoor unit (only for cooling and heating unit)
Connect pipes of outdoor unit
Start installation
Fix outdoor unit
Installation procedures
Page 28
26
Service Manual
No. Name No. Name
1 Indoor unit 8 Sealing gum 2 Outdoor unit 9 Wrapping tape
3 Connection pipe 10
Support of outdoor unit
4 Drainage pipe 11 Fixing screw
5
Wall-mounting frame
12
Drainage plug(cooling
and heating unit)
6
Connecting cable(power cord)
13
Owner’s manual,
remote controller
7 Wall pipe
1. Safety Precaution
(1) Must follow the electric safety regulations when installing the unit. (2) According to the local safety regulations, use qualified power supply circuit and air switch. (3) Make sure the power supply matches with the requirement
of air conditioner. Unstable power supply or incorrect wiring
may result in electric shock,re hazard or malfunction. Please install proper power supply cables before using the air
conditioner.
(4) Properly connect the live wire, neutral wire and grounding wire of power socket. (5) Be sure to cut off the power supply before proceeding any work related to electricity and safety. (6) Do not put through the power before nishing installation. (7) For appliances with type Y attachment,the instructions shall contain the substance of thefollowing.If the supply cord is damaged,it must be replaced by the manufacturer,its service agent or similarly qualied persons in order to avoid a hazard. (8) The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube. (9) The appliance shall be installed in accordance with national
wiring regulations.
8.2 Installation Parts-checking
8.3 Selection of Installation Location
8.4 Requirements for electric connection
8.5 Installation of Indoor Unit
1.Please contact the local agent for installation.
2.Don't use unqualied power cord.
1. Basic Requirement:
Installing the unit in the following places may cause malfunction. If it is unavoidable, please consult the local dealer: (1) The place with strong heat sources, vapors, ammable or explosive gas, or volatile objects spread in the air. (2) The place with high-frequency devices (such as welding machine, medical equipment). (3) The place near coast area. (4) The place with oil or fumes in the air. (5) The place with sulfureted gas. (6) Other places with special circumstances. (7) Do not use the unit in the immediate surroundings of a laundry a bath a shower or a swimming pool.
2. Grounding Requirement:
(1) The air conditioner is rst class electric appliance. It must be properly grounding with specialized grounding device by a professional. Please make sure it is always grounded effectively, otherwise it may cause electric shock. (2) The yellow-green wire in air conditioner is grounding wire, which can't be used for other purposes. (3) The grounding resistance should comply with national
electric safety regulations.
(4) The appliance must be positioned so that the plug is
accessible.
(5) An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in xed wiring.
1. Choosing Installation Iocation
Recommend the installation location to the client and then conrm it with the client.
2. Install Wall-mounting Frame
(1) Hang the wall-mounting frame on the wall; adjust it in horizontal position with the level meter and then point out the screw xing holes on the wall. (2) Drill the screw xing holes on the wall with impact drill (the specification of drill head should be the same as the plastic expansion particle) and then ll the plastic expansion particles
2. Indoor Unit:
(1) There should be no obstruction near air inlet and air outlet. (2) Select a location where the condensation water can be dispersed easily andwon't affect other people. (3) Select a location which is convenient to connect the outdoor unit and near the power socket. (4) Select a location which is out of reach for children.
(5)
The location should be able to withstand
the weight of
indoor unit and won't increase noise and vibration. (6)
The appliance must be installed 2.5m above oor.
(7) Don't install the indoor unit right above the electric
appliance.
(8) Please try your best to keep way from uorescent lamp.
Note:
in the holes. (3) Fix the wall-mounting frame on the wall with tapping screws (ST4.2X25TA) and then check if the frame is rmly installed by pulling the frame. If the plastic expansion particle is loose, please drill another xing hole nearby.
Please notice that the unit is lled with ammable gas R32. Inappropriate treatment of the unit involves the risk of severe damages of people and material. Details to this refrigerant are found in chapter “refrigerant”.
Page 29
27
Service Manual
Left
Rear left
Right
Rear right
Cut off the hole
Left Right
5-10
°
Φ55mm
Indoor
Outdoor
(1) Pay attention to dust prevention and take relevant safety measures when opening the hole. (2) The plastic expansion particles are not provided and should be bought locally.
Fig.1
Fig.2
Fig.3
Fig.4
3. Install Wall-mounting Frame
(1) Choose the position of piping hole according to the direction of outlet pipe. The position of piping hole should be a little lower than the wall-mounted frame.(As show in Fig.1)
4. Outlet Pipe
(1)
The pipe can be led out in the direction of right, rear right, left or rear left.(As show in Fig.3) (2) When selecting leading out the pipe from left or right, please cut off the corresponding hole on the bottom case.(As show
in
Fig.4)
(2) Open a piping hole with the diameter of Φ55mm on the selected outlet pipe position.In order to drain smoothly, slant the piping hole on the wall slightly downward to the outdoor side with the gradient of 5-10°.(As show in Fig.2)
Note:
Insulating pip
e
Torque wrenc
h
Open-end
wrench
Indoor pipe
Pipe
Union nut
Union nutPipe joint
Pipe
Hex nut diameter(mm) Tightening torque(N m)
Φ6 15~20
Φ9.52 30~40
Φ12 45~55 Φ16 60~65 Φ19 70~75
Refer to the following table for wrench moment of force
:
Fig.5 Fig.6
Fig.7
5. Connect the Pipe of Indoor Unit
(1) Aim the pipe joint at the corresponding bellmouth.(As show
in Fig.5)
(2) Pretightening the union nut with hand. (3) Adjust the torque force by referring to the following sheet. Place the open-end wrench on the pipe joint and place the torque wrench on the union nut. Tighten the union nut with torque wrench.(As show in Fig.6) (4) Wrap the indoor pipe and joint of connection pipe with insulating pipe, and then wrap it with tape.(As show in Fig.7)
6. Install Drain Hose
(1) Connect the drain hose to the outlet pipe of indoor unit.(As show in Fig.8) (2) Bind the joint with tape.(As show in Fig.9)
Left
Wall
Φ55mm
Right
Mark in the middle of it
Level meter
Rear piping hole
Wall
Space
to the
wall
above
150mm
Space
to the
wall
above
150mm
Φ55mm
Rear piping hole
.
Outlet pipe
Drain hos
e
Drain hose
Tape
Outlet pipe
Drain hose
Insulating pip
e
(1) Add insulating pipe in the indoor drain hose in order to
prevent condensation.
(2) The plastic expansion particles are not provided. (As show in Fig.10)
Fig.8
Fig.9
Fig.10
Note:
Page 30
28
Service Manual
(4) Put wiring cover back and then tighten the screw. (5) Close the panel.
Note: The wiring connect is for reference only, please refer to the actual one.
Indoor unit
Gas pipe
Indoor and
outdoor power cord
Liquid pipe
Drain hose
Band
Drain hose
Band
Connection pipe
Indoor power cord
Power connection
wire
Cable-cross
hole
(2) If the length of power connection wire is insufcient, please contact the supplier for a new one. Avoid extending the wire by
yourself.
(3) For the air conditioner with plug, the plug should be reachable after nishing installation. (4) For the air conditioner without plug, an air switch must be installed in the line. The air switch should be all-pole parting and the contact parting distance should be more than 3mm.
(1) All wires of indoor unit and outdoor unit should be
connected by a professional.
(1) The power cord and control wire can't be crossed or
winding.
(2) The drain hose should be bound at the bottom.
7. Connect Wire of Indoor Unit
(1) Open the panel, remove the screw on the wiring cover and then take down the cover.(As show in Fig.11)
8. Bind up Pipe
(1) Bind up the connection pipe, power cord and drain hose with the band.(As show in Fig.14) (2) Reserve a certain length of drain hose and power cord for installation when binding them. When binding to a certain degree, separate the indoor power and then separate the drain hose.(As show in Fig.15) (3) Bind them evenly. (4) The liquid pipe and gas pipe should be bound separately at the end.
(2) Make the power connection wire go through the cable-cross hole at the back of indoor unit and then pull it out from the front side.(As show in Fig.12)
(3) Remove the wire clip; connect the power connection wire to the wiring terminal according to the color; tighten the screw and then x the power connection wire with wire clip.(As show
in Fig.13)
Note:
Note:
Fig.11
Fig.12
Fig.13
Fig.14
Fig.15
wiring cover
screw
panel
N(1) 23
blue brownblack
yellow­green
Outdoor unit connection
9. Hang the Indoor Unit
(1) Put the bound pipes in the wall pipe and then make them pass through the wall hole. (2) Hang the indoor unit on the wall-mounting frame. (3) Stuff the gap between pipes and wall hole with sealing gum. (4) Fix the wall pipe.(As show in Fig.16) (5) Check if the indoor unit is installed rmly and closed to the wall.(As show in Fig.17)
Do not bend the drain hose too excessively in order to prevent blocking.
Note:
Indoor
Outdoor
Wall pipe
Sealing gum
Upper hook
Lower hook of
wall-mounting frame
Fig.16
Fig.17
Page 31
29
Service Manual
NO. Items to be checked Possible malfunction
1
Has the unit been installed rmly?
The unit may drop, shake or
emit noise.
2
Have you done the refrigerant leakage test?
It may cause insufcient cooling (heating) capacity.
3
Is heat insulation of pipeline sufcient?
It may cause condensation and water dripping.
4 Is water drained well?
It may cause condensation and water dripping.
5
Is the voltage of power supply according to the voltage marked on the nameplate?
It may cause malfunction or
damage the parts.
6
Is electric wiring and pipeline installed
correctly?
It may cause malfunction or
damage the parts.
7
Is the unit grounded securely?
It may cause electric leakage.
8
Does the power cord follow the specication?
It may cause malfunction or
damage the parts.
9
Is there any obstruction in air inlet and air outlet?
It may cause insufcient cooling (heating) capacity.
10
The dust and
sundries caused during installation are
removed?
It may cause malfunction or
damaging the parts.
11
The gas valve and liquid
valve of connection pipe
are open completely?
It may cause insufcient cooling (heating) capacity.
12
Is the inlet and outlet of piping hole been covered?
It may cause insufcient cooling (heating) capacity or waster
eletricity.
1. Check after Installation
Check according to the following requirement after finishing
installation.
8.6 Check after Installation and Test Operation
2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client. (2) Method of test operation
● Put through the power, press ON/OFF button on the remote
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16℃, the air conditioner can’t start cooling.
Page 32
30
Service Manual
9. Maintenance
9.1 Error Code
1. Malfunction display requirement
When there are several malfunctions, they will be displayed circularly.
2. Malfunction display method
(1) Hardware malfunction: immediate display; refer to “error code list”; (2) Operation state: immediate display; refer to “error code list”; (3) Other malfunctions: it is displayed after the compressor stops for 200s; refer to “error code list”.
Note: when the compressor is restarted, the malfunction display delay time (200s) is cleared.
3. Malfunction display control
The indicator lamp and dual 8 nixie tube displays shall be synchronized. That is when the indicator lamp blinks, the dual 8 nixie tube displays the corresponding malfunction code.
4. Display control viaremote controller
Enter display control: press light button successively for 4 times within 3s to display the corresponding malfunction code; Exit display control: pressing light button successively for 4 times within 3s or after display is shown for 5min, the display will
terminate.
Error Code List
Malfunction Name Malfunction types
Dual-8
Nixie Tube
Indicator Display
Operation
indicator
Cooling
indicator
Heating
indicator
Fault in input power zero Hardware malfunction U8 blink 17 times Jumper cap malfunction protection Hardware malfunction C5 blink 15 times
No feedback of indoor fan motor Hardware malfunction H6 blink 11 times Indoor ambient sensor open or short circuit Hardware malfunction F1 blink once Indoor tube sensor open or short circuit Hardware malfunction F2 blink twice
Inlet tube sensor malfunction Hardware malfunction b5 blink 19 times Outlet tube sensor malfunction Hardware malfunction b7 blink 22 times IPM sensor circuit malfunction Hardware malfunction P7 blink 18 times Outdoor ambient sensor open or short circuit Hardware malfunction F3 blink 3 times Inlet pipe temperature sensor of outdoor
condenser is open-circuit/short circuit(commercial
air con)
Hardware malfunction A5
Outdoor tube sensor open or short circuit Hardware malfunction F4 blink 4 times outlet pipe temperature sensor of outdoor
condenser is open-circuit/short circuit(commercial
air con)
Hardware malfunction A7
Exhaust sensor open or short circuit Hardware malfunction F5 blink 5 times Communication failure between indoor unit and outdoor unit
Hardware malfunction E6 blink 6 times
Compressor phase current detection circuit
malfunction
Hardware malfunction U1 blink 12 times
Compressor demagnetization protection It can be displayed
through remote
controller within 200s
and displayed directly
after 200s
HE blink 14 times
PN voltage drop protection U3 blink 20 times
IPM high temperature protection P8 blink 19 times
Refrigerant-lacking or blockage protection F0 blink 10 times
Capacitor charge malfunction Hardware malfunction PU blink 17 times Refrigerant system high pressure protection Hardware malfunction E1 blink once
system low-pressure protection (reserved) Hardware malfunction E3 blink 3 times
Compressor over load protection
It can be displayed
through remote
controller within 200s
and displayed directly
after 200s
H3 blink 3 times
Fault in matching Hardware malfunction LP blink 19 times Loading EEPROM malfunction Hardware malfunction EE blink 15 times AC current detect circuit malfunction Hardware malfunction U5 blink 13 times Outdoor DC fan motor malfunction Hardware malfunction
L3 blink 23 times
Mode conict operation status E7 blink 7 times
Page 33
31
Service Manual
Note: Please refer to service manual for the troubleshooting procedure for outdoor unit.
Recovery refrigerant mode operation status Fo blink once blink once Startup failure
It can be displayed
through remote
controller within 200s
and displayed directly
after 200s
Lc blink 11 times
Compressor exhaust high temperature protection E4 blink 4 times Anti-high temperature protection E8 blink 8 times AC over-current protection E5 blink 5 times Over compressor phase current protection P5 blink 15 times Compressor loss step protection H7 blink 7 times Compressor loss of phase protection Ld
IPM protection H5 blink 5 times Low PN voltage protection PL blink 21 times Over voltage protection for PN PH blink 11 times PFC protection HC blink 6 times 4-way valve reversal abnormal U7 blink 20 times
Page 34
32
Service Manual
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process:
Is the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
Start
Insert the temperature
sensor tightly
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Replace it with a
temperature sensor with
the same model
Make the parts upright
Is there short circuit due to trip-
over of the parts
Is the temperature sensor normal
according to the resistance table?
Replace the mainboard with
the same model.
End
Page 35
33
Service Manual
2. Malfunction of Blocked Protection of IDU Fan Motor H6
Main detection points:
● SmoothlyIs the control terminal of PG motor connected tightly?
● SmoothlyIs the feedback interface of PG motor connected tightly?
● The fan motor can't operate?
● The motor is broken?
● Detectioncircuit of the mainboard is dened abnormal?
Malfunction diagnosis process:
Start
While power is off stir the blade
with a tool to see whether the
blade rotates smoothly
Check if the connection of PG
motor feedback terminal is rm
Check if the connection of PG
motor control terminal is rm
Turn on the unit again; measure
whether the output voltage on
control terminal for PG motor is
more than 50V within 1 min after
the louvers are opened
Tighten the screw; reassemble the blade, motor
and shaft bearing rubber base sub-assy to make
sure there is no foreign object between them
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Is the motor started up
Replace PG motor
Replace the mainboard
with the same model
Measure the voltage of this foot to
neutral wire on the mainboard
End
Reinstall the blade
and motor correctly
Insert the control terminal
of PG motor tightly
Page 36
34
Service Manual
3. Malfunction of Protection of Jumper Cap C5
Main detection points:
● Is there jumper cap on the mainboard?
● Is the jumper cap inserted correctly and tightly?
● The jumper is broken?
● The motor is broken?
● Detection circuit of the mainboard is dened abnormal?
Malfunction diagnosis process:
Start
Is there jumper cap on the mainboard?
Is the jumper cap inserted correctly
and tightly?
Replace the jumper cap with
the same model
Appearance of the
jumper cap
Assemble the jumper
cap with the same model
Insert the jumper
cap tightly
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Replace the mainboard
with the same model
End
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Page 37
35
Service Manual
4. Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8
Main detection points:
● Instant energization afte de-energization while the capacitordischarges slowly?
● The zero-cross detectioncircuit of the mainboard is dened abnormal?
Malfunction diagnosis process:
Turn power off for
1minute,the turn
back on
The unit returns to normal.
Conclusion:U8 is displayed due to
power off/on while the capacitor discharges slowly.
U8 is still
displayed
The zero-cross detection circuit
of the mainboard is dened
abnormal.Replace the mainboard
with the same model
Yes
No
Start
End
Page 38
36
Service Manual
5. Malfunction of Overcurrent Protection E5
Main detection points:
● Is the supply voltage unstable with big uctuation?
● Is the supply voltage too low with overload?
● Hardware trouble?
Malfunction diagnosis process:
Start
Is the supply voltage unstable
with big uctuation?
Normal uctuation should be within 10 % of the rated voltage on the nameplate
Adjust the supply voltage to maintain it within normal range
Clean the indoor and outdoor heat exchangers and remove the blockage
of air inlet and outlet
Check the motor and reinstall the motor to have the fan run normally
Replace the mainboard with the same
model
Flush the heat exchangers with high
pressure nitrogen
Replace the compressor
Replace the mainboard
with the same model
End
Is the supply voltage too low
with overload?
Is the indoor / outdoor
heat exchanger dirty,or are the air inlet
and outlet blocked?
The fan is abnormal? Fan
speed is too low or fan doesn’t rotate
Measure the current of live wire on
the main board with a clamp ampere
meter. Is the current higher than the value of the overcurrent protection?
Is there blockage inside the system?
(Filth blockage, ice plug, greasy
blockage, the cut off valve hasn’t been
opened completely)
Is the compressor running abnormally? Is there abnormal sound or oil leakage; Is the temperature of the shell too high,
etc.?
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Yes Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No No
No
No
No
No
No No
No
No
No
No
No
Page 39
37
Service Manual
6. High temperature and overload protection (AP1 below means control board of outdoor unit) E8
Main detection points:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
Malfunction diagnosis process:
Start
If the outdoor ambient temperature is
higher than 53°C?
If the airow of indoor and outdoor unit
is good?
If the indoor and outdoor fan are
running normally?
Replace outdoor
mainboard
Connect normally?
Adjust the
connection
Replace fan
capacitor
Replace motor
Fan capacitor is broken?
Motor is broken?
Replace mainboard
Improve the radiating environment of
unit (clean the heat exchanger and
remove surrounding obstacles)
Normal protection, please use it
after improving the outdoor ambient
temperature
Unit restarts
normally
Unit restarts
normally
End
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Page 40
38
Service Manual
7.
Overload Protection Compressor
H3
Main detection points:
● Heat exchange of unit is not good? (heat exchanger is dirty and unit radiating environment is bad)
● Fan motor is not working?
● Too much load of the system causes high temperature of compressor after working for a long time?
● Whether high pressure switch is normal?
● If the refrigerant is leaked?
Malfunction diagnosis process:
Start
Outdoor and indoor heat
exchangers are too dirty or the air
inlet/outlet is blocked.
Clean the outdoor and indoor heat exchangers and remove blockage of air inlet/outlet.
Malfunction is eliminated.
Malfunction is eliminated.
Malfunction is eliminated.
Malfunction is eliminated.
Malfunction is eliminated.
Malfunction is eliminated.
Check motor and re-install the motor to make it run normally.
Make compressor run normally.
Remove blockage in the system.
Replace high pressure switch
Check the leaking status of refrigerant and charge refrigerant
Fan motor is not working.
Abnormal fan speed; fan speed is too
low or the fan doesn't run.
Compressor doesn't work
normally. Strange noise or leakage occurs.
Temperature of the shell is too high.
System is blocked inside
(dirt block, ice block, oil block, Y-valve not
fully open).
Check whether high
pressure switch is normal
Check whether the
refrigerant is leaking and cause
overheating protection to compressor
Replace a main
board of the
same model.
End
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
Page 41
39
Service Manual
9.2 Maintenance Method for Normal Malfunction
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Set temperature is improper Observe the set temperature on remote controller Adjust the set temperature
Rotation speed of the IDU fan
motor is set too low
Small wind blow Set the fan speed at high or medium
Filter of indoor unit is blocked Check the lter to see it's blocked Clean the lter
Installation position for indoor unit and outdoor unit is improper
Check whether the installation postion is proper
according to installation requirement for air conditioner
Adjust the installation position, and install the
rainproof and sunproof for outdoor unit
Refrigerant is leaking
Discharged air temperature during cooling is higher than normal discharged wind temperature; Discharged air temperature during heating is lower than normal discharged wind temperature; Unit's pressure is much lower than regulated
range
Find out the leakage causes and deal with it.
Add refrigerant.
Malfunction of 4-way valve Blow cold wind during heating Replace the 4-way valve
Malfunction of capillary
Discharged air temperature during cooling is higher than normal discharged wind temperature; Discharged air temperature during heating is lower than normal discharged wind temperature; Unit't pressure is much lower than regulated range. If refrigerant isn’t leaking, part of capillary is blocked
Replace the capillary
Flow volume of valve is
insufcient
The pressure of valves is much lower than that stated in the specication
Open the valve completely
Malfunction of horizontal louver Horizontal louver can’t swing
Refer to point 3 of maintenance method for
details
Malfunction of the IDU fan motor The IDU fan motor can’t operate
Refer to troubleshooting for H6 for maintenance method in details
Malfunction of the ODU fan motor The ODU fan motor can't operate
Refer to point 4 of maintenance method for
details
Malfunction of compressor Compressor can't operate
Refer to point 5 of maintenance method for
details
1. Air Conditioner Can't be Started Up
2. Poor Cooling (Heating) for Air Conditioner
3. Horizontal Louver Can't Swing
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
No power supply, or poor
connection for power plug
After energization, operation indicator isn’t bright and the buzzer can't give out sound
Conrm whether it's due to power failure. If yes, wait for power recovery. If not, check power supply circuit and make sure the power plug is
connected well.
Wrong wire connection between
indoor unit and outdoor unit,
or poor connection for wiring terminals
Under normal power supply circumstances, operation indicator isn't bright after energization
Check the circuit according to circuit diagram and connect wires correctly. Make sure all wiring terminals are connected rmly
Electric leakage for air conditioner
After energization, room circuit breaker trips off at
once
Make sure the air conditioner is grounded
reliably
Make sure wires of air conditioner is connected
correctly
Check the wiring inside air conditioner. Check whether the insulation layer of power cord is damaged; if yes, place the power cord.
Model selection for air switch is
improper
After energization, air switch trips off Select proper air switch
Malfunction of remote controller
After energization, operation indicator is bright, while no display on remote controller or buttons have no action.
Replace batteries for remote controller Repair or replace remote controller
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Wrong wire connection, or poor
connection
Check the wiring status according to circuit
diagram
Connect wires according to wiring diagram to
make sure all wiring terminals are connected rmly
Stepping motor is damaged Stepping motor can't operate Repair or replace stepping motor
Main board is damaged
Others are all normal, while horizontal louver
can't operate
Replace the main board with the same model
Page 42
40
Service Manual
7. Abnormal Sound and Vibration
Possible causes Discriminating method (air conditioner status) Troubleshooting When turn on or turn off the unit, the panel and other parts will expand and there's abnormal
sound
There's the sound of "PAPA"
Normal phenomenon. Abnormal sound will
disappear after a few minutes.
When turn on or turn off the unit, there's abnormal sound due to ow of refrigerant inside air
conditioner
Water-running sound can be heard
Normal phenomenon. Abnormal sound will
disappear after a few minutes.
Foreign objects inside the indoor unit or there're parts touching together inside the indoor unit
There's abnormal sound fro indoor unit
Remove foreign objects. Adjust all parts' position of indoor unit, tighten screws and stick
damping plaster between connected parts
Foreign objects inside the outdoor unit or there're parts touching together inside the outdoor unit
There's abnormal sound fro outdoor unit
Remove foreign objects. Adjust all parts' position of outdoor unit, tighten screws and stick damping plaster between connected parts
Short circuit inside the magnetic
coil
During heating, the way valve has abnormal
electromagnetic sound
Replace magnetic coil
Abnormal shake of compressor Outdoor unit gives out abnormal sound
Adjust the support foot mat of compressor, tighten the bolts
Abnormal sound inside the
compressor
Abnormal sound inside the compressor
If add too much refrigerant during maintenance,
please reduce refrigerant properly. Replace
compressor for other circumstances.
6. Air Conditioner is Leaking
Possible causes Discriminating method (air conditioner status) Troubleshooting
Drain pipe is blocked Water leaking from indoor unit
Eliminate the foreign objects inside the drain
pipe
Drain pipe is broken Water leaking from drain pipe Replace drain pipe
Wrapping is not tight
Water leaking from the pipe connection place of
indoor unit
Wrap it again and bundle it tightly
5. Compressor Can't Operate
Possible causes Discriminating method (air conditioner status) Troubleshooting
Wrong wire connection, or poor
connection
Check the wiring status according to circuit
diagram
Connect wires according to wiring diagram to
make sure all wiring terminals are connected rmly
Capacity of compressor is damaged
Measure the capacity of fan capacitor with an universal meter and nd that the capacity is out of the deviation range indicated on the nameplate of
fan capacitor.
Replace the compressor capacitor
Power voltage is a little low or
high
Use universal meter to measure the power supply voltage. The voltage is a little high or low
Suggest to equip with voltage regulator
Coil of compressor is burnt out
Use universal meter to measure the resistance
between compressor terminals and it's 0
Repair or replace compressor
Cylinder of compressor is blocked Compressor can't operate Repair or replace compressor
4. ODU Fan Motor Can't Operate
Possible causes Discriminating method (air conditioner status) Troubleshooting
Wrong wire connection, or poor
connection
Check the wiring status according to circuit
diagram
Connect wires according to wiring diagram to
make sure all wiring terminals are connected rmly
Capacity of the ODU fan motor is
damaged
Measure the capacity of fan capacitor with an universal meter and nd that the capacity is out of the deviation range indicated on the nameplate of
fan capacitor.
Replace the capacity of fan
Power voltage is a little low or
high
Use universal meter to measure the power supply voltage. The voltage is a little high or low
Suggest to equip with voltage regulator
Motor of outdoor unit is damaged
When unit is on, cooling/heating performance
is bad and ODU compressor generates a lot of
noise and heat.
Change compressor oil and refrigerant. If no better, replace the compressor with a new one
Page 43
44
Service Manual
11. Removal Procedure
Caution: discharge the refrigerant
completely before removal.
a
b
Axile bush
Push out the axile bush on horizontal louver. Bend the horizontal louver with hand and then separate the horizontal louver from the crankshaft of step motor
to remove it.
Horizontal louver
Location of step motor
ProcedureStep
1.Remove lter assy
2. Remove horizontal louver
Front panel
Front case
Right lter
Groove
Left lter
Open the front panel. Push the left and right filters to make them break away from the groove on the front case. Then remove the left and right filters one by
one.
Screw off the 2 screws that are locking the display board. Separate the display board from the front panel.
Separate the panel rotation shaft from the groove xing the front panel and then removes the front panel.
Panel
Screws
Display
Front panel
Panel rotation
Groove
3. Remove panel
Page 44
45
Service Manual
a
b
ProcedureStep
Remove the screws on the electric box cover 2 to remove the electric box cover 2.
Remove the screws xing front case.
Note:
1.Open the screw caps before removing the screws around the air outlet.
2.The quantity of screws fixing the front
case sub-assy is different for different models.
Loosen the connection clasps between
vertical louver and bottom case to remove vertical louver.
Loosen the connection clasps between
front case sub-assy and bottom case. Lift
up the front case sub-assy and take it out.
Electric box cover 2
Screw
4. Remove electric box cover 2
5. Remove front case sub-assy
6. Remove vertical louver
Front case sub-assy
Front case sub-assy
Clasp
Screw caps
Screws
Bottom case
Screw
Vertical louver
Vertical louver
Clasps
Bottom case
Page 45
46
Service Manual
a
b
c
d
ProcedureStep
Loosen the connection clasps between shield cover of electric box sub-assy and electric box, and then remove the shield
cover of electric box sub-assy.
Remove the screw xing electric box assy .
Remove the cold plasma generator by
screwing off one locking screw on the
generator.
Take off the indoor tube temperature
sensor.
Screw off one grounding screw.
Remove the wiring terminals of motor and
stepping motor.
Remove the electric box assy.
Twist off the screws that are locking lead
wire and rotate the electric box assy.
Twist off the screws that are locking wire
clip.
Loosen the power cord and remove its wiring
terminal. Lift up the main board and take it
off.
Remove the display board by taking out its
wiring terminal.
Remove temperature sensor by taking out
its wiring terminal.
7. Remove electric box assy
Electric box
Electric box assy
Clasps
Shield cover of electric box sub-assy
Cold plasma generator
Grounding
screw
Screw
Power cord
Screw
Wiring terminal
of display board
Wiring terminal of
temperature sensor
Wire clip
Screw
Main board
Main board
Screw
Screw
Indoor tube temperature sensor
Wiring
terminal
of motor
Wiring
terminal
of stepping
motor
Page 46
47
Service Manual
a
c
d
b
First remove the left side of evaporator from
the groove of bottom shell and then remove
the right side from the clasp on the bottom
shell.
Instruction: Some wiring terminal of this
product is with lock catch and other devices.
The pulling method is as below:
1.Remove the soft sheath for some terminals
at rst, hold the circlip and then pull out the
terminals.
2.Pull out the holder for some terminals at
rst (holder is not available for some wiring
terminal), hold the connector and then pull the
terminal.
Circlip
Soft sheath
Holder
Connector
ProcedureStep
Remove 3 screws xing evaporator assy.
8. Remove evaporator assy Screws
Connection pipe clamp
Evaporator assy
Evaporator assy
Screw
Groove
Bottom shell
Clasp
Connection pipe
At the back of the unit, remove the
screw fixing connection pipe clamp
and then remove the connection pipe
clamp.
Adjust the position of connection pipe on evaporator slightly and then lift the
evaporator upwards to remove it.
Page 47
48
Service Manual
ProcedureStep
Remove the screws fixing motor clamp and then remove the motor clamp.
Remove the screws at the connection place of cross flow blade and motor; lift the motor and cross flow blade upwards to remove them. Remove the bearing holder sub-assy. Remove the screw xing step motor and then remove the step motor.
Screws
Screw
Motor clamp
9. Remove motor and cross ow blade
Motor
Cross ow
Holder sub-assy
Step motor
Screws
a
b
Page 48
49
Service Manual
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Set temperature
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Ambient temperature
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
32/33 32 0 55/56 55.4 13 79/80 78.8 26 34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28 37/38 37.4 3 61/62 60.8 16 84/85 84.2 29 39/40 39.2 4 63 62.6 17 86/87 86 30 41/42 41 5 64/65 64.4 18 88/89 87.8 31 43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33 46/47 46.4 8 70/71 69.8 21 93/94 93.2 34 48/49 48.2 9 72 71.6 22 95/96 95 35 50/51 50 10 73/74 73.4 23 97/98 96.8 36 52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6
12 77/78 77 25
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit
display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
61 60.8 16 69/70 69.8 21 78/79 78.8 26 62/63 62.6 17 71/72 71.6 22 80/81 80.6 27 64/65 64.4 18 73/74 73.4 23 82/83 82.4 28 66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Appendix 2: Conguration of Connection Pipe
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each additional 5m of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter
1. Standard length of connection pipe
● 5m, 7.5m, 8m.
2. Min. length of connection pipe is 3m.
3. Max. length of connection pipe and max. high difference.(See the specication)
Additional refrigerant charging amount for R32
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(mm) Gas pipe(mm) Cooling only,
cooling and heating(g / m)
Cooling only
(g / m)
Cooling and heating
(g/m)
Ф6 Ф9.5 or Ф12 16 12 16
Ф6 or Ф9.5 Ф16 or Ф19 40 12 40
Ф12 Ф19 or Ф22.2 80 24 96 Ф16 Ф25.4 or Ф31.8 136 48 96 Ф19 / 200 200 200
Ф22.2 / 280 280 280
Page 49
50
Service Manual
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the port again according to the steps above.
The length is equal
Improper expanding
leaning
damaged
surface
crack uneven
thicknes
s
Smooth surface
Downwards
Pipe
Shaper
Union pipe
Pipe
Expander
Hard mold
Pipe
Pipe
Pipe cutter
Leaning Uneven Burr
Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps:
A:Cut the pip
● Conrm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
B:Remove the burrs
● Remove the burrs with shaper and prevent the burrs from getting into the pipe.
C:Put on suitable insulating pipe
D:Put on the union nut
● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe.
E:Expand the port
● Expand the port with expander.
● "A" is different according to the diameter, please refer to the sheet below:
Outer diameter(mm)
A(mm)
Max Min
Ф6 - 6.35 (1/4") 1.3 0.7
Ф9.52 (3/8”) 1.6 1.0 Ф12 - 12.70 (1/2”) 1.8 1.0 Ф16 - 15.88 (5/8”) 2.4 2.2
Appendix 3: Pipe Expanding Method
Note:
Note:
Page 50
51
Service Manual
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-19 138.1 20 18.75 59 3.848 98 1.071
-18 128.6 21 17.93 60 3.711 99 1.039
-17 121.6 22 17.14 61 3.579 100 1.009
-16 115 23 16.39 62 3.454 101 0.98
-15 108.7 24 15.68 63 3.333 102 0.952
-14 102.9 25 15 64 3.217 103 0.925
-13 97.4 26 14.36 65 3.105 104 0.898
-12 92.22 27 13.74 66 2.998 105 0.873
-11 87.35 28 13.16 67 2.896 106 0.848
-10 82.75 29 12.6 68 2.797 107 0.825
-9 78.43 30 12.07 69 2.702 108 0.802
-8 74.35 31 11.57 70 2.611 109 0.779
-7 70.5 32 11.09 71 2.523 110 0.758
-6 66.88 33 10.63 72 2.439 111 0.737
-5 63.46 34 10.2 73 2.358 11 2 0.717
-4 60.23 35 9.779 74 2.28 113 0.697
-3 57.18 36 9.382 75 2.206 11 4 0.678
-2 54.31 37 9.003 76 2.133 11 5 0.66
-1 51.59 38 8.642 77 2.064 11 6 0.642
0 49.02 39 8.297 78 1.997 117 0.625
1 46.6 40 7.967 79 1.933 118 0.608
2 44.31 41 7.653 80 1.871 119 0.592
3 42.14 42 7.352 81 1.811 120 0.577
4 40.09 43 7.065 82 1.754 121 0.561
5 38.15 44 6.791 83 1.699 122 0.547
6 36.32 45 6.529 84 1.645 123 0.532
7 34.58 46 6.278 85 1.594 124 0.519
8 32.94 47 6.038 86 1.544 125 0.505
9 31.38 48 5.809 87 1.497 126 0.492
10 29.9 49 5.589 88 1.451 127 0.48
11 28.51 50 5.379 89 1.408 128 0.467
12 27.18 51 5.197 90 1.363 129 0.456
13 25.92 52 4.986 91 1.322 130 0.444
14 24.73 53 4.802 92 1.282 131 0.433
15 23.6 54 4.625 93 1.244 132 0.422
16 22.53 55 4.456 94 1.207 133 0.412
17 21.51 56 4.294 95 1.171 134 0.401
18 20.54 57 4.139 96 1.136 135 0.391
19 19.63 58 3.99 97 1.103 136 0.382
Appendix 4: List of Resistance for Temperature Sensor
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K)
Page 51
52
Service Manual
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-19 181.4 20 25.01 59 5.13 98 1.427
-18 171.4 21 23.9 60 4.948 99 1.386
-17 162.1 22 22.85 61 4.773 100 1.346
-16 153.3 23 21.85 62 4.605 101 1.307
-15 145 24 20.9 63 4.443 102 1.269
-14 137.2 25 20 64 4.289 103 1.233
-13 129.9 26 19.14 65 4.14 104 1.198
-12 123 27 18.13 66 3.998 105 1.164
-11 116.5 28 17.55 67 3.861 106 1.131
-10 110.3 29 16.8 68 3.729 107 1.099
-9 104.6 30 16.1 69 3.603 108 1.069
-8 99.13 31 15.43 70 3.481 109 1.039
-7 94 32 14.79 71 3.364 11 0 1.01
-6 89.17 33 14.18 72 3.252 111 0.983
-5 84.61 34 13.59 73 3.144 112 0.956
-4 80.31 35 13.04 74 3.04 11 3 0.93
-3 76.24 36 12.51 75 2.94 11 4 0.904
-2 72.41 37 12 76 2.844 115 0.88
-1 68.79 38 11.52 77 2.752 116 0.856
0 65.37 39 11.06 78 2.663 117 0.833
1 62.13 40 10.62 79 2.577 118 0.811
2 59.08 41 10.2 80 2.495 119 0.77
3 56.19 42 9.803 81 2.415 120 0.769
4 53.46 43 9.42 82 2.339 121 0.746
5 50.87 44 9.054 83 2.265 122 0.729
6 48.42 45 8.705 84 2.194 123 0.71
7 46.11 46 8.37 85 2.125 124 0.692
8 43.92 47 8.051 86 2.059 125 0.674
9 41.84 48 7.745 87 1.996 126 0.658
10 39.87 49 7.453 88 1.934 127 0.64
11 38.01 50 7.173 89 1.875 128 0.623
12 36.24 51 6.905 90 1.818 129 0.607
13 34.57 52 6.648 91 1.736 130 0.592
14 32.98 53 6.403 92 1.71 131 0.577
15 31.47 54 6.167 93 1.658 132 0.563
16 30.04 55 5.942 94 1.609 133 0.549
17 28.68 56 5.726 95 1.561 134 0.535
18 27.39 57 5.519 96 1.515 135 0.521
19 26.17 58 5.32 97 1.47 136 0.509
Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)
Page 52
53
Service Manual
Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ) Temp(oC) Resistance(kΩ)
-29 853.5 10 98 49 18.34 88 4.75
-28 799.8 11 93.42 50 17.65 89 4.61
-27 750 12 89.07 51 16.99 90 4.47
-26 703.8 13 84.95 52 16.36 91 4.33
-25 660.8 14 81.05 53 15.75 92 4.20
-24 620.8 15 77.35 54 15.17 93 4.08
-23 580.6 16 73.83 55 14.62 94 3.96
-22 548.9 17 70.5 56 14.09 95 3.84
-21 516.6 18 67.34 57 13.58 96 3.73
-20 486.5 19 64.33 58 13.09 97 3.62
-19 458.3 20 61.48 59 12.62 98 3.51
-18 432 21 58.77 60 12.17 99 3.41
-17 407.4 22 56.19 61 11.74 100 3.32
-16 384.5 23 53.74 62 11.32 101 3.22
-15 362.9 24 51.41 63 10.93 102 3.13
-14 342.8 25 49.19 64 10.54 103 3.04
-13 323.9 26 47.08 65 10.18 104 2.96
-12 306.2 27 45.07 66 9.83 105 2.87
-11 289.6 28 43.16 67 9.49 106 2.79
-10 274 29 41.34 68 9.17 107 2.72
-9 259.3 30 39.61 69 8.85 108 2.64
-8 245.6 31 37.96 70 8.56 109 2.57
-7 232.6 32 36.38 71 8.27 11 0 2.50
-6 220.5 33 34.88 72 7.99 111 2.43
-5 209 34 33.45 73 7.73 112 2.37
-4 198.3 35 32.09 74 7.47 11 3 2.30
-3 199.1 36 30.79 75 7.22 11 4 2.24
-2 178.5 37 29.54 76 7.00 11 5 2.18
-1 169.5 38 28.36 77 6.76 11 6 2.12
0 161 39 27.23 78 6.54 117 2.07
1 153 40 26.15 79 6.33 118 2.02
2 145.4 41 25.11 80 6.13 11 9 1.96
3 138.3 42 24.13 81 5.93 120 1.91
4 131.5 43 23.19 82 5.75 121 1.86
5 125.1 44 22.29 83 5.57 122 1.82
6 119.1 45 21.43 84 5.39 123 1.77
7 113.4 46 20.6 85 5.22 124 1.73
8 108 47 19.81 86 5.06 125 1.68
9 102.8 48 19.06 87 4.90 126 1.64
Resistance Table of Discharge Temperature Sensor for Outdoor(50K)
Page 53
PARTS GUIDE
MULTI VARIABLE SERIES
WALL MOUNTED – FOCUS
MV-HXXBIF
Page 54
MV-H07BIF
Page 55
No Description Part Code Note Qty
Price Code
1 Front Panel 27230009455 1 AN 2 Display Board 300001000081 1 AR 3 Front Case Assy 00000200040 1 AP 4 Helicoid Tongue 26112508 1 AE 5 Left Axile Bush 10512037 1 AB 6 Rear Case assy 20162010 1 AY 7 Drainage Hose 0523001408 1 AD 8 Ring of Bearing 26152022 1 AC 9 O-Gasket sub-assy of Bearing 76512051 1 AC 10 Evaporator Support 24212180 1 AE 11 Cold Plasma Generator 1114001603 1 AP 12 Evaporator Assy 0110010009505 1 BB 13 Wall Mounting Frame 01252043 1 AK 14 Cross Flow Fan 10352059 1 AM 15 Fan Motor 150120874 1 AX 16 Connecting pipe clamp 2611216401 1 AB 17 Rubber Plug (Water Tray) 76712012 1 AC 18 Stepping Motor 1521212901 1 AF 19 Crank 73012005 1 AB 20 Electric Box Assy 100002002491 1 BB 21 Axile Bush 10542036 1 AB 22 Terminal Board 42011233 1 AE 23 Jumper 4202021904 1 AA 24 Main Board 300002000288 1 AX 25 Electric Box Cover Sub-Assy 0140206501 1 AD 26 Shield Cover of Electric Box Cover 01592150 1 AD 27 Electric Box Cover 20112207 1 AD 28 Power Cord none 0 ­29 Connecting Cable none 0 ­30 Connecting Cable 4002052317 1 AN 31 Remote Controller
305001000118_L41851
1 -
32 Test Board Assy
000409000002_L41851
1 ­33 Guide Louver 1051276301 1 AF 34 Swing Louver 10512721 1 AB
MODEL: MV-H07BIF Wall mounted unit
The data are subject to change without notice.
Page 56
MV-H09BIF
Page 57
No Description Part Code Note Qty
Price Code
1 Front Panel 27230009455 1 AN 2 Display Board 300001000081 1 AR 3 Front Case Assy 00000200040 1 AP 4 Helicoid Tongue 26112508 1 AE 5 Left Axile Bush 10512037 1 AB 6 Rear Case assy 20022682 1 AY 7 Drainage Hose 0523001408 1 AD 8 Ring of Bearing 26152022 1 AC 9 O-Gasket sub-assy of Bearing 76512051 1 AE 10 Evaporator Support 24212180 1 AE 11 Cold Plasma Generator 1114001603 1 AP 12 Evaporator Assy 0110010009505 1 BB 13 Wall Mounting Frame 01252043 1 AK 14 Cross Flow Fan 10352059 1 AM 15 Fan Motor 150120874 1 AX 16 Connecting pipe clamp 2611216401 1 AB 17 Rubber Plug (Water Tray) 76712012 1 AC 18 Stepping Motor 1521212901 1 AF 19 Crank 73012005 1 AB 20 Electric Box Assy 100002062337 1 BB 21 Axile Bush 10542036 1 AB 22 Terminal Board 42011233 1 AE 23 Jumper 4202021908 1 AA 24 Main Board 300002060228 1 AX 25 Electric Box Cover Sub-Assy 0140206501 1 AD 26 Shield Cover of Electric Box Cover 01592150 1 AD 27 Electric Box Cover 20112207 1 AD 28 Power Cord none 0 ­29 Connecting Cable none 0 ­30 Connecting Cable 4002052317 1 AN 31 Remote Control
305001060023_L41851
1 ­32 Test Board Assy
000409000002_L41851
1 ­33 Guide Louver 1051276301 1 AF 34 Swing Louver 10512740 1 AB
MODEL: MV-H09BIF Wall mounted unit
The data are subject to change without notice.
Page 58
MV-H12BIF
Page 59
No Description Part Code Note Qty
Price Code
1 Front Panel 27230009457 1 AN 2 Display Board 300001000081 1 AR 3 Front Case Assy 00000200045 1 AQ 4 Helicoid Tongue 26112436 1 AE 5 Left Axile Bush 10512037 1 AB 6 Rear Case assy 00000100092 1 AY 7 Drainage Hose 05230014 1 AD 8 Ring of Bearing 26152022 1 AC 9 O-Gasket sub-assy of Bearing 76512051 1 AC 10 Evaporator support 24212179 1 AE 11 Cold Plasma Generator 1114001603 1 AP 12 Evaporator Assy 011001060162 1 BC 13 Wall Mounting Frame 01252484 1 AK 14 Cross Flow Fan 10352056 1 AN 15 Fan Motor 15012146 1 AX 16 Connecting pipe clamp 2611216401 1 AB 17 Rubber Plug (Water Tray) 76712012 1 AC 18 Stepping Motor 1521210108 1 AG 19 Crank 73012005 1 AB 20 Electric Box Assy 100002062377 1 ­21 Axile Bush 10542036 1 AB 22 Terminal Board 42011233 1 AE 23 Jumper 4202021917 1 AA 24 Main Board 300002060230 1 AX 25 Electric Box Cover Sub-Assy 0140206501 1 AD 26 Shield Cover of Electric Box Cover 01592150 1 AD 27 Electric Box Cover 2011220701 1 AD 28 Power Cord none 0 ­29 Connecting Cable none 0 ­30 Connecting Cable 4002052317 1 AN 31 Remote Control
305001060023_L41851
1 ­32 Test Board Assy
000409000001_L41851
1 ­33 Guide Louver 1051293101 1 AF 34 Air Louver (Auto) 10512727 1 AB
MODEL: MV-H12BIF Wall mounted unit
The data are subject to change without notice.
Page 60
MV-H18BIF
Page 61
No Description Part Code Note Qty
Price Code
1 Decorative Strip 1 none 0 ­2 Front Panel 27230009459 1 AN 3 Display Board 300001000081 1 AR 4 Filter Sub-Assy 1112208906 2 AD 5 Decorative Board (Left and Right) 20192662 1 AE 6 Front Case Assy 00000200042 1 AS 7 Guide Louver 1051276501 1 AF 8 Axile Bush 10542036 2 AB 9 Air Louver 10512736 1 AB 10 Helicoid Tongue 26112512 1 AE 11 Left Axile Bush 10512037 1 AB 12 Rear Case assy 00000100001 1 AX 13 Rubber Plug (Water Tray) 76712012 1 AC 14 O-Gasket sub-assy of Bearing 76512051 1 AC 15 Ring of Bearing 26152025 1 AC 16 Evaporator Support 24212177 1 AE 17 Evaporator Assy 011001000207 1 BE 18 Cross Flow Fan 10352060 1 AN 19 Fan Motor 1501214502 1 AX 20 Motor Press Plate 26112511 1 AE 21 Wall Mounting Frame 01362026 1 AK 22 Connecting pipe clamp 2611218801 1 AB 23 Crank 73012005 1 AB 24 Stepping Motor 1521240212 1 AG 25 Drainage Hose 05230014 1 AD 26 Electric Box Assy 100002062372 1 ­27 Lower Shield of Electric Box 01592139 1 AD 28 Electric Box 20112211 1 AG 29 Jumper 4202021921 1 AA 30 Main Board 300002060236 1 AX 31 Shield Cover of Electric Box 01592176 1 AD 32 Electric Box Cover 20112209 1 AD 33 Terminal Board 42011233 1 AE 34 Decorative Board (Right) none 0 ­35 Screw Cover 2425201726 3 AB 36 Electric Box Cover2 20112210 1 AD 37 Power Cord none 0 ­38 Connecting Cable none 0 ­39 Connecting Cable 4002052317 1 AN 40 Remote Control
305001060023_L41851
1 ­41 Cold Plasma Generator 1114001602 1 AP
MODEL: MV-H18BIF Wall mounted unit
The data are subject to change without notice.
Page 62
MV-H24BIF
Page 63
No Description Part Code Note Qty
Price Code
1 Front Panel 27230009461 1 AN 2 Filter Sub-Assy 1101200703 2 AD 3 Screw Cover 2425245301 3 AB 4 Front Case Assy 00000200043 1 AU 5 Air Louver 10512744 1 AB 6 Helicoid Tongue sub-assy 26112384 1 AE 7 Left Axile Bush 10512037 1 AB 8 Rear Case assy 22202736 1 AZ 9 Rubber Plug (Water Tray) 76712012 1 AC 10 Ring of Bearing 26152025 1 AC 11 O-Gasket sub-assy of Bearing 76512051 1 AC 12 Cross Flow Fan 10352057 1 AP 13 Evaporator Support 24212178 1 AE 14 Evaporator Assy 01100100007303 1 BK 15 Cold Plasma Generator 1114001602 1 AP 16 Wall Mounting Frame 01252229 1 AL 17 Motor Press Plate 26112515 1 AE 18 Fan Motor 15012145 1 AZ 19 Connecting pipe clamp 26112514 1 AB 20 Drainage Hose 0523001405 1 AD 21 Stepping Motor 1521240212 1 AG 22 Crank 73012005 1 AB 23 Guide Louver 1051232001 1 AF 24 Axile Bush 10542036 2 AB 25 Electric Box 2011221102 1 AG 26 Terminal Board 42011233 1 AE 27 Electric Box Cover2 20112210 1 AD 28 Main Board 300002060239 1 AX 29 Display Board 300001000081 1 AR 30 Shield Cover of Electric Box 01592176 1 AD 31 Electric Box Cover 20112209 1 AD 32 Jumper 4202021925 1 AA 33 Lower Shield of Electric Box 01592139 1 AD 34 Electric Box Assy 100002062378 1 ­35 Power Cord none 0 ­36 Connecting Cable 4002052317 1 AN 37 Connecting Cable none 0 ­38 Temperature Sensor 3900031302 1 AE 39 Remote Control 305001060023_L41851 1 -
MODEL: MV-H24BIF Wall mounted unit
The data are subject to change without notice.
Page 64
NOTE CONCERNING PROTECTION OF ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal procedures. The materials are recyclable in accordance with their respective symbols. By means of re-use, material recycling or any other form of recycling old appliances you are making an important contribution to the protection of our environment. Please ask your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT MEDIUM
This unit is containing fluorinated gases included in the Kyoto protocol. The maintenance and the liquidation must be carried out by qualified personnel. Type of refrigerant: R32 The quantity of the refrigerant: please see the unit label. The value GWP: 675 (1 kg R32 = 0,675 t CO2 eq) GWP = Global Warming Potential
Appliance filled with flammable gas R32.
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain
www.sinclair-world.com
This product was manufactured in China (Made in China).
REPRESENTATIVE
SINCLAIR EUROPE spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
TECHNICAL SUPPORT
NEPA spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
Tel.: +420 800 100 285
Fax: +420 541 590 124
www.sinclair-solutions.com info@sinclair-solutions.com
Loading...