Sinclair MULTI VARIABLE SERIES, MV-D12BI, MV-D24BI, MV-D18BI, MV-D09BI Service Manual

Page 1
MULTI VARIABLE SERIES
DUCT
MV-DxxBI
SERVICE MANUAL
EN
Page 2
“Originalinstructions”
IMPO
RTANT N
OTE:
Read this manual ca
r
efully befo
r
e installing
or operating your new air conditioning unit. Make sure to save this manual for futu
re r
efe
r
ence.
Page 3
Service Manual
Table of Contents
Part
: Technical Information
.......................................................................1
1. Summary
......................................................................................................................1
2. Specications
..........................................................................................................2
3. Outline Dimension Diagram
........................................................................6
4. Refrigerant System Diagram
......................................................................7
5. Electrical Part
...........................................................................................................8
5.1 Wiring Diagram .................................................................................................................8
5.2 PCB Printed Diagram .......................................................................................................9
6. Function and Control
......................................................................................10
6.1 Remote Controller Introduction .....................................................................................10
6.2 Brief Description of Modes and Functions ......................................................................14
6.3 Wired Remote Controller XK19 ......................................................................................16
Part
: Installation and Maintenance
................................................25
7. Indoor Unit Installation
................................................................................25
8. Maintenance
............................................................................................................36
8.1 Error Code List ...............................................................................................................36
8.2 Troubleshooting for Main Malfunction ............................................................................37
9. Exploded View and Parts List
.................................................................41
10. Removal Procedure
.......................................................................................47
Page 4
1
Service Manual
1. Summary
Part
: Technical Information
Indoor Unit
MV-D09BI MV-D12BI MV-D18BI MV-D24BI
Remote Controller
YT1F(MOTO)
Page 5
2
Service Manual
Parameter Unit Value
Model
MV-D09BI MV-D12BI
Product Code CN210N0150 CN210N0160
Power
Supply
Rated Voltage V~ 220-240 220-240 Rated Frequency Hz 50 50
Phases 1 1 Cooling Capacity W 2500 3500 Heating Capacity W 2800 3850 Air ow volume(SH/H/M/L/SL) m
3
/h -/450/350/280/- -/550/400/300/­Dehumidifying Volume L/h 0.8 1.4 Fan Type Centrifugal Centrifugal Fan Diameter-height mm Φ139.45-134.62 Φ139.45-134.62 Fan Motor Speed rpm 950/750/650/550 1000/920/780/720 Fan Motor Power Output W 40 30 Fan Motor Power Input W 75 65 Motor Full Load Amp(FLA) A 0.34 0.34 Fan Motor Capacitor μF 3.0 3.0
Evaporator Material Inner Groove Copper -Aluminum Inner Groove Copper -Aluminum Evaporator Pipe Diameter mm Φ7 Φ7 Evaporator Number of Rows-Fin Pitch mm 2-1.6 3-1.6
Evaporator Length(L)XHeight(H)XWidth(W) mm 527X209.55X25.4 527X209.55X25.4
Fuse Current A 3.15 3.15
Sound Pressure Level(SH/H/M/L/SL) dB (A) 37/34/31/47/41 39/35/32/49/42 Sound Power Level(SH/H/M/L/SL) dB (A) 47/44/41/57/51 49/45/42/59/52
Dimension of Outline(LXWXH) mm 700X615X200 700X615X200 Dimension of Carton Box(LXWXH) mm 890X740X290 890X740X290
Dimension of Package(LXWXH) mm 893X743X305 893X743X305 Net Weight kg 21 22 Gross Weight kg 26 28 Liquid pipe mm Φ6 Φ6 Gas Pipe(to indoor unit) mm Φ9.52 Φ9.52
2. Specications
2.1 Specication Sheet
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Page 6
3
Service Manual
Parameter Unit Value
Model
MV-D18BI
Product Code CN210N0170
Power
Supply
Rated Voltage V~ 220-240 Rated Frequency Hz 50
Phases 1 Cooling Capacity W 5000 Heating Capacity W 5500 Air ow volume(SH/H/M/L/SL) m
3
/h -/700/600/500/­Dehumidifying Volume L/h 1.8 Fan Type Centrifugal Fan Diameter-height mm Φ139.45-134.62 Fan Motor Speed rpm 1140/955/755/670 Fan Motor Power Output W 40 Fan Motor Power Input W 80 Motor Full Load Amp(FLA) A 0.51 Fan Motor Capacitor μF 3.0
Evaporator Material Inner Groove Copper -Aluminum Evaporator Pipe Diameter mm Φ7 Evaporator Number of Rows-Fin Pitch mm 3-1.6
Evaporator Length(L)XHeight(H)XWidth(W) mm 725X209.55X38.1
Fuse Current A 3.15
Sound Pressure Level(SH/H/M/L/SL) dB (A) 41/33/51/43/- Sound Power Level(SH/H/M/L/SL) dB (A) 51/43/61/53/-
Dimension of Outline(LXWXH) mm 900X615X200 Dimension of Carton Box(LXWXH) mm 1120X740X290 Dimension of Package(LXWXH) mm 1123X743X305 Net Weight kg 26
Gross Weight kg 32 Liquid pipe mm Φ6 Gas Pipe(to indoor unit) mm Φ12
The above data is subject to change without notice. Please refer to the nameplate of the unit.
MV-D24BI
CN210N0130
220-240
50
1 7100 8000
-/1000/750/550/-
2.5
Centrifugal
Φ139.45-134.62
1185/1070/910/810
80.00
110.00
0.64
3.50
Inner Groove Copper -Aluminum
Φ7
3-1.6
925X209.55X38.1
3.15
42/34/52/44/-
52/44/62/55/­1100X615X200 1320X740X290 1323X743X305
30 40
Φ9.52
Φ16
Page 7
5
Service Manual
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27ć
DB, 19ć
WB. Outdoor Temperature is 35ćDB. The rated heating capacity data is measured under the following
work condition: Indoor Temperature is 20ćDB. Outdoor Temperature is 7ćDB, 6ćWB.
b.
The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
Working Temperature Range
Sorts
etats edis roodnI
Dry bulb temp. ć Wet bulb temp. ć
Rated Cooling 27 19
Max. cooling 32 23
Min. cooling 21 15
Rated Heating 20 15
Max. heating 27
Min. heating 20 15
Page 8
6
Service Manual
3. Outline Dimension Diagram
Unit:mm
Item
Model
A B C D E F G H I J
MV-D09BI
742 491 662 620 700 615 782 156 200 635
MV-D12BI
MV-D18BI
942 491 862 820 900 615 982 156 200 635
1142 491 1062 1020 1100 615 1182 156 200 635
MV-D24BI
Page 9
7
Service Manual
4. Refrigerant System Diagram
Schematic Diagram of Super Free Match Series Inverter Heat Pump Multi System
The units start to work once the power is switched on.
During the cooling operation, the low temperature, low pressure refrigerant gas from the heat exchanger of
each indoor unit gets together and then is taken into the compressor to be compressed into high temperature, high
pressure gas, which will soon go to the heat exchanger of the outdoor unit to exchange heat with the outdoor air
and then is turned into refrigerant liquid. After passing through the BU module, the temperature and pressure of
the refrigerant liquid will further decrease and then go the main valve. After that, it will be divided and go to the
heat exchanger of each indoor unit to exchange heat with the air which needs to be conditioned. Consequently, the
refrigerant liquid become low temperature, low pressure refrigerant gas again. Such a refrigeration cycle goes
round and round to achieve the desired refrigeration purpose.
During the heating operation, the four-way valve is involved to make the refrigeration cycle run reversely.
The refrigerant radiates heat in the heat exchanger of the indoor unit (so do the electric heating devices) and
absorb heat in the heat exchanger of the outdoor unit for a heat pump heating cycle so as to achieve the desired
heating purpose.
Page 10
8
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Indoor Unit
● Instruction
Symbol Symbol Color Symbol Symbol Color Symbol Name
WH White GN Green CAP Jumper cap
YE Yellow BN Brown COMP Compressor
RD Red BU Blue Grounding wire
YEGN Yellow/Green BK Black / /
VT Violet OG Orange / /
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
63625690
These circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
0
&1&1
57 57
0
. .
$3
75$16)250(5
&
3(
1&1&
(<.%*2%8
%1
5'
:+
$3
&1 &1&1
$3
<(*1
)$102725
/,48,' 3803
3$1(/ %2$5' 7(03 7(03
6(1625 6(1625
7&
8QLW
2XWGRRU
%. %1
%8
3(
3(
6:,7&+
5(&(,9,1*0$18$/ (19,250(173,3(
/
/
Ė
Ę
ė
0$*1(7,& 5,1*
127($3LVRSWLQDODFFHVRUU\ ZKHQ$3DQG$3DUHFRQQHFWHG DWWKHVDPHWLPH$3LVWKH GHIDXOWGHYLFH
75287
75,1
&1
3PLG ,Q(QY
;
;1
;$&/
&1
1
;7
1
Page 11
9
Service Manual
5.2 PCB Printed Diagram
No. Name
1
Fan terminal
7
Communication terminal for indoor unit and outdoor unit
2
Water pump terminal
8
Liquid level switch inspection
3 Live wire 9 Output terminal of transformer
4
Neutral wire
10
Ambient temperature sensor
5
Fuse
11
Tube temperature sensor
6
Transformer input
12
Wired controller
Top view
Bottom view
1
23 45 6
78
910
1112
Page 12
10
Service Manual
6. Function and Control
6.1 Remote Controller Introduction
operation mode
auto mode
cool mode
dry mode
fan mode
heat mode
clock
sleep mode
Note:
set fan speed
send signal
X-fan mode
ventilation operation
set temperature
turbo mode
set time
TIMER ON/TIMER OFF
child lock
light
swing
Temp. display type
:set temp. :outdoor ambient temp.
:indoor ambient temp.
health function I feel
2
3
6
8
11
13
14
1
7
4
5
9
10
12
15
This is a general use remote controller
, it could be used for the air conditioners with multifunction; For some function, which the model
don't have, if press the corresponding button on the remote controller that the unit will keep the original running status
.
Page 13
11
Service Manual
AUTO COOL DRY FAN HEAT
Page 14
12
Service Manual
(horizontal louvers stops at current position)
no display
no display
Page 15
13
Service Manual
Sketch map for
replacing batteries
Page 16
14
Service Manual
6.2 Brief Description of Modes and Functions
1.Basic function of system
(1)Cooling mode
(1) Under this mode, fan and swing operates at setting status. Temperature setting range is 16~30ºC.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(2)Drying mode
(1) Under this mode, fan operates at low speed and swing operates at setting status. Temperature setting range is 16~30ºC.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(3) Protection status is same as that under cooling mode.
(4) Sleep function is not available for drying mode.
(3)Heating mode
(1) Under this mode, Temperature setting range is 16~30ºC.
(2) Working condition and process for heating mode:
When turn on the unit under heating mode, indoor unit enters into cold air prevention status. When the unit is stopped or at OFF status,
and indoor unit has been started up just now, the unit enters into residual heat-blowing status.
(4)Working method for AUTO mode:
1.Working condition and process for AUTO mode:
a.Under AUTO mode, standard heating Tpreset=20ºC and standard cooling Tpreset=25ºC. The unit will switch mode automatically
according to ambient temperature.
2.Protection function
a. During cooling operation, protection function is same as that under cooling mode.
b. During heating operation, protection function is same as that under heating mode.
3. Display: Set temperature is the set value under each condition. Ambient temperature is (Tamb.-Tcompensation) for heat pump unit
and Tamb. for cooling only unit.
4. If theres I feel function, Tcompensation is 0. Others are same as above.
(5)Fan mode
Under this mode, indoor fan operates at set fan speed. Compressor, outdoor fan, 4-way valve and electric heating tube stop operation.
Indoor fan can select to operate at high, medium, low or auto fan speed. Temperature setting range is 16~30ºC.
2. Other control
(1) Buzzer
Upon energization or availably operating the unit or remote controller, the buzzer will give out a beep.
(2) Auto fan
Heating mode: During auto heating mode or normal heating ode, auto fan speed will adjust the fan speed automatically according to
ambient temperature and set temperature.
(3) Sleep
After setting sleep function for a period of time, system will adjust set temperature automatically.
(4) Timer function:
General timer and clock timer functions are compatible by equipping remote controller with different functions.
(5) Memory function
memorize compensation temperature, off-peak energization value.
Memory content: mode, up&down swing, light, set temperature, set fan speed, general timer (clock timer cant be memorized).
After power recovery, the unit will be turned on automatically according to memory content.
(6)Refrigerant recovery function:
(1) Enter refrigerant recycling function
Within 5min after energizing (unit ON or OFF status is ok), continuously press LIGHT button for 3 times within 3s to enter refrigerant
recycling mode; Fo is displayed and refrigerant recycling function is started. At this moment, the maintenance people closes liquid
valve. After 5min, stick the thimble of maintenance valve with a tool. If there is no refrigerant spraying out, close the gas valve
immediately and then turn off the unit to remove the connection pipe.
Page 17
15
Service Manual
(2) Exit refrigerant recycling function
After entering refrigerant recycling mode, when receive any remote control signal or enter refrigerant recycling mode for 25min, the unit will
exit refrigerant recycling mode automatically If the unit is in standby mode before refrigerant recycling, it will be still in standby mode after
nishing refrigerant recycling; if the unit is in ON status before refrigerant recycling, it will still run in original operation mode.
(7)Off-peak energization function:
Adjust compressors minimum stop time. The original minimum stop time is 180s and then we change to:
The time interval between two start-ups of compressor cant be less than 180+T s(0≤T≤15). T is the variable of controller. Thats to say
the minimum stop time of compressor is 180s~195s. Read-in T into memory chip when refurbish the memory chip each time. After power
recovery, compressor can only be started up after 180+T s at least.
(8) X-fan mode
When X-fan function is turned on, after turn off the unit, indoor fan will still operate at low speed for 2min and then the complete unit will be
turned off. When x-fan function is turned off, after turn off the unit, the complete unit will be turned off directly.
(9) 8º heating function
Under heating mode, you can set 8º heating function by remote controller. The system will operate at 8ºset temperature.
(10) Turbo fan control function
Set turbo function under cooling or heating mode to enter into turbo fan speed. Press fan speed button to cancel turbo wind.
No turbo function under auto, dry or fan mode.
Page 18
16
Service Manual
6.3 Wired Remote Controller XK19
Page 19
17
Service Manual
Page 20
18
Service Manual
Page 21
19
Service Manual
Page 22
20
Service Manual
Page 23
21
Service Manual
memmorizing
memmorizing
Page 24
22
Service Manual
Page 25
23
Service Manual
Page 26
24
Service Manual
Page 27
25
Service Manual
Part
: Installation and Maintenance
7. Indoor Unit Installation
7.1
7.1.1
7.1.2
7.1.3
Page 28
26
Service Manual
09/12K
18K
24K
7.1.4
7.1.5
Page 29
27
Service Manual
7.1.6
Page 30
28
Service Manual
7.1.7
7.1.8
Page 31
29
Service Manual
Page 32
30
Service Manual
7.1.9
7.1.10
Page 33
31
Service Manual
7.1.11
7.1.12
Page 34
32
Service Manual
7.1.13
Page 35
33
Service Manual
The Refrigerant
●To realize the function of the air conditioner unit, a special refrigerant circulates .
leads to explosion
. It can
● Compared to common refrigerants, R32 is a nonpolluting refrigerant with no
lower. R32 has got very good thermodynamic features which lead to a really high
WARNING:
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.Should repair be necessary, contact your nearest authorized Service Centre.
The appliance shall be stored in a room without continuously operating ignition
electric heater.) Do not pierce or burn.
than “X”m (see table 1).(only applies to appliances that are not fixed appliances)
Appliance shall be installed, operated and stored in a room with a floor area larger
2
’s
instructions only. Be aware that refrigrants not contain odour. Read specialist’s manual.
Please read this operating manual carefully before operating the unit.
to the material objects for reference.
Page 36
34
Service Manual
All the work men who are engaging in the refrigeration system should bear the valid certification awarded by the authoritative organization and the qualification for dealing with the refrigeration system recognized by this industry. If it needs other technician to maintain and repair the appliance, they should be supervised by the person who bears the qualification for using the flammable refrigerant.
It can only be repaired by the method suggested by the equipment’s manufacturer.
Qualification requirement for installation and maintenance man
Installation notes
The air conditioner is not allowed to use in a room that has running fire (such as fire
source, working coal gas ware, operating heater).
Maintenance notes
Welding
Check whether the maintenance area or the room area meet the requirement of the nameplate.
- It’s only allowed to be operated in the rooms that meet the requirement of the Check whether the maintenance area is well-ventilated.
- The continuous ventilation status should be kept during the operation process. Check whether there is fire source or potential fire source in the maintenance area.
- The naked flame is prohibited in the maintenance area; and the “no smoking”
warning board should be hanged.
nameplate.
Check whether the appliance mark is in good condition.
- Replace the vague or damaged warning mark.
If you should cut or weld the refrigerant system pipes in the process of maintaining,
please follow the steps as below:
It is not allowed to drill hole or burn the connection pipe. The air conditioner must be installed in a room that is larger than the minimum room
area. The minimum room area is shown on the nameplate or following table a. Leak test is a must after installation.
table a - Minimum room area ( m )
2
Charge amount (kg)
≤1.2 1.31.4 1.51.6 1.71.8 1.92 2.12.2 2.32.4 2.5
4
4
4
4
14.5 16.8 19.322 24.8 27.831 34.3 37.8 41.5 45.4 49.4 53.6
5.26.1 77.9 8.910 11.2 12.4 13.615 16.3 17.8 19.3
4.24.6 55.5 6
4
4444
floor location
wall mounted
window mounted
ceiling mounted
Minimum
room
2
area( m )
Safety operation of flammable refrigerant
a. Shut down the unit and cut power supply b. Eliminate the refrigerant c. Vacuuming d. Clean it with N2 gas e. Cutting or welding f. Carry back to the service spot for welding
The refrigerant should be recycled into the specialized storage tank.
Make sure that there isn’t any naked flame near the outlet of the vacuum pump and it’s well-ventilated.
4
4444
4
4444
444
444
Page 37
35
Service Manual
other technician to maintain and repair the appliance, they should be supervised by the person who bears the qualification for using the flammable refrigerant.
It can only be repaired by the method suggested by the equipment’s manufacturer.
Installation notes
The air conditioner is not allowed to use in a room that has running fire (such as fire source, working coal gas ware, operating heater).
Maintenance notes
Welding
Check whether the maintenance area or the room area meet the requirement of the nameplate.
- It’s only allowed to be operated in the rooms that meet the requirement of the Check whether the maintenance area is well-ventilated.
- The continuous ventilation status should be kept during the operation process.
Check whether there is fire source or potential fire source in the maintenance area.
- The naked flame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged.
nameplate.
Check whether the appliance mark is in good condition.
- Replace the vague or damaged warning mark.
If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below:
It is not allowed to drill hole or burn the connection pipe.
The air conditioner must be installed in a room that is larger than the minimum room
area. The minimum room area is shown on the nameplate or following table a. Leak test is a must after installation.
table a - Minimum room area ( m )
2
Charge amount (kg)
≤1.2 1.31.4 1.51.6 1.71.8 1.922.12.2 2.32.4 2.5
4
4
4
4
14.5 16.8 19.322 24.8 27.831 34.3 37.8 41.5 45.4 49.4 53.6
5.26.1 77.9 8.910 11.2 12.4 13.615 16.3 17.8 19.3
4.24.6 55.5 6
4
4444
floor location
wall mounted
window mounted
ceiling mounted
Minimum
room
2
area( m )
Filling the refrigerant
Safety instructions for transportation and storage
a. Shut down the unit and cut power supply b. Eliminate the refrigerant c. Vacuuming d. Clean it with N2 gas e. Cutting or welding f. Carry back to the service spot for welding
The refrigerant should be recycled into the specialized storage tank.
Make sure that there isn’t any naked flame near the outlet of the vacuum pump and it’s well-ventilated.
Use the refrigerant filling appliances specialized for R32. Make sure that different
kinds of refrigerant won’t contaminate with each other.
After filling is finished, please do the leakage detection before test running; another
time of leak detection should be done when it’s removed.
Please use the flammable gas detector to check before unload and open the container.
No fire source and smoking. According to the local rules and laws.
The refrigerant tank should be kept upright at the time of filling refrigerant.
Stick the label on the system after filling is finished (or haven’t finished).
Don’t overfilling.
4
4444
4
4444
444
444
Page 38
36
Service Manual
8. Maintenance
8.1 Error Code List
In defect of refrigerant
The Dual-8 Code Display will show F0 and the complete unit stops.
1. In defect of refrigerant;
2. Indoor evaporator temperature sensor works abnormally;
3. The unit has been plugged up somewhere.
F0
5
E9
Water level switch
If cut-off of water level switch is detected for 8s successively once energized, the system will enter full water protection. In this case, switch off the unit and then switch it on to eliminate this malfunction.
Full water protection
Page 39
37
Service Manual
8.2 Troubleshooting for Main Malfunction
●Indoor unit:
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process:
Is the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
Start
Insert the temperature
sensor tightly
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Replace it with a
temperature sensor with
the same model
Make the parts upright
Is there short circuit due to trip-
over of the parts
Is the temperature sensor normal
according to the resistance table?
Replace the mainboard with
the same model.
End
Page 40
38
Service Manual
2. Communication malfunction E6
Start
Cut off power supply. Check if connection line of IDU and ODU and the wire inside electric box are correctly connected.
Correct connection?
Main board matches
with display board? Main board of
IDU matches with that of ODU?
Communication cord is damaged?
Replace IDU's main board
Malfunction eliminated?
End
Connect the line according to wiring diagram.
Match correctly according to product specification
Replace communication cord
Replace ODU's main board.
Malfunction eliminated?
Malfunction eliminated?
Malfunction eliminated?
yes
yes
yes
yes
yes
yes
yes
no
no
no
no
no
no
no
Page 41
39
Service Manual
3.E9 Full Water Protection
E9 protection
If the unit is
installed with
water pump
No
Yes
Replace the water pump
Short circuit the full water
protection interface on indoor
mainboard according to the circuit
diagram
Check if the water pump
works normally
No
Replace the full water switch
or make sure the float of full
water switch works normally
Yes
Page 42
40
Service Manual
4. Malfunction of Insufcient uorine protection F0
The refrigerant is leaking
Check the leaking status of refrigerant and charge refrigerant
Clean the heat exchangers
and remove
blockage of air inlet/outlet.
Heat exchangers are
too dirty or the air inlet/outlet
is blocked.
End
Remove blockage in the system
System is blocked inside
(dirt block, ice block, oil block, Y-valve no
fully open).
Compressor doesn't work
normally. Strange noise or leakage occurs.
Make compressor run normally.
Casing is too hot.
Replace a main board with the same model.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Troubleshooting
for F0 malfunction
Yes
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page 43
47
Service Manual
10. Removal Procedure
Caution: discharge the refrigerant
completely before removal.
2.Remove the
cover plate for
return air
a) Remove the filter
screen
b) Unscrew the fixed
screws of the return
air
3.Remove the rear
volute
Undo the buckle of the
rear and front volutes and
then remove the rear
volute away.
4. Remove the front
volute
Unscrew the fixed
screws of the front volute
and then remove it away
snoitcurtsnI noitarepO snoitartsullI spetS
1.Pull out the
electric wire of the
motor
Open the cover plate of the
electric box and then pull
out the electric wire inside
the box.
Page 44
48
Service Manual
6. Remove the
motor away.
a) Separate the motor
away from the motor
support.
b) Remove the fan
blade
c) Take the motor out
from the return air
frame
Note: the motor support
shall be removed in
advance and then changed
to the unit.
7.Replace with a
new motor
Assemble the fan as the
reverse disassembly order
and then take a power-on
test.
5.Loosen the fan
blade and fan
motor
Unscrew the fixed screws
of the fan blades and then
undo the buckle of the
motor
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 E-mail: gree@gree.com.cn www.gree.com
HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED
Add: Unit 2612,26/F.,Miramar Tower 132 Nathan Road,TST,Kowloon,HK Tel: (852) 31658898 Fax: (852) 31651029
For product improvement, specifications and appearance in this manual are subject to change without prior notice.
Page 45
PARTS GUIDE
MV-D09BI, MV-D12BI,
MV-D18BI, MV-D24BI
DUCT
MULTI VARIABLE SERIES
103
Page 46
MV-D09BI
Page 47
No Description Part Code Note Qty
Price Code
1 Air outlet frame assy 01865216 1 AH 2 Cover of air outlet 01265298 1 AG 3 Water Tray Assy 01285332 1 AW 4 Top Cover Board Assy 01265200099 1 AT 5 Evaporator Assy 011001060406 1 BE 6 Sealplate sub-assy (evaporator) 01495317 1 AH 7 Left Side Plate Assy 01315334 1 AK 8 Sealplate sub-assy (outlet) 01495316 1 AE 9 Front Volute Casing 26905205 2 AH 10 Rear Volute Casing 26905206 2 AH 11 Centrifugal Fan 10425200 2 AR 12 Transformer 4311023303 1 AM 13 Terminal Board 420001000002 1 AF 14 Main Board 30226338 1 AY 15 Capacitor CBB61S 3301074704 1 AH 16 Electric Box Sub-Assy 01395100 1 AM 17 Electric Box Assy 01395983 1 BB 18 Electric Box Cover 01424253 1 AF 19 Cover board (Fan motor) 01265300 1 AM 20 Bottom Cover Plate 01265299 1 AP 21 Supporter 01895225 2 AH 22 Bar Clasp 012133000018 2 AB 23 Fan Motor 1570520103 1 BB 24 Motor Support 01804348 1 AK 25 Fan Motor Mounting Plate Sub-Assy 01325200007 1 AP 26 Right Side Plate Assy 01315335 1 AM 27 Display Board
300001060284_L41851
1 ­28 Ambient Temperature Sensor 39000206 1 AD 29 Temperature Sensor 390001982G 1 AD 30 Water Pump Assy 15405200082 1 BD 31 Water Level Switch 45020216 1 AQ 32 Water Pump 43130324 1 BC 33 Remote Controller 305100491_L41851 1 AT
MODEL: MV-D09BI Duct unit
The data are subject to change without notice.
Page 48
MV-D12BI
Page 49
No Description Part Code Note Qty
Price Code
1 Air outlet frame assy 01865216 1 AH 2 Cover of air outlet 01265298 1 AG 3 Water Tray Assy 01285332 1 AW 4 Top Cover Board Assy 01265325 1 AT 5 Evaporator Assy 011001060291 1 BE 6 Sealplate sub-assy (evaporator) 01495317 1 AH 7 Left Side Plate Assy 01315334 1 AK 8 Sealplate sub-assy (outlet) 01495316 1 AE 9 Front Volute Casing 26905205 2 AH 10 Rear Volute Casing 26905206 2 AH 11 Centrifugal Fan 10425200 2 AR 12 Transformer 4311023303 1 AM 13 Terminal Board 420001000002 1 AF 14 Main Board 30226338 1 AY 15 Capacitor CBB61S 3301074704 1 AH 16 Electric Box Sub-Assy 01395100 1 AM 17 Electric Box Assy 01395983 1 BB 18 Electric Box Cover 01424253 1 AF 19 Cover board (Fan motor) 01265300 1 AM 20 Bottom Cover Plate 01265299 1 AP 21 Supporter 01895225 2 AH 22 Bar Clasp 012133000018 2 AB 23 Fan Motor 15010100007001 1 BA 24 Motor Support 01804348 1 AK 25 Fan Motor Mounting Plate Sub-Assy 01325200007 1 AP 26 Right Side Plate Assy 01315335 1 AM 27 Display Board
300001060284_L41851
1 ­28 Ambient Temperature Sensor 39000206 1 AD 29 Temperature Sensor 390001982G 1 AD 30 Water Pump Assy 15405200082 1 BD 31 Water Level Switch 45020216 1 AQ 32 Water Pump 43130324 1 BC 33 Remote Controller 305100491_L41851 1 AT
MODEL: MV-D12BI Duct unit
The data are subject to change without notice.
Page 50
MV-D18BI
Page 51
No Description Part Code Note Qty
Price Code
1 Air outlet frame assy 01865217 1 AM 2 Cover of Air Outlet 01265331 1 AG 3 Water Tray Assy 01285333 1 AW 4 Evaporator Assy 011001060407 1 BE 5 Top Cover Board Assy 01265328 1 AU 6 Left Side Plate Assy 01315334 1 AK 7 Sealplate sub-assy (evaporator) 01495317 1 AH 8 Sealplate sub-assy (outlet) 01495316 1 AE 9 Front Volute Casing 26905205 3 AH 10 Rear Volute Casing 26905206 3 AH 11 Bottom Cover Plate 01265332 1 AQ 12 Transformer 4311023303 1 AM 13 Terminal Board 420001000002 1 AF 14 Main Board 30226338 1 AY 15 Capacitor CBB61S 3301074704 1 AH 16 Electric Box Sub-Assy 01395100 1 AM 17 Electric Box Assy 01395984 1 BB 18 Electric Box Cover 01424253 1 AF 19 Temperature Sensor 390001982G 1 AD 20 Ambient Temperature Sensor 39000206 1 AD 21 Cover board (Fan motor) 01265333 1 AM 22 Fan Motor 15010100007401 1 BB 23 Bar Clasp 012133000018 2 AB 24 Motor Support 01804348 1 AK 25 Joint Slack 73018731 1 AK 26 Supporter 01895225 2 AH 27 Rotary Axis Sub-Assy 73018020 1 AP 28 Centrifugal Fan 10425200 3 AR 29 Fan Motor Mounting Plate Sub-Assy 01325200006 1 AR 30 Right Side Plate Assy 01305263 1 AM 31 Display Board
300001060284_L41851
1 ­32 Water Pump Assy 15405200082 1 BD 33 Water Level Switch 45020216 1 AQ 34 Water Pump 43130324 1 BC 35 Remote Controller 305100491_L41851 1 AT
MODEL: MV-D18BI Duct unit
The data are subject to change without notice.
Page 52
MV-D24BI
Page 53
No Description Part Code Note Qty
Price Code
1 Air outlet frame assy 01375224 1 AM 2 Cover of Air Outlet 01265335 1 AG 3 Water Tray Assy 01285334 1 AX 4 Evaporator Assy 011001060408 1 BE 5 Lower Cover Plate Sub-Assy 01265339 1 AW 6 Left Side Plate Assy 01315334 1 AK 7 Sealplate sub-assy (evaporator) 01495317 1 AH 8 Sealplate sub-assy (outlet) 01495316 1 AE 9 Front Volute Casing 26905205 4 AH 10 Rear Volute Casing 26905206 4 AH 11 Bottom Cover Plate 01265337 1 AR 12 Transformer 4311023303 1 AM 13 Terminal Board 420001000002 1 AF 14 Main Board 30226338 1 AY 15 Capacitor CBB61S 3301074705 1 AH 16 Electric Box Sub-Assy 01395100 1 AM 17 Electric Box Assy 100002003008 1 AZ 18 Electric Box Cover 01424253 1 AF 19 Cover board (Fan motor) 01265338 1 AM 20 Temperature Sensor 390001982G 1 AD 21 Ambient Temperature Sensor 39000206 1 AD 22 Fan Motor 150101000059 1 BB 23 Bar Clasp 012133000018 1 AB 24 Motor Support 01804348 1 AK 25 Joint Slack 73018731 1 AK 26 Supporter 01895225 2 AH 27 Rotary Axis Sub-Assy 73018000013 1 AQ 28 Centrifugal Fan 10425200 4 AR 29 Fan Motor Mounting Plate Sub-Assy 01325200005 1 AS 30 Right Side Plate Assy 01305263 1 AM 31 Display Board
300001060284_L41851
1 ­32 Water Pump Assy 15405200082 1 BD 33 Water Level Switch 45020216 1 AQ 34 Water Pump 43130324 1 BC 35 Remote Controller 305100491_L41851 1 AT
MODEL: MV-D24BI Duct unit
The data are subject to change without notice.
Page 54
Page 55
NOTE CONCERNING PROTECTION OF ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal procedures. The materials are recyclable in accordance with their respective symbols. By means of re-use, material recycling or any other form of recycling old appliances you are making an important contribution to the protection of our environment. Please ask your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT MEDIUM
This unit is containing fluorinated gases included in the Kyoto protocol. The maintenance and the liquidation must be carried out by qualified personnel. Type of refrigerant: R32 The quantity of the refrigerant: please see the unit label. The value GWP: 675 (1 kg R32 = 0,675 t CO2 eq) GWP = Global Warming Potential
Appliance filled with flammable gas R32.
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain
www.sinclair-world.com
This product was manufactured in China (Made in China).
REPRESENTATIVE
SINCLAIR EUROPE spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
TECHNICAL SUPPORT
NEPA spol. s r.o. Purkynova 45 612 00 Brno Czech Republic
Tel.: +420 800 100 285
Fax: +420 541 590 124
www.sinclair-solutions.com info@sinclair-solutions.com
Loading...