Sinclair MV-F09BI, MV-F12BI, MV-F18BI, MV-F24BI User Manual

Page 1
MULTI VARIABLE
Floor Ceiling
MV-FxxBI
USER'S MANUAL
EN
Page 2
IMPO
RTANT N
OTE:
Read this manual ca
r
efully befo
r
e installing
or operating your new air conditioning unit. Make sure to save this manual for futu
re r
efe
r
ence.
Page 3
Contents
1 Safety Precautions ............................................................... 1
2 Outline of the Unit and Main Parts ....................................... 2
4 Preparative for Installation ..................................................10
4.1 Standard Accessory Parts ....................................................10
4.2 Selection of the Installation Location ....................................10
4.3 Connection Pipe Requirement .............................................11
4.4 Electrical Requirement .........................................................12
3.5 Operation guide.......................................................................9
3.6 Replacement of batteries in remote controller...........................................9
3 Operation of remote controller................................................3
3.1 Buttons on remote controller ..................................................3
3.2 Introduction for icons on display screen..................................3
3.3 Introduction for buttons on remote controller...........................4
3.4 Function introduction for combination buttons...........................................8
5 Installation of the Unit .........................................................13
5.1 Installation of the Indoor Unit ................................................13
5.2 Installation of the Connection Pipe .......................................16
5.3 Vacuum and Gas Leakage Inspection ..................................20
5.4 Installation of the Drain Pipe ................................................22
5.5 Electrical Wiring ...................................................................25
6 Installation of Controllers ................................................... 29
7 Test Running ...................................................................... 30
7.1 Trial Operation and Testing ..................................................30
8 Troubleshooting and Maintenance ..................................... 32
8.1 Troubleshooting ...................................................................32
8.2 Routine Maintenance ...........................................................33
Page 4
The Refrigerant
To realize the function of the air conditioner unit, a special refrigerant circulates
.
leads to explosion
. It can
Compared to common refrigerants, R32 is a nonpolluting refrigerant with no
lower. R32 has got very good thermodynamic features which lead to a really high
WARNING:
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.Should repair be necessary, contact your nearest authorized Service Centre.
The appliance shall be stored in a room without continuously operating ignition
electric heater.) Do not pierce or burn.
than “X”m (see table 1).(only applies to appliances that are not fixed appliances)
Appliance shall be installed, operated and stored in a room with a floor area larger
2
’s
instructions only. Be aware that refrigrants not contain odour. Read specialist’s manual.
Please read this operating manual carefully before operating the unit.
to the material objects for reference.
Page 5
1
1 Safety Precautions
WARNING!
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
CAUTION!
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
WARNING!
(1). For operating the air conditioner pleasantly, install it as outlined in this installation manual.
(2). Connect the indoor unit and outdoor unit with the room air conditioner piping and cord
available from our standard parts. This installation manual describes the correct connections using the installation set available from our standard parts.
(3). Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
(4). If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in
contact with a flame, it produces toxic gas.
(5). Do not power on until all installation work is complete.
(6). During installation, make sure that the refrigerant pipe is attached firmly before you run the
compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
(7). During the pump-down operation, make sure that the compressor is turned off before you
remove the refrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigerant cycle that leads to breakage and even injury.
(8). When installing and relocating the air conditioner do not mix gases other than the specified
refrigerant (R32) to enter the refrigerant cycle. If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc.
(9). This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
(10). If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
(11). Correct Disposal of this product
(12). The appliance shall not be installed in the laundry.
GWP
R32:675
This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe rec
ycling.
Page 6
2
2 Outline of the Unit and Main Parts
Fig.1
Notes: The connection pipe and duct for this unit should be prepared by the user.
Page 7
7
2
1
8
10
12
15
14
13
11
9
6
5
4
3
1 ON/OFF button
2 MODE button
3 +/- button
4 FAN button
5 I FEEL button
11
X-FAN button
Note: X-FAN is the same with BLOW
12 TEMP button
13 TURBO button
15 LIGHT button
14 SLEEP button
10
TIMER ON/TIMER OFF button
9 CLOCK button
Send signal
Turbo mode
X-fan mode
Set temperature
Set time
TIMER ON / TIMER OFF
Child lock
Up & down swing
Set fan speed
AIR function I feel
Light
Temp. display type
:Set temp.
:Outdoor ambient temp.
:Indoor ambient temp.
Sleep mode
Clock
Health function
Heat mode
Fan mode
Dry mode
Cool mode
Auto mode
Operation mode
8 button
6 button
7 button
3 Operation of remote controller
3.1 Buttons on remote controller
3.2 Introduction for icons on display screen
3
Page 8
4
● After selecting auto mode, air conditioner will operate automatically according to ambient temperature. Set temperature can’t be adjusted and will not be displayed as well. Press "FAN" button can adjust fan speed. Press " " button can adjust fan blowing angle.
After selecting cool mode, air conditioner will operate under cool mode. Press "+" or "-" button to adjust set temperature. Press "FN" button to adjust fan speed. Press " " button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Under dry mode, fan speed can’t be adjusted. Press " " button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating. All indicators are OFF. Operation indicator is ON. Press "FAN" button to adjust fan speed. Press
● When selecting heating mode, the air conditioner operates under heat mode. Press "+" or "-" button to adjust set temperature. Press "FAN" button to adjust fan speed. Press " " button to adjust fan blowing angle. (Cooling only unit won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor ambient temperature).
● Set temperature range from remote controller: 16~30℃; Fan speed: auto, low speed, medium speed, high speed.
Note:
After putting through the power, the air conditioner will give out a sound. After that, you can operate the air conditioner by using remote controller.
ON/OFF button
MODE button
1
2
Press this button can turn on or turn off the air conditioner. After turning on the air conditioner, operation indicator " "on indoor unit’s display is ON (green indicator. The colour is different for different models), and indoor unit will give out a sound.
Press this button to select your required operation mode.
AUTO COOL FANDRY HEAT
" " button to adjust fan blowing angle.
● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
3.3 Introduction for buttons on remote controller
Page 9
FAN button
I FEEL button
4
5
6
7
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium ( ), high( ).
Note:
● Under AUTO Speed,IDU fan motor will adjust the fan speed (high, medium or
low speed) according to ambient temperature.
● Fan speed under dry mode is low speed.
Press this button to start I FEEL function and " " will be displayed on the remote controller. After this function is set, the remote controller will send the detected ambient temperature to the controller and the unit will automatically adjust the indoor temperature according to the detected temperature. Press this button again to close I FEEL function and " " will disappear.
● Please put the remote controller near user when this function is set. Do not put
the remote controller near the object of high temperature or low temperature in order to avoid detecting inaccurate ambient temperature.
Press this button to set HEALTH function ON or OFF. After the unit is turned on, it defaults to HEALTH function ON.
Press this button to select AIR function ON or OFF.
button
button
(Only available for some models)
● This function is applicable to partial of models.
Auto
+/- button
3
● Press "+" or "-" button once increase or decrease set temperature 1℃.
Holding "+" or "-" button, 2s later, set temperature on remote controller will
tor on indoor unit will change accordingly. (Temperature can’t be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press "+" or "-" button to
adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF buttons) When setting TIMER ON, TIMER OFF or CLOCK, press "+" or "-" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF buttons)
● When I FEEL function is turned on, the remote controller should be put within the
area where indoor unit can receive the signal sent by the remote controller.
5
Page 10
Press this button to set clock time. " " icon on remote controller will blink. Press "+" or "-" button within 5s to set clock time. Each pressing of "+" or "-" button, clock time will increase or decrease 1 minute. If hold "+" or "-" button, 2s later, time will change quickly. Release this button when reaching your required time. Press
"CLOCK" button to confirm the time. " " icon stops blinking.
Note:
● Clock time adopts 24-hour mode.
The interval between two operation can’t exceeds 5s. Otherwise, remote contro-
ller will quit setting status. Operation for TIMER ON/TIMER OFF is the same.
CLOCK button
9
TIMER ON / TIMER OFF button
10
TIMER ON button "TIMER ON" button can set the time for timer on. After pressing this button, " " icon disappears and the word "ON" on remote controller blinks. Press "+" or "-" button to adjust TIMER ON setting. After each pressing "+" or "-" button, TIMER ON setting will increase or decrease 1min. Hold "+" or "-" button, 2s later, the time will change quickly until reaching your required time. Press "TIMER ON" to confirm it. The word "ON" will stop blinking. " " icon resumes displaying. Cancel TIMER ON: Under the condition that TIMER ON is
8
Press this button can select up&down swing angle. Fan blow angle can be selected circularly as below:
● When selecting " ", air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at maximum angle.
● When selecting " 、 、 、 、 ", air conditioner is blowing fan at fixed position. Horizontal louver will stop at the fixed position.
● When selecting " 、 、 " , air conditioner is blowing fan at fixed angle. Horizontal louver will send air at the fixed angle.
● Hold " "button above 2s to set your required swing angle. When reaching your
required angle, release the button.
Note:
● " 、 、 " may not be available. When air conditioner receives this signal, the
air conditioner will blow fan automatically.
button
no display (horizontal louvers stops at current position)
6
Page 11
started up, press "TIMER ON" button to cancel it.
TIMER OFF button "TIMER OFF" button can set the time for timer off. After pressing this button," " icon disappears and the word "OFF" on remote controller blinks. Press "+" or "-" button to adjust TIMER OFF setting. After each pressing "+" or "-" button, TIMER OFF setting will increase or decrease 1min. Hold "+" or "-" button, 2s later, the time will change quickly until reaching your required time. Press "TIMER OFF" word "OFF" will stop blinking. " " icon resumes displaying. Cancel TIMER OFF. Under the condition that TIMER OFF is started up, press "TIMER OFF" button to cancel it.
Note:
● Under on and off status, you can set TIMER OFF or TIMER ON simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
After starting up TIMER ON or TIMER OFF, set the constant circulating valid.
After that, air conditioner will be turned on or turned off according to setting time. ON/OFF button has no effect on setting. If you don’t need this function, please use remote controller to cancel it.
X-FAN button
11
12
Press this button under cool and dry mode to start up x-fan function, and " " icon on remote controller will be displayed. Press this button again to cancel x-fan function, and " "icon will disappear.
Note:
● When x-fan function is on, if the air conditioner is turned off, indoor fan will still operate at low speed for a while to blow the residual water inside the air duct.
● During x-fan operation, press X-FAN button to turn off x-fan function. Indoor fan will stop operation immediately.
TEMP button
By pressing this button, you can see indoor set temperature, indoor ambient temp-
erature or outdoor ambient temperature on indoor unit’s display. The setting on remote controlleris selected circularly as below:
no display
● When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature.
7
Page 12
TURBO button
13
Under COOL or HEAT mode, press this button to turn to quick COOL or quick HEAT mode. " " icon is displayed on remote controller. Press this button again to exit turbo function and " " icon will disappear.
Child lock function
Press "+" and "-" simultaneously to turn on or turn off child lock function. When child lock function is on, " " icon is displayed on remote controller. If you operate the remote controller, the " " icon will blink three times without sending signal to the unit.
Temperature display switchover function
Under OFF status, press "-" and "MODE" buttons simultaneously to switch temp­erature display between ℃ and ℉.
Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn on display light. " " icon is displayed.
SLEEP button
LIGHT button
14
15
● When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
Outdoor temperature display is not available for some models. At that time, indoor
unit receives " "signal, while it displays indoor set temperature.
● It’s defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display.
● When selecting displaying of indoor or outdoor ambient temperature, indoor
temperature indicator displays corresponding temperature and automatically turn
Under COOL, HEAT mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this button again to cancel sleep function and " " icon will disappear.
8
3.4 Function introduction for combination buttons
Page 13
1.
After putting through the power, press "ON/OFF" button on remote controller to
turn on the air conditioner.
2.
Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN,
HEAT.
3.
Press "+" or "-" button to set your required temperature. (Temperature can’t be
adjusted under auto mode).
4.
Press "FAN" button to set your required fan speed: auto, low, medium and high
speed.
5.
Press " " button to select fan blowing angle.
1. Press the back side of remote controller marked
the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar are correct.
3. Reinstall the cover of battery box.
signal sender
battery
Cover of battery box
remove
reinstall
NOTICE
● During operation, point the remote control signal sender at the receiving window on indoor unit.
The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles between them.
or wireless telephone; remote controller should be close to indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the
batteries.
● If the display on remote controller is fuzzy or there’s no display, please replace batteries.
3.5 Operation guide
3.6 Replacement of batteries in remote controller
9
Page 14
10
4 Preparative for Installation
4.1 Standard Accessory Parts
The standard accessory parts listed below are furnished and should be used as
required.
Table 1
Indoor Unit Accessories
No. Name Appearance Q'ty Usage
1 Nut with Washer 8
To fix the hook on the cabinet of the unit.
2
Wireless Controller +
Battery
1+2 To control the indoor unit
3 Insulation 1 To insulate the gas pipe
4 Insulation 1 To insulate the liquid pipe
5 Installation Paperboard 2 To insulate the drain pipe
6 Fastener 4 To fasten the sponge
7 Nut 1 To connect gas pipe
8 Nut 1 To connect liquid pipe
4.2 Selection of the Installation Location
Decide the installation location with the customer as follows:
WARNING!
The unit must be installed where strong enough to withstand the weight of the unit and fixed securely
otherwise the unit would topple or fall off.
CAUTION!
.
Do not install where there is a danger of combustible gas leakage.
.
Do not install the unit near heat source, steam, or flammable gas.
.
Children under 10 years old must be supervised not to operate the unit.
Page 15
11
4.2.1 Indoor Unit
(1). Install the unit at a place where is strong enough to withstand the weight of
the unit.
(2). The air inlet and outlet of the unit should never be clogged so that the
airflow can reach every corner of the room.
(3). Leave service space around the unit as required in Fig. 2
Fig. 2
(4). Install the unit where the drain pipe can be easily installed.
(5). The space from the unit to the ceiling should be kept as much as possible
so as for more convenient service.
4.3 Connection Pipe Requirement
CAUTION!
The maximum length of the connection pipe is listed in the Table below. Do not place the units
between which the distance exceeds the maximum length of the connection pipe.
Page 16
12
Table 2
(1). The connecting pipe should be thermally insulated properly.
(2). The pipe wall thickness shall be 0.5-1.0 mm and the pipe wall shall be able
to withstand the pressure of 6.0 MPa. The longer the connecting pipe, the
lower the cooling and heating effect performs.
(3). The pipe wall thickness shall be 0.5-1.0mm and the pipe wall shall be able
to withstand the pressure of 6.0 MPa. The longer the connecting pipe, the
lower the cooling and heating effect performs.
Item
Model
Size of Fitting Pipe(Inch)
Max.
Pipe
Length
(m)
Max. Height
Difference
between Indoor
Unit and Outdoor
Unit (m)
Indoor unit
Drainage
pipe(Outer
Diameter ×
wall thickness)
(mm)
Liquid Gas
MV-F09BI
MV-F12BI
1/4 3/8 20 10 Φ17×1.75
1/4 1/2 20 10 Φ17×1.75
MV-F18BI
1/4 1/2 20 10 Φ17×1.75
MV-F24BI
3/8 5/8 20 10 Φ17×1.75
4.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 3
Notes:
①.
The fuse is located on the main board.
②.
Install the disconnect device with a contact gap of at least 3 mm in all poles
nearby the units (Both indoor unit and outdoor unit).The appliance must be
positioned so that the plug is accessible.
③.
The specifications of the power cable listed in the Table above
are determined based on the maximum power (maximum amps)
of the unit.
④.
The specifications of the power cable listed in the Table above are applied to
the conduit-guarded multi-wire copper cable (like, YJV copper cable,
consisting of PE insulated wires and a PVC cable jacket) used at 40°С and
resistible to 90°С(see IEC 60364-5-52). If the working condition changes, they
should be modified according to the related national standard.
Indoor Units
Power Supply
Fuse
Capacity
Min. Power
Supply Cord
V/Ph/Hz A mm
2
9~24k
220-240V~
50Hz
5 0.75
Page 17
13
5 Installation of the Unit
5.1 Installation of the Indoor Unit
5.1.1 Indoor unit dimension
Fig. 3
WARNING !
①.
Install the indoor unit in a location which can withstand a load of at least five times the
weight of the main unit and which will not amplify sound or vibration.
②.
If the installation location is not strong enough, the indoor unit may fall and cause injuries.
③.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
Page 18
14
Table 4 Unit: mm
5.1.2 Preparation for Installing the Indoor Unit
(1). Open the air inlet grille and the screw cover, and remove the screws.
(2). Release the claws in the 3 places indicated.
(3). Release the center hook and remove the front panel.
(4). Release the claws in the 2 or 3 places indicated and remove the electric
component cover.
5.1.3 Indoor Unit Installation
(1). Determine the location of the hanger through the paper template, and then
remove the paper template.
Fig. 4
(2). Insert the anchor bolts into the drilled holes, and drive the pins completely
into the anchor bolts with a hammer.
(3). Remove the right and left side panels.
(4). Put the hanger bolt into the clasp of the indoor unit and tighten screws on
the hanger to prevent the indoor unit from moving.
Model A B C D H
MV-F09BI
870 235 812 318 665
MV-F18BI
MV-F12BI
1200 235 1142 318 665
MV-F24BI
Page 19
15
(5). Adjust the height of the unit to make the drain pipe slant slightly downward
so that the drainage will become much smoother.
Floor type
Fig. 5
Ceiling type
Fig. 6
(6). Reinstall and tighten the right and left side panel.
Page 20
16
5.1.4 Leveling
The water level test must be done after installing the indoor unit to make the
unit is horizontal, as shown below.
Fig. 7
5.2 Installation of the Connection Pipe
5.2.1 Flare Processing
(1). Cut the connection pipe with the pipe cutter and remove the burrs.
(2). Hold the pipe downward to prevent cuttings from entering the pipe.
(3). Remove the flare nuts at the stop valve of the outdoor unit and inside the
accessory bag of the indoor unit, then insert them to the connection pipe,
after that, flare the connection pipe with a flaring tool.
(4). Check if the flare part is spread evenly and there are no cracks (see Fig. 8).
Fig. 8
Page 21
17
5.2.2 Bending Pipes
(1). The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 9
(2). Do not bend the pipes in an angle more than 90°.
(3). When pipes are repeatedly bent or stretched, the material will harden,
making it difficult to bend or stretch them any more. Do not bend or stretch
the pipes more than three times.
(4). When bending the pipe, do not bend it as is.
The pipe will be collapsed. In this case, cut
the heat insulating pipe with a sharp cutter as
shown in Fig. 10, and bend it after exposing
the pipe. After bending the pipe as you want,
be sure to put the h
eat insulating pipe back
on the pipe, and secure it with tape.
Fig. 10
CAUTION!
①.
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
curvature of 150 mm or over.
②.
If the pipe is bent repeatedly at the same place, it will break.
Page 22
18
5.2.3 Connecting the Pipe at the Indoor Unit Side
Detach the caps and plugs from the pipes.
When connecting the pipe to the unit or removing it from the unit, please do use
both the spanner and the torque wrench. (Fig. 11)
When connecting, smear both inside and outside of the flare nut with
refrigeration oil, screw it hand tight and then tighten it with the spanner.
Refer to Table 7 to check if the wrench has been tightened properly (too tight
would mangle
the nut and lead to leakage).
Examine the connection pipe to see if it leaks, then take the treatment of heat
insulation, as shown in the Fig. 12.
Use the medium-sized sponge to insulate the coupler of the gas pipe.
Fig. 11
Fig. 12
Table 5 Flare nut tightening torque
CAUTION!
①.
Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is
improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
②.
Do not remove the flare nut until the connection pipe is to be connected so as to prevent dust and impurities from coming into the pipe system.
Page 23
19
Pipe Diameter Tightening Torque
1/4
〞(
Inch
15-30 (N·m)
3/8
〞(
Inch
35-40 (N·m)
1/2
〞(
Inch
45-50 (N·m)
5/8
〞(
Inch
60-65 (N·m)
3/4
〞(
Inch
70-75 (N·m)
7/8
〞(
Inch
80-85 (N·m)
5.2.4 Connecting the Pipe at the Outdoor Side Unit
5.2.5 Checking the Pipe Connections for Gas Leaking
For both indoor and outdoor unit side, check the joints for gas leaking by the
use of a gas leakage detector without fail when the pipes are connected.
5.2.6 Heat Insulation on the Pipe Joints (Indoor Side Only)
Stick coupler heat insulation (large and small) to the place where connecting
pipes.
Fig. 14
CAUTIO N!
Be sure to connect the gas pipe after connecting the liquid pipe completely.
Tighten the flare nut of the connection pipe at the
outdoor unit valve connector. The tightening method is
the same as that as at the indoor side
Fig. 13
Page 24
20
5.2.7 Liquid Pipe and Drain Pipe
5.3 Vacuum and Gas Leakage Inspection
(1). If the outdoor unit is installed lower
than the indoor unit. (See Fig. 15)
1). A drain pipe should be above
ground and the
end of the pipe
does not dip into water. All pipes
must be restrained to the wall by
saddles.
2). Taping pipes must be done from
bottom to top.
3). All pipes are bound together by
tape and restrained to wall by
saddles.
Fig. 15
(2). If the outdoor unit is installed higher
than the indoor unit.
1). Taping should be done from lower
to the upper part.
2). All pipes are bound and taped
together and also should be
trapped to prevent water from
returning to the room (See Fig. 16)
3). Restraint all pipes to the wall with
saddles.
Fig. 16
CAUTION!
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is
no extra refrigerant in the outdoor unit for air purging!
Page 25
21
valves should be kept closed in case of refrigerant leak.
(3). Connect the hose used for evacuation to the vacuum pump.
(4). Open the switch at the lower pressure side of the manifold valve assembly
and start the vacuum pump. Meanwhile, the switch at the high pressure
side of the manifold valve assembly should be kept closed, otherwise
evacuation would fail.
(5). The evacuation duration depends on the unit’s capacity, generally, 20
minu
tes for the 9k/12k/18k units, 30 minutes for the 24k units. And verify if
the pressure gauge
at the low pressure side of the manifold valve assembly
reads -1.0Mp (-75cmHg), if not, it indicates there is leak somewhere. Then,
close the switch fully and then stop the vacuum pump.
(6). Wait for some time to see if the system pressure can remain unchanged, 5
minutes for the 9k/12k/18k/24k units. During this time, the reading of the
pressure gauge at the low pressure side can not be larger than 0.005Mp
(0.38cmHg).
(7). Slightly open the liquid valve and let some refrigerant go to
the connection
pipe to balance
the pressure inside and outside of the connection pipe, so
that air will not come into the connection pipe when removing the hose.
Note that the gas and liquid valve can be opened fully only after the
manifold valve assembly is removed.
(8). Place back the caps of the liquid valve, gas valve and also the service port.
5.3.1 Vacuum
(1). Remove the caps of the liquid valve, gas valve and also the service port.
(2). Connect the hose at the low pressure side of the manifold valve assembly
to the service port of the unit’s gas valve, and meanwhile the gas and liquid
Page 26
22
service ports to quicken the evacuating speed.
Fig. 17
Note: For the large-sized unit, it has the service port for both the gas valve and the liquid valve.
During evacuation, it is available to connect two hoses of the manifold valve assembly to two
5.4 Installation of the Drain Pipe
5.4.1 Precautions When Doing the Piping Work
CAUTION!
Install the drain hose in accordance with the instructions in this installation manual and keep the
area warm enough to prevent condensation. Problems with the piping may lead to water leaks.
Page 27
23
(1). Keep piping as short as possible and slope it downwards at a gradient of at
least 1/100 so that air may not remain trapped inside the pipe.
(2). Keep pipe size equal to or greater than that of the connecting pipe.
(3). Install the drain piping as shown and take measures against condensation.
Improperly rigged piping could lead to leaks and eventually wet furniture
and belongings.
Fig. 19
(4). Connect the drain hose.(Fig. 20)
Fig. 20
5.4.2 Installing the Drain Pipes
(1). For determining the position of the drain hose, perform the following
procedures.
(2). Insert the drain pipe to the drain outlet of the unit and then tighten the
clamp securely with tape. (Fig. 21)
(3). Connect the extension drain pipe to the drain pipe and then tighten the
clamp with tape.
Page 28
24
Fig. 21 Fig. 22 Fig. 23
Tighten the clamp until the screw head is less than 4 mm from the hose. (Fig.
22)
- Metal clamp②- Drain hose③- Grey tape
Insulate the pipe clamp and the drain hose using heat insulation sponge. (Fig.
23)
- Metal clamp ②- Insulation sponge
(1). When drain hose requires extension, obtain an extension hose
commercially available.
(2). After connecting the local drain hose,
tape the slits of the heat insulation
tube.
(3). Connect the
drain hose to the local drain pipe. Position the inner
connecting wire in the same direction as the piping.
5.4.3 Connecting the Drain Hose
(1). Connect the extension auxiliary pipe to the local piping.
(2). Prepare the local piping at the connection point for the drain pipe, as
shown in the installation drawings.
Note: Be sure to place the drain hose as shown in the diagram below, in a downward sloping
direction.
Page 29
25
Fig. 24
5.4.4 Testing of Drain Piping
(1).
After piping work is finished, check if drainage flows smoothly.
(2).
As shown in the Figure, pour water into the drain pan from the right side to
check that water flows smoothly from the drain hose.
Fig. 25
5.5 Electrical Wiring
5.5.1 Wiring Precautions
WARNING!
①.
Before obtaining access to terminals, all supply circuits must be disconnected.
②.
The rated voltage of the unit is as shown as Table 3
③.
Before turning on, verify that the voltage is within the 185~264V range (for single phrase
unit) or 342~457V range (for three-phrase unit).
④.
Always use a special branch circuit and install a special receptacle to supply power to the
air conditioner.
Page 30
26
5.5.2 Electrical Wiring
(1). For solid core wiring (Fig. 26)
1). Cut the wire end with a wire cutter or wire-cutting pliers, then strip the
insulation about 25 mm (15/16").
2). Using a screwdriver, remove the terminal screw(s) on the terminal board.
3). Using pliers, bend the solid wire to form a loop suitable for the terminal
screw.
4). Shape the loop wire properly, place it on the terminal board and tighten
securely with the terminal screw using a screwdriver.
(2). For strand wiring (Fig. 26)
1). Cut the wire end with a wire cutter or wire-cutting pliers, then strip the
insulation about 10 mm (3/8").
2). Using a screwdriver, remove the terminal screw (s) on the terminal board.
3). Using a round terminal fastener or pliers, securely clamp a round terminal
to each stripped wire end.
4). Position the round terminal wire, and replace and tighten the terminal
screw with a screwdriver.(Fig. 27
)
⑤.
.
The special branch circuit breaker is installed in the permanent wiring. Always use a circuit
that can trip all the poles of the wiring and has an isolation distance of at least 3 mm
between the contacts of each pole.
⑦.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Install a leakage special branch circuit breaker in accordance with the related laws and regulations and electric company standards.
CAUTION!
①.
The power source capacity must be the sum of the air conditioner current and the current
of other electrical appliances. When the current contracted capacity is insufficient, change
the contracted capacity.
②.
When the voltage is low and the air conditioner is difficult to start, contact the power
company to raise the voltage.
Page 31
27
Fig. 26
Fig. 27 Fig. 28
(3). How to fix connection cord and power cord by cord clamp
After passing the connection cord fasten it with the cord clamp. (Fig. 28)
WARNING!
①.
Before starting work, check that power is not being supplied to the indoor unit and outdoor
unit.
②.
Match the terminal block numbers and connection cord colors with those of the indoor unit side.
③.
Erroneous wiring may cause burning of the electric parts.
④.
Connect the connection cords firmly to the terminal block. Imperfect installation may cause
a fire.
⑤.
Always fasten the outside covering of the connection cord with cord clamps. (If the
insulator is not clamped, electric leakage may occur.)
⑥.
Always connect the ground wire.
Page 32
28
(4). Electric wiring between the indoor and outdoor units
Single-phase units (9~24k)
Outdoor unit connection
N(1) 2 3
blue brownblack
yellow­green
Page 33
29
(5). Electric wiring of indoor unit side
Remove the left cover plate and the electric box cover then insert the end of the
communication cord and the power cable into the terminal board.
Fig. 30
CAUTION!
. Tighten the power cord respectively on the terminal boards with screws. Faulty
connection may cause a fire.
.
If the power supply are wired incorrectly, the air conditioner may be damaged.
. Connect the indoor unit connection cord properly based on the corresponding marks as
shown in Fig. 29.
. Ground both the indoor and outdoor units by attaching a ground wire.
. Unit shall be grounded in compliance with the applicable local and national codes.
6 Installation of Controllers
Refer to the Installation Manual of the controller for more details.
Page 34
30
7 Test Running
7.1 Trial Operation and Testing
(1).
The meaning of error codes as shown below:
Table 7
Note: If there're other error codes, please contact qualified professionals for service.
When the unit is connected with the wired controller, the error code will be simultaneously shown on it.
(2).
Instructions to the Error Indicating Lamps on the Panel of the Floor Ceiling
Type Unit.
Fig. 31
Number Error code Error
1 E1 Compressor high pressure protection
2 E2 Indoor anti-freeze protection
3 E3
Compressor low pressure protection, refrigerant lack
protection and refrigerant colleting mode
4 E4 Compressor high discharge temperature protection
6 E6 Communication error
9 F1 Indoor ambient temperature sensor is open/short circuited
10 F2 Indoor evaporator temperature sensor is open/short circuited
11 F3 Outdoor ambient temperature sensor is open/short circuited
12 F4 Outdoor condenser temperature sensor is open/short circuited
Outdoor discharge temperature sensor is open/short circuited
13 F5
14 C5
15 EE
5 E5
8 E8
7 E7
Loading EEPROM malfunction
Anti-high temperature protection
Jumper cap malfunction protection
AC over-current protection
Mode conflict
Page 35
31
States of the Indicating Lamps:
①.
Indicating Lamp of “POWER”:
The indicating lamp will shine when power on, while it will go out when power
off.
②.
Indicating Lamp of “COOL” :
The indicating lamp will shine when “COOL” is activated, while it will go out
when “COOL” is deactivated.
③.
Indicating Lamp of “HEAT”:
The indicating lamp will shine when “HEAT” is activated, while it will go out
when “HEAT” is deactivated.
④.
Indicating Lamp of “TIMER”
Timer indicator on indoor unit will be on when timer ON is set under off status and
timer OFF is set under on status.
(1) If the light of indoor unit is turned off, when operating the remote controller to send
NOTE:
command, the display will be on for 3s and then off.
(2) When the wired controller is connected, the indoor unit display is invalid and the unit won’t receive the remote control command.
Page 36
32
8 Troubleshooting and Maintenance
8.1 Troubleshooting
If your air-conditioning unit suffers from abnormal operation or failure, please
first check the following points before repair:
Table 9
Note: After carrying out the check of the above items and taking relevant measures to solve
the problems found but the air-conditioning unit still does not function well, please stop the
operation of the unit immediately and contact the local service agency designated by Gree.
Only ask professional serviceman to check and repair the unit.
Failure Possible Reasons
The unit cannot be
started.
①.
The power supply is not connected.
②.
Electrical leakage of air-conditioning unit causes tripping of the
leakage switch.
③.
The operating keys are locked.
④.
The control loop has failure.
The unit operates for a
while
and then stops.
①.
There is obstacle in front of the condenser.
②.
The control loop is abnormal.
③.
Cooling operation is selected when the outdoor ambient temperature is above 46°C.
Poor cooling effect.
①.
The air filter is dirty or blocked.
②.
There is heat source or too many people inside the room.
③.
The door or window is open.
④.
There is obstacle at the air intake or outlet.
⑤.
The set temperature is too high.
⑥.
There is refrigerant leakage.
⑦.
The performance of room temperature sensor becomes worse
Poor heating effect
①.
The air filter is dirty or blocked.
②.
The door or window is not firmly closed.
③.
The set room temperature is too low.
④.
There is refrigerant leakage.
⑤.
The outdoor ambient temperature is lower than -5°C.
⑥.
Control loop is abnormal.
Page 37
33
8.2 Routine Maintenance
(1). Disassembly method of filter screen and electric box cover
WARNING!
①.
Do turn off the unit and cut off the main power supply when cleaning the air conditioner,
otherwise electric shock may happen.
②.
Do not make the air conditioner wet or electric shock may be lead; Ensure that the air
conditioner will not be cleaned by water rinsing under any circumstance.
③.
Volatile liquid like thinner or gasoline would damage the appearance of air conditioner. (So,
only soft dry cloth and wet cloth moistened by neutral cleaning fluid could be used to clean the surface panel of air conditioner.)
1. Open the air inlet grille
①.
Firstly unfix two buckles on the grille as shown on the picture.
②.
Remove the screws under the buckles by a
screwdriver and then open the inlet grille.
2.Clean the filer screen
Clean the filer screen by a vacuum cleaner or
wash it by flashing water. If the oil stain on the filter can not be removed or cleaned up, wash it by warm
water meld with the detergent. Dry the filer in the
shadow.
Note: Never use hot water over 45
in case of
color fading or turning yellow.
Never dry it by fire so as to prevent the filter
caught fire or deformation.
3.Disassemble the left and right side board
①.
After the grille is removed, use a screwdriver to remove the screws shown on the picture.
②.
Push the side plate as per the arrowed
direction and take it down.
4. Disassemble the right side board
Disassembly method of right side board
Step 3
Page 38
NOTE CONCERNING PROTECTION OF ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal procedures. The materials are recyclable in accordance with their respective symbols. By means of re-use, material recycling or any other form of recycling old appliances you are making an important contribution to the protection of our environment. Please ask your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT MEDIUM
This unit is containing fluorinated gases included in the Kyoto protocol. The maintenance and the liquidation must be carried out by qualified personnel. Type of refrigerant: R32 The quantity of the refrigerant: please see the unit label. The value GWP: 675 (1 kg R32 = 0,675 t CO2 eq) GWP = Global Warming Potential
Appliance filled with flammable gas R32.
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain
www.sinclair-world.com
This product was manufactured in China (Made in China).
REPRESENTATIVE
SINCLAIR EUROPE spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
TECHNICAL SUPPORT
NEPA spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
Tel.: +420 800 100 285
Fax: +420 541 590 124
www.sinclair-solutions.com info@sinclair-solutions.com
Loading...