Sinclair ASGE-24AI S, ASGE-42AI-3 S, ASGE-36AI S, ASGE-36AI-3 S Service Manual

Page 1
SERVICE MANUAL
CASSETTE, FLOOR&CEILING, DUCT UNITS
DC INVERTER
SERIES
OUTDOOR UNITS
OUTDOOR AND INDOOR UNITS
Page 2
Page 3
2
PRODUCT
1 MODELS LIST
1.1 Outdoor Unit
Model Name
Nominal Capacity
Cooling/Heating
(Btu/h)
Ref.
Power supply
(V, Ph, Hz)
Appearance
ASGE-18AI 1
7060/19790 R
410A 2
20-240,1,50
ASGE-24AI 2
3880/27330 R
410A 2
20-240,1,50
ASGE-24AI S
23880/27330
R410A 2
20-240,1,50
ASGE-36AI S 34100/36800 R410A
220-240,1,50
ASGE-42AI-3 S 40600/40500 R410A
220-240,1,50
ASGE-36AI
36000/42000
220-240,1,50
ASGE-36AI-3
36000/42000
R410A
380-415,3,50
ASGE-42AI-3
42000/48000
380-415,3,50
Note:1 Ton =12000Btu/h = 3.517kW ASGE
ASGE-36AI-3 S
34100/36800 R410A 380-415~,3,50
Page 4
NOTE: all indoor units are single phase
1.2 Indoor Unit
Type Model Name
Nominal Capacity
Cooling/Heating
(Btu/h)
Ref.
Power supply
(V, Ph, Hz)
Appearance
ASD-18AI
17060/19790
ASD-24AI
23880/27330
ASD-36AI
36000/42000
ASD-36AI S 34100/36800
ASD-42AI
42000/48000
ASD-42AI S 40600/45000
Duct Type
220-240
1Ph
50Hz
ASF-18AI
17060/19790
ASF-24AI
23880/27300
ASF-36AI
36000/42000
R410A
ASF-36AI S
34100/36800
ASF-42AI
40940/44350
ASF-42AI S
42000/48000
Ceiling
Type
ASC-18AI
17060/19790
ASC-24AI
23880/27300
ASC-36AI
36000/42000
ASC-36AIS 34100/36800
ASC-42AI
42000/48000
ASC-42AI S 40600/44350
Cassette
Type
Page 5
2. Model Designation
A S C – 36 A I - 3 S
3phase
Inverter
Refrigerant type(A - R410A)
Cooling Capacity in HP (x100) HP
Type
SINCLAIR
Air Conditioner
2.1 Regulation of Units Classification
Units classification Code Outdoor unit GE Cassette type C Floor/Ceiling type F Duct type D
Model Designation
1ASGE-18AI means universal outdoor unit with nominal cooling capacity of 18000Btu, signle phase
power supply of 22
0~240V50Hz, heat pump, DC inverter,T1 condition and refrigerant of R410a .
2ASGE-42AI-3 means universal outdoor unit with nominal cooling capacity of 42000Btu, three phase
power supply of 380
~415V50Hz, heat pump, DC inverter,T1 condition and refrigerant of R410a .
3ASD-24AI means duct type indoor unit with nominal cooling capacity of 24000Btu, single phase
power supply of 22
0~240V50Hz, heat pump, DC inverter,T1 condition and refrigerant of R410a .
Note:1 Ton =12000Btu/h = 3.517kW NOTES: The universal outdoor units means that the customer can choose any of three kind of indoor unit to match the outdoor unit without any change with it.
- small pipe diameter
()ASD-42AI-3 S means duct type indoor unit with nominal cooling capacity of 42000Btu, single phase
power supply of 22
0~240V50Hz, heat pump, DC inverter,T1 condition and refrigerant of R410a,
Page 6
3 FUNCTION
Function Description
Memory function
when unit restarts after power off, it will run on former status, the mode and parameter are kept the same
Remote control function
wireless controller and remote controller can be selected, and the maximum control distance of remote controller is 10m.
Timing function
it can timing ON/ OFF separately, meanwhile, it can also timing on circularly
Self-diagnosis with alarm function
Once the unit has malfunction, the malfunction code will be indicated and alarm rings immediately
Sleep function it can self control for saving energy in energy saving mode.
Automatic function
the fan of indoor unit can adjust fan speed automatically based on actual demand when cooling or heating under automatic mode
Cool air proof function
the fan starts only when the temperature of indoor unit heat exchanger is higher than indoor temperature under heating mode
Weekly Time
Centralized Control and Weekly Timer Functions: The centralized controller and the weekly timer are integrated in the same wire controller. The system has both the centralized control and the week timing functions. Up to 16 sets of units can be controlled simultaneously by the centralized controller (weekly timer). The weekly timer has the function of invalidating the lower unit. The weekly timing function is able to realized four timing ON/OFF periods for any unit every day, so
as to achieve fully automatic operation. No timing control can be set for holidays. High/low pressure protection
when suction pressure is too low or discharge pressure is too high, compressor
will stop and unit display malfunction code
Overload protection
compressor has its own overheat protection.Once the temperature of
compressor is higher than allowable level, compressor will stop and only when
temperature recovery, compressor restart
Over current protection
once the current of compressor is higher than normal level, compressor will stop
and unit display malfunction code Discharge high temperature protection
once the discharge temperature of compressor is higher than allowable value,
compressor will stop and unit display malfunction code Reverse (open) phase protection
once the phase sequence of power supply is incongruent or the phase is absent,
unit can’t work. Anti-high temperature protection
once the heat exchanger temperature of indoor unit is too high, compressor will
stop.
Timing ON/OFF display
display and timing turn ON/OFF timeonly with wired controller have this
function
Fan speed display
display the speed (high,medium,low) of fanonly with wired controller have this
function
Function model display
cooling mode,dry mode,heating mode,fan modeonly with wired controller have
this function Testing display display testing modeonly with wired controller have this function
Temperature display
display room temperature and set temperatureonly with wired controller and
remoter board have this function
Page 7
4 PRODUCT DATA
4.1 Product Data at Rated Condition
4.1.1 Duct Type
Indoor unit ASD-18AI
Model
Outdoor unit ASGE-18AI
kW 5.0
Cooling
Btu/h
17000
kW 5.8
Nominal
Capacity
Heating
Btu/h 19800
Cooling kW 1.57
wer
Input
Heating kW 1.53
EER/COP W/W 3.18/3.79
Indoor Unit ASD-18AI
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan
Drive Direct Driver
Motor Output kW 0.06
Air Flow m3/h 840
Fan
Ext. Static Pressure Pa 60
Sound Pressure Level(H/M/L) dB(A) 42/40/38
Air Filter Standard washable synthetic
Drain Piping mm φ32×1.5
Dimensions (W×H×D)
(Outline/Package)
mm
1012×266×736
/1120×323×795
Weight(Net/Gross) kg 34/41
Outdoor Unit ASGE-18AI
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.03
Fan Motor Speed rpm 850
Type ROTARY
Compressor
Power Input W 1630
Type R410A
Control Electronic Expansion Valve
Refrigerant
Charge kg 1.5
Dimensions (W×H×D)
(Outline/Package)
mm
820×540×320
/870×590×360
Weight(Net/Gross) kg 36/40
Liquid mm 6.35
Gas mm 12.7
Max. Length m 20
Piping
Connections
Max. Height Difference m 15
Power
Page 8
Continued: 1
Indoor unit
ASD-24AI
ASD-36AI
Model
Outdoor unit ASGE-24AI ASGE-36AI
kW 7.0 10.0
Cooling
Btu/h 24000
341
00
kW 8.0 12.0
Nominal
Capacity
Heating
Btu/h 27300 40900
Cooling kW 2.41 3.5 Power
Input
Heating kW 2.28 3.8
EER/COP W/W 2.90/3.51 2.86/3.16
Indoor Unit
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.15 0.5
Air Flow m3/h 1600 2000
Fan
Ext. Static Pressure Pa 80 150
Sound Pressure Level(H/M/L) dB(A) 47/44/42 50/48/46
Air Filter
Standard washable synthetic
Drain Piping mm φ20×1.2 φ20×1.2
Dimensions (W×H×D)
(Outline/Package)
mm
1270×268×530
/1345×283×594
1226×290×775
/1335×305×834
Weight(Net/Gross) kg 37/43
54/61
Outdoor Unit
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.068 0.092×2
Fan
Fan Motor Speed (H/M/L) rpm 840/620/400 940/-/700
Type
ROTARY SCROLL
Compressor
Power Input W 1630 3240
Type
R410A
Control
Electronic Expansion Valve
Refrigerant
Charge kg 1.8
4.0
Dimensions (W×H×D)
(Outline/Package)
mm
913×680×378
/994×750×428
1032×1250×412 /1110×1385×450
Weight(Net/Gross) kg 51/55 128/139
Liquid mm 9.52 12.7
Gas mm 15.8 19.05
Max. Length m 30 50
Piping
Connections
Max. Height Difference m 15 30
ASD-24AI ASD-36AI
ASGE-24AI
ASGE-36AI
(old unit)
Page 9
Continued: 2
Indoor unit ASD-36AI ASD-42AI
Model
Outdoor unit ASGE-36AI-3 ASGE-42AI-3
kW 10.0 12.0
Cooling
Btu/h 34100 41000
kw 12.0 14.0
Nominal
Capacity
Heating
Btu/h 40900
48000
Cooling kW 3.3
4.45
Power
Input
Heating kW 3.7 4.65
EER/COP W/W 3.05/3.3 2.70/3.01
Indoor Unit ASD-36AI ASD-42AI
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan Drive Direct Driver
Motor Output kW 0.5
Air Flow m3/h 2000
Fan
Ext. Static Pressure Pa 150
Sound Pressure Level(H/M/L) dB(A) 50/48/46
Air Filter Standard washable synthetic
Drain Piping mm φ20×1.2
Dimensions (W×H×D)
(Outline/Package)
mm
1226×290×775
/1335×305×834
Weight(Net/Gross) kg 54/61
Outdoor Unit ASGE-36AI-3 ASGE-42AI-3
Power Supply
380-415V~/3 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.092×2 0.092×2
Fan
Fan Motor Speed (H/M/L) rpm 940/-/700 940/-/700
Type SCROLL
Compressor
Power Input W 4160
Type R410A
Control Electronic Expansion Valve
Refrigerant
Charge kg
4.0
Dimensions (W×H×D)
(Outline/Package)
mm
1032×1250×412 /1110×1385×450
Weight(Net/Gross) kg 128/139
Liquid mm
12.7
Gas mm 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
Page 10
Continued: 4
Indoor unit
Model
Outdoor unit
kW 7.0 10.0
Cooling
Btu/h 24000 34100
kW 8.0 10.8
Nominal
Capacity
Heating
Btu/h 27300 36800
Cooling kW 2.41 3.50 Power
Input
Heating kW 2.28 2.90
EER/COP W/W 2.90/3.51 2.85/3.72
Indoor Unit
Power Supply
220~240V-50Hz-1Ph
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.15×1 0.50×1
Air Flow m3/h 1600/1400/1200 2000
Fan
Ext. Static Pressure Pa 80 150
Sound Pressure Level(H/M/L) dB(A) 47/44/42 50/48/46
Air Filter
Standard washable synthetic
Drain Piping mm
φ26×2
Dimensions (W×H×D)
(Outline/Package)
mm
1270×268×530
/1345×283×594
1226×290×775
/1335×305×834
Weight(Net/Gross) kg 37/43 54/61
Outdoor Unit
Power Supply
220~240V-50Hz-1Ph
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.068×1 0.093×1
Fan
Fan Motor Speed (H/M/L) rpm 840/620/400 780/-/500
Type
ROTARY
Compressor
Output Input W 1630 3010±7.5%
Type
R410A
Control
Electronic expansion valve
Refrigerant
Charge kg 1.8 2.6
Dimensions (W×H×D)
(Outline/Package)
mm
980×790×427
/1080×840×485
Weight(Net/Gross) kg 51/55 70/78
Liquid mm 9.52
Gas mm 15.88
Max. Length m 30
Piping
Connections
Max. Height Difference m 15
ASGE-24AI S
ASD-24AI ASD-36AI S
ASD-36AI S
ASGE-36AI S
ASGE-36AI S
ASD-24AI
ASGE-24AI S
(new unit)
Page 11
Continued: 5
Indoor unit ASD-36AI S ASD-42AI S
Model
Outdoor unit ASGE-36AI-3 S ASGE-42AI-3 S
kW 10.0 11.9
Cooling
Btu/h 34100 40600
kW 10.8 13.2
Nominal
Capacity
Heating
Btu/h 36800 45000
Cooling kW 3.50 4.17 Power
Input
Heating kW 2.90 3.94
EER/COP W/W 2.85/3.72
2.85/3.3
5
Indoor Unit
Power Supply
220~240V-50Hz-1Ph
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.5×1
Air Flow m3/h 2000
Fan
Ext. Static Pressure Pa 150
Sound Pressure Level(H/M/L) dB(A) 50/48/46
Air Filter
Standard washable synthetic
Drain Piping mm
26×2
Dimensions (W×H×D)
(Outline/Package)
mm
1226×290×775
/1335×305×834
Weight(Net/Gross) kg 54/61
Outdoor Unit
Power Supply
380~415V-50Hz-3Ph
220~
240V-50Hz-1Ph
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.93×1
Fan
Fan Motor Speed (H/M/L) rpm 780/-/500 820±20
Type
ROT
ARY
Compressor
Power Input kW 3010±7.5%
Type
R410A
Control
Electronic Expansion Valve
Refrigerant
Charge kg 2.6 3.5
Dimensions (W×H×D)
(Outline/Package)
mm
980×790×427
/1080×840×485
1107×1100×440
/1155×1220×490
Weight(Net/Gross) kg 70/78 88/98
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Max. Length m 30 50
Piping
Connections
Max. Height Difference m 15 30
ASD-36AI S ASD-42AI S
ASGE-36AI-3 S
ASGE-42AI-3 S
Page 12
Note
Nominal capacities are based on the follow conditions.
Indoor Outdoor
Cooling
DB27 (80.6 )℃℉
WB19 (66.2 )℃℉
DB35 (95 )℃℉
WB24 (75.2 )℃℉
Heating
DB20 (68 )℃℉
WB-- (℃ -- )
DB7(44.6)℃℉
WB6(42.8)℃℉
Piping Length 5m
The air volume is measured at the relevant standard external static pressure.
󰷅 Noise is tested in the Semianechoic Room, so it should be slightly higher in the actual
operation due to environmental change.
Page 13
4.1.2 Ceiling Type
Indoor unit ASF-18AI
Models
Outdoor unit
ASGE-
18AI
kW 5.0
Cooling
Btu/h 1700
kW 5.8
Nominal Capacity
Heating
Btu/h 19800
Cooling kW 1.81 Power
Input
Heating kW 1.94
EER/COP W/W
2.76/2.99
Indoor Unit ASF-18AI
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.04
Fan
Air Flow m3/h 700
Sound Pressure Level(H/M/L) dB(A) 54/50/46
Air Filter
Standard washable synthetic
Drain Piping mm φ28×1.5
Dimensions (W×H×D)
(Outline/Package)
mm
836×238×695
/935×295×805
Weight(Net/Gross) kg 26/33
Outdoor Unit ASGE-18AI
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.03
Fan Motor Speed rpm 850
Type
ROTARY
Compressor
Power Input W 1630
Type
R410A
Control
Electronic Expansion Valve
Refrigerant
Charge kg 1.50
Dimensions (W×H×D)
(Outline/Package)
mm
820×540×320
/870×360×590
Weight(Net/Gross) kg 36/40
Liquid mm 6.35
Gas mm 12.70
Max. Length m 20
Piping
Connection
s
Max. Height Difference m 15
Page 14
Continued: 1
Indoor unit ASF-24AI ASF-36AI
Models
Outdoor unit ASGE-24AI ASGEASGE-36AI
kW 7.0 10.0
Cooling
Btu/h 24000 34100
kW 8.0 12.0
Nominal
Capacity
Heating
Btu/h 27300 40900
Cooling kW 2.43 3.35 Power
Input
Heating kW 2.2 3.95
EER/COP W/W 2.88/3.64 2.98/3.04
Indoor Unit
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.1 0.085
Fan
Air Flow m
3
/h
117
0 1800
Sound Pressure Level(H/M/L) dB(A) 50/48/46 54/51/48
Air Filter
Standard washable synthetic
Drain Piping mm φ28×1.5 φ28×1.5
Dimensions (H×W×D)
(Outline/Package)
mm
1300×188×600
/1414×248×724
1590×238×695/
1714×330×830
Weight(Net/Gross) kg 33/40 48/58
Outdoor Unit
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.068 0.092×2
Fan
Fan Motor Speed (H/M/L) rpm 840/620/400 940/-/700
Type
ROTARY SCROLL
Compressor
Power Input W 1630 3240
Type
R410A
Control
Electronic expansion valve
Refrigerant
Charge kg 1.8
4.0
Dimensions (W×H×D)
(Outline/Package)
mm
913×680×378
/994×750×428
1032×1250×412 /1110×1385×450
Weight(Net/Gross) kg 51/55 128/139
Liquid mm 9.52 12.7
Gas mm 15.8 19.05
Max. Length m 30 50
Piping
Connections
Max. Height Difference m 15 30
ASF-24AI
ASF-36AI
ASGE-24AI
ASGE-36AI
Page 15
Continued: 2
Indoor unit ASF-36AI ASF-42AI
Models
Outdoor unit ASGE-36AI-3 ASGE-42AI-3
kW 10.0 12.0
Cooling
Btu/h 34100 41000
kW 12.0 14.0
Nominal
Capacity
Heating
Btu/h 40900 48000
Cooling kW 3.4 4.3
Power
Input
Heating kW 4.0 4.8
EER/COP W/W 2.94/3.00 2.79/2.92
Indoor Unit
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan Drive Direct Driver
Motor Output kW 0.085
Fan
Air Flow m3/h 1800
Sound Pressure Level(H/M/L) dB(A) 54/51/48
Air Filter Standard washable synthetic
Drain Piping mm φ28×1.5
Dimensions (W×H×D)
(Outline/Package)
mm
1590×238×695
/1714×330×830
Weight(Net/Gross) kg 48/58
Outdoor Unit
Power Supply 380-415V~/3 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.092×2
Fan
Fan Motor Speed (H/M/L) rpm 940/-/700
Type SCROLL
Compressor
Power Input W
4160
Type R410A
Control Electronic Expansion Valve
Refrigerant
Charge kg 4.0
Dimensions (W×H×D)
(Outline/Package)
mm
1032×1250×412
/1110×1380×450
Weight(Net/Gross) kg 128/139
Liquid mm 12.7
Gas mm 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
ASF-36AI ASF-42AI
ASGE-36AI-3 ASGE-42AI-3
Page 16
Continued: 4
Indoor unit ASF-24AI ASF-36AI S
Models
Outdoor unit ASGE-24AI S ASGE-36AI S
kW 7.0 10.0
Cooling
Btu/h 24000 34100
kW 8.0 10.8
Nominal
Capacity
Heating
Btu/h 27300 36800
Cooling kW 2.43 3.4 Power
Input
Heating kW
2.20 2.90
EER/COP W/W 2.88/3.64 2.94/3.72
Indoor Unit
Power Supply
220~240V-50Hz-1Ph
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
direct
Motor Output kW 0.05×1 0.085×1
Fan
Air Flow m
3
/h 1170 1800
Sound Pressure Level(H/M/L) dB(A) 50/48/46 54/51/48
Air Filter
Standard washable synthetic
Drain Piping mm
17×2.5
Dimensions (H×W×D)
(Outline/Package)
mm
1300×188×600/14
14×248×724
1590×238×695/ 1 714×330×830
Weight(Net/Gross) kg
33/40
48/58
Outdoor Unit
Power Supply
220~240V-50Hz-1Ph
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.068×1 0.093×1
Fan
Fan Motor Speed (H/M/L) rpm 840/620/400 780/-/500
Type
ROTARY
Compressor
Power Input W 1630 3010±7.5%
Type
R410A
Control
Electronic expansion valve
Refrigerant
Charge kg 1.8 2.6
Dimensions (W×H×D)
(Outline/Package)
mm
913×680×378/
994×750×428
980×790×427/
1080×840×485
Weight(Net/Gross) kg 51/55 70/78
Liquid mm
9.52
9.52
Gas mm 15.88 15.88
Max. Length m 30
Piping
Connections
Max. Height Difference m 15
ASF-24AI
ASGE-24AI S
ASF-36AI S
ASGE-36AI S
Page 17
Continued: 5
Indoor unit
ASF-36AI S ASF-42AI S
Models
Outdoor unit
ASGE-36AI-3 S ASGE-42AI-3 S
kW
10 12
Cooling
Btu/h
34100 40940
kW
10.8 13.0
Nominal
Capacity
Heating
Btu/h
36800 44350
Cooling kW
3.40 4.14
Power
Input
Heating kW
2.90 3.94
EER/COP W/W 2
.94/3.72 2.90/3.30
Indoor Unit
Power Supply 220~240V-50Hz-1Ph
Heat Exchange Cross Fin Coil
Type Centrifugal fan Drive Direct Driver
Motor Output kW 0.085×1
Fan
Air Flow m3/h 1800
Sound Pressure Level(H/M/L) dB(A) 54/51/48
Air Filter Standard washable synthetic
Drain Piping mm 17×2.5
Dimensions (W×H×D)
(Outline/Package)
mm
1590×238×695/
1714×330×830
Weight(Net/Gross) kg
48/58
Outdoor Unit
Power Supply
380~415V-50Hz-3
Ph
220~240V-50Hz-1Ph
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.093×1
Fan
Fan Motor Speed (H/M/L) rpm 780/-/500 820±20
Type ROTARY
Compressor
Power Input W
3010±7.5%
Type R410A
Control Electronic expansion valve
Refrigerant
Charge kg 2.6 3.5
Dimensions (W×H×D)
(Outline/Package)
mm
980×790×427
/1080×840×485
1107×1100×440
/1155×1220×490
Weight(Net/Gross) kg 70/78
88/98
Liquid mm 9.52
Gas mm 15.88
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
ASF-
36AI S
ASGE-36AI-3 S
ASF-42AI S
ASGE-42AI-3 S
Page 18
Note
Nominal capacities are based on the follow conditions.
Indoor Outdoor
Cooling DB27 (80.6 )℃℉
WB19 (66.2 )℃℉
DB35 (95 )℃℉
WB24 (75.2 )℃℉
Heating DB20 (68 )℃℉
WB-- (℃ -- )
DB7(44.6)℃℉
WB6(42.8)℃℉
Piping Length 5m
The air volume is measured at the relevant standard external static pressure.
Noise is tested in the Semianechoic Room, so it should be slightly higher in the actual
operation due to environmental change.
Page 19
4.1.3 Cassette Type
Indoor unit ASC-18AI ASC-24AI ASC-36AI
Models
Outdoor unit ASGE-18AI ASGE-36AI
kW 5.0 7.0 10.0
Cooling
Btu/h 17000 24000 341
kW 5.8 8.0 12.0
Nominal
Capacity
Heating
Btu/h 19800 27300 40900
Cooling kW 1.71 2.49 3.4
Power
Input
Heating kW 1.93 2.11 4.0
EER/COP W/W 2.92/3.00 2.81/3.79 2.98/3.00
Indoor Unit
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan Drive Direct Driver
Motor Output kW 0.011 0.035 0.06
Fan
Air Flow m3/h 680 1180 1660
Sound Pressure Level(H/M/L) dB(A) 47/45/42 47/45/42 53/51/48
Air Filter Standard washable synthetic
Drain Piping mm φ31×3 φ32×3 φ32×3
Indoor Unit Dimensions
(Outline/Package) (W×H×D)
mm
600×230×600
/848×310×678
840×240×840
/960×310×960
840×320×840
/960×394×960
Weight(Net/Gross) kg 20/27 30/38 32/43
Panel Dimensions
(Outline/Package) (W×H×D)
mm
650×50×650
/670×102×730
950×60×950
/1025×115×1040
950×60×950
/1025×115×1040
Panel Weight(Net/Gross) kg 2.5/3.5 6.5/10 6.5/10
Outdoor Unit
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.03 0.068 0.093×2
Fan
Fan Motor Speed (H/M/L) rpm 850 840/620/400 940/-/700
Type ROTARY SCROLL
Compressor
Power Input W
1630 3240
Type R410A
Control Electronic Expansion Valve
Refrigerant
Charge kg 1.5 1.8 4.0
Dimensions (W×H×D)
(Outline/Package)
mm
820×540×320/
878×590×360
913×680×378 994×750×428
1032×1250×412/
1110×1385×450
Weight(Net/Gross) kg 36/40 51/55 128/139
Liquid mm 6.35 9.52 12.7
Gas mm 12.7 15.8 19.05
Max. Length m 20 30 50
Piping
Connections
Max. Height Difference m 15 15 30
ASC-18AI
ASGE-18AI
ASC-24AI
ASGE-24AI
ASC-36AI
ASGE-36AI
ASGE-24AI
Page 20
Continued: 1
Indoor unit ASC-36AI
Models
Outdoor unit ASGE-36AI-3
kW 10
Cooling
Btu/h 34100
kW 12
Nominal
Capacity
Heating
Btu/h
40900
Cooling kW 3.4
Power
Input
Heating kW 4.0
EER/COP W/W 2.94/3.00
Indoor Unit
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan Drive Direct Driver
Motor Output kW 0.06
Fan
Air Flow m3/h
1660
Sound Pressure Level(H/M/L) dB(A) 53/51/48
Air Filter Standard washable synthetic
Drain Piping mm φ32×3
Indoor Unit Dimensions
(Outline/Package) (W×H×D)
mm
840×320×840/
960×394×960
Weight(Net/Gross) kg 32/43
Panel Dimensions
(Outline/Package) (W×H×D)
mm
950×60×950/
1025×115×1040
Panel Weight(Net/Gross) kg
6.5/10
Outdoor Unit
Power Supply
380-415V~/3
Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.092×2
Fan Motor Speed (H/M/L) rpm 940/-/700
Type SCROLL
Type R410A
Control Electronic Expansion Valve
Refrigerant
Charge kg
4.0
Dimensions (W×H×D)
(Outline/Package)
mm
1032×1250×412/
1110×1385×450
Weight(Net/Gross) kg 128/139
Liquid mm 12.7
Gas mm 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
ASC-36AI
ASGE-36AI-3
Page 21
Continued: 2
Indoor unit ASC-42AI
Models
Outdoor unit
ASGE-42AI-3
kW 12.0
Cooling
Btu/h 41000
kW 14.0
Nominal
Capacity
Heating
Btu/h 48000
Cooling kW 4.7
Power Input
Heating kW 4.7
EER/COP W/W 2.55/2.98
Indoor Unit
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan Drive Direct Driver
Motor Output kW 0.06
Fan
Air Flow m3/h 1660
Sound Pressure Level(H/M/L) dB(A) 53/51/48
Air Filter Standard washable synthetic
Drain Piping mm φ32×3
Indoor Unit Dimensions
(Outline/Package) (W×H×D)
mm
840×320×840/
960×394×960
Weight(Net/Gross) kg 32/43
Panel Dimensions
(Outline/Package) (W×H×D)
mm
950×60×950/
1025×115×1040
Panel Weight(Net/Gross) kg 6.5/10
Outdoor Unit
Power Supply 380-415V~/3 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.092×2
Fan
Fan Motor Speed (H/M/L) rpm 940-/700
Type SCROLL
Compressor
Power Input W
4160
Type R410A
Control Electronic Expansion Valve
Refrigerant
Charge kg 4.0
Dimensions (W×H×D)
(Outline/Package)
mm
1032×1250×412/
1110×1385×450
Weight(Net/Gross) kg 128/139
Liquid mm 12.7
Gas mm 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
ASC-42AI
ASGE-42AI-3
Page 22
Continued: 3
Indoor unit
ASC-24AI
ASC-36AI S
Models
Outdoor unit
ASGE-24AI S
ASGE-36AI S
kW 7.0 10.0
Cooling
Btu/h 24 34100
kW 8.0 10.8
Nominal
Capacity
Heating
Btu/h 27300 368 00
Cooling kW 2.49 3.60 Power
Input
Heating kW 2.11 3.00
EER/COP W/W 2.81/3.79 2.78/3.6
Indoor Unit
Power Supply 220~240V-50Hz-1Ph
Heat Exchange Cross Fin Coil
Type Centrifugal fan Drive Direct Driver
Motor Output kW 0.035×1 0.06×1
Fan
Air Flow m
3
/h 1180 1660
Sound Pressure Level(H/M/L) dB(A) 47/45/42 53/51/48
Air Filter Standard washable synthetic
Drain Piping mm
32×3
32×3
Indoor Unit Dimensions
(Outline/Package) (W×H×D)
mm
840×240×840
/960×310×960
840×320×840
/960×394×960
Weight(Net/Gross) kg
30/38
32/43
Panel Dimensions
(Outline/Package) (W×H×D)
mm
950×60×950
/1025×115×1040
950×60×950
/1025×115×1040
Panel Weight(Net/Gross) kg 6.5/10
6.5/10
Outdoor Unit
Power Supply 220~240V-50Hz-1Ph
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.068×1 0.093×1
Fan
Fan Motor Speed (H/M/L) rpm 840/620/400 780/-/500
Type ROTARY
Compressor
Power Input W
163
0
3010±7. 5%
Type R410A
Control Electronic expansion valve
Refrigerant
Charge kg 1.8 2.6
Dimensions (W×H×D)
(Outline/Package)
mm
913×680×378/
994×750×428
980×790×427/
1080×840×485
Weight(Net/Gross) kg
51/55
70/78
Liquid mm 9.52
Gas mm 15.88
Max. Length m 30
Piping
Connections
Max. Height Difference m 15
ASC-24AI
ASC-36AI S
ASGE-24AI S
ASGE-36AI S
Page 23
Continued: 4
Indoor unit
ASC-36AI S
ASC-42AI S
Models
Outdoor unit ASGE-42AI-3 S
kW 10.0 11.9
Cooling
Btu/h 34100 40600
kW 10.8 13.0
Nominal
Capacity
Heating
Btu/h 36800 44300
Cooling kW 3.60 4.22
Power
Input
Heating kW 3.0 4.0
EER/COP W/W 2 .78/3.6 2.82/3.25
Indoor Unit
Power Supply 220~240V-50Hz-1Ph
Heat Exchange Cross Fin Coil
Type centrifugal fan Drive Direct Driver
Motor Output kW 0.06×1 0.06×1
Fan
Air Flow m3/h 1800 1660
Sound Pressure Level(H/M/L) dB(A) 54/51/48 53/51/48
Air Filter Standard washable synthetic
Drain Piping mm φ32×3 φ32×3
Indoor Unit Dimensions
(Outline/Package) (W×H×D)
mm
840×320×840/
960×394×960
840×320×840/
960×394×960
Weight(Net/Gross) 32/43 32/43
Panel Dimensions
(Outline/Package) (W×H×D)
mm
950×60×950
/1025×115×1040
950×60×950
/1040×115×1025
Panel Weight(Net/Gross) kg 6.5/10 6.5/10
Outdoor Unit
Power Supply - 380~415V-50Hz-3Ph 220~240V-50Hz-1Ph
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.093×1
Fan
Fan Motor Speed (H/M/L) rpm 780/-/500 820±20
Type ROTARY
Compressor
Power Input W
3010±7.5%
Type R410A
Control Electronic expansion valve
Refrigerant
Charge kg 2.6 3.5
Dimensions (W×H×D)
(Outline/Package)
mm
980×790×427
/1080×840×485
1107×1100×440
/1155×1220×490
Weight(Net/Gross) kg 70/78
88/98
Liquid mm 9.52
Gas mm 15.88
Max. Length m 30 50
Piping
Connections
Max. Height Difference m 15 30
ASC-36AI S
ASGE-36AI-3 S
ASGE-36AI-3 S
ASC-42AI S
ASGE-42AI-3 S
Page 24
Note  Nominal capacities are based on the follow conditions.
Mode Indoor Outdoor
Cooling
DB27 (80.6 )℃℉ WB19 (66.2 )℃℉
DB35 (95 )℃℉ WB24 (75.2 )℃℉
Heating
DB20 (68 )℃℉ WB-- (℃ -- )
DB7(44.6)℃℉ WB6(42.8)℃℉
Piping Length 5m
The air volume is measured at the relevant standard external static pressure. Noise is tested in the Semianechoic room, so it should be slightly higher in the actual
operation due to environmental change.
4.2 Operation Range
Mode Range of Outdoor Temperature ( )℃℉
Cooling
18-43
-7-43 (with low Ambient kit)
Heating -7-24
Page 25
4.3 Electrical Data
Compressor Fan Motor
Power
Supply
Qty. LRA RLA
Condenser
Fan
Motors
Supply Blower
Motor
Max. Fuse
Breaker Size
(Indoor/Outdoor)
Min. Disconnect Size (Indoor/Outdoor)
Model
V,Ph,Hz — Each Each FLA Each FLA Each Amperes Amperes
ASD-18AI 0.63 1/10.7 ASF-18AI 0.36 1/10.7
ASGE-18AI
ASC-18AI
1 41 8.38 0.27
0.1
6/20
1/10.7
ASD-24AI 1.35 2/11.1 ASF-24AI 0.36 1.5/11.1
ASGE-24AI
ASC-24AI
1 41 8.38 0.61
0.32
6/20
1/11.1
ASD-24AI S 1.35
2/11.1
ASF-24AI S 0.36 1.5/11.1
ASGE-24AI S
ASC-24AI S
1 41 8.38 0.61
0.32
6/20
1/11.1
ASD-36AI 4.5 5.7/20.6
ASF-36AI 1.35 2/20.6
ASGE-36AI
ASC-36AI
1
15.8 0.8
0.54
10/32
1/20.6
ASD-36AIS 3.26 5.7/20.6
ASF-36AIS 0.8 2/20.6
ASGE-36AI S
ASC-36AI S
1
󰷅
13.5 0.85
0.87
10/32
1/20.6
ASD-42AIS 1.17 5.7/20.6 ASF-42AIS 0.7 2/20.6
ASGE-42AI-3 S
ASC-42AIS
1
󰷅
13.5 0.85
0.3
10/32
1/20.6
220-240
1,
50
Page 26
Compressor Fan Motor
Power
Supply
Qty. LRA RLA
Condenser
Fan
Motors
Supply Blower
Motor
Max. Fuse
Breaker Size
(Indoor/Outdoor)
Min.
Disconnect Size
(Indoor/Outdoor)
Model
V,Ph,Hz — Each Each FLA Each FLA Each Amperes Amperes
ASD-36AI 4.5 5.7/19.8 ASF-36AI 1.35 2/19.8
ASGE-36AI-3
ASC-36AI
1
15.2 0.8
0.54
10/25
1/19.8
ASD-36AI S 3.26 5.7/19.8
ASF-36AI S 0.8 2/19.8
ASGE-36AI-3 S
ASC-36AI S
1
󰷅
13.5 0.85
0.87
10/25
1/19.8
ASD-42AI 4.5 5.7/19.8
ASF-42AI 1.35 2/19.8
ASGE-42AI-3
ASC-42AI
1
15.2 0.8
0.54
10/25
1/19.8
380-415~
3
50
Notes RLARated load amperes LRALocked rotor amperes FLAFull load current
5 PIPING DIAGRAM
Page 27
CONTROL
Page 28
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
CONTROL
1 OPERATION FLOWCHART
1.1 Cooling/Dry Operation
Page 29
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
1.2 Heating Operation
When indoor room temp. is 1°C above set temperature, unit stop heating.
When ind. room temp.< 1°C under set temperature unit starts heating.
Page 30
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
2 MAIN LOGIC
2.1 Cooling
After the cooling command is sent out, the indoor fan will run at high speed for 5 seconds before it is put into operation according to the setting. Then, it is started to calculate the system load demand value. If the load is 0, the other loads except the indoor fan will not be put into operation (The water pump will run according to the pump control logic behind). If the load is >0, the EXV will be firstly opened to step X; then the indoor fan is started. After 30 seconds, the compressor is started at initial frequency 40Hz and will be maintained for 3 minutes. After that, the compressor, EXV and outdoor fan will adjust according to logic.
Compressor
Outdoor fan
Cooling mode
3 min.
Send out switch-off command
Acc. to
control logic
Acc. to
control logic
Capacity demand >0
480 steps
6
0
sec.
150 sec.
150s after the compressor is stopped
Firstly switch off to step 0 and then switch off step 60.
Send out cooling command
Indoor fan
(cooling)
4-way valve
30 sec.
3sec.
X steps
Page 31
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
2.2 Dry Mode
The dry mode is basically same as cooling mode. The difference is that:
The indoor fan is fixed at low speed.
Max. capacity output: A×90%
Compressor
Outdoor fan
Indoor fan
(cooling)
4-way valve
Capacity demand >0
Dry Mode
Max. capacity output: A×90%
480 steps
6
0
sec.
150 sec.
30 sec.
3 min.
3 sec.
Send out switch-off command
Acc. to
control logic
Acc. to
control logic
150s after the compressor is stopped
Firstly switch off to step 0 and then switch off step 60.
Send out dry command
X steps
Page 32
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
2.3 Heating Mode
When the heating command is sent out, it is started to calculate the system load demand value. If the
load is 0, all the loads will not be put into operation. If the load is >0, the EXV will be firstly opened to step
Y; then the outdoor fan is started. After 30 seconds, the compressor will increase its frequency to the
required initial frequency 40Hz before it started. It is started to count the time when the compressor
frequency is increased to 20Hz. After 10 seconds, the 4-way valve is energized and then the indoor fan
will run as per cold air prevention mode. The compressor will keep running at initial frequency for 3
minutes. After that, the compressor, EXV and outdoor fan will adjust according to logic.
Compressor
Outdoor fan
Indoor fan
(cooling)
4-way valve
480 steps
6
0
sec.
150 sec.
30 sec.
3 min.
3sec.
Send out switch-off command
Acc. to
control logic
Acc. to
control logic
120 sec.
X
steps
10 sec.
150s after the compressor is stopped
Firstly switch off to step 0 and then switch off step 60.
Run as per cold
air prevention
mode
Blow residual heats
Capacity demand >0
Send out Heating command
Heating Mode
Page 33
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
2.4 Defrosting
The conditions for starting the defrosting are as follows:
The defrosting is started when one of the following three conditions is satisfied:
The total time for outdoor defrost sensor to run below 3 is longer than 40 minutes and this
temperature is kept lower than -6 for over 3 minutes.
The outdoor temperature sensor keeps lower than 3 for at least 80 minutes and keeps lower than
-4 for at least 3 minutes.
The outdoor temperature sensor keeps lower than 3 for at least 120 minutes and keeps lowers
than -3 for at least 3 minutes
The conditions for ending the defrosting are as follows:
The defrosting is ended when one of the following three conditions is satisfied:
When the temperature of o utdoor heat exchanger rises to higher than 10 .
When the temperature of outdoor heat exchanger rises to higher than 8 and this lasts for over 80
Variable Frequency
Compressor
Outdoor fan
Indoor fan
4-way valve
Heating / Defrosting Time Sequence Chart
Defrosting marking
Defrosting frequenc
y
Conditions for
ending the defrost
A
djust per PI
High fan
Energized
De-energized
A
uxiliary power
A
cc. to outdoor fan control logic
Fixed step
Y
A
djust according to control logic
Cold air prevention
A
cc. to the conditions for
starting the auxiliary power
Meet the conditions for ending the defrost
Time
Defrosting ends
30s
Page 34
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
seconds.
When the defrosting keeps for 10 minutes.
2.5 Fan Mode
OFF
OFF
OFF
OFF
OFF
OFF
H
The indoor fan will run at high speed for 5 seconds before running at preset speed
Compressor
Outdoor fan
Indoor fan
4-way valve
Fan Mode
Start
Manual Stop
Run at preset
speed
Time
HIGH
Page 35
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
3 WIRELESS REMOTE CONTROLLER
3.1 Operation View
3.1.1 Controller-Duct Type (ASD)
ON/OFF
MODE
AUTO FAN
SWING
AUTO

OPER
AIR

NO. Name Function description
1 ON/OFF button Press the button to set turning on/off the unit
2 Mode button
Press the button to select the mode,
cooling , heating , fan or auto mode.
3 Increase/Decrease button Press this button to increase/decrase the setup temp
4 LCD Screen Display the status of remote information
5 Swing button Press this button set swing function
6 Fan speed button Press this button to set fan speed
Page 36
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
3.1.2 Controller-Cassette Type and Ceiling Type (ASC and ASF)
ON/OFF
MODE
LIGHT
AUTO
TIMER ON/OFF
SWING HUMID
SWING
Auto Fan
SAVE
HR
AIR
FAN
OPER
TIMER ON/OFF
ON/OFF
ANION
TIME OFFTIME ON
MODE
LIGHT
SLEEP
SAVE
HUMID
AIR
HR
LIGHT
AUTO FAN
SWING
HUMID
AUTO

SAVE
OPER
AIR

NO. Name Function description
1 Swing button Press this button to set swing function
2 Increase/Decrease button Press this button to increase/decrase the setup temp
3 Mode button
Press the button to select the mode,
cooling , heating , fan or auto mode.
4 ON/OFF button Press the button to set start or close unit
5 LCD Screen Display the status of remote information
6 Fan speed button Press this button to set fan speed
7 Sleep button Press the button to set sleep function
8 Time on Press the button to set time on function
9 Time off Press the button to set time off function
Page 37
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
3.2 Display View
LIGHT
AUTO
TIMER ONOFF
SWING
HUMID
SWING
AUTO FAN
SAVE
HR
AIR
FAN
OPER
No. Display Function description
1 Fan Speed
auto fan speed, low fan speed,
middle fan speed high fan speed
2 Run Mode
Auto running Cool running
Dry Running Fan Running
Heat running (Heat and Cool unit only)
3 Setup temp Temperature value of setting
4 Swing function Swing is on
5 Sleep mode Sleep mode is on
6 Time value Timing value of setting
7 OPER The controller is on
Page 38
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
4 WIRED REMOTE CONTROLLER
4.1 Operation View
4.1.1 Wired Controller-Duct Type (ASD)
MODE
ON/OFF
FAN
SLEEP
TIMER
4.1.2 Wired Controller-Cassette Type and Ceiling Type (ASC and ASF)
MODE
ON/OFF
FAN
SWING
TIMER
Page 39
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
NO. Name Function description
1 MODE button
Press the button to select the mode,
cooling , heating , fan or auto mode.
2 Increasing button Press this button to increase the setup temp.
3 Decreasing button Press this button to decrase the setup temp.
4 Fan speed button Press this button to set fan speed
5 Sleep/SWING button Press the button to set sleep/swing function
6 Timer button Press the button to set timer function
7 On/off button Press the button to turn on or off the unit
8 Remote window Get remote information
9 LCD display Display unit information
Note:
1) SAVE set up: At unit turned off, to press the “FAN” +“” buttons continuously 5 seconds, it can
come enter save set up interface; the unit will run at save mode.
2) FRESH valve setup: At unit is turned off, press the “ FAN” button for 5seconds,And set up the fresh
air setup.
3) Outer ambient temperature display: Under normal condition, “ENV” will display the room ambient
temperature, at unit turned on, or unit turned off status, press “SLEEP/SWING” button last for 5
seconds, the LCD will display “OUT ENV”.
4) MEMORY function setup: At unit turned off, press “MODE” button for 10 seconds, could switch
whether turn on or off the unit state after powered off.
5) Debugging function: At unit off, continuously press “FAN” + “SLEEP” buttons lasting for 10seconds,
call out debugging menu, and displays “Debugging” icons, use “MODE” button adjust setting item, by
pressing “▲”,“▼” button to set up the detailed value.
(A) Ambient sensor set up: it can set three kinds styles.
6) Lock function: Press “”and“” at the same time for 5 seconds, the set temp. will display “EE” and
shield, all buttons will sound; and repress the“”and “”at the same time for 5 seconds, the lock
function will be released.(for details, please read corresponding parts of manual).
Page 40
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
4.2 Display View
MODE
ON/OFF
FAN
SWING
TIMER
NO. Name Function description
1 Timer value Display time value
2 Timer on/off
: display timer on, : display timer off,
3 Fan speed display
auto fan speed , : low fan speed,
: middle fan speed, : high fan speed
4 Set temp display
Display set temp value, its range is 16~30
5 Run mode display
: auto mode, : cool mode, : dry mode,
: fresh fan mode, : fan mode,
: heat mode(only cool and heat unit)
6 Indoor temp display Display surrounding temp indoor
7
Outdoor temp display
Display surrounding temp outdoor
8 Frost display When unit frosts ,it display
9 Sleep display Display sleep at Sleep mode
10 Swing display When setting swing function, it displays,
11 Error display When unit error, error code display
Page 41
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
4.3 Dimension
4.4 Installation
First select an installation position. According to the size of the communication line of the wire
controller, leave a recess or a embedded wire hole to bury the communication line.
If the communication line between the wire controller (85×85×20) and the indoor unit is
surface-mounted, use 1# PVC pipe and make matching recess in the wall (refer to Figure 6); If
concealed installation is adopted, 1# PVC pipe can be used (Refer to Figure 7).
No matter if surface mounting or concealed mounting is selected, it is required to drill 2 holes (in the
same level) which distance shall be the same as the distance (60mm) of installation holes in the
bottom plate of the wire controller. Then insert a wood plug into each hole. Fix the bottom plate of
the wire controller to the wall by using the two holes. Plug the communication line onto the control
panel. Lastly install the panel of the wire controller.
Caution:
During the installation of the bottom plate of the wire controller, pay attention to the direction of the
bottom plate. The plate’s side with two notches must be at the lower position, and otherwise the panel of
the wire controller cannot be correctly installed.
Page 42
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
󰷅
Fig6Surface Mounting of Cable Fig7Concealed mounting of Cable

Fig 8 Schematic Diagram of Installation
No. Name
1 Wall Surface
2 Bottom Plate of Wire Controller
3 Screw M4X10
4 Panel of Wire Controller
Caution:
The communication distance between the main board and the wire controller can be as far as 20m
(The standard distance is 8m).
The wire controller shall not be installed in a place where there is water drop or large amount of
water vapor.
Page 43
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5 CENTRALIZED CONTROLLER
5.1 Centralized Controller-not with week timer
5.1.1 Function
Centralized Controller-not with week timer only control on-off function of every unit. Up to 16 sets of
units can be controlled simultaneously by the centralized controller-not with week timer.
ration View
Name Function description
N button Press the button to set start unit
5.1.2 Ope
NO.
1 O
2 OFF button Press the button to set close unit 3 LCD display Display unit information 4 LED LED indication
5 Increasing / Decreasing button Press buttons select the unit
5.1.3 Display View
Display unit address value in the net.
5.1.4 Dimensions
Page 44
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.2 Centralized Controller-week timer
5.2.1 Function
Centralized Control and Week Timer Functions: The centralized controller and the weekly timer are integrated in the same wire controller. The system has both the centralized control and the week timing functions. Up to 16 sets of units can be controlled simultaneously by the centralized controller (weekly timer). The weekly timer has the function of invalidating the lower unit. The weekly timing function is able to realized four timing ON/OFF periods for any unit every day, so as to achieve fully automatic operation. No timing control can be set for holidays. On and off of every duct type unit can be done through the Timer On/Off of this WEEKLY TIMERit can not set other functions except on-off function of units.
Page 45
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.2.2 Operation View
NO. Name Function description
1 ENTER button Press the button to let setting validate.
2 Increasing button
Press “” and selected the unit or a certain day in one week or specific
value. Press “” can set week part of time.
3 Decreasing button
Press “
” and selected the unit or a certain day in one week or
specific value. Press “ ” can set week part of time.
4
CANCEL/DELET
E
button
short-press “cancel/delete” to back to default page or last process, long-press “cancel/delete” to cancel timer of a certain time period in a
certain day
5
SINGLLE/GROU
P
button
short-press “single/group” to enter single control setting. “SINGLE” displayed. long-press “single/group” to enter group control setting. “GROUP” displayed
6
TIMER/TIME
button
Short-press “timer/time” to enter timer setting. Long-press “timer/time” under default page can begin time setting.
7 On/off button Press the button to set start or close unit
8 LCD display Display unit information
Page 46
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.2.3 Display View
NO. Name Function description
1 Unit’s no. displays Display unit’s numbers
2 Group control displays when group controls, it will display
3 Single control displays when single unit controls, it will display
4 Timer time in week displays Display time in week
5 Timer displays Display time
6 timer state displays
“on”: when set unit on, “on” will display;
“off”: when set unit off, “off” will display;
7 timer on time displays Display starts time
8 on control displays When set unit or group on, it will display,
9 off control displays When set unit or group off, it will display,
10 present time in week display Display present time of week.
11 present time in Hr:Min displays Display time of hour and minute now
12 timer off time displays Display over time
13 timer period displays Set to different time segment
Note:
Please read corresponding manual of weekly timer controller to be familiar with it.
Page 47
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.2.4 Dimensions
Page 48
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.3 Field Setting
The centralized controller will display the code of each unit. The unit code is decided by the position
of DIP switch on the wired controller for each air duct (on the back of wired controller). From right to left,
the dial value corresponds to pin 4~1 of the DIP switch. It is “0” if dialed to “ON" and “1” if dialed to “OFF”
on opposite end.
Example 1: If the dial value is “0111”, this represents that the serial number is “8”, the pins 1, 2 & 3
of the DIP switch are dialed to the opposite end of “ON”, and the pin 4 is dialed to “ON”.
Example 2: If the dial value is “1010”, this represents that the serial number is “11”, the pins 2 & 4 of
the DIP switch are dialed to the opposite end of “ON”, and the pin 1 & 3 is dialed to “ON”.
Position Number Position Number Position Number Position Number
0000 1 0100 5 1000 9 1100 13 0001 2 0101 6 1001 10 1101 14 0010 3 0110 7 1010 11 1110 15
0011 4 0111 8 1011 12 1111 16
See below:
󰇧

󰇧

󰇧 
󰇧

󰇧

󰇧

󰇧 
󰇧

󰇧

󰇧

󰇧

󰇧

󰇧

󰇧

󰇧

󰇧

Unit Code 1
Unit Code 2
Unit Code 3
Unit Code 4
Unit Code 5
Unit Code 6 Unit Code 7
Unit Code 8
Unit Code 9
Unit Code 10
Unit Code 11
Unit Code 12
Unit Code 13
Unit Code 14
Unit Code 15
Unit Code 16
Page 49
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.4 Control Wiring Design
16 Units in Max
Week timer
Wired remote controller
LCD LCD LC
Wired remote controlle
Telephone wire box Telephone wire box Telephone wire box
Twisted-wire with crystal joint
Longest distance 1200m
AC-LAC-N
Power supply
Corresponding relation between code switch and sequence of unit (Note:Putting code switch to ON means 0.)
P S P S P S P S 0000 1 0010 5 0001 9 0011 13
1000 2 1010 6 1001 10 1011 14 0100 3 0110 7 0101 11 0111 15 1100 4 1110 8 1101 12 1111 16
Page 50
Chapter III Installation and Test (HV)
Chapter IV Repair and Maintenance
1. List of Error Codes
Table1 Definition of Error Codes on Display Panel
Error code
Malfunction E0 Water pump malfunction E1
High pressure protection of compressor E2 Indoor anti-frozen protection E3 Low pressure protection of compressor E4 Air discharge high-temperature protection of compressor E5 Overload protection of compressor or Inverter error E6 Transmit malfunction E8 Indoor fan protection E9 Water flow protection
F0 Malfunction of indoor environment sensor at air return vent F1 Evaporator sensor malfunction F2 Condenser sensor malfunction
F3 Outdoor environment sensor malfunction F4 Malfunction of air discharge sensor F5 Malfunction of environment sensor on displayer
EH Auxiliary electric heater malfunction
Page 51
Table 2 LED Indication Codes of Outdoor Main Control Board
LED Indication of Outdoor Main Control Board
Display
Indication
Item
LED6 LED5 LED4 LED3 LED2 LED1
DC bus overvoltage protection ON BLINK ON ON ON ON E5
Radiator fin overheat protection ON BLINK ON ON ON BLINK E5
Current sensor fault ON BLINK ON ON BLINK ON E5
Radiator sensor fault ON BLINK ON BLINK ON ON E5
Compressor current protection ON BLINK ON BLINK ON BLINK E5
DC bus undervoltage protection ON BLINK ON BLINK BLINK ON E5
Compressor startup failure ON BLINK OFF ON ON ON E5
PFC abnormal ON BLINK OFF ON ON OFF E5
Compressor clogged ON BLINK OFF ON ON BLINK E5
IPM module resetting ON BLINK OFF ON OFF ON E5
Loss-of-synchronization of compressor motor ON BLINK OFF ON OFF OFF E5
Inverter phase-failure or loss-of-regulation ON BLINK OFF ON OFF BLINK E5
Communication fault from inverter to main controller
ON ON OFF OFF OFF BLINK E5
IPM module protection ON BLINK BLINK ON ON ON E5
Compressor overspeed ON BLINK BLINK ON ON OFF E5
Sensor connection protection ON BLINK BLINK ON ON BLINK E5
Temperature shift protection ON BLINK BLINK ON OFF ON E5
A
C contactor protection ON BLINK BLINK ON OFF OFF E5
A
C current protection (input side) ON BLINK ON BLINK ON OFF E5
Inverter ambient sensor fault ON BLINK ON BLINK OFF ON E5
High pressure protection ON BLINK OFF OFF OFF BLINK E1
Low pressure protection ON BLINK OFF OFF BLINK OFF E3
Exhaust protection ON BLINK OFF OFF BLINK BLINK E4
Overload protection of compressor ON BLINK OFF BLINK OFF OFF E5
Communication fault (indoor / outdoor unit, manual controller)
ON BLINK OFF BLINK BLINK OFF E6
Outdoor ambient sensor fault ON BLINK BLINK OFF OFF OFF F3
Outdoor coil middle sensor fault ON BLINK BLINK OFF BLINK OFF F2
Inverter exhaust temp. fault ON BLINK BLINK BLINK OFF BLINK F4
Defrost (not fault) ON BLINK OFF BLINK BLINK BLINK Defrost
Oil return (not fault) ON BLINK BLINK BLINK ON BLINK No display
Indoor and outdoor unit incompatible ON BLINK OFF BLINK ON BLINK No display
Note: No indicator LED6 for ASGE-18AI.
Page 52
INSTALLATION
Page 53
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
INSTALLATION
1 INDOOR UNIT INSTALLATION
1.1 Installation of Duct Type
1.1.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or
internal damage, please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the specification and quantity of accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing
possible hazard. For the sake of protection and safety, it is suggested to move the unit with the packaging box. Even though it is not permitted to do like this under special occasions, do not remove the packaging box, thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of
the building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
1.1.2 Installation Site
Ensure the top hanging piece has strong strength to withstand the weight of the unit. The drainage pipe has convenient flow of water. There is no obstacle blocking the return air inlet and exhaust outlet, so as to ensure sound air
circulation.
The installation spaces required by the drawing must be ensured, so as to provide enough space for
the service and maintenance.
The installation site must be far away from heat source, leakage of inflammable gas or smoke. The indoor unit is of ceiling mount (indoor unit is hidden inside the ceiling). The indoor and outdoor units, the power cable and the connecting electrical lines must be at least 1
meter from any TV set or radio. This is to avoid image interference or noise of the TV set or radio. (Even if the distance is 1 meter, noise can also exist if there is strong electric wave.)
1.1.3 Caution for Installation
1 Generally, the unit is installed indoor on ceiling. For ceiling mounting, ensure that the hangers on
ceiling have adequate strength to support the weight of the unit.
2 To meet the noise and vibration requirements, the unit shall be installed by using rubber pad
(thickness 20mm) and rubber connector.
3 Insert a M10 expansion bolt into the hole. Drive a nail into the bolt. Refer to the profile dimensions
drawing of the indoor unit for the distance between the holes. Refer to Figure 1 for the installation of the expansion boltas Figure 1-1-1 shows.
Page 54
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-1-1 Figure 1-1-2
Figure 1-1-3
4 Install the hanger onto the indoor unit as Figure 1-1-2 and Figure 1-1-3 shows.
5 Install the indoor unit at the ceiling as Figure 1-1-5 shows.
Nut
Hanger
Screw
mm
I Enlargement
Return
air
Supply air
Figure 1-1-5
6 Precautions for unfavorable installation:
The preparation of all pipes (connecting pipes and drainage pipes) and cables (connecting lines of
wire controller, indoor unit and outdoor unit) must be ready before the installation, so as to achieve
smooth installation.
Drill an opening on the ceiling. Maybe it is required to support the ceiling to ensure the evenness of
it and avoid the vibration of it. Consult with the user or a construction company for details.
In case the strength of ceiling is not enough, use angle iron sections to set up a beam support.
Place the unit at the beam and fix it.
Page 55
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
7 Level inspection of the indoor unit
After completing the installation of indoor unit, we must check the level of entire unit to ensure that the unit is positioned on the same level from front to back or from left to right, as shown in Fig. 1-1-6.
Air Supply
Air Intake
i
Condensate Drainpipe
Level Instrument
Condensate Drainpipe
Enlarged View
As the inside of the unit is in the negative pressure status, it is required to set up a backwater elbow. The requirements is:
A=B
P/10+20(mm)
P is the absolute pressure inside the unit.
The unit of the pressure is Pa.
Figure 1-1-6
1.1.4 Dimension Data
Figure 1-1-7
Unitmm
Page 56
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Model A B C D E F G H I J
ASD-18AI 932 432 738 894 1012 736 738 125 207 266
ASD-24AI
1101 515 820 1159 1270 530 1002 160 235 268
ASD-36AI
ASD-36AI S
ASD-42AI
ASD-42AI S
1011 748 820 1115 1226 775 979 160 231 290
Installation Accessories List for Duct-type Indoor Unit (ASD)
Name & Shape QTY Notes
Installation and Operating Instructions 1
Insulation materials for gas pipe 1 Used for gas pipe connector on indoor unit
Insulation materials for liquid pipe 1 Used for liquid pipe connector on indoor unit
Insulation materials for drainage pipe 2
Used for wrapping the condensate pipe and
rubber plug.
Nut M8 with gasket 8 Use for fixing the hanger hook
4
Nut and spring gasket 4
4 sets, used for ceiling mounting of the
indoor unit
Hook 4 Used for ceiling mounting of the indoor unit
Strap 4 or 8 pcs 4 pcs for 18KBtu/h unit and 8 pcs for others
Wired controller 1
Remote controller 1
Battery 2
Fexible pipe 0.2 or 4 pcs
0 pc for 18 KBtu/h unit; 2 pcs for
22.5,27KBtu/h unit; and 4 pcs for
36-45KBtu/h unit
Power cord 1 – 2 pcs
2 pcs for36-45 KBtu/h unit and 1 pc for
others
Connection wire
Page 57
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.1.5 Installation Clearance Data
only for ASD-24AI and above models
Figure 1-1-8
1.1.6 Drain Piping Work 1 Installation of Drainage Pipeline
A drainage outlet is located at both the left and right sides of the indoor unit. After selecting one
drainage outlet, the other outlet shall be blocked by rubber plug. Bundle the blocked outlet with
string to avoid leakage, and also use thermal insulation materials to wrap the blocked outlet.
When shipped out from factory, both the Drainage outlets are blocked by rubber plugs.
When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline at the
side of the unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When
carrying out connection, place the end of the PVC pipeline into the drainage hole. Use flexible
drainage tube and tighten it with thread loop. Never use adhesive to connect the drainage hole and
the flexible drainage tube. (As shown in Figure 1-1-9)
When the laid drainage pipe is used for multiple units, the common pipe shall be about 100mm
lower than the drainage outlet of each set of unit. A pipe with thicker wall shall be used for such
purpose.
Spring gasket of nut
Nut with gasket
Page 58
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-1-9
2 Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system.
During the test, check if the water correctly flows through the pipelines. Carefully observe the joints
to ensure that there is no leakage. If the unit is to be installed in a new house, carry out testing
before decorating the ceiling.
3 Matters of Attention
The joint of Drainage Pipeline must not have leakage.
The Drainage Pipeline shall be installed with an inclining angel of 510°, so as to facilitate the
drainage of condensate. The joints of the Drainage Pipeline must be covered by thermal insulation
materials to avoid generation of exterior condensate. (As shown in Figure 1-1-10)
Thermal insulation layer of condensate pipe
Pipe cover
Figure 1-1-10
1.1.7 Installation of air duct and round duct for duct-type unit
Caution:
The supply air duct, the return air duct and the fresh air duct must be covered with a layer of thermal
insulation, so as to avoid thermal leakage and condensation. Firstly apply liquid nail on the duct,
and then attach the thermal insulation cotton with a layer of tinfoil. Use the liquid nail cover to fix it.
Lastly use tinfoil adhesive tape to carefully seal the joints; other good thermal insulation materials
can also be used.
The supply air duct and the return air duct shall be fixed to the prefabricated boards of the ceiling by
using iron supports. The joints of the pipes must be sealed by glue so as to avoid leakage.
Pipe cover
Page 59
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
The design and installation of air duct must be in conformity with the relevant state engineering
criteria.
The edge of the return air duct must be at least 150mm away from the wall. The return air inlet must
be covered with filter.
Silencing and shock absorption shall be considered in the design and installation of the air duct.
Additionally, the noise source must be far away from where people stay. The return air inlet shall not
be located above the place where users stay (offices and rest places, etc.).
1 Installation of supply air duct
Installation of rectangular air duct, as shown in Fig. 1-1-11
Figure 1-1-11
Serial No. Name Serial No. Name
1 Hanger rod 5 Filter
2 Return air duct 6 Main supply air duct
3 Canvas air duct 7 Supply air outlet
4 Return air inlet
Page 60
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Installation of round air duct, as shown in Fig. 1-1-12
Figure 1-1-12
Number Name Number Name
1 Hanger rod 6 Transition air duct
2 Return air duct 7 Supply air duct
3 Canvas air duct 8 Diffuser
4 Return air louver 9 Diffuser joint
5 Supply air outlet
Notes:
The above two figures only indicate the installation of back return return air inlet. Down return air inlet may also be used as needed for actual installation. The installation method is similar to that of back return air inlet. Among all the Supply air outlets, at least one shall be kept open. Round air duct can also be used, in which a thermally insulated round hose is used to supply the air to the room. Both the supply air duct and return air duct shall be thermally insulated. 2 Installation of fresh air duct (Limited to excessive residual pressure unit with a cooling
capacity over 6000W)
Cut off the fresh air baffle when connecting the fresh air duct, as shown in Fig. 1-1-13(a). If not using
the fresh air duct, please use sponge to seal the fresh air baffle clearance.
Mount the round flange for connection of the fresh air duct, as shown in Fig. 1-1-14(b).
Both the air duct and round flange shall be well sealed and thermally insulated.
The fresh air shall be the air that is filtered.
Page 61
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
(a) (b)
Figure 1-1-13
3 Installation of return air duct
The square flange is mounted on rear section when it is shipped. The return air inlet cover plate is
mounted beneath, as shown in Fig. 1-1-14.
Figure 1-1-14
If down return air inlet is to be used, just change the position between square flange and cover plate
of return air inlet.
Rivet the return air duct to the return air inlet of indoor unit and connect another end to return air
window. For free adjustment of the height, you may fabricate a section of canvas air duct and
reinforce with 8# iron wire in folded form. You may select the installation methods in overall
consideration of the building and maintenance conditions, as shown in Fig. 1-1-15.
Round air duct
Down return air inlet
Down return air inlet
Cover plate of return air inlet
Page 62
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Number Name Number Name
Return air window (with
filter)
Canvas air duct
Supply air duct
Return air duct 6 Test grill
Figure 1-1-15
Return air
Supply air
Return air
Supply air
Page 63
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
4 Installation of round Supply air outlet
Figure 1-1-16
1.2 Installation of Ceiling Type
1.2.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or
internal damage, please immediately report to the transport company or equipment company in
writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the
specification and quantity of accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing
possible hazard. For the sake of protection and safety, it is suggested to move the unit with the
packaging box. Even though it is not permitted to do like this under special occasions, do not
remove the packaging box, thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of
the building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
1.2.2 Installation Site
Such a place where cool air can be distributed throughout the room.
Such a place where condensation water is easily drained out.
Such a place that can handle the weight of indoor unit.
Such a place which has easy access for maintenance.
Such a place where is permitting easy connection with the outdoor unit.
Page 64
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Such a place where is 1m or more away from other electric appliances such as television, audio
device, etc.
Avoid a location where there is heat source, high humidity or inflammable gas.
Do not use the unit in the immediate surroundings of a laundry, a bath, a shower or a swimming
pool.
Be sure that the installation conforms to the installation dimension diagram.
The space around the unit is adequate for ventilation
1.2.3 Caution for Installation
Adjust the distance from the unit to the ceiling slab beforehand (Refer to Figure 1-2-1).
Fix the hanger bracket to the suspension bolt (Refer to Figure 1-2-2).
Make sure that extended suspension bolt from the ceiling stays inside the arrowed position.
Readjust the hanger bracket when it is outside the arrowed position. (Refer to Figure 1-2-3)
Suspension bolt stays inside the cap of indoor unit .Never remove the cap. Lift the unit and slide
forward unit the dent. (Refer to Figure 1-2-4)
Screw tightly both hanger bracket setting bolts (M8) (Refer to Figure 1-2-2)
Screw tightly both hanger bracket fixing bolts (M6) to prevent the movement of the indoor unit.
(Refer to Figure 1-2-2)
Adjust the height by turning the nut with a spanner. Insert the spanner from the hanger bracket
opening. (Refer to Figure 1-2-5)
Hanger bracket Figure 1-2-1 Figure 1-2-2
Figure 1-2-3 Hanger bracket Figure 1-2-4
In case of hanging:
It is possible to install using inward facing hanger bracket by not removing the brackets from the indoor unit. (Refer to Figure 1-2-6) Be sure to use only the specified accessories and parts for installation work.
Page 65
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-2-5 Figure 1-2-6
1.2.4 Dimension Data
Figure 1-2-7
Unit: mm
Model A B C D E
ASF-18AI
836 238 745 695 260
ASF-24AI
1300 188 1202 600 260
ASF-36AI ASF-36AI S ASF-42AI ASF-42AI S
1590 238 1491 695 260
Page 66
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.2.5 Installation Clearance Data
Figure 1-2-8
1.2.6 Drain Piping Work 1 Installation of Drainage Pipeline
A Drainage outlet is located at both the left and right sides of the indoor unit. After selecting one
Drainage outlet, the other outlet shall be blocked by rubber plug. Bundle the blocked outlet with string to avoid leakage, and also use thermal insulation materials to wrap the blocked outlet.
When shipped out from factory, both the Drainage outlets are blocked by rubber plugs. When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline at the
side of the unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When
carrying out connection, place the end of the PVC pipeline into the drainage hole. Use flexible drainage tube and tighten it with thread loop. Never use adhesive to connect the drainage hole and the flexible drainage tube. (As shown in Figure 1-2-9)
When the laid drainage pipe is used for multiple units, the common pipe shall be about 100mm
lower than the drainage outlet of each set of unit. A pipe with thicker wall shall be used for such purpose.
Page 67
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-2-9
2
Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system. During the test, check if the water correctly flows through the pipelines. Carefully observe the joints
to ensure that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating the ceiling.
3 Matters of Attention
The drain pipe outlet direction can be chosen from either the right rear or right.
The diameter of the drain pipe should be equal to or greater than the diameter of the connecting
pipe. (Vinyl tube; pipe size: 20mm; outer dimension: 26mm)
Keep the drain pipe short and incline downwards at a gradient of at least 1/100 to prevent air
pockets. (Refer to Figure 1-2-10)
Figure 1-2-10
No folding of drain hose inside the indoor unit. (Refer to Figure 1-2-11)
Confirm that smooth drainage is achieved after the piping work. Pour 600 cc of water into the drain
pan from the air outlet for confirming drainage. (Refer to Figure 1-2-12
)
Page 68
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-2-11 Figure 1-2-12
1.3 Installation of Cassette Type
1.3.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or
internal damage, please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the specification and quantity of accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing
possible hazard. For the sake of protection and safety, it is suggested to move the unit with the packaging box. Even though it is not permitted to do like this under special occasions, do not remove the packaging box, thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of
the building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
1.3.2 Installation Site
Obstruct should put away from the intake or outlet vent of the indoor unit so that the airflow can be
blown though all the room.
Make sure that the installation had accord with the requirement of the schematic diagram of
installation spaces.
Select the place where can stand 4 times of the weight of the indoor unit and would not increase the
operating noise and oscillate.
The horizontally of the installation place should be guaranteed.
Select the place where is easy to drain out the condensate water, and connect with outdoor unit.
Make sure that there are enough space for care and maintenance. Make sure that the weight
between the indoor unit and ground is above 2300mm.
When installing the steeve bolt, check if the install place can stand the weight 4 times
Page 69
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
of the unit’s. If not, reinforce before installation. (Refer to the install cardboard and find where should be reinforced) The appliance shall not be installed in laundry.
Cautions:
There will be lots of lampblack and dust stick on the acentric, heat exchanger and water pump in dining room and kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal operation of the water pump.
The following treatment should be taken under this circumstance:
Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the
indraft of the lampblack by the air conditioner.
Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air
conditioner.
1.3.3 Caution for Installation
1
Important notice:
To guarantee the good performance, the unit must be installed by professional personnel according
with this instruction.
Please contact the local special nominated repair department before installation. Any
malfunction caused by the unit that is installed by the department that is not special nominated by supplyer would not deal with on time by the inconvenience of the business contact.
Page 70
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
2) Dimension of ceiling opening and location of the hoisting screw (M10)
󰷅󰷅

󰷅

󰷅󰷅



ASC-18AI Figure 1-3-1
pe piantergirefR

ewcrng sistoiH
dsorwer scngitsi honeewte bspaG

t unirndoo I

gnng openiileiC

dsarboac efrud setarcoeD

sdare bocafd surtearcoeD

ingpeng oilinCe

itnuordon I

sdo rwe scrngtisi honeetw bepsGa
840
ASC-24AI, ASC-36AI, ASC-36AI S ASC-42AI, ASC-42AI S
Figure 1-3-2
Page 71
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
The drilling of holes in the ceiling must be done by the professional personnel.
Figure 1-3-3
Cautions:
The dimension for the ceiling openings with * marks can be as large as 910mm. But the overlapping
sections of the ceiling and the decorated surface boards should be maintained at no less than 20mm.
Page 72
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
2
Main body of hoisting air conditioner
Bolt attachment
Bolt(attachment
[Fix the install cardboard]
Center of the ceiling opening
Bolt of one of the angle of outlet pipe is fix on the angle of the drainage slot
Install cardboard
Nut (supplied at scene)
Gasket (attachment)
Tighten (double nuts)
Hoisting stand
[Fix the hoisting stand firmly]
Insert
Gasket anchor board (attachment)
[Fix the gasket firmly]
Water lever
Polyethylene pipe
Figure 1-3-4
The primary step for install the indoor unit.
When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper
and lower of the hoisting stand to fix it. The use of gasket anchor board can prevent gasket break
off.
Use install cardboard
Please refer to the install cardboard about the dimension of ceiling opening.
The central mark of the ceiling opening is marked on the install cardboard.
Install the install cardboard on the unit by bolt (3 piece), and fix the angle of the drainage pipe at the
outlet vent by bolt.
Adjust the unit to the suitable install place.
Check if the unit is horizontal.
Inner drainage pump and bobber switch are included in the indoor unit, check if 4 angle of every unit
are horizontal by water lever. (If the unit is slant toward the opposite of the coagulate water flow,
there may be malfunction of the bobber switch and lead water drop.)
Backout the gasket anchor board used to prevent gasket break off and tighten the nut on it.
Backout the install cardboard.
Cautions:
Please do tighten the nuts and bolts to prevent air conditioner break off.
Page 73
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.3.4 Dimension Data
Figure 1-3-5
Model H A B C D E
ASC-18AI 245 650 400 606 440 66
ASC-24AI
275 950 680 840 720 76
ASC-36AI
ASC-36AI S
ASC-42AI
ASC-42AI S
345 950 680 840 720 76
Page 74
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.3.5 Installation Clearance Data





Figure 1-3-6
Models H(mm)
ASC-18AI
230
ASC-24AI
260
ASC-36AI ASC-36AI S ASC-42AI ASC-42AI S
320
1.3.6 Drain Piping Work 1
Installation of Drainage Pipeline
When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline at the
side of the unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When
carrying out connection, place the end of the PVC pipeline into the drainage hole. Use flexible
drainage tube and tighten it with thread loop. Never use adhesive to connect the drainage hole and
the flexible drainage tube. (As shown in Figure 1-3-7)
When the laid drainage pipe is used for multiple units, the common pipe shall be about 100mm
lower than the drainage outlet of each set of unit. A pipe with thicker wall shall be used for such
purpose.
Page 75
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-3-7
2
Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system. During the test, check if the water correctly flows through the pipelines. Carefully observe the joints
to ensure that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating the ceiling.
3 Matters of Attention
The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The diameter
of polythene pipe: Outer diameter 25mm Surface thickness ≥1.5mm)
Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of
air bubble.
If drain hose cannot has enough drooping gradient, drain raising pipe should be added. To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m. (As
shown in Figure 1-3-8)

(Correct) 1/100 or more gradient
(wrong)
Figure 1-3-8
The install height of the drain raising pipe should less than 280mm. The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond
300mm. (As shown in Figure 1-3-9)
Celling
1-1.5m
Hanger bracket
Below
1120mm
Above 280mm
200mm
Drainage raising pipe
Drainage hose
(attachment)
Cassette type unit
with in 300mm
Clamp(attachment)
Figure 1-3-9
The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t
Page 76
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
has to endure the unnecessary outside force. (As shown in Figure 1-3-10)
Drain hose(attachment)
Below75mm
Below500mm
Figure 1-3-10
Please install the drain hose according to the following process if several drain hoses join together.
(As shown in Figure 1-3-11)
T-tie in join drain hose
Above100mm
The specs of the selected join drain hose should fits the running capacity of the unit.
Figure 1-3-11
Check the smoothness of drain after installation.
Check the drain state by immiting 600cc water slowly from the outlet vent or test hole. (As shown in
Figure 1-3-12)
Check the drain in the state of refrigerating after installation of the electric circuit.
Test hole cover
Drain hose
< Immiting water from the rest hole>

Drain vent for repair use (plastic
stopper is included) (drain the water
in waterspout by this outlet vent)
[Way of immiting]
Test hole
<Immiting water from the outlet
vent terminal>
Plastic water pot (The length of the pipe should be about 100mm.)
Figure 1-3-12
Page 77
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.3.7 Installation of panel 1
Set the panel to the indoor unit body by matching the position of the swing flap motor
of the decoration panel to the piping position of the panel to the piping position of the
indoor unit as shown in Figure 1-3-13.
Figure 1-3-13
Hang the latch, which is located on the opposite side of the swing flap motor on the panel,
temporarily to the book of the indoor unit. (2 Positions)
Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be careful not
to let the swing motor lead wire get caught in the sealing material.)
Screw all 4 hexagon head screws located right beneath the latches in approximately 15mm.(Panel
will rise)
Adjust the panel by turning it to the arrowed direction in Fig.4 so that the ceiling opening is
completely covered.
Tighten the screws until the thickness of the sealing material between the panel and the indoor unit
body is reduced to 5~8 mm.
2 Precautions:
Improper screwing of the screws may cause the troubles shown in Figure 1-3-14.
Page 78
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-3-14
If gap is still left between the ceiling and the panel after screwing the screws, readjust the height of
the indoor unit body (Refer to Figure 1-3-15)
Figure 1-3-15
After fixing be sure no gap left between the ceiling and the panel
3 Wiring of the decoration panel.
Connect the joints for swing flap motor lead wire (at 2 places) installed on the panel (Refer to Figure
1-3-16)
Figure 1-3-16
Page 79
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
2 OUTDOOR UNIT INSTALLATION
2.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or
internal damage, please immediately report to the transport company or equipment company in
writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the
specification and quantity of accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing
possible hazard. For the sake of protection and safety, it is suggested to move the unit with the
packaging box. Even though it is not permitted to do like this under special occasions, do not
remove the packaging box, thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of
the building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
2.2 Installation Site
To ensure the unit in proper function, selection of installation location must be in accordance with
following principles:
Outdoor unit shall be installed so that the air discharged by outdoor unit will not return and that
sufficient space for repair shall be provided around the machine.
The installation site must have good ventilation, so that the outdoor unit can take in and exhaust
enough air. Ensure that there is no obstacle for the return air inlet and exhaust of the outdoor unit. If
there is any obstacle blocking the return air inlet or exhaust, remove it.
Place of installation shall be strong enough to support the weight of outdoor unit, and it shall be able
to insulate noise and prevent vibration. Ensure that the wind and noise from the unit will not affect
your neighbors.
Avoid direct sunshine over the unit. It is better to set up a sun shield as the protection.
Place of installation must be able to drain the rainwater and defrosting water.
Place of installation must ensure the machine will not be buried under snow or subject to the
influence of rubbish or oil fog.
The installation site must be at a place where the air exhaust outlet does not face strong wind.
he outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect the
Page 80
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
air conditioner and avoid knocking the metal parts, thus to prevent rusting in the future.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using rubber
damping pad or spring damper.
The installing dimension shall comply with the installation requirements in these instructions. The
outdoor unit must be fixed at the installing position.
The installation shall be done by specialist technicians.
2.3 Caution for Installation
The outdoor unit shall be so installed that the air discharged out of the outdoor unit will not flow back
and that enough space shall be maintained around the machine for repair;
The installing position shall be in good ventilation, so that the machine can breathe and exhaust
enough air. Ensure that there is no obstruction at the inlet and outlet of the machine. If any, please
remove the obstructions blocking the air inlet and outlet.
If the outdoor unit is installed on concrete or solid ground, it shall be fixed by using M10 bolts and
nuts. And ensure that the machine is kept vertical and horizontal.
The outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect
the air conditioner and avoid knocking the metal parts, thus to prevent rusting in the future.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using rubber
damping pad or spring damper.
To install the drainage pipe, please insert the drainage joint to the drainage hole on the outdoor
chassis and connect a drainage pipe on the drainage joint. (The installing height of outdoor unit
shall be at least 5cm if drainage joint is to be used).
To insert the pipe through the wall, the wall-cross tube must be installed.
The installing dimension shall comply with the installation requirements in these instructions. The
outdoor unit must be fixed at the installing position.
The installation shall be done by specialist technicians.
Page 81
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
2.4 Dimension Data
Figure 2-4-1
Unitmm
Model A B H C D
ASGE-18AI
820 320 540 540 286
ASGE-24AI ASGE-24AI S
913 378 680 548 340
ASGE-36AI S
ASGE-36AI-3 S
󰷅 980 427 790 610 395
ASGE-42AI-3 S 1107 440 1100 631 󰷅
400
ASGE-36AI
ASGE-36AI-3
ASGE-42AI-3
1032 412 1250 572 378
Page 82
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
2.5 Installation Clearance Data
Figure 2-5-1
3 REFRIGERATION PIPING WORK
3.1 Refrigeration Piping Work Procedures
1
Connection Pipe
The connection pipe must meet the following requirements. The three basic principles are that the
pipe shall be kept dry, clean and no leakage
.
Figure 3-1-1
Align the flared end of copper pipe with the center of threaded connector and use your hands to
securely tighten the flared nuts.
Tighten the flared nuts with torque wrench, until you hear a ‘KATA” sound from the torque wrench,
as shown in Fig. 3-1-1. See Table 3-1-1 for the torque required for tightening the nuts.
Page 83
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 3-1-2
Form 3-1-1 the tightening torque needed for tightening nut
Pipe diameter Tightening Torque
1/4 15-30 (N·m)
3/8 35-40 (N·m)
5/8
60-65 (N·m)
1/2 45-50 (N·m)
3/4 70-75 (N·m)
The bend of pipe shall not be too small; otherwise the pipe might be broken. Please use pipe
bender to bend the pipe.
Generally, the pipe shall be welded with the weld junction upward or horizontal. Avoid welding with
the pipe opening downward. (Downward welding is easy to cause defects, which may affect the
weld quality or even cause leakage, as show in Fig. 3-1-3).
Figure 3-1-3
Use sponge to wrap the connection pipes and connectors that are not thermally insulated, and
tighten with plastic tapes.
2 Vacuum and Leakage Detection
Remove the cap from liquid valve and gas valve. Align with the pipe center and tighten the jointing nuts adequately with your hand. Tighten the nuts with wrench.
Page 84
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Remove the 1-way cap from the gas valve. Use the hexagonal socket spanner to rotate the element of liquid valve for 1/4 turns and use the
screwdriver to prop up the element of gas valve to discharge the gas.
Discharge the gas for 15 seconds, until refrigerant gas appears. The, immediately close the 1-way
valve and tighten the valve cap.
Open the element of liquid valve and gas valve to full (See Fig. 3-1-4).
Figure 3-1-4
Tighten the valve cap and then use soap water or leakage detector to check the connection
between outdoor unit and pipe for any leakage.
Caution
If possible, it is best to discharge the air out of the machine from the valve by using vacuum pump. To establish vacuum by using vacuum pump, please operate as follows:
Take out the nut cover of the inlet for refrigerant. Connect the tube of the vacuum watch with the vacuum pump, having the low-pressure end linking
to the inlet for refrigerant. (As shown in Figure 3-1-5)
Figure 3-1-5
Starting the vacuum pump, when the indicator turns to-1 bar, closing the low pressure handle and
stopping vacuumize. Keep for 15 minutes, ensuring the pressure of the vacuum watch remains.
Take out the valve cover of the gas valve together with the liquid valve.
Page 85
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Loosing the cord of liquid valve until the pressure rise to 0 bar.
Dismantle the tube from the cover of the inlet for refrigerant then, tighten the cover.
Loose the valve cord of the gas valve as well as the liquid valve entirely.
Tighten the valve cover of the gas valve and liquid valve so as to check whether leakage occurred.
3) Installation of Protective Layer of Connecting Pipe
To avoid generation of condensate on the connecting pipe and avoid leakage, the big pipe and the
small pipe of the connecting pipe must be covered by thermal insulation materials, be bundled by
adhesive tape, and be isolated from air.
The joint connecting to the indoor unit must be wrapped by thermal insulation material. There shall
be no gap between the connecting pipe joint and the wall of the indoor unit. Refer to Figure 3-1-6.
Figure 3-1-6 Figure 3-1-7
Use adhesive tape to bundle the connecting pipe and the cables together. To prevent condensate
from overflowing out from the drainage pipe, separate the drainage pipe firm the connecting pipe
and the cables.
Use thermal insulation tape to wrap the pipes from the bottom of the outdoor unit until the upper end
of the pipe where the pipe enters the wall. When wrapping thermal insulation tape, the later circle of
tape must cover half of the front circle of tape (Figure 3-1-7).
Wrapped pipe must be fixed to wall using pipe clamps.
Caution:
After the pipes are wrapped by protective materials, never bend the pipes to form very small angle,
and otherwise the pipes may crack or break.
Do not wrap the protective tape too tight, otherwise the efficiency of thermal insulation may be
decreased. Ensure that the condensate drainage flexible tube is separate from the bundled pipes.
After the protective work is completed and the pipes are wrapped, use seal material to block the
hole in the wall, so as to prevent rain and wind from entering the room.
3.2 Caution in Connecting Pipes
The layout of connection pipes shall be in reference to the following principles according to site
conditions:
Shorten the connection pipe to minimum, preferably within 5m.
Reduce the height difference between indoor and outdoor units as it might be.
Page 86
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Minimize the number of elbows on connection pipe.
If the connection pipe is longer than 20m, it is needed to check if the lubricating oil in the system is
enough. Add if needed.
The refrigerant charge volume inside the machine is suitable for 7m connection pipe. To extend the
length of connection pipe, it is needed to add an appropriate quantity of refrigerant. For extension of
pipe length by every 1 meter, the refrigerant to be added is as follows. The maximum allowable
length of pipe is as follows.
If the height difference between indoor and outdoor units is over 10m, it is required to install an oil
trap every 6 meters.
When the indoor and outdoor units are on different height, please refer to Fig. 30201 for pipe layout.
Liquid pipe (i.e. fine pipe)
- - - - - -Gas pipe (i.e. coarse pipe)
Figure 3-2-1
Gas pipe
Outdoor unit
Oil elbow in
gas pipe
One oil trap shall be arranged every 4-6
m
Liquid pipe
Indoor unit
Page 87
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
3.3 Specification of Connection Pipe
External Diameter
Maximum
Length of
Connection
Pipe
Maximum Difference in
Height between
Outdoor and Indoor
Unit
Additional Charge of
Refrigerant
Model
Gas Pipe
Liquid
Pipe
(m) (m) (g/m)
ASGE-18AI
φ1/2 φ1/4
20 15 30
ASGE-24AI ASGE-24AI S
ASGE-36AI S
ASGE-36AI-3 S
φ5/8 φ3/8
30 15 60
ASGE-42AI-3 S
φ5/8 φ3/8
50 30 60
ASGE-36AI ASGE-36AI-3
ASGE-42AI-3
φ3/4
φ1/2
50 30
120
4 ELECTRIC WIRING WORK
4.1 Wiring Principle
4.1.1General
Perform wiring of the power supply in conformance with the regulations of the local electric
company.
For the control wires connecting indoor units, and between indoor and outdoor units, use of
double-core shield wires is recommended to prevent noise trouble.
Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor
unit.
Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each
outdoor unit.
Store wiring system for control and refrigerant piping system in the same line.
Arrange the cables so that the electric wires do not come to contact with high-temperature part of
the refrigerant pipe; otherwise coating melts and an accident may be caused.
Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish.
Installation should be conducted by National Wiring Regulation.
The rated voltage and exclusive power supply must be adopted for the air conditioners.
Page 88
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
The power cable should be reliable and fixed, in order to avoid the wiring terminal be suffered from
force. And do not drag the power cable forcibly.
The wire diameter of power cable should be large enough, if power cable and connection wire be
damaged, it should be replaced by the exclusive cable.
All electric installation must be done by professional personnel according to local law, regulation and
this manual.
It should be reliably earthed, and it should be connected to the special earth device, the installation
work should be operated by the professional.
The creepage protect switch and air switch must be installed.
Air switch should have the thermal dropout and magnetic dropout function, in order to avoid the
short circuit and overload.
The on spot connection should refer to the circuit diagram, which is stuck on the unit body.
The unit should be reliably earth, if it is improperly earthed that may cause electric shock or fire.
Air conditioner is the “I” class electric appliance, thus please do conduct reliable grounding
measure.
The yellow-green two-color wiring of air conditioner is grounding wire and cannot be used for other
purposes. It cannot be cut off and be fixed by screw, otherwise it would cause electric shock.
The user must offer the reliable grounding terminal. Please don’t connect the grounding wire to the
following places:
Water pipe Ga s pipe Blowing pipe Other places that professional personnel consider them unreliable.
4.1.2 Connection between power cables and wiring terminals
Caution Before installing the electrical equipment, please pay attention to the following matters which have been specially pointed out by our designers:
Check to see if the power supply used conforms to the rated power supply specified on the
nameplate.
The capacity of the power supply must be large enough. The section area of fitting line in the room
shall be larger than 2.5mm
2
.
The lines must be installed by professional personnel.
An electricity leakage protection switch and an air switch with gap between electrode heads larger
than 3 mm shall be installed in the fixed line.
1 Connection of single wire
Use wire stripper to strip the insulation layer (25mm long) from the end of the single wire.
Remove the screw at the terminal board of the air-conditioning unit.
User pliers to bend the end of the single wire so that a loop matching the screw size is formed.
Put the screw through the loop of the single wire and fix the loop at the terminal board.
2 Connection of multiple twisted wires
Use wire stripper to strip the insulation layer (10mm long) from the end of the multiple twisted wires.
Page 89
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Remove the screw at the terminal board of the air-conditioning unit.
Use crimping pliers to connect a terminal (matching the size of the screw) at the end of the multiple
twisted wires.
Put the screw through the terminal of the multiple twisted wires and fix the terminal at the terminal
board.
Warning:
If the power supply flexible line or the signal line of the equipment is damaged, only use special
flexible line to replace it.
Before connecting lines, read the voltages of the relevant parts on the nameplate. Then carry out
line connection according to the schematic diagram.
The air-conditioning unit shall have special power supply line which shall be equipped with
electricity leakage switch and air switch, so as to deal with overload conditions.
The air-conditioning unit must have grounding to avoid hazard owing to insulation failure.
All fitting lines must use crimp terminals or single wire. If multiple twisted wires are connected to
terminal board, arc may arise.
All line connections must conform to the schematic diagram of lines. Wrong connection may cause
abnormal operation or damage of the air-conditioning unit.
Do not let any cable contact the refrigerant pipe, the compressor and moving parts such as fan.
Do not change the internal line connections inside the air-conditioning unit. The manufacturer shall
not be liable for any loss or abnormal operation arising from wrong line connections.
4.1.3 Power Cable Connection
1) Air-conditioning unit with single-phase power supply
Remove the front-side panel of the outdoor unit.
Pass the cable though rubber ring.
Connect the power supply cable to the “L, N” terminals and the grounding screw.
Use cable fastener to bundle and fix the cable.
2) Air-conditioning unit with 3-phase power supply
Remove the front-side panel of the outdoor unit.
Attach rubber ring to the cable-cross hole of the outdoor unit.
Pass the cable though rubber ring.
Page 90
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Connect the power cable to the terminal and earthing screws marked “L1, L2, L3 & N”.
Use cable fastener to bundle and fix the cable.
Caution:
For air-conditioner with auxiliary heater, it is required to connect the power cable to the “L1, L2
L3”terminals and the grounding screw.
4.1.4 Connection of Signal Line of Wire Controller
Caution: Take great care when carrying out the following connections, so as to avoid malfunction of the air-conditioning unit because of electromagnetic interference.
The signal line of the wire controller must be separated from the power line and the connecting line
between the indoor unit and the outdoor unit.
In case the unit is installed in a place vulnerable by electromagnetic interference, it is better to
use shielded cable or double-twisted cable as the signal line of the wire controller.
Open the cover of the electric box of the indoor unit.
Pull the signal cable of the wire controller through the rubber ring.
Plug the signal line of the wire controller onto the 4-bit pin socket at the circuit board of the indoor
unit.
Use cable fastener to bundle and fix the signal cable of the wire controller.
4.1.5 Cable Connection
Remove the right side plate of the indoor unit and punch through the cable-cross hole. Mount the
cable-cross loop.
Remove the cable clamp. Connect the power cable to the terminal and fix it.
Fix the power cable and signal control wire with cable clamp. Then, connect to corresponding
connector properly.
Confirm if the cables are securely fixed.
Mount the front side plate.
Page 91
Wiring diagram ASGE-18AI main board WZD35B (30224042)
Page 92
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
4.2 Electric Wiring Design
Field Wiring Diagrams:
ASGE-18AI + ASD-18AI
ASGE-18AI + ASF-18AI
ASGE-18AI + ASC-18AI
Page 93
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
ASGE-24AI + ASD-24AI, ASGE-24AI S + ASD-24AI, ASGE-36AI S + ASD-36AI S, ASGE-42AI-3 S + ASD-42AI S
ASGE-24AI + ASF-24AI, ASGE-24AI S + ASF-24AI S, ASGE-36AI S + ASF-36AI S, ASGE-42AI-3 S + ASF-42AI S
ASGE-24AI + ASC-24AI, ASGE-24AI S + ASC-24AI S,ASGE-36AI S + ASC-36AI S,ASGE-42AI-3 S + ASC-42AI S
Page 94
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
ASGE-36AI + ASD-36AI
ASGE-36AI + ASF-36AI,
ASGE-36AI + ASC-36AI,
Page 95
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
93
ASGE-36AI-3 + ASD-36AI, ASGE-36AI-3 S + ASD-36AI S
ASGE-42AI-3 + ASD-42AI
ASGE-36AI-3 + ASF-36AI, ASGE-36AI-3 S + ASF-36AI S, ASGE-42AI-3 + ASF-42AI
ASGE-36AI-3 + ASC-36AI, ASGE-36AI-3 S + ASC-36AI S, ASGE-42AI-3 + ASC-42AI
Page 96
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
4.3 Specification of Power Supply Wire and Air Switch
Model
Power
Supply
Capability of
Air Switch(A)
(Outdoor
/Indoor)
Minimum
Sectional Area of
Earth Wire(mm
2
)
(Outdoor /Indoor)
Minimum
Sectional Area of
Power Supply
Wire(mm
2
)
(Outdoor /Indoor)
ASGE-18I/ ASD-18AI 20/6 2.5/1.0 2.5/1.0 ASGE-24AI/ ASD-24AI 20/10 2.5/1.5 2.5/1.5
ASGE-24AI S/ ASD-24AI S 20/10 2.5/1.5 2.5/1.5
ASGE-36AI/ ASD-36AI 32/10 6.0/1.5 6.0/1.5
ASGE-36AI S/ ASD-36AI S
32/10 6.0/1.5 6.0/1.5
ASGE-42AI-3 S/ ASD-42AI S
32/10 6.0/1.5 6.0/1.5
220-240V~
1 Ph
50HZ
ASGE-36AI-3/ ASD-36AI
25/10 4.0/1.5 4.0/1.5
ASGE-36AI-3 S/ ASD-36AI S
25/10 4.0/1.5 4.0/1.5
ASGE-42AI-3/ ASD-42AI
25/10 4.0/1.
5 4.0/1.5
380-415V~
3 Ph
50HZ
ASGE-18AI/ ASF-18AI
20/6 2.5/1.0 2.5/1.0
ASGE-24AI/ ASF-24AI
20/10 2.5/1.5 2.5/1.5
ASGE-24AI S/ ASF-24AI S
20/10 2.5/1.5 2.5/1.5
ASGE-36AI/ ASF-36AI
32/10 6.0/1.5 6.0/1.5
ASGE-36AI S/ ASF-36AI S
32/10 6.0/1.
5 6.0/1.5
ASGE-42AI-3 S/ ASF-42AI S
32/10 6.0/1.5 6.0/1.5
220-240V~
1 Ph
50HZ
ASGE-36AI-3/ ASF-36AI
25/10 4.0/1.5 4.0/1.5
ASGE-36AI-3 S/ ASF-36AI S
25/10 4.0/1.5 4.0/1.5
ASGE-42AI-3/ ASF-42AI
25/10 4.0/1. 5 4.0/1.5
380-415V~
3 Ph
50HZ
Page 97
DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
95
Model
Power
Supply
Capability of
Air Switch(A)
(Outdoor
/Indoor)
Minimum
Sectional Area of
Earth Wire(mm
2
)
(Outdoor /Indoor)
Minimum
Sectional Area of
Power Supply
Wire(mm
2
)
(Outdoor /Indoor)
ASGE-18AI/ ASC-18AI 20/6 2.5/1.0 2.5/1.0 ASGE-24AI/ ASC-24AI 20/10 2.5/1.5 2.5/1.5 ASGE-24AI S/ ASC-24AI S 20/10 2.5/1.5 2.5/1.5
ASGE-36AI/ ASC-36AI 2/10 6.0/1.5 6.0/1.5 ASGE-36AI S/ ASC-36AI 2/10 6.0/1.5 6.0/1.5
ASGE-42AI-3 S/ ASC-42AI S
2/10 6.0/1.5 6.0/1.5
220-240V~
1 Ph
50HZ
ASGE-36AI-3/ ASC-36AI 25/10 4.0/1.5 4.0/1.5
ASGE-36AI-3 S/ ASC-36AI 25/10 4.0/1.5 4.0/1.5
ASGE-42AI-3/ ASC-42AI 25/10 4.0/1.5 4.0/1.5
380-415V~
3 Ph
50HZ
Note
The specification of power cord mentioned hereby is defined as the required specification when
wiring with BV single core cable (2 ~ 4 pieces) under the cover of PVC pipe, and environment
temperature shall be at 40 ; Air switch shall be selected accordi ng to 40 temperature condition,
and shall in “D” type. if the installation condition on site changed, please consider the modification
on the required specification of Power cord and Air switch, according to the specification manual
provided by manufacture.
Determine the wire size for indoor unit according to the number of connected indoor units
downstream.
Observe local regulation regarding wire size selection and installation.
Caution:
Keeps the refrigerant piping system and the indoor-indoor / indoor-outdoor control wiring systems
together.
When running power wires and control wires parallel to each other, either run them through
separate conduits, or maintain a suitable distance between them. (Current capacity of power wires:
10A or less for 300m,50A or less for 500m)
Page 98
4 Power Distribution of Unit Using the unit with the most complete function as the example, the power distribution is as follows:
Note: The bold line indicates the main circuit and the fine line indicates the control circuit. The element on actual model shall be based on the actual circuit diagram.
Page 99
Indoor and outdoor Ambient temp. sensor resistance Vs. temp. deg (15K)
deg(℃)
resistance
k
deg(℃)
resistance
k
deg(℃)
resistance
k
deg(℃)
resistance
k
-19 138.100 20 18.750 59 3.848 98 1.071
-18 128.600 21 17.930 60 3.711 99 1.039
-17 121.600 22 17.140 61 3.579 100 1.009
-16 115.000 23 16.390 62 3.454 101 0.980
-15 108.700 24 15.680 63 3.333 102 0.952
-14 102.900 25 15.000 64 3.217 103 0.925
-13 97.400 26 14.360 65 3.105 104 0.898
-12 92.220 27 13.740 66 2.998 105 0.873
-11 87.350 28 13.160 67 2.896 106 0.848
-10 82.750 29 12.600 68 2.797 107 0.825
-9 78.430 30 12.070 69 2.702 108 0.802
-8 74.350 31 11.570 70 2.611 109 0.779
-7 70.500 32 11.090 71 2.523 110 0.758
-6 66.880 33 10.630 72 2.439 111 0.737
-5 63.460 34 10.200 73 2.358 112 0.717
-4 60.230 35 9.779 74 2.280 113 0.697
-3 57.180 36 9.382 75 2.206 114 0.678
-2 54.310 37 9.003 76 2.133 115 0.660
-1 51.590 38 8.642 77 2.064 116 0.642 0 49.020 39 8.297 78 1.997 117 0.625 1 46.600 40 7.967 79 1.933 118 0.608 2 44.310 41 7.653 80 1.871 119 0.592 3 42.140 42 7.352 81 1.811 120 0.577 4 40.090 43 7.065 82 1.754 121 0.561 5 38.150 44 6.791 83 1.699 122 0.547 6 36.320 45 6.529 84 1.645 123 0.532 7 34.580 46 6.278 85 1.594 124 0.519 8 32.940 47 6.038 86 1.544 125 0.505 9 31.380 48 5.809 87 1.497 126 0.492
10 29.900 49 5.589 88 1.451 127 0.480 11 28.510 50 5.379 89 1.408 128 0.467 12 27.180 51 5.197 90 1.363 129 0.456 13 25.920 52 4.986 91 1.322 130 0.444 14 24.730 53 4.802 92 1.282 131 0.433 15 23.600 54 4.625 93 1.244 132 0.422 16 22.530 55 4.456 94 1.207 133 0.412 17 21.510 56 4.294 95 1.171 134 0.401 18 20.540 57 4.139 96 1.136 135 0.391 19 19.630 58 3.990 97 1.103 136 0.382
Page 100
Indoor and outdoor Tube temp. sensor resistance Vs. temp. deg (20K)
deg(℃)
resistance
k
deg(℃)
resistance
k
deg(℃)
resistance
k
deg(℃)
resistance
k
-19 181.400 20 25.010 59 5.130 98 1.427
-18 171.400 21 23.900 60 4.948 99 1.386
-17 162.100 22 22.850 61 4.773 100 1.346
-16 153.300 23 21.850 62 4.605 101 1.307
-15 145.000 24 20.900 63 4.443 102 1.269
-14 137.200 25 20.000 64 4.289 103 1.233
-13 129.900 26 19.140 65 4.140 104 1.198
-12 123.000 27 18.130 66 3.998 105 1.164
-11 116.500 28 17.550 67 3.861 106 1.131
-10 110.300 29 16.800 68 3.729 107 1.099
-9 104.600 30 16.100 69 3.603 108 1.069
-8 99.130 31 15.430 70 3.481 109 1.039
-7 94.000 32 14.790 71 3.364 110 1.010
-6 89.170 33 14.180 72 3.252 111 0.983
-5 84.610 34 13.590 73 3.144 112 0.956
-4 80.310 35 13.040 74 3.040 113 0.930
-3 76.240 36 12.510 75 2.940 114 0.904
-2 72.410 37 12.000 76 2.844 115 0.880
-1 68.790 38 11.520 77 2.752 116 0.856 0 65.370 39 11.060 78 2.663 117 0.833 1 62.130 40 10.620 79 2.577 118 0.811 2 59.080 41 10.200 80 2.495 119 0.770 3 56.190 42 9.803 81 2.415 120 0.769 4 53.460 43 9.420 82 2.339 121 0.746 5 50.870 44 9.054 83 2.265 122 0.729 6 48.420 45 8.705 84 2.194 123 0.710 7 46.110 46 8.370 85 2.125 124 0.692 8 43.920 47 8.051 86 2.059 125 0.674 9 41.840 48 7.745 87 1.996 126 0.658
10 39.870 49 7.453 88 1.934 127 0.640 11 38.010 50 7.173 89 1.875 128 0.623 12 36.240 51 6.905 90 1.818 129 0.607 13 34.570 52 6.648 91 1.736 130 0.592 14 32.980 53 6.403 92 1.710 131 0.577 15 31.470 54 6.167 93 1.658 132 0.563 16 30.040 55 5.942 94 1.609 133 0.549 17 28.680 56 5.726 95 1.561 134 0.535 18 27.390 57 5.519 96 1.515 135 0.521 19 26.170 58 5.320 97 1.470 136 0.509
Loading...