Sinclair ASH-18AK Series, ASH-24AK Series, King ASH-18AK, King ASH-24AK Service Manual

Page 1
SERVICE MANUAL
KING
SERIES
ASH-18AK, ASH-24AK
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8
Page 9
Page 10
Page 11
66
6
66
Manual of functions of remote controller and operation method
Manual
1 of functions of remote controller
6.1.1 Temperature parameter
The room setting temperature(Tpreset)
The room ambient temperature (Tamb)
6.1.2
Basic Functions
Once energized, the compressor should in no way be restarted unless after 3-minute time interval at least. For the first ene
rgization, the compressor will be started without 3-minute lag. The compressor, once started,will not be stopped
within 6 minutes with the change of room temperature.
Cooling Mode
Cooling Conditions and Process
When T and the indoor fan
When T When T
Under this mode, the switchover valve will not be powered on, and the setting temperature range is16 ~30 .
amb
amb.≤Tpreset
preset
.T
+1, the unit will run under cooling mode, in which case the compressor and outdoor fan will start
preset
will run at setting speed.
-1, the compressor and the outdoor fan will stop, the indoor fan will run at setting speed.
-1 <T
amb.
< T
preset
+1 , the unit will maintain its original operating status.
T
+1
-1
amb
6 min.
3 min.
6 min.
T
T
preset
preset
Start cooling
Original operating status
Stop cooling
Compressor
Outdoor fan
Indoor fan
Preset speed
6.1.2.1.3 Protection
Antifreeze Protection
Run
Stop
If it is detected that the system is under antifreeze protection, the compressor and outdoor fan will be stopped, and the indoor fan will run at setting speed. When antifreeze protection is released and the compressor has stopped for 3 minutes, the unit will resume its original operating status.
During antifreeze protection
Compressor
3 min.
Outdoor fan
Preset speed
Stop
6.1.2.2 DRY Modes
Indoor fan
Run
6.1.2.2 .1 The conditions and process of DRY
When T
amb.
> T
preset
+2 , the unit will run under DRY cooling mode, in which case the compressor and outdoor fan
will be started and the indoor fan will run at low speed.
When T
preset
-2℃≤T
amb.≤Tpreset
+2, the unit will run under DRY mode, in which case the indoor fan will keep run
at low speed, the compressor and the outdoor fan will be stopped after 6 minutes . After 4 minutes,the compressor
and the outdoor fan will be restarted. The dehumidifying process is so repeated in cycle.
When T
Under this mode, the switchover valve will not be powered on, and the setting temperature range is16 ~30 .
.
amb
.< T
-2, the compressor and outdoor fan will be stopped, the indoor fan will run at low speed.
preset
Page 12
Cooling
T
preset
+2
T
amb
Dry
T
-2
preset
6 min. 6 min.
4 min.
4 min.
Stop
Compressor
Outdoor fan
Indoor fan
low speed
Run Stop
6.1.2.2.3 Protection
Antifreeze Protection
Upon meeting the cooling condition, if it is detected that the system is under antifreeze protection, the compressor and outdoor fan will be stopped,and the indoor fan will run at low speed. When antifreeze protection is released and the compressor has stopped for 3 minutes, the complete unit will resume its original operating status.
Upon meeting the dehumidify condition, if it is detected that the system is under antifreeze protection, the com
-pressor and outdoor fan will be stopped,and the indoor fan will run at low speed. When antifreeze protection is released and the compressor has stopped for 4 minutes, the complete unit will resume its original operating status.
6.1.2.3 HEAT Mode (there is no this mode for cooling only unit)
6.1.2.3 .1The conditions and process of heating
When Tamb Tset +2 ,the system enters heating running, in this case, the reversal valve, compressor, outer fan enter simultaneously running.The indoor fan will delay at most for 2min to run.
When Tamb Tset +4 ,the compressor and outdoor fan will stop, but the reversal valve is still with power on, the indoor unit will run at setting fan speed for 60s then will stop . When Tset +2 <Tamb < Tset +4 ,the unit will maintain its original operating status.
Under this mode, the switchover valve will be powered on, and the setting temperature range is16 ~30 .
Tset
Tset
Tamb.
6Min.
3Min.
6Min.
Stop heating
Original running state
Start heating
Compressor
6.1.2.3.3 Conditions and processes of defrost
Outer fan
Inner fan
Reversal valve
2Min.
Running
Setting fan speed
2Min.
Stop
Setting fan speed
This unit adopt intelligent defrosting,it can defrost according to the frosting conditions,dual 8 display H1
6.1.2.3.4 Protection
High
Temp. Protection
If it is detected that the evaporator tube temperature is too high, the outdoor fan will be stopped. When the tube temperature resumes to normal, the outdoor fan will be restarted.
Noise
Silencing Protection: If the unit is stopped by pressing ON/OFF, the reversal valve will be stopped after
2-minute lag; or 2 minutes will be delayed upon mode switching.
6.1.2.4 Fan mode
Under FAN mode, only the indoor fan runs at setting speed.The RUN indicator will be bright. Double 8 module indicator
will display the setting temperature. When stand by, the power indicator is bright but the unit does not run.
6.1.2.5 Auto Mode
Under this mode, the system will automatically select its run mode (cool, dehumidify, heat or fan) with the change of ambient temperature. For protection function, same as under cooling and heating mode.
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 21
Page 22
Page 23
Page 24
Page 25
Page 26
Page 27
Page 28
Page 29
Page 30
PARTS GUIDE
KING
ASH-18AK, ASH-24AK
SERIES
Page 31
Page 32
Page 33
Parts List for ASH-18AK Indoor unit
No. Description Parts No. Qty
Price
rank
ASH-18AK Indoor unit
1 Wall Mounting Frame 01252004 1 AK 2 Rear Case 22202329 1 AW 3 O-Gasket of Cross Fan Bearing 76512203 1 AC 4 Screw Cap 24252015 3 AA 5 Round Louver 10512429 11 AB 6 Swing Lever 10582057 1 AC 7 Swing Lever 10582058 1 AC 8 Water Tray 20182057 1 AW
9 Upper Air Deflector 10512085 1 AF 10 Lower Guide Louver 10512086 1 AF 11 Cross Flow Fan 10352022 1 AN 12 Evaporator Assy 0100224502 1 BD 13 Drain Pipe 05230014 1 AD 14 Evaporator Support 24212067 1 AF 15 Filter Sub-Assy 11122048 2 AD 16 Front Case Assy 20002652 1 AU 17 Front Panel Assy 20002843 1 AM 18 Remote Controller 30510041 1 AT 19 Displaying Light Board 30545033 1 AZ 20 Electric Box Cover 20112019 1 AE 21 Fixed Clamp 71010103 1 AB 22 Terminal Board 42010262 1 AD 23 Electric Box Cover 20112020 1 AE 24 Main PCB 30135096 1 BA 25 Transformer 57X25C 43110237 1 AM 26 Ambient Temperature Sensor 390000451 1 AD 27 Tube Sensor 390000591 1 AD 28 Sensor Insert 42020063 1 AD 29 Electric Box 20112018 1 AK 30 Lower Shieldof Electric Box 01592037 1 AE 31 Upper Shieldof Electric Box 01592038 1 AD 32 Stepping Motor 15213001 1 AK 33 Motor Press Plate 26112095 1 AE 34 Helicoid tongue 26252009 1 AH 35 Fan Motor 15012077 1 AX 36 Pipe Clamp 26112096 1 AD 37 Connecting Cable 400205402 1 AN
The data are subject to change without notice.
Page 34
Parts List for ASH-24AK Indoor unit
No. Description Parts No. Qty
Price
rank
ASH-24AK Indoor unit
1 Wall Mounting Frame 01252004 1 AK
2 Rear Case 22202329 1 AW
3 O-Gasket of Cross Fan Bearing 76512203 1 AC
4 Screw Cap 24252015 3 AA
5 Round Louver 10512429 11 AB
6 Swing Lever 10582057 1 AC
7 Swing Lever 10582058 1 AC
8 Water Tray 20182057 1 AW
9 Upper Air Deflector 10512085 1 AF 10 Lower Guide Louver 10512086 1 AF 11 Cross Flow Fan 10352022 1 AN 12 Evaporator Assy 010022365 1 BF 13 Drain Pipe 05230014 1 AD 14 Evaporator Support 24212067 1 AF 15 Filter Sub-Assy 11122048 2 AD 16 Front Case Assy 20002652 1 AU 17 Front Panel Assy 20002843 1 AM 18 Remote Controller 30510041 1 AT 19 Displaying Light Board 30545033 1 AZ 20 Electric Box Cover 20112019 1 AE 21 Fixed Clamp 71010103 1 AB 22 Terminal Board 4201026201 1 AD 23 Electric Box Cover 20112020 1 AE 24 Main Board 30135163 1 BB 25 Transformer 57X25C 43110237 1 AM 26 Ambient Temperature Sensor 390000451 1 AD 27 Tube Sensor 390000591 1 AD 28 Sensor Insert 42020063 1 AD 29 Electric Box 20112018 1 AK 30 Lower Shieldof Electric Box 01592037 1 AE 31 Upper Shieldof Electric Box 01592038 1 AD 32 Stepping Motor 15213001 1 AK 33 Motor Press Plate 26112095 1 AE 34 Helicoid tongue 26252009 1 AH 35 Fan Motor 15012077 1 AX 36 Pipe Clamp 26112096 1 AD 37 Connecting Cable 400205382 1 AN
The data are subject to change without notice.
Page 35
Page 36
Parts List for ASH-18AK Outdoor unit
No. Description Parts No. Qty
Price
rank
ASH-18AK Outdoor unit
1 Small Handle 26235401 1 AC
2 Axial Flow Fan 10333426 1 AR
3 Fan Motor 15013070 1 AZ
4 Motor Support 01703059 1 AF
5 Condenser Assy 01113033 1 BK
6 Condenser Clamp 01175202 2 AB
7 Top Cover 01255001 1 AH
8 Rear Grill 014730371 1 AG
9 Electrical Box 01403835 1 AF 10 Capacitor CBB61 3.5kuF/450V 33010010 1 AG 11 Capacitor Clamp 02141375 1 AB 12 Capacitor 33000039 1 AM 13 Terminal Board 2-8 42011103 1 AD 14 Terminal Board 42010265 1 AE 15 4-way Valve 430004032 1 BA 16 4-way Valve Accessary 430004002 1 AM 17 Capillary Assy 03103555 1 AZ 18 Right Side Plate 01305013 1 AH 19 Handle 26235254 1 AC 20 Gas Valve Assy 07130213 1 AH 21 Cut-off Valve 07100003 1 AG 22 Valve support 01713076 1 AD
23.1 Compressor and Fittings 00103007 1 BW
23.2 Build in
23.3 Compressor Gasket 4CYC00008 76710202 3 AE 24 Clapboard Sub-Assy 01233035 1 AK 25 Drainage Connecter 06123401 1 AA 26 Chassis 0120362602P 1 AU 27 Front Side Plate 01305015 1 AW 28 Front Grill 22415001 1 AL
The data are subject to change without notice.
Page 37
Page 38
Parts List for ASH-24AK Outdoor unit
No. Description Parts No. Qty
Price
rank
ASH-24AK Outdoor unit
1 Panel Grille 22414102 1 AL 2 Front Plate 01433017 1 AW 3 Axial Flow Fan φ472X165 10338731 1 AR 4 Fan Motor 15015421 1 BA 5 Motor Support 01703027 1 AE 6 Condenser Assy 01113034 1 BL 7 Top Cover 01255262 1 AQ 8 Mesh Enclosure 01473028 1 AG
9 Electric Box Cover Plate 01413047 1 AF 10 Electric Box Sub-Assy 01403248 1 AF 11 Capacitor CBB65 50uF/450V φ50X120 33000001 1 AL 12 Capacitor CBB61 3.5kuF/450V 33010010 1 AG 13 Terminal Board 42010194 1 AD 14 4-way Valve 03023724 1 AY 15 Terminal Board 2-8 42011103 1 AD 16 4-way Valve Accessary 430004002 1 AM 17 4-way Valve 430004032 1 BA 18 Handle 26235253 1 AC 19 Gas Valve Sub-Assy 07103030 1 AV 20 Liquid Valve Assy 07133024 1 AU 21 Rear Side Plate Sub-Assy 01303115 1 AM 22 Valve Support Sub-Assy 01715001 1 AD 23 Capillary Assy 03103556 1 AZ
24.1 Compressor and Fittings 00100525 1 CA
24.2 Build in
24.3 Compressor Gasket 4CYC00008 76710202 3 AE 25 Isolation Washer 70410523 1 AC 26 Mid Clapboard Sub-Assy 01233024 1 AK 27 Underpan Sub-Assy 01205073 1 AU 28 Front Side Plate 01303023 1 AG
The data are subject to change without notice.
Page 39
99
9
Failure and analysis
99
Note: When replacing the controller, make sure insert the wire jumper into the new controller, otherwise, the running indicator off 3s, blink 15 times, (the dual eight will display C5) but cannot turn on the unit.
Trip of breaker or blow of fuse
The air conditioner does not react after it is powered ( after the plug is inserted, the buzzer does not sound and the remote startup has no response)
Air conditioner can not start up
The breaker trips at once when it
is set to "ON".
The breaker trips in few minutes when it is set to "ON"
No power
Power plug is not well plugged in and poor con­nection
Fuse of controller burnt out
The transformer connection is loose or has bad contact or the transformer has malfunction
Controller is broken
Measure insulation resistance to ground to see if there is any leakage.
The circuit or the part of the air conditioner has malfunction. They heat and break the insulation and lead to short circuit or creepage. Measure the insulation resistance or eliminate the malfunc­ tion one by one. If the breaker itself has
malfunction, then replace the breaker.
Check power supply circuit.
Check if the plug is properly plugged in and make the loose contact firm.
Change controller fuse
Fasten the wiring; measure the output voltage of the transformer, if it is incorrect, change the transformer
Check remote controller
In cool, heat mode,the outdoor unit and compressor will not run.
The remote controller
does not receive
signals (after it is
powered, the buzzer
will sound, unless it
has malfunction)
Power voltage is too low
Controller malfunction (IC2003 broken,
creepage of parallel capacitor of relay loop,
relay is broken etc.)
Wire loose or wrong connection
Improper setting of temperature
Remote controller is short of power
Remote controller malfunction
Receiver loose or poor connection
Receiver is broken
Change batteries
First, press the manual switch button AUTO, if there is no response,check based on the above methods. If it runs normally after pressing the button,check again whether the installation position and the connection wire of the reception head is correct. If it is correct,then replace the receiver or the re-
mote controller.
heck the voltage. If it is lower than 10£¥ of the rated voltage, check the
cause, improve the power supply condition and add the stabilized voltage power supply.
Change controller
Correctly wire according to the drawing
Adjust setting temp.
Page 40
Improper set of temperature
Adjust set temperature
Poor COOL(HEAT) operation
If cooling (heating) load is proper
The refrigerant has leakage or is insufficient
Leakage between the high pres-
Malfunction of refrigerant flow
sure and the low pressure in­side the compressor
Malfunction of four-way valve Replace the four-way valve
Local block of capillary Replace the capillary
Blockage of cooling system
Heat insulation for the connection pipes of the indoor unit and the out­door unit is bad.
Block of outdoor heat ex­changer
Check the forecasted load of cooling (heating)
heck and fill the leakage, then vacuumize it and supplement the re­frigerant as required
Replace the compressor
Judge whether the system is blocked by observing the condensation of evapora­tor and the pressure value of the high pressure manometer and take measures to deal with the system.
Make sure that heat insulation for the thick and thin pipes is good. Heat insulation must also be provided for the joint andthe exposed part of the copper pipe .
Clean the dust accumulated on the surface of the heat exchanger.
Air filter were blocked
Fan speed was set too slow
Air circulation is insufficient
Fan rotation speed becomes low
The installation position of the outdoor unit is not appropriate.
The outdoor temperature is too high.
The air tightness is not enough. People come in and out too frequently. There are heating devices indoors.
Clean the filter
To set the fan speed to high or middle speed
Capacitor damage
Motor damage
Good ventilation must be provided for the installation position of the outdoor unit.
Properly install the rainproof plate or the sunproof plate. If the maximum cool air still can not meet the requirement, it is sug­gested to replace the air conditioner.
Replace the capaci­tor
Replace the motor
Keep certain air tightness indoors, try not to use electricalappliance with large quantity of heat
Page 41
The fan does not run when it is set to supply air.
The indoor fan motor is burned or breaks or has the heat protector malfunction.
The built-in heat protector of the motor breaks frequently because the motor is abnormal.
Wrong connection
Replace the fan motor or the defective part.
Replace the fan motor
Make the correction connection based on the circuit drawing.
In the cooling and heating mode, the compressor runs, but the outdoor fan does not run.
The compres­sor is too hot and leads to the action of the protector.
The fan capacitor has open circuit or is damaged.
The outdoor fan motor is damaged.
Wrong connection
The outdoor fan capacitor is damaged.
Malfunction of compressor
Breakage of running capacitor of compressor
The voltage is too low or too high.
Wrong wire connection
The protector itself has malfunction.
The refrigerant is not enough or is too much.
Replace the fan capacitor of the same type and same specification.
Replace the fan motor
Make the correct connection based on the circuit drawing
Replace the fan capacitor
Replace the compressor
Replace the capacitor
Manostat is recommended.
Connect the circuit diagram correctly
Use the multimeter to check whether the con­tact of the compressor is on when it is not overheated. If it is not on, then replace the pro­tector
Adjust the volume of the refrigerant
The compres­sor is too hot and leads to the action of the protector.
The swing fan does not run.
The capillary is blocked and the tem­perature rises.
The compressor does not run smoothly or is stuck. The air dis­charge valve is damaged
The protector itself has malfunction.
The torque of the swing motor is not enough
Wrong connection
The controller is damaged(IC2003 is damaged, the swing relay can not close, etc)
Replace the capillary
Replace the compressor
Replace the protector
First, check whether the connection is wrong. If no, replace the parts
Page 42
Water leakage
Drainage pipe blocked or broken Change drainage pipe
Wrap of refrigerant pipe joint is not close enough.
Re-wrap and make it tight.
Fan of indoor unit contacts other parts. Adjust fan location.
Foreign object in indoor unit
Compressor shakes too much.
Touch of pipeline of outdoor unit
Abnormal sound
Take out the foreign object.
Adjust support washer of compressor, and tighten loosen screws.
Separate the touching pipeline.
and shake
Touch of inner plates
1. Tighten connect screw.
2. Stick absorbing clay between plates.
Louver of outdoor unit touched outer case.
Abnormal sound inside compressor
Abnormal solenoid sound from 4-way valve when heating
Adjust location of louver.
Change compressor
Circuit-short inside solenoid of the valve and change the solenoid valve.
There are no heating malfunctions in the above for the cooling only unit.
Page 43
Loading...