Sinclair MS-E36AI, MS-E42AI User Manual

Page 1
USER'S MANUAL
MULTI SYSTEM SERIES
outdoor unit
MS-E36AI, MS-E42AI
EN
Page 2
I
User Notice
The total capacity of the indoor units which runs at the same time can not exceed
150% of that of the outdoor units, otherwise, the cooling (heating) effect of each indoor unit would be poor.
Switch the main power on 8 hours before starting the unit, helpful for a successful
startup.
It is a normal phenomenon that the indoor unit fan will still run for 20~70 seconds
after the indoor unit receives the “stop” signal so as to make full use of after-heat for the next operation.
When the running modes of the indoor and outdoor units conflict, it will be
indicated on the display of the wired controller in five seconds and then the indoor unit will stop. In this case, they can back to the normal condition by harmonizing their running modes: the cooling mode is compatible with the dehumidifying mode and the fan mode can go with any other mode. If the supply power fails when the
unit is running, then the indoor unit will send the “start” signal to the outdoor unit
three minutes later after power recovery.
Do not frequently power on/off the unit, otherwise it would cause the compressor,
fan, mainboard, electrostatic expansion valve, or other important component damaged, and then make the unit fail.
During installation, the communication cable and the power cord must not be
twisted together but instead separated with an interval of at least 2cm, otherwise the unit is likely to run abnormally.
Cautions for the Debugging and Maintenance Personnel. During debugging and maintenance, prior to the startup of the compressor make
sure the heating belt of the compressor has been energized for at least eight hours! Once the compressor is started, it must be guaranteed that it works continuously for at least 30 minutes, otherwise it would be damaged!
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Page 3
II
The appliance shall be installed in accordance with national wiring regulations. If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
This series outdoor
Multi system series
thewithmatchedunits are
conditons
working
sametheunderunitindoor
exported to European Union.
Correct Disposal of this product
This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.
R410A(R32/125:50/50):2087.5
Page 4
Contents
1 Safety Precautions ................................................................... 1
2 Installation Instructions ............................................................ 2
2.1 Installation Location and Matters Needing Attention ................... 2
2.2 Installation of the Outdoor Unit ................................................... 6
2.3 Connection between Indoor and Outdoor Units .......................... 8
2.4 Refrigerant Charging and Trial Running ................................... 11
3 Working Principles of the Unit ................................ ................ 15
4 Parts and Components of the Unit ......................................... 16
5 Maintenance .......................................................................... 17
5.1 Check before the Seasonal Use ............................................... 17
5.2 Check after the Seasonal Use .................................................. 17
6 Troubleshooting ..................................................................... 18
6.1 Check before Contacting Service Center ................................. 18
6.2 Problem Handling .................................................................... 19
6.3 Error Description ...................................................................... 19
6.4 After-Sales Service................................................................... 26
7 Function Description .............................................................. 26
8 Performance Parameters ....................................................... 27
Page 5
1
1 Safety Precautions
Please read this manual carefully before using and operating correctly as
instructed in this manual.
Please especially take notice of the following two symbols: Warning! It indicates improper operation which will lead to human casualty or
severe injury.
Caution! It indicates improper operation which will lead to injury or property
damage.
Warning!
The installation should be committed to the appointed service center,
otherwise it will cause water leakage, electric shock or fire etc..
Please install the unit in a place where is strong enough to withstand the
weight of the unit, otherwise, the unit would fall down and cause injury or death.
The drain pipe should be installed as instructed in the manual to guarantee the
proper drainage, meanwhile it should be insulated to prevent condensing, otherwise the improper installation would cause water leakage and then wet the household wares in the room.
Do not use or place any inflammable, combustible or any noxious substance
next to the unit.
Under the occurrence of an error (like burning smell etc.), please cut off the
main power supply of the unit.
Keep good ventilation in the room to avoid oxygen deficit.  Never insert your finger or any other object into the air outlet/inlet grille.  Please take notice of the supporting frame of the unit to see if it is damaged
over the long time period of use.
Never refit the unit and contact the sales agent or the professional installation
personnel for the repair or relocation of the unit.
Non-professional personnel are prohibited to dismantle the electric box owing
to the high voltage of the outdoor unit.
An all-pole disconnection switch having a contact separation of at least 3mm
in all poles should be connected in fixed wiring.
Page 6
2
Caution!
Before installation, please check if the power supply corresponds with the
requirement specified on the nameplate and also check its security.
Before using the unit, please check if the piping and wiring are correct to avoid
water leakage, refrigerant leakage, electric shock, or fire etc..
The main power supply must be earthed to avoid the hazard of electric shock
and never connect this earth wire to the gas pipe, running water pipe, lightening rod or phone cable’s earth lead.
Turn off the unit after it runs at least five minutes, otherwise its service life will
be shortened.
Do not allow children operate this unit.  Do not operate this unit with wet hands.  Cut off the main power supply prior to the cleaning of the unit or the
replacement of the air filter.
When the unit is not to be used for a long time, please cut off the main power
supply of the unit.
Do not expose the unit to the moist or corrosive circumstances.  Never step on the unit or place any object on it.  It is suggested to have a power-on test annually.
2 Installation Instructions
2.1 Installation Location and Matters Needing Attention
The installation of the unit must comply with the national and local safety regulations. The installation quality directly affects the normal use, so the user should not carry out the installation personally, instead, the installation and debugging should be done by technician according to this manual. Only after that, can the unit be energized.
(1) How to select the installation location for the indoor unit
1) Where there is no direct sunlight.
2) Where the top hanger, ceiling and the building structure are strong enough to withstand the weight of the unit.
3) Where the drain pipe can be easily connected to outside.
4) Where the flow of the air inlet/outlet is not blocked.
5) Where the refrigerant pipe of the indoor unit can be easily led to outside.
6) Where there is no inflammable, explosive substances or their leakage.
Page 7
3
7) Where there is no corrosive gas, heavy dust, salt mist, smog or moisture.
(2) How to select the installation location for the outdoor unit
1) The outdoor unit must be installed where the bearing surface is stable and secure enough.
2) The outdoor unit and indoor unit should be placed as close as possible to minimize the length and bends of the refrigerant pipe.
3) Do not install the outdoor unit under the window or between the buildings to prevent the normal running noise entering the room.
4) Where the flow of the air inlet/outlet is not blocked.
5) The outdoor unit should be installed where ventilation is in good condition so that the unit can take in and discharge enough air.
6) Do not install the unit where there are inflammable and explosive substances and where there is heavy dust, salt fog and other severely polluted air.
No air guiding pipe is allowed to be installed at the air inlet/outlet of the outdoor unit.
Under the heating mode, the condensate water would drip down from the base frame and would be frozen when the outdoor ambient temperature is lower than 0℃(32℉).
Besides, the installation of the outdoor unit should not affect the heat radiation of the unit.
CAUTION!
The unit installed in the following places is likely to run abnormally. If unavoidable,
please contact the professional personnel at the Sinclair appointed service center.
Where is full of oil. Alkaline soil off the sea. Where there is sulfur gas (like sulfur hot spring). Where there are devices with high frequency (like wireless devices, electric
welding devices, or medical equipments).
Special circumstances.
(3) Electric Wiring
1) The installation must be done in accordance with the national wiring regulations.
2) Only the power cord with the rated voltage and exclusive circuit for the air conditioning can be used.
3) Do not pull the power cord by force.
4) The electric installation should be carried out by the professional personnel as instructed by the local laws, regulations and also this manual.
5) The diameter of the power cord should be large enough and once it is
Page 8
4
damaged it must be replaced by the dedicated one.
6) The earthing should be reliable and the earth wire should be connected to the dedicated device of the building by the professional personnel. Besides, the air switch coupled with the leakage current protection switch must be equipped, which is of enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload.
Table 1
Models Power Supply Capacity of the Air Switch
Recommended Cord
pieces× sectional area)
MS-E36AI 220-240V~ 50Hz 32A 4mm2×3 MS-E42AI 220-240V~ 50Hz 32A 4mm2×3
Notes:
①.
The specifications of the breaker and power cable listed in the table above are determined based on the maximum power (maximum amps) of the unit.
②.
The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-wire copper cable (like, YJV copper cable,
consisting of PE insulated wires and a PVC cable jacket) used at 40°С and
resistible to 90°С (see IEC 60364-5-52). If the working condition changes,
they should be modified according to the related national standard.
③.
The specifications of the breaker listed in the table above are applied to the
breaker with the working temperature at 40°С. If the working condition
changes, they should be modified according to the related national standard.
(4) Earthing Requirements
1) The air conditioner is classified into the Class I appliances, so its earthing must be reliable.
2) The yellow-green line of the air conditioner is the earth line and can not be used for other purpose, cut off or fixed by the tapping screw, otherwise it would cause the hazard of electric shock.
3) The reliable earth terminal should be provided and the earth wire can not be connected to any of the following places.
a) Running water pipe. b) Coal gas pipe. c) Sewage pipe. d) Other places where the professional personnel think unreliable.
Page 9
5
MS-E36AI
Fig.1
MS-E42AI
Fig.2
(5) Noise Precautions
1) The air conditioning unit should be installed where ventilation is in good condition, otherwise the working capability of the unit would be reduced or working noise would be increased.
2) The air conditioning unit should be installed on the base frame which is stable and secure uncouth to withstand the weight of the unit, otherwise it would incur vibration and noise.
Page 10
6
3) During the installation, a consideration should be taken that the produced hot air or noise should not affect neighbors or surroundings.
4) Do not stack obstacles near the air outlet of the outdoor unit, otherwise it would reduce the working capability of the unit or increase the working noise.
5) In the event of the occurrence of abnormal noise, please contact the sales agent as soon as possible.
(6) Accessories for Installation
Refer to the packing list for the accessories of the indoor and outdoor units
respectively.
2.2 Installation of the Outdoor Unit
(1) Precautions for the Installation of the Outdoor Unit
The following rules should be followed when the installation location is being
considered so as to let the unit run well enough.
1) The discharged air from the outdoor unit won’t return back and enough space should be left for maintenance around the unit.
2) The installation location should be in good condition so that the unit is able to take in and discharge enough air. Besides, make sure there is no obstacle at the air inlet/outlet of the unit. If there is, remove it.
3) The unit must be installed where it is secure enough to support the weight of the unit and capable of reducing to some extent noise and vibration to make sure they do not bother your neighbors.
4) The designated lifting hole must be used for lifting the unit and protect the unit carefully during lifting to prevent damaging the mental sheet which would result in rusting in future.
5) The unit should be installed where there is as little as direct sunlight.
6) The unit must be installed where the rain water and defrosting water can be drained.
7) The unit must be installed where the unit won’t be covered by the snow and won’t be affected by rubbish and oil fog.
8) Rubber or spring shock absorbers should be used during the installation of the outdoor unit to meet the noise and vibration requirements.
9) The installation dimensions should meet the requirement covered in this manual and the outdoor unit must be fixed securely.
10) The installation should be carried out by the professionally skilled personnel.
Page 11
7
(2) Installation of the Outdoor Unit
1) Outline dimension of the outdoor unit.
MS-E36AI
Fig.4
MS-E42AI
Fig.5
2) During the transportation of the outdoor unit, two lifting ropes long enough must be used in four directions and the separation included angle must be less than 40°prevent the center of unit deviating.
3) During the installation, M12 screws should be used to fix the support leg and base frame of the unit.
4) The unit should be installed on a concrete base frame with a height of 10cm.
5) The installation space of the unit should be as required in Fig.6.
Installation Space Requirements of the Outdoor Unit:
Page 12
8
Fig.6
2.3 Connection between Indoor and Outdoor Units
(1) Wiring of the Power Cord
CAUTION!
A breaker must be installed, capable of cutting off the power supply for the whole
system.
1) Open the side plate.
2) Let the power cord go through the rubber ring.
3) Connect the power card to the terminals “L”, “N” and also the earthing bolt,
and then connect the wiring terminals “N(1),2,3” of the indoor unit to those of
the outdoor unit correspondingly.
4) Fix the power cord with wire clips.
(2) Energy Level and Capacity Code of the Indoor and Outdoor Units
Table2
Energy Level Capacity Code
Indoor Unit
09 25 12 35 18 50 21 60 24 71
Outdoor Unit
36 100 42 120
1) The outdoor unit with capacity level 36 can drive up to four sets of indoor units, while the outdoor unit 42 can drive up to five.
2) The sum of the capacity codes of the indoor units should be among 50%-150% of that of the outdoor unit.
Page 13
MS-E36AI MS-E42AI
m
70 80
m
20 25
Outdoor unit is installed under the lower side of indoor unit
m
15 15
Outdoor unit is installed on the upper side of indoor unit
m
15 15
g/m
40 50
Refrigerant charge volume
22
Model Max. connection pipe length
Max. connection pipe length (One indoor unit)
Max. installation altitude
Max. connection pipe length (Under the condition of no need to charge the refrigerant, liquid pipe total length)
m
Page 14
9
(3) Allowable Length and Height Fall of the Refrigerant Pipe
Table 3
Allowable Length Refrigerant Pipe
36 42 36 42
Total Length(m) 70 80 L1+L2+L3+ L4 L1+L2+L3+ L4+ L5
Max. Length for Single Unit(m) 20 25 LX
Max.
installation
altitude
Outdoor unit and
indoor unit
15 15 H1
Indoor unit and
indoor unit
7.5 7.5 H2
Table 4 Dimension of the Refrigerant Pipe of the Indoor Unit
Unit: mm
Capacity Level of the Indoor Unit Gas Pipe Liquid Pipe
09,12 Ф9.52 Ф6.35
18 Ф12.7 Ф6.35
21,24 Ф15.9 Ф9.52
(4) Piping between the Indoor and Outdoor Units
1) Refer to Fig.6 for the moments of torque for tightening screws.
2) Let the flare end of the copper pipe point at the screw and then tighten the screw by hand.
3) After that, tighten the screw by the torque wrench unit it clatters (as shown in Fig.6).
4) The bending degree of the pipe can not be too small, otherwise it will crack. And please use a pipe tube bender to bend the pipe.
5) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape.
Fig. 7
Page 15
10
Table 5 Moments of Torque for Tightening Screws
Diameter
Wall Thickness(mm)
Moment of Torque
Ф6.35mm
0.5
15-30(N·m)
Ф9.52mm
0.71
30-40(N·m)
Ф12.7mm
1
45-50(N·m)
Ф15.9mm
1
60-65(N·m)
CAUTION!
①.
During the connection of the indoor unit and the refrigerant pipe, never pull any joints of the indoor unit by force, otherwise the capillary pipe or other pipe may crack, which then would result in leakage.
②.
The refrigerant pipe should be supported by brackets, that is, don’t let the unit
withstand the weight of it.
CAUTION!
For the Multi system air conditioner unit, each pipe should be labeled to tell which
system it belongs to avoid mistaken inaccurate piping.
(5) Installation of the Protection Layer of the Refrigerant Pipe
1) The refrigerant pipe should be insulated by the insulating material and plastic tape in order to prevent condensation and water leakage.
2) The joints of the indoor unit should be wrapped with the insulating material and no gap is allowed on the joint of the indoor unit, as shown in Fig.8.
Fig. 8
CAUTION!
After the pipe is protected well enough, never bend it to form a small angle,
otherwise it would crack or break.
(6) Wrap the Pipe with Tape
1) Bundle the refrigerant pipe and electric wire together with tape, and separate them from the drain pipe to prevent the condensate water overflowing.
2) Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where
Page 16
11
it enters the wall. During the wrapping, the later circle should cover half of the former one.
3) Fix the wrapped pipe on the wall with clamps.
CAUTION!
①.
Do not wrap the pipe too tightly, otherwise the insulation effect would be weakened. Additionally, make sure the drain hose is separated from the pipe.
②.
After that, fill the hole on the wall with sealing material to prevent wind and rain coming into the room.
2.4 Refrigerant Charging and Trial Running
(1) Refrigerant Charging
1) The refrigerant has been charged into the outdoor unit before shipment, while additional refrigerant still need be charged into the refrigerant pipe during the field installation.
2) Check if the liquid valve and the gas valve of the outdoor unit are closed fully.
3) As shown in the following figure (Fig.9), expel the gas inside the indoor unit and refrigerant pipe out by the vacuum pump.
Fig. 9
4) When the compressor is not running, charge the R410A refrigerant into the refrigerant pipe from the liquid valve of the outdoor unit (do not do it from the gas valve).
(2) Calculation of the Additional Refrigerant Chargeing
1) Refrigerant Charge in the Outdoor Unit before Shipment
Table 6
Model
MS-E36AI
MS-E42AI
Refrigerant
Charge (kg)
4.3
4,8
Page 17
12
Notes:
①.
The refrigerant charge mentioned in the table above is not included those charged additionally in the indoor unit and the refrigerant pipe.
②.
The amount of the additional refrigerant charge is dependent on the diameter and length of the liquid refrigerant pipe which is decided by the actual yield installation requirement.
③.
Record the additional refrigerant charge for future maintenance.
2) Calculation of the Additional Refrigerant Charge
If the total refrigerant pipe length (liquid pipe) is smaller than that listed in the table
below, no additional refrigerant will be charged.
Table 7
Model Total Liquid Pipe Length (a+b+c+d+e)
MS-E36AI
40m
MS-E42AI
50m
pipeLength×22g/m(liquidPipeLiquidCharge2=∑ExtraRefrigerantAdditional
1/4"). Note:
If the total refrigerant pipe length is larger than that listed in the table above, the
additional refrigerant for the extra length of the pipe needs to be charged as per 22g/m.
3) Example : MS-E42AI
Fig.10
Table 8 Indoor Unit
Serial No. Model
Indoor Unit⑤
Ducted Type MS-D09AI
Indoor Unit④
Ducted Type MS-D09AI
Indoor Unit③
Ducted Type MS-D09AI
Indoor Unit②
Ducted Type MS-D09AI
Indoor Unit①
Ducted Type MS-D18AI
Page 18
13
Table 9 Liquid Refrigerant Pipe
Serial No. e d c b a
Diameter Ф6.35 Ф6.35 Ф6.35 Ф6.35 Ф9.52
Length 20m 20m 15m 5m 5m
The total length of each liquid refrigerant pipe is: e+d+c+b+a=20+20+15+5+5=65m.
Thus, the minimum additional refrigerant charge=(65-50)×0.022=0.33kg (Note: no additional refrigerant is needed for the liquid pipe within 50m).
4) Additional Refrigerant Charge Record
Table 10 Indoor Unit
No. Indoor Unit Model Additional Refrigerant Charge(kg)
1 2
……
N
Total
Table 11 Refrigerant Pipe
Diameter Total Length(m) Additional Refrigerant Charge(kg)
Φ15.9 Φ12.7 Φ9.52 Φ6.35
Total
(3) Items to be checked after the Installation
Table 12
Items to be Checked Possible Errors Check Results
Has each part and component of the unit been installed securely?
The unit may fall off, vibrate or generate noise.
Has the gas leakage test been taken?
The cooling (heating) capacity may be poor.
Is the thermal insulation sufficient? Dews and water drops may be generated.
Does the drainage go well? Dews and water drops may be generated. Is the actual power voltage in line with
the value marked on the nameplate?
The unit may break down or some components may be burnt out.
Page 19
14
Are the wiring and the piping correct?
The unit may break down or some
components may be burnt out. Has the unit been earthed reliably? There may be a danger of electric shock. Does the wire meet the regulated
requirement?
The unit may break down or the
component may be burnt out. Is there any obstacle at the air
inlet/outlet of the indoor/outdoor unit?
The cooling (heating) capacity may be
poor. Have the length of the refrigerant pipe
and the refrigerant charge been recorded?
It may be hard to know the exact
refrigerant charge.
(4) Trial Running
1) Check before the Trial Running a) Check if the appearance of the unit and the piping system are damaged
during the transportation. b) Check if the wiring terminals of the electronic component are secure. c) heck if the rotation direction of the fan motor is right. d) Check if all valves in the system are fully opened.
2) Trial Running a) The trial running should be carried out by the professionally skilled
personnel on the premise that all items listed above are in normal conditions.
b) Let the unit energized and switch the wired controller or the remoter
controller to “ON”.
c) The fan motor and compressor of the outdoor unit will run automatically in
one minute.
d) If there is some unusual sound after the compressor is started, turn off the
unit for an immediate check.
Page 20
15
3 Working Principles of the Unit
Schematic Diagram of Multi system series Inverter Heat Pump
Fig. 11 Schematic Diagram of Multi system Series Inverter Heat Pump
The outdoor and indoor units start to work once the power is switched on. During the cooling operation, the low temperature, low pressure refrigerant gas from the heat exchanger of each indoor unit gets together and then is taken into the compressor to be compressed into high temperature, high pressure gas, which will soon go to the heat exchanger of the outdoor unit to exchange heat with the outdoor air and then is turned into refrigerant liquid. After passing through the throttling device, the temperature and pressure of the refrigerant liquid will further decrease and then go the main valve. After that, it will be divided and go to the heat exchanger of each indoor unit to exchange heat with the air which needs to be conditioned. Consequently, the refrigerant liquid become low temperature, low pressure refrigerant gas again. Such a refrigeration cycle goes round and round to achieve the desired cooling purpose. During the heating operation, the four-way valve is involved to make the refrigeration cycle run reversely.
Page 21
16
The refrigerant radiates heat in the heat exchanger of the indoor unit (so do the electric heating devices) and absorb heat in the heat exchanger of the outdoor unit for a heat pump heating cycle so as to achieve the desired heating purpose.
4 Parts and Components of the Unit
System Structure
Fig. 12
For the Multi system air conditioner unit, one outdoor unit is able to drive up to
four or five indoor units which can be cassette type, duct type, wall-mounted or floor ceiling type. Among them, the cassette type and the wall-mounted indoor units should be controlled by the remote controller, while the ducted type can be controlled by either the remote controller or the wired controller. The outdoor unit will run as long as any one indoor unit receives the running command, and all indoor units stop once the outdoor unit is turned off.
Page 22
17
5 Maintenance
WARNING!
①.
The unit can only be cleaned after the unit is turned off and the main power is cut off, otherwise it would cause an electric shock hazard.
②.
Do not dampen the air conditioner, as it would cause an electric shock hazard and never rinse the unit with water in any event.
CAUTION!
①.
Volatile liquid, like thinner, gasoline etc would damage the appearance of the air conditioning unit. (Only use the soft dry cloth or the wet cloth with neutral detergent clean the outer shell of the air conditioning unit)
②.
Do not clean the outer shell of the air conditioning unit with more than 45℃ hot water to prevent discoloration or deformation.
③.
Do not dry the air filter screen of the indoor unit on the fire to prevent combustion or deformation.
5.1 Check before the Seasonal Use
(1) Check if the inlet/outlet of the indoor/outdoor unit is clogged. (2) Check if the earth lead is earthed reliably. (3) Check if the batteries of the remote controller are replaced. (4) Check if the air filter screen is installed properly. (5) Check if the installation of the outdoor is secure. If there is something
abnormal, please contact the Sinclair appointed service center.
(6) When restarting the unit which is not used for a long time, switch on the main
power supply eight hours ahead, helpful for a successful startup.
5.2 Check after the Seasonal Use
(1) Clean the filter screen and body of the indoor and outdoor units. (2) Cut off the main power supply of the air conditioning system. (3) Remove the dust and the foreign matters of the outdoor unit. (4) In the event of rusting, use the anti-rust paint to stop spreading of rust.
Refer to the Installation and Operation Manual of each indoor unit respectively for
detailed maintenance.
Page 23
18
6 Troubleshooting
WARNING!
①.
In the event of abnormal conditions (like, stinky smell), please shut off the main power supply immediately and then contact the Sinclair appointed
service center, otherwise the continuous abnormal running would damage the air conditioning unit and also would cause electric shock or fire hazard etc..
②.
Do not repair the air conditioning personally but instead contact the professionally skilled personnel at the Sinclair appointed service center, as the incorrect repair would cause electric shock or fire hazard etc..
6.1 Check before Contacting Service Center
Please check the following items before contacting the maintenance serviceman.
Table 13
Conditions Causes Corrective Actions
The unit
does not run
Broken fuse or opened breaker Change the fuse or close the breaker Power off Restart the unit when power on Power supply plug is loose Plug the power supply properly
Insufficient batteries voltage of the remote controller
Change new batteries
Remoter controller out of the control scope
Keep the control distance within 8 meters
The unit stops soon
after it starts
Clogged inlet/outlet of the indoor/outdoor unit
Clear the obstacle
Cooling/Heating is
abnormal
Clogged inlet/outlet of the indoor/outdoor unit
Clear the obstacle
Improperly set temperature
Adjust the setting of the remote or wired controller
Too low set fan speed
Adjust the setting of the remote or wired controller
Improper airflow direction
Adjust the setting of the remote or wired controller
Opened door and window Close the door and window Direct sunlight Hang a curtain or blinds over the window Too much people in the room Too much heat sources in the room Reduce the heat sources Dirty filter screen Clean the filter screen
Page 24
19
Note:
If the air conditioner still runs abnormally after the above check and handling, please contact the maintenance serviceman at the local appointed service center and also give a description of the error occurred as well as the model of the unit.
6.2 Problem Handling
The conditions listed below are not classified into errors.
Table 14
Conditions Causes
The unit
does not run
When restart the unit soon after it is
stopped.
The overload protection switch of the unit let
the startup delayed for three minutes.
As soon as power is on.
The unit will stand by for approximate one
minute.
The unit
blows out mist
When the cooling operation starts. The hi-humidity air indoor is cooled quickly.
The unit
generates noise
The unit “clatters” as soon as it
starts running.
It is the sound generated during the
initialization of the electronic expansion
valve.
The unit “swishes” during the
cooling operation.
It is the sound when the refrigerant gas runs
inside the unit.
The unit “swishes” when it is started
or stopped.
It is the sound when the refrigerant gas stops
running.
The unit “swishes” when it is in and
after the running.
It is the sound when the draining system is
operating.
The unit “squeaks” when it is in and
after the running.
It is the sound of frication generated by the
skin plate etc which swells due to the
temperature change.
The unit
blows out dust
When the unit restarts after it is not
used for a long time.
The dust inside the unit is blown out again.
The unit
emits odors
When the unit is running. The odors absorbed in are blown out again.
6.3 Error Description
If some error occurs when the unit is running, the error code will be displayed on the wired controller and the main board of the outdoor unit.Check for more details
about the meaning of each error, as shown in table 15(a),15(b).
The error codes for duct, cassette and floor ceiling type unit are shown in the following table 15(a):
Page 25
20
Table 15(a)
Error Item
Outdoor
Unit 88
Display
Indicating LED Flashing Times
88
Display
Wired
Controler
Display
Error Type
Running
LED
Cooling
LED
Heating
LED
High Pressure
Protection
E1
Flash
once
/ / E1 E1 Outdoor
Shutdown for
Whole Unit
Anti-Freeze
Protection
E2
Flash
twice
/ / E2 E2 System E
rror
Low Pressure
Protection
E3
Flash 3
times
/ / E3 E3 Outdoor
High Discharge
Temp Protection
E4
Flash 4
times
/ / E4 E4 Outdoor
Communication
Error
E6
Flash 6
times
/ / E6 E6
Outdoor &
Indoor
Indoor Unit Water
Full Error
E9 / Flashing Flashing E9 E9 Indoor
Refrigerant
Recovery Mode
Fo
Quick
Flashing
Quick
Flashing
/ Fo Fo
Special
Mode
Outdoor Ambient
Temp Sensor Error
F3 /
Flash 3
times
/ F3 F3 Outdoor
Outdoor Mid-Coil
Temp Sensor Error
F4 /
Flash 4
times
/ F4 F4 Outdoor
Outdoor Discharge
Air Temp Sensor
Error
F5 /
Flash 5
times
/ F5 F5 Outdoor
Oil Return for
Cooling
F7 / / / / /
Special
Mode
Forced Defrosting H1
Quick
Flashing
/ / H1 H1
Special
Mode
Oil Return for
Heating or Defrosting
H1 / / Flash once H1
Special
Mode
Compressor
Overheat
Protection
H3 / /
Flash 3
times
H3 H3 Drive Error
IPM Protection H5 / /
Flash 5
times
H5 H5 Drive Error
Motor
Desynchronizing
H7 / /
Flash 7
times
H7 H7 Drive Error
PFC Error Hc / /
Flash 6
times
Hc Hc Drive Error
Startup Failure Lc / /
Flash 11
times
Lc Lc Drive Error
Page 26
21
DC Fan motor Error LA / / / / / Outdoor
No indoor fan
motor
H6
Flash 11
times
/ / / / Indoor
Compressor phase
circuit detection
error
U1 / /
Flash 12
times
/ / Outdoor
DC link voltage
drop error
U3 / /
Flash 20
times
/ / Outdoor
Zero detection
circuit error
U8
Flash 17
times
/ / / / Outdoor
Phase Loss Ld
Flash 3
times
Flash 3
times
Flash 3
times
Ld Ld Drive Error
Compressor
Stalling
LE
Flash 3
times
Flash 3
times
Flash 3
times
LE LE Drive Error
Over-Speed LF
Flash 3
times
Flash 3
times
Flash 3
times
LF LF Drive Error
IPM Reset P0
Flash 3
times
Flash 3
times
Flash 3
times
P0 P0 Drive Error
Compressor
Current Protection
P5 / /
Flash 15
times
P5 P5 Drive Error
Communication Error between the Inverter Drive and
the Main Controller
P6
Flash 16
times
/ / P6 P6 Drive Error
Radiator Temp
Sensor Error
P7 / /
Flash 18
times
P7 P7 Drive Error
Radiator Overheat
Protection
P8 / /
Flash 19
times
P8 P8 Drive Error
AC Contactor
Protection
P9
Flash 3
times
Flash 3
times
Flash 3
times
P9 P9 Drive Error
Current Sensor
Error
Pc / /
Flash 12
times
U1 Drive Error
Sensor Connection
Protection
Pd
Flash 3
times
Flash 3
times
Flash 3
times
Pd Pd Drive Error
Over Voltage
Protection
PH /
Flash 11
times
/ PH PH Drive Error
Low Voltage
Protection
PL / /
Flash 21
times
PL PL Drive Error
Temp Drift
Protection
PE
Flash 3
times
Flash 3
times
Flash 3
times
PE PE Drive Error
Drive Board
Ambient Temp
Sensor Error
PF
Flash 3
times
Flash 3
times
Flash 3
times
PF PF Drive Error
AC Current
Protection
PA
Flash 5
times
/ / E5 E5 Drive Error
Page 27
22
Charging Circuit
Error
PU / /
Flash 17
times
PU PU Drive Error
AC Input Voltage
Anomaly
PP
Flash 3
times
Flash 3
times
Flash 3
times
PP PP Drive Error
Unit
communication
error
See
Table 16
Flash 6
times
/ / E6 E6 Indoor
Unit n indoor pipe
midway temperature sensor error
See
Table 16
/ Flash twice / E2 E2 Indoor
Indoor Evaporator
Temp Sensor
Short/Open-Circuit
See
Table 16
/ Flash twice / F2 F2 Indoor
(Air Valve) Unit n
indoor unit pipe
outlet temperature
sensor error
See
Table 16
/
Flash 22
times
/ b7 b7 Indoor
(Liquid Valve) Unit
n indoor pipe inlet
temperature sensor error
See
Table 16
/
Flash 19
times
/ b5 b5 Indoor
Unit n mode
conflict
See
Table 16
/ Flash once / F1 F1 Indoor
Mode Conflict
See
Table 16
Flash 7
times
/ / E7 E7 Indoor
The error codes for wall mounted type unit are shown in the following table: Table
15(b):
Table 15(b)
Error Item
Outdoor
Unit 88
Display
Indicating LED Flashing Times
88
Display
Wired
Controler
Display
Error Type
Running
LED
Cooling
LED
Heating
LED
High Pressure
Protection
E1
Flash
once
/ / E1 E1 Outdoor
Shutdown for
Whole Unit
Anti-Freeze
Protection
E2
Flash
twice
/ / E2 E2 System Error
Low Pressure
Protection
E3
Flash 3
times
/ / E3 E3 Outdoor
High Discharge
Temp Protection
E4
Flash 4
times
/ / E4 E4 Outdoor
Communication
Error
E6
Flash 6
times
/ / E6 E6
Outdoor &
Indoor
Page 28
23
Indoor Unit Water
Full Error
E9
Flash 9
times
/ / E9 E9 Indoor
Refrigerant
Recovery Mode
Fo
Flash
once
Flash once / Fo Fo
Special
Mode
Outdoor Ambient
Temp Sensor
Error
F3 /
Flash 3
times
/ F3 F3 Outdoor
Outdoor Mid-Coil
Temp Sensor
Error
F4 /
Flash 4
times
/ F4 F4 Outdoor
Outdoor
Discharge Air
Temp Sensor
Error
F5 /
Flash 5
times
/ F5 F5 Outdoor
Oil Return for
Cooling
F7 /
Flash 7
times
/ / /
Special
Mode
Forced Defrosting H1
Quick
Flashing
/ / H1 H1
Special
Mode
Oil Return for
Heating or Defrosting
H1 / /
Flash
once
H1
Special
Mode
Compressor
Overheat
Protection
H3 / /
Flash 3
times
H3 H3 Drive Error
IPM Protection H5 / /
Flash 5
times
H5 H5 Drive Error
Motor
Desynchronizing
H7 / /
Flash 7
times
H7 H7 Drive Error
PFC Error Hc / /
Flash 6
times
Hc Hc Drive Error
Startup Failure Lc / /
Flash 11
times
Lc Lc Drive Error
DC Fan motor
Error
LA
Flash 24
times
/ / LA LA Outdoor
Phase Loss Ld / / / Ld Ld Drive Error
Compressor
Stalling
LE / / / LE LE Drive Error
Over-Speed LF / / / LF LF Drive Error
IPM Reset P0 / / / P0 P0 Drive Error
Compressor
Current Protection
P5 / /
Flash 15
times
P5 P5 Drive Error
Communication
Error between the
P6
Flash 16
times
/ / P6 P6 Drive Error
Page 29
24
Inverter Drive and
the Main
Controller
Radiator Temp
Sensor Error
P7 / /
Flash 18
times
P7 P7 Drive Error
Radiator Overheat
Protection
P8 / /
Flash 19
times
P8 P8 Drive Error
AC Contactor
Protection
P9 / / / P9 P9 Drive Error
Sensor
Connection
Protection
Pd / / / Pd Pd Drive Error
Over Voltage
Protection
PH /
Flash 11
times
/ PH PH Drive Error
Low Voltage
Protection
PL / /
Flash 21
times
PL PL Drive Error
Temp Drift
Protection
PE / / / PE PE Drive Error
Drive Board
Ambient Temp
Sensor Error
PF / / / PF PF Drive Error
Charging Circuit
Error
PU / /
Flash 17
times
PU PU Drive Error
Unit n
communication
error
See
Table 16
Flash 6
times
/ / E6 E6 Indoor
Unit n indoor pipe
midway temperature sensor error
See
Table 16
/ Flash twice / E2 E2 Indoor
Indoor Evaporator
Temp Sensor
Short/Open-Circuit
See
Table 16
/ Flash twice / F2 F2 Indoor
(Air Valve) Unit n
indoor unit pipe
outlet temperature
sensor error
See
Table 16
/
Flash 22
times
/ b7 b7 Indoor
(Liquid Valve)
Unit n indoor pipe
inlet temperature
sensor error
See
Table 16
/
Flash 19
times
/ b5 b5 Indoor
Unit n mode
conflict
See
Table 16
/ Flash once / F1 F1 Indoor
Mode Conflict
See
Table 16
Flash 7
times
/ / E7 E7 Indoor
Page 30
25
Table 16
Error
Code
Error Description
Error Code
Error Description
Error
Code
Error Description
13
Unit A indoor unit pipe outlet temperature sensor error
23
Unit B indoor unit pipe outlet temperature sensor error
33
Unit C indoor unit pipe outlet temperature sensor error
14
Unit A indoor pipe inlet temperature sensor error
24
Unit B indoor pipe inlet temperature sensor error
34
Unit C indoor pipe inlet temperature sensor error
15
Unit A indoor ambient temperature sensor error
25
Unit B indoor ambient temperature sensor error
35
Unit C indoor ambient temperature sensor error
16 Unit A mode conflict 26 Unit B mode conflict 36 Unit C mode conflict 17
Unit A anti-freezing protection
27
Unit B anti-freezing protection
37
Unit C anti-freezing protection
41
Unit D communication error
46 Unit D mode conflict 54
Unit E indoor pipe inlet temperature sensor error
42
Unit D indoor pipe midway temperature sensor error
47
Unit D anti-freezing protection
55
Unit E indoor ambient temperature sensor error
43
Unit D indoor unit pipe outlet temperature sensor error
51
Unit E communication error
56 Unit E mode conflict
44
Unit D indoor pipe inlet temperature sensor error
52
Unit E indoor pipe midway temperature sensor error
57
Unit E anti-freezing protection
45
Unit D indoor ambient temperature sensor error
53
Unit E indoor unit pipe outlet temperature sensor error
C5 Jumper terminal error
Page 31
26
(Note: Refer to the real products for the exact position of each component.) Once errors are displayed on the controller, please shut off the air conditioning unit
and contact the professionally skilled personnel for troubleshooting.
6.4 After-Sales Service
If there is any quality or other issue, place contact the Sinclair after-sales service
center.
7 Function Description
Refrigerant Recovery
The refrigerant can be recovered from either the indoor unit or the outdoor unit. From the outdoor unit: it is available to recover the refrigerant from the outdoor unit
by pressing “SW3” for
a long time period. From the indoor unit: When the unit is powered on and runs under the COOL mode, it is available within
five minutes to go to refrigerant recovery mode by pressing three times the “LIGHT”
button on the wireless controller in three seconds with “F0” displayed.
How to quit the refrigerant recovery:
When the refrigerant recovery has started, it will quit when the “SW3” is pressed
down for a long time period or there is a signal from the wireless controller or it has run for ten minutes.
Forcible Defrosting
How to activate this function: when indoor unit runs under the HEAT mode and at
16℃, it will activate the forcible defrosting by pressing the “+” and “-” buttons alternately three times in five seconds.
How to quit this function: the function will quit when the mode of indoor units
conflict.
Switchover of the Defrosting Modes
Under the unit is under the “Off” status, if “H1” is not displayed on the wireless
controller, then the unit will go to the defrosting mode 1 when it is turned on through the wireless controller.
Under the unit is under the “Off” status, if “H1” is displayed on the wireless
controller, the unit will go the defrosting mode 2 when it is turned on through the wireless controller.
Page 32
27
Under the unit is under the “Off” status, it is available to switch over the defrosting
mode 1 and defrosting mode 2 by pressing the “Mode” and “Blow” buttons
simultaneously.
8 Performance Parameters
Rated Working Conditions of the Air Conditioning Unit
Table 18 Working Temperature Range
Indoor side state Outdoor side state
Dry bulb temp. ℃
Wet bulb temp. ℃
Dry bulb
temp. ℃
Wet bulb temp. ℃
Rated Cooling 27 19 35 24
Max. cooling 32 23 48 26
Min. cooling 21 15 18
Rated Heating 20 15 7 6
Max. heating 27 24 18
Min. heating 20 15
15
16
Notes:
①.
The heating/cooling capacity and noise listed below are all measured before the shipment.
②.
All parameters listed above are measured under the standard working conditions. If there is any change, the parameters marked on the nameplate always prevail.
③.
The heating capacity of the indoor unit just involves that of the heat pump but apart from that of the auxiliary electric heater.
Page 33
NOTE CONCERNING PROTECTION OF ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal procedures. The materials are recyclable in accordance with their respective symbols. By means of re-use, material recycling or any other form of recycling old appliances you are making an important contribution to the protection of our environment. Please ask your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT MEDIUM
This unit is containing fluorinated gases included in the Kyoto protocol. The maintanance and the liquidation must be carried out by qualified personel. Type of refrigerant: R410A The composition of the cooling medium R410A: (50% HFC-32, 50% HFC-125) The quantity of the refrigerant: please see the unit label. The value GWP: 2088 GWP = Global Warming Potential
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain
www.sinclair-world.com This product was manufactured in China (Made in China).
REPRESENTATIVE, TECHNICAL SUPPORT
NEPA spol. s r.o. Purkyňova 45 612 00 Brno Czech republic
Tel.: +420 541 590 140 Fax: +420 541 590 124
www.sinclair-solutions.com info@sinclair-solutions.com
Loading...