Sinclair ASGE-48A, ASGE-12A, ASGE-36A, ASGE-42A, ASGE-60A Service Manual

...
Page 1
SERVICE MANUAL
INDOOR UNITS: ASCU-**A, ASDU-**A, ASFU-**A
UNI ON/OFF SERIE
OUTDOOR UNITS: ASGE-**A
Page 2
Page 3
1
PRODUCT
Page 4
U-MATCH AIR CONDITIONERS PRODUCT
2
PRODUCT
1 MODELS LIST
1.1 Outdoor Unit
Model
Ref.
Power
Supply
Appearance
ASGE-09A R410a
220-240 ,1,50
ASGE-12A R410a
220-240 ,1,50
ASGE-18A R410a
220-240 ,1,50
ASGE-24A R410a
220-240 ,1,50
ASGE-36A R410a
220-240 ,1,50
ASGE-36A R410a
380-415 ,3,50
ASGE-42A R410a
380-415 ,3,50
ASGE-48A R410a
380-415 ,3,50
ASGE-60A R410a
380-415 ,3,50
Note:1Ton =12000Btu/h = 3.517kW
Note:
Filling amount of refrigerant in the system is matched to a 7m connecting pipe
Page 5
U-MATCH AIR CONDITIONERS PRODUCT
3
1.2 Indoor Unit
1.2.1 Duct Type
Type
Model
Nominal Capacity
Cooling/Heating
(Btu/h)
Ref.
Power
Supply
Appearance
ASDU-09A
8900/9700
ASDU-12A
11900/12300
ASDU-18A
17000/19400
ASDU-24A
24000/27300
ASDU-36A
33400/37500
ASDU-42A
33400/37500
ASDU-48A
41000/48000
Duct Type
ASDU-60A
48000/52900
R410a
220-240
1Ph
50Hz
Page 6
U-MATCH AIR CONDITIONERS PRODUCT
4
1.2.2 Floor- Ceiling Type
Type
Model
Nominal Capacity
Cooling/Heating
(Btu/h)
Ref.
Power
Supply
Appearance
ASFU-09A 8
900/9700
ASFU-12A
11900/12300
ASFU-18A
17000/19400
ASFU-24A
24000/27300
ASFU-36A
33400/37500
ASFU-42A
33400/37500
Floor- Ceiling Type
ASFU-48A
41000/48000
R410a
220-240
1Ph
50Hz
1.2.3 Cassette Type
Type
Model
Nominal
Capacity
Cooling/Heating
(Btu/h)
Ref.
Power
Supply
Appearance
ASCU-18A
17000/19400
ASCU-36A
33400/37500
ASCU-12A
11900/12300
ASCU-24A
24000/27300
ASCU-42A
33400/37500
Cassette Type
ASCU-48A
41000/48000
R410a
220-240
1Ph 50Hz
Note:1 Ton =12000Btu/h = 3.517kW
Page 7
PRODUCT
4
2 NOMENCLATURE
A S C U - 09 A WK
1 2 3 4 5 6
7
NO. Description Options
1 Airconditioner
2 Sinclair
D=Duct Type C=Cassette Type F= Floor & Ceiling Type
3 Product Type
G=Outdoor unit H=Wall mounted Type
4 Series Type
U=Uni On/Off Series E=External unit
5 Nominal Cooling Capacity
Nominal Cooling Capacity
=Number×1000Btu/h
6 Refrigerant
A=R410A
7 Assembly winterkit
Page 8
U-MATCH AIR CONDITIONERS PRODUCT
6
3 FUNCTION
Function Description
Memory function
when unit restart after power off, it will run on former status, the mode and
parameter are kept the same
Remote control function
wireless controller and remote controller can be opted, and the maximum
control distance of remote controller is 10m.
Timing function
it can timing ON/ OFF separately, meanwhile, it can also can timing on
circularly
Self-diagnosis with alarm function
once unit has malfunction, the malfunction code will be indicated and alarm
ring immediately
Sleep function it can self control for saving energy in energy saving mode.
Automatic function
the fan of indoor unit can adjust fan speed automatically based on actual
demand when cooling or heating under automatic mode
Cool air proof function
the fan starts only when the temperature of indoor unit heat exchanger is higher
than indoor temperature under heating mode
Weekly Timer
Centralized Control and Week Timer Functions: The centralized controller and
the weekly timer are integrated in the same wire controller. The system has both
the centralized control and the week timing functions. Up to 16 sets of units can
be controlled simultaneously by the centralized controller (weekly timer). The
weekly timer has the function of invalidating the lower unit. The weekly timing
function is able to realized four timing ON/OFF periods for any unit every day,
so as to achieve fully automatic operation. No timing control can be set for
holidays.
High/low pressure protection
when suction pressure is too low or discharge pressure is too high, compressor
will stop and unit display malfunction code
Overload protection
compressor has its own overheat protection, once the temperature of compressor
is higher than allowable level, compressor will stop and only when temperature
recovery, compressor restart
Over current protection
once the current of compressor is higher that normal level, compressor will stop
and unit display malfunction code
Discharge high
temperature protection
once the discharge temperature of compressor is higher than allowable value,
compressor will stop and unit display malfunction code
Reverse (open) phase protection
once the phase sequence of power supply is incongruent or the phase is absent,
unit can’t work and display malfunction code
Anti-high temperature protection once the heat exchanger temperature of indoor unit is too high, compressor stop.
Timing ON/OFF display
display and timing turn ON/OFF timeonly with wired controller have this
function
Fan speed display
display the speed (high, medium, low) of fanonly with wired controller have
this function
Function model display
cooling mode, dehumidifying mode, heating mode, fan modeonly with wired
controller have this function
Testing display display testing modeonly with wired controller have this function
Temperature display
display room temperature and set temperaturewith wired controller or remoter
board have this function
Page 9
U-MATCH AIR CONDITIONERS PRODUCT
7
4 PRODUCT DATA
4.1 Product Data at Rated Condition
4.1.1 Duct Type
Indoor unit ASDU-09A ASDU-12A ASDU-18A
Model
Outdoor unit ASGE-09A WK ASGE-12A WK ASGE-18A WK
kW 2.6 3.5 5.0
Cooling
Btu/h 8900 11900 17000
kW 2.85 3.6 5.7
Nominal
Capacity
Heating
Btu/h 9700 12300 19400
Cooling kW 1.0 1.2 2.1 Power
In
put
Heating kW 0.97 1.1 1.8
EER/COP W/W 2.60/2.94 2.92/3.27 2.38/3.17
Indoor Unit ASDU-09A
ASDU-12A ASDU-18A
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.03 0.04 0.06
Air Flow m3/h 550/470/400 600/540/490 840/750/680
Fan
Ext. Static Pressure Pa 25 25 25
Sound Pressure Level(H/M/L)
dB(A) 37/36/34 40/38/36 42/40/38
Air Filter
Standard washable synthetic
Drain Piping mm φ20×1.2 φ20×1.2 φ30×1.5
Dimensions (W×D×H)
(Outline/Package)
mm
913×680×220 995×750×273
913×680×220/
995×750×273
1012×736×266 1120×795×323
WeightNet/Gross
kg 24/29 25/30 34/41
Outdoor Unit ASGE-09A
WK ASGE-12A WK ASGE-18A WK
Power Supply
220-240V~/1Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.03 0.048 0.03
Fan
Fan Motor Speed rpm 900
Type
ROTARY
Compressor
Motor Output kW 0.922 1.185 1.9
Type
R410A
Control
Capillary Tube
Refrigerant
Charge kg 1.1 1.0 1.5
Dimensions (W×D× H)
(Outline/Package)
mm
820×320×540/
870×360×590
820×320×540/
870×360×590
820×320×540/
870×360×590
WeightNet/Gross
kg 32/37 32/37 40/45
Liquid mm 6.35 6.35 6.35
Gas mm 9.52 12.7 12.7
Max. Length m 20 20 20
Piping
Connections
Max. Height Difference m 15 15 15
Page 10
U-MATCH AIR CONDITIONERS PRODUCT
8
Continued
Indoor unit ASDU-24A
Model
Outdoor unit ASGE-24A WK
kW 7.0
Cooling
Btu/h 24000
kW 8.0
Nominal
Capacity
Heating
Btu/h 27300
Cooling kW 2.66 Power
Input
Heating kW 2.51
EER/COP W/W 2.63/3.19
Indoor Unit ASDU-24A
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.15
Air Flow m3/h 1600/1400/1200
Fan
Ext. Static Pressure Pa 25
Sound Pressure Level(H/M/L)
dB(A) 47/44/42
Air Filter
Standard washable synthetic
Drain Piping mm φ20×1.2
Dimensions (W×D×H)
(Outline/Package)
mm
1270×530×268/
1345×594×283
WeightNet/Gross
kg 37/43
Outdoor Unit ASGE-24A WK
Power Supply
220-240V~/1Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.092
Fan
Fan Motor Speed(H/M/L) rpm 940
Type
ROTARY
Compressor
Motor Output kW 2.475
Type
R410A
Control
Capillary Tube
Refrigerant
Charge kg 2.2
Dimensions (W×D×H)
(Outline/Package)
mm
1018×412×695/
1100 ×450×755
WeightNet/Gross
kg 59/64
Liquid 9.52 9.52
Gas mm 15.9
Max. Length m 30
Piping
Connections
Max. Height Difference m 15
Page 11
U-MATCH AIR CONDITIONERS PRODUCT
9
Continued 1
Indoor unit ASDU-36A
Model
Outdoor unit ASGE-36A WK
kW 9.8
Cooling
Btu/h
33400
kW 11
Nominal
Capacity
Heating
Btu/h 37500
Cooling kW 4.0 Power
Input
Heating kW 3.5
EER/COP W/W
2.45/3.14
Indoor Unit ASDU-36A
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.5
Air Flow m3/h 2000/1900/1800
Fan
Ext. Static Pressure Pa 37
Sound Pressure Level(H/M/L)
dB(A)
50/48/46
Air Filter
Standard washable synthetic
Drain Piping mm φ20×1.2
Dimensions (W×D×H)
(Outline/Package)
mm
1226×775×290/
1335×834×305
WeightNet/Gross
kg 54/61
Outdoor Unit ASGE-36A WK
Power Supply
380-415V~/3Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.092
Fan
Fan Motor Speed(H/M/L) rpm 920/780
Type
SCROLL
Compressor
Motor Output kW 3.65
Type
R410A
Control
Capillary Tube
Refrigerant
Charge kg 3.2
Dimensions (W×D×H)
(Outline/Package)
mm
1018 ×412×840/
1100×450×985
WeightNet/Gross
kg 90/100
Liquid mm
12.7
Gas mm
19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
Page 12
U-MATCH AIR CONDITIONERS PRODUCT
10
Continued 2
Indoor unit ASDU-42A ASDU-48A ASDU-60A
Model
Outdoor unit ASGE-42A WK ASGE-48A WK ASGE-60A WK
kW 12 14 16
Cooling
Btu/h 41000 48000 54600
kW 14 15.5 18.5
Nominal
Capacity
Heating
Btu/h 48000 52900 63100
Cooling kW 5.3 5.8 6.5 Power
Input
Heating kW 4.9 5.4 5.5
EER/COP W/W 2.26/2.86 2.41/2.87 2.46/3.36
Indoor Unit ASDU-42A
ASDU-48A ASDU-60A
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.5
Air Flow m3/h 2000/1900/1800 2300/2110/1850 2500/2070/1730
Fan
Ext. Static Pressure Pa 50 50 50
Sound Pressure Level(H/M/L)
dB(A) 50 / 48 /46 53/50/46 53 / 50 /48
Air Filter
Standard washable synthetic
Drain Piping mm φ20×1.2 φ20×1.2 φ32×1.5
Dimensions (W×D×H)
(Outline/Package)
mm
1226×775×290/
1335 ×83×305
1226×775×290/
1335×834×305
1226×815×330/
1335×882×345
WeightNet/Gross
kg 54/61 57/67 66/76
Outdoor Unit ASGE-42A WK ASGE-48A WK ASGE-60A WK
Power Supply
380-415V~/3 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.092
Fan
Fan Motor Speed(H/M/L) rpm 840/620/400 738/1218/44 940
Type
SCROLL
Compressor
Motor Output kW 4.75 4.5 5.75
Type
R410A
Control
Capillary Tube
Refrigerant
Charge kg 3.55 3.8 5.0
Dimensions (W×D×H)
(Outline/Package)
mm
1032×412×1250
/1100 ×450×1385
1032×412×1250
/1110×450×1385
1032×412×1250
/1110×450×1385
WeightNet/Gross
kg 112/123 112/123 123/134
Liquid mm 12.7 12.7 12.7
Gas mm 19.05 19.05 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
Page 13
U-MATCH AIR CONDITIONERS PRODUCT
11
Note: ① Nominal capacities are based on the follow conditions.
Indoor Outdoor
Cooling
DB:27℃(80.6)
WB:19℃(66.2)
DB:35℃(95)
WB:24℃(75.2)
Heating
DB:20℃(68)
WB--(--)
DB:7℃(44.6)
WB:6℃(42.8)
Piping Length 5m
The air volume is measured at the relevant standard external static pressure.
Noise is tested in the Semi anechoic Room, so it should be slightly higher in the actual operation due to
environmental change.
Page 14
U-MATCH AIR CONDITIONERS PRODUCT
12
4.1.2 Ceiling Type
Indoor unit ASFU-09A ASFU-12A ASFU-18A
Models
Outdoor unit ASGE-09A WK ASGE-12A WK ASGE-18A WK
kW 2.6 3.5 5.0
Cooling
Btu/h 8900 11900 17000
kW 2.85 3.6 5.7
Nominal
Capacity
Heating
Btu/h 9700 12300 19400
Cooling kW 1 1.17 2.03 Power
Input
Heating kW 1 1.1 2.07
EER/ COP W/W 2.60/2.85 2.99/3.27 2.46/2.75
Indoor Unit ASFU-09A
ASFU-12A
ASFU-18A
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.01 0.01 0.04
Fan
Air Flow m
3
/h 550/470/380 550/470/380 700/640/570
Sound Pressure Level(H/M/L)
dB(A) 47/44/41 46/44/41 54/50/46
Air Filter
Standard washable synthetic
Drain Piping mm φ28×1.5
Dimensions (W×D×H)
(Outline/Package)
mm
836×695×238/
935×805×295
836×695×238/
935×805×295
836×695×238/
935×805×295
WeightNet/Gross
kg 25/32 26/33 26/33
Outdoor Unit ASGE-09A WK ASGE-12A WK ASGE-18A WK
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.03 0.048 0.048
Fan
Fan Motor Speed rpm 850 900 900
Type
ROTARY
Compressor
Motor Output kW 0.922 1.185 1.9
Type
R410A
Control
Capillary Tube
Refrigerant
Charge kg 1.1 1.0 1.5
Dimensions (W×D×H)
(Outline/Package)
mm
820×320×540
/870×360×590
820×320×540
/870×360×590
820×320×540
/870×360×590
WeightNet/Gross
kg 32/37 32/37 40/45
Liquid mm 6.35 6.35 6.35
Gas mm 9.52 12.7 12.7
Max. Length m 20 20 20
Piping
Connections
Max. Height Difference m 15 15 15
Page 15
U-MATCH AIR CONDITIONERS PRODUCT
13
Continued
Indoor unit ASFU-24A
Models
Outdoor unit ASGE-24A WK
kW 7.0
Cooling
Btu/h 24000
kW 8.0
Nominal
Capacity
Heating
Btu/h 27300
Cooling kW 2.61 Power
Input
Heating kW 2.59
EER/ COP W/W 2.68/3.09
Indoor Unit
ASFU-24A
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.05
Fan
Air Flow m
3
/h 1170/1080/1000
Sound Pressure Level(H/M/L)
dB(A) 50/48/46
Air Filter
Standard washable synthetic
Drain Piping mm φ28×1.5
Dimensions (W×D×H)
(Outline/Package)
mm
1300×600×188
/1414×724×248
WeightNet/Gross
kg 33/40
Outdoor Unit
ASGE-24A WK
Power Supply
220-240V~/1 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.092
Fan
Fan Motor Speed rpm 940
Type
ROTARY
Compressor
Motor Output kW 2.475
Type
R410A
Control
Capillary Tube
Refrigerant
Charge kg 2.2
Dimensions (W×D×H)
(Outline/Package)
mm
1018×412×695/
1100×450×755
WeightNet/Gross
kg 59/64
Liquid mm 9.52
Gas mm 15.8
Max. Length m 30
Piping
Connections
Max. Height Difference m 15
Page 16
U-MATCH AIR CONDITIONERS PRODUCT
14
Continued 1
Indoor unit ASFU-36A
Models
Outdoor unit ASGE-36A WK
kW 9.8
Cooling
Btu/h
33400
kW
10.78
Nominal
Capacity
Heating
Btu/h 36800
Cooling kW
3.6
Power
Input
Heating kW 3.3
EER/ COP W/W
2.72/3.27
Indoor Unit ASFU-36A
Power Supply
220-240V~/1Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.085
Fan
Air Flow m3/h
1800/1630/1520
Sound Pressure Level(H/M/L)
dB(A 54/51/48
Air Filter
Standard washable synthetic
Drain Piping mm φ28×1.5
Dimensions (W×D×H)
(Outline/Package)
mm
1590×695×238/
1714×830×330
WeightNet/Gross
kg 48/58
Outdoor Unit
ASGE-36A WK
Power Supply
380-415V~/3Ph/50
HZ
Heat Exchange
Cross Fin Coil
Type
Axial fan
Motor Output kW 0.092
Fan
Fan rpm
900
Type
SCROLL
Compress
or
Motor Output kW 3.65
Type
R410A
Control
Capillary Tube
Refrigeran
t
Charge kg 3.2
Dimensions (W×H×D)
(Outline/Package)
mm
1018×412×840/
1100×450×985
WeightNet/Gross
kg
90/100
Liquid mm
12.7
Gas mm
19.05
Max. Length m
50
Piping
Connectio
ns
Max. Height m 30
Page 17
U-MATCH AIR CONDITIONERS PRODUCT
15
Continued 2
Indoor unit ASFU-42A ASFU-48A
Models
Outdoor unit ASGE-42A WK ASGE-48A WK
kW 12 14
Cooling
Btu/h 41000 48000
kW 14 15.5
Nominal
Capacity
Heating
Btu/h 48000 52900
Cooling kW 4.8 6.1 Power
Input
Heating kW 4.7 5.8
EER/ COP W/W 2.50/2.98 2.30/2.67
Indoor Unit ASFU-42A ASFU-48A
Power Supply
220-240V~/1Ph/50HZ
Heat Exchange
Cross Fin Coil
Type
Centrifugal fan
Drive
Direct Driver
Motor Output kW 0.085 0.085
Fan
Air Flow m
3
/h 1800/1630/1520 2100/1900/1800
Sound Pressure Level(H/M/L)
dB(A) 54/51/48 58/55/52
Air Filter
Standard washable synthetic
Drain Piping mm φ28×1.5
Dimensions (W×D×H)
(Outline/Package)
mm
1590×695×238/
1714×830×330
1590×695×238/
1714×830×330
WeightNet/Gross
kg 48/58 48/58
Outdoor Unit ASGE-42A WK ASGE-48A WK
Power Supply
380-415V~/3 Ph/50HZ
Heat Exchange
Cross Fin Coil
Type Axial fan
Motor Output kW 0.068 0.092
Fan
Fan MotorSpeed(H/M/L) rpm 840/620/400 940
Type
SCROLL
Compressor
Motor Output kW 4.75 4.5
Type
R410A
Control
Capillary Tube
Refrigerant
Charge kg 3.55 3.8
Dimensions (W×D×H)
(Outline/Package)
mm
1032×412×1250/
11105× 450 ×1385
1032×412×1250/
1110× 450×1385
WeightNet/Gross
kg 112/123
Liquid mm 12.7
Gas mm 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
Page 18
U-MATCH AIR CONDITIONERS PRODUCT
16
Note: ① Nominal capacities are based on the follow conditions.
Indoor Outdoor
Cooling
DB:27℃(80.6)
WB:19℃(66.2)
DB:35℃(95)
WB:24℃(75.2)
Heating
DB:20℃(68)
WB--(--)
DB:7℃(44.6)
WB:6℃(42.8)
Piping Length 5m
The air volume is measured at the relevant standard external static pressure.
Noise is tested in the Semianechoic Room, so it should be slightly higher in the actual operation
due to environmental change.
Page 19
U-MATCH AIR CONDITIONERS PRODUCT
17
4.1.3 Cassette Type
Indoor unit ASCU-12A ASCU-18A ASCU-24A
Models
Outdoor unit ASGE-12A WK ASGE-18A WK ASGE-24A WK
kW 3.5 5.0 6.8
Cooling
Btu/h 11900 17000 23200
kW 3.6 5.4 7.5
Nominal
Capacity
Heating
Btu/h 12300 18400 25600
Cooling kW 1.17 2.0 2.62
Power
Input
Heating kW 1.1 1.9 2.5
EER/COP W/W 2.99/3.27 2.50/2.84 2.60/3.00
Indoor Unit ASCU-12A ASCU-18A ASCU-24A
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan
Drive Direct Driver
Motor Output kW 0.011 0.011 0.035
Fan
Air Flow m3/h 550/490/420 550/490/420 1180/1080/1000
Sound Pressure Level(H/M/L) dB(A) 47/45/43
Air Filter Standard washable synthetic
Drain Piping mm φ31×3 φ31×3 φ32×3
Indoor Unit Dimensions
(Outline/Package) (W×D×H)
mm
600×600×230/
848×678×310
600×600×230/
848×678×310
840×840×240/
960×960×310
Panel Dimensions
(Outline/Package) (W×D×H)
mm
650×650×50/
670×730×102
650×650×50/
670×730×102
950×950×60/
1025×1040×115
WeightNet/Gross kg 20/27 20/27 27/36
Outdoor Unit ASGE-12A WK ASGE-18A WK ASGE-24A WK
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.048 0.048 0.092
Fan
Fan Motor Speed(H/M/L) rpm 900 900 940
Type ROTARY
Compressor
Motor Output kW 1.185 1.9 2.475
Type R410A
Control Capillary Tube
Refrigerant
Charge kg 1.0 1.5 2.2
Dimensions (W×D×H)
(Outline/Package)
mm
820×320×540/
870×360×590
820×320×540/
870×360×590
1018×412×695/
1100×450×755
WeightNet/Gross kg 32/37 40/45 59/64
Liquid mm 6.35 6.35 9.52
Gas mm 12.7 12.7 15.8
Max. Length m 20 20 30
Piping
Connections
Max. Height Difference m 15 15 15
Note: Water pump discharge height : ASCU-12A - 500mm (from bottom edge)
ASCU-18A - 500mm (from bottom edge)
ASCU-24A - 1125mm (from bottom edge)
Page 20
U-MATCH AIR CONDITIONERS PRODUCT
19
Continued 1
Indoor unit ASCU-36A
Models
Outdoor unit ASGE-36A WK
kW 10
Cooling
Btu/h 34100
kW 11
Nominal Capacity
Heating
Btu/h 37500
Cooling kW 3.6
Power
Input
Heating kW 3.1
EER/COP W/W
2.78/3.55
Indoor Unit ASCU-36A
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan
Drive Direct Driver
Motor Output kW 0.06
Fan
Air Flow m3/h 1660/1570/1500
Sound Pressure Level(H/M/L) dB(A) 53/51/48
Air Filter Standard washable synthetic
Drain Piping mm φ32×3
Indoor Unit Dimensions
(Outline/Package) (W×D×H)
mm
840×840×320/
960×960×394
Panel Dimensions
(Outline/Package) (W×D×H)
mm
950×950×60/
1025×1040×115
WeightNet/Gross) kg 32/43
Outdoor Unit
ASGE-36A WK
Power Supply
380-415V~/3Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.092
Fan
Fan Motor Speed(H/M/L) rpm 900
Type SCROLL
Compressor
Motor Output kW 3.65
Type R410A
Control Capillary Tube
Refrigerant
Charge kg 3.2
Dimensions (W×D×H)
(Outline/Package)
mm
1018×412×840/
1100×450×985
WeightNet/Gross) kg 90/100
Liquid mm 12.7
Gas mm 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
Note: Water pump discharge height : ASCU-36A - 1125mm (from bottom edge)
Page 21
U-MATCH AIR CONDITIONERS PRODUCT
20
Continued 2
Indoor unit ASCU-42A ASCU-48A
Models
Outdoor unit ASGE-42A WK ASGE-48A WK
kW 12 14
Cooling
Btu/h 41000 48000
kW 14 15.5
Nominal Capacity
Heating
Btu/h 48000 52900
Cooling kW 4.8 5.8
Power
Input
Heating kW 5.0 6.2
EER/COP W/W 2.50/2.80 2.41/2.50
Indoor Unit ASCU-42A ASCU-48A
Power Supply 220-240V~/1 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Centrifugal fan
Drive Direct Driver
Motor Output kW 0.06
Fan
Air Flow m3/h 1660/1570/1500 1660/1570/1500
Sound Pressure Level(H/M/L) dB(A) 53/ 51 /48
Air Filter Standard washable synthetic
Drain Piping mm φ32×3
Indoor Unit Dimensions
(Outline/Package) (W×D×H)
mm
840×840×320/
960×960×394
Panel Dimensions
(Outline/Package) (W×D×H)
mm
950×950×60/
1025×1040×115
WeightNet/Gross kg 32/43
Outdoor Unit ASGE-42A WK ASGE-48A WK
Power Supply 380-415V~/3 Ph/50HZ
Heat Exchange Cross Fin Coil
Type Axial fan
Motor Output kW 0.068 0.092
Fan
Fan Motor Speed(H/M/L) rpm 840/620/400
Type SCROLL
Compressor
Motor Output kW 4.75 4.5
Type R410A
Control Capillary Tube
Refrigerant
Charge kg 3.55 3.8
Dimensions ()
(Outline/Package) (W×D×H)
mm
1032×412×1250/
1110 ×450 × 1385
WeightNet/Gross kg 112/123
Liquid mm 12.7
Gas mm 19.05
Max. Length m 50
Piping
Connections
Max. Height Difference m 30
Note: Water pump discharge height : ASCU-42A - 1125mm (from bottom edge)
ASCU-48A - 1125mm (from bottom edge)
Page 22
U-MATCH AIR CONDITIONERS PRODUCT
21
Note: ① Nominal capacities are based on the follow conditions.
Indoor Outdoor
Cooling
DB:27℃(80.6)
WB:19℃(66.2)
DB:35℃(95)
WB:24℃(75.2)
Heating
DB:20℃(68)
WB--(--)
DB:7℃(44.6)
WB:6℃(42.8)
Piping Length 5m
The air volume is measured at the relevant standard external static pressure. Noise is tested in the Semianechoic room, so it should be slightly higher in the actual operation due to
environmental change.
4.2 Operation Range
Mode
Range of Outdoor Temperature℃ (℉)
Cooling
18-43
-7-43(with low Ambient kit)
Heating
-7-24
Page 23
Power Supply
Ot
y
LRA RLA
Condenser Fan Motors
Supply Blower Motor
V,P h ,H z
-
Each Each FLA Each FLA Amperes Amperes
Max. Fuse Breaker
Size
(Indoor/Outdoor)
Min. Disconnect Size (Indoor/Outoor)
Fan MotorCompressor
4.3 Electrical Data
Model
V,P h ,H z
Each
Each
FLA Each
FLA
Each
Amperes
Amperes
ASDU-09A
0.18 6/16 6/16
ASFU-09A
0.09 6/16 6/16
ASDU-12A
0.18 6/16 6/16
ASFU-12A
0.09 6/16 6/16
ASCU-12A
0.1 6/16 6/16
ASDU-18A
0.63 6/20 6/20
0.27
0.27
4.28
5.6
18
32
220-240,
1, 50
1
1
ASGE-09A WK
ASGE-12A WK
ASGE-18A WK
ASFU-18A
0.36
6/20
6/20
ASCU-18A
0.1 6/20 6/20
ASDU-24A
1.35 6/25 6/25
ASFU-24A
0.9 6/25 6/25
ASCU-24A
0.32 6/25 6/25
ASDU-36A
4.5 10/16 10/16
ASFU-36A
1.35 6/16 6/16
ASCU-36A
0.54 6/16 6/16
0.86.58
0.27
0.61
8.8
11.2
40
60
67
1
1
1
ASGE-36A WK
ASGE-24A WK
ASDU-42A
4.5 10/20 10/25
ASFU-42A
1.35 6/20 6/25
ASCU-42A
0.54 6/20 6/25
ASDU-48A
4.5 10/25 10/25
ASFU-48A
1.62 6/25 6/25
ASCU-48A
0.54 6/25 6/25
ASGE-60A WK ASDU-60A
1 67 9.77 0.8 4.5 10/25 10/25
Notes
0.8
0.8
8.22
816659.4
1
ASGE-42A WK
ASGE-48A WK
380-415,
3, 50
Notes
RLARated load amperes LRALocked rotor amperes FLAFull load curent
Page 24
U-MATCH AIR CONDITIONERS PRODUCT
23
5 PIPING DIAGRAM
Page 25
24
CONTROL
Page 26
U-MATCH AIR CONDITIONERS CONTROL
25
CONTROL
1 OPERATION FLOWCHART
1.1 Cooling/Dry Operation
Page 27
U-MATCH AIR CONDITIONERS CONTROL
26
1.2 Heating Operation
Page 28
U-MATCH AIR CONDITIONERS CONTROL
27
2 MAIN LOGIC
2.1 Cooling
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
H
When T
amb.≥Tpreset t
+1, the unit begins cooling operation and the compressor and the outdoor
fan are running; and the indoor fan is running at a set speed.
When T
amb.
t≤T
preset
-1, the unit is in the cooling shutdown state, and the compressor and the
outdoor fan stop running; and the indoor fan is running at a set speed.
When T
preset
-1℃<T
amb.<Tpreset
+1, the unit keeps in the operation state.
Cooling mode
Compressor
Outdoor fan
Indoor fan
4-way valve
Manual shutdown
Starting up
Operation at a set speed
Time
H grade
Page 29
U-MATCH AIR CONDITIONERS CONTROL
28
2.2 Dry Mode
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
H
When T
amb.≥Tpreset
+2, the unit begins cooling operation and the compressor and the outdoor fan
are running; and the indoor fan is running at a low speed.
When T
amb.≤Tpreset
-2, the unit is in the cooling shutdown state and the compressor and the
outdoor fan stop running.
When T
prese
-2℃<T
amb.<Tpreset
+2, the unit is in the six-minute stop and four-minute operation
state, that is, the compressor runs for 6 minutes and then stops for 4 minutes, in such cycle
repeatedly; and the indoor fan operates at a low speed.
Compressor
Outdoor fan
Indoor fan
4-way valve
Dry Mode
Manual shutdown
Starting up
Operation at a low speed
H grade
Time
Page 30
U-MATCH AIR CONDITIONERS CONTROL
29
2.3 Heating Mode
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
When T
amb.≤Tpreset
-1, the unit begins heating operation and the compressor and the outdoor fan
are running; and the indoor fan is running at a set speed according to cold fan prevention
conditions.
When T
amb.≥Tpreset
+1, the compressor and the outdoor fan stop running and the four-way valve
keeps energized; and the indoor fan is running according to afterheat blowing conditions.
When T
-1℃<T
amb.<Tpreset
+1℃, the unit keeps in the previous operation state.
Compressor
Outdoor fan
Indoor fan
4-way valve
Heating Mode
Manual shutdown
Starting up
Auxiliary heating
Operation at a
set speed
Operation under normal conditions
Operation in blowing
afterheat state
Cold blast prevention
Time
Page 31
U-MATCH AIR CONDITIONERS CONTROL
30
2.4 Defrosting
ON
ON
OFF
ON
OFF
OFF
OFF
ON
ON ON
ON
ON
ON
Defrosting start conditions: after the heating operation runs for an accumulated period of 44
minutes and the compressor continues to operate for 4 hours and 50 seconds, and a one-minute
duration of T
cond.
-5℃is detected, the unit begins defrosting. If an auxiliary heater is available, it
must be stopped firstly, and after 10 seconds, the four-way valve, the indoor fan, the outdoor fan
and the compressor will run compulsively.
Defrosting completion conditions: when defrosting runs 10 minutes or T
cond.
10℃, defrosting will
be completed. In such case, the four-way valve is running, the outdoor fan is running, the
compressor is running compulsively, and the indoor fan operates according to cooling fan proof
conditions.
Compressor
Outdoor fan
Indoor fan
4-way valve
Auxiliary heating
Defrosting
Enter the
defrosting mode
Withdraw the
defrosting mode
Operation at a
set speed
Operation under
normal conditions
Cold blast prevention
Time
Page 32
U-MATCH AIR CONDITIONERS CONTROL
31
2.5 Fan Mode
OFF
OFF
OFF
OFF
OFF
OFF
H
The indoor fan runs at a fast speed for 5s and then runs at a set speed.
Compressor
Outdoor fan
Indoor fan
4-way valve
Fan Mode
Time
Manual shutdown
Starting up
Operation at a
set speed
H grade
Page 33
U-MATCH AIR CONDITIONERS CONTROL
32
3 WIRELESS REMOTE CONTROLLER
3.1 Operation View
(1) Controller-Duct Type
ON/OFF
MODE
AUTO FAN
SWING
AUTO
SWING
OPER
AIR
FAN
NO. Name Function description
1 ON/OFF button Press the button to set start or close unit
2 Mode button
Press the button to select the mode,
cooling , heating , fan or auto mode.
3 Increase/Decrease button Press this button to increase/decrase the setup temp
4 LCD Screen Display the status of remote information
5 Swing button Press this button set swing function
6 Fan speed button Press this button to set fan speed
ZY512A
Page 34
U-MATCH AIR CONDITIONERS CONTROL
33
(2)Controller-Cassette Type and Ceiling Type
ON/OFF
MODE
LIGHT
AUTO
TIMER ON/OFF
SWING HUMID
SWING
Auto Fan
SAVE
HR
AIR
FAN
OPER
TIMER ON/OFF
ON/OFF
ANION
TIME OFFTIME ON
MODE
LIGHT
SLEEP
SAVE
HUMID
AIR
HR
LIGHT
AUTO FAN
SWING
HUMID
AUTO
SWING
SAVE
OPER
AIR
FAN
NO. Name Function description
1 Swing button Press this button to set swing function
2 Increase/Decrease button Press this button to increase/decrase the setup temp
3 Mode button
Press the button to select the mode,
cooling , heating , fan or auto mode.
4 ON/OFF button Press the button to set start or close unit
5 LCD Screen Display the status of remote information
6 Fan speed button Press this button to set fan speed
7 Sleep button Press the button to set sleep function
8 Time on Press the button to set time on function
9 Time off Press the button to set time off function
Page 35
U-MATCH AIR CONDITIONERS CONTROL
34
3.2 Display View
LIGHT
AUTO
TIMER ONOFF
SWING
HUMID
SWING
AUTO FAN
SAVE
HR
AIR
FAN
OPER
No. Display Function description
1 Fan Speed
auto fan speed, low fan speed,
middle fan speed high fan speed
2 Run Mode
Auto running Cool running;
Dry Running Fan Running
Heat running (Heat and Cool unit only)
3 Setup temp Temperature value of setting
4 Swing function Swing is on
5 Sleep mode Sleep mode is on
6 Time value Timing value of setting
7 OPER The controller is on
Page 36
U-MATCH AIR CONDITIONERS CONTROL
35
4 WIRED REMOTE CONTROLLER
4.1 Operation View
1Wired Controller-Duct Type
MODE
ON/OFF
FAN
SLEEP
TIMER
2Wired Controller-Cassette Type and Ceiling Type
MODE
ON/OFF
FAN
SWING
TIMER
Z4B351
Z4B351
Page 37
U-MATCH AIR CONDITIONERS CONTROL
36
NO. Name Function description
1 MODE button
Press the button to select the mode,
cooling , heating , fan or auto mode.
2 Increasing button Press this button to increase the setup temp.
3 Decreasing button Press this button to decrase the setup temp.
4 Fan speed button Press this button to set fan speed
5 Sleep/SWING button Press the button to set sleep/swing function
6 Timer button Press the button to set timer function
7 On/off button Press the button to set start or close unit
8 Remote window Get remote information
9 LCD display Display unit information
Note
1SAVE set up :At unit turned off, to press the “FAN” +“” buttons continuously 5 seconds, it can come
enter save set up interphase, the unit will run at save mode.
2FRESH valve setup : At unit is turned off, press the “ FAN” button for 5seconds,And set up the fresh air
setup.
3Outer ambient temperature display: Under normal condition, “ENV” will display the room ambient
temperature, at unit turned on, or unit turned off status, press “SLEEP/SWING” button last for 5 seconds,
the LCD will display “OUT ENV”.
4MEMORY function setup: At unit turned off, press “MODE” button for 10 seconds, could switch
whether turn on or off the unit state after powered off.
5Debugging function: At unit off, continuously press “FAN” + “SLEEP” buttons lasting for 10seconds,
call out debugging menu, and displays “Debugging” icons, use “MODE” button adjust setting item, by
pressing “”, “” button to set up the detailed value.
(A) Ambient sensor set up: it can set three kinds styles.
6Lock function: Press “▲”and“” at the same time for 5 seconds, the set temp. will display “EE” and
shield, all buttons will sound; and repress the“”and “”at the same time for 5 seconds, the lock
function will be released.
(for details, please read corresponding parts of manual).
Page 38
U-MATCH AIR CONDITIONERS CONTROL
37
4.2 Display View
MODE
ON/OFF
FAN
SWING
TIMER
NO. Name Function description
1 Timer value Display time value
2 Timer on/off
display timer on :display timer off
3
Fan speed
display
auto fan speed low fan speed
middle fan speed high fan speed
4 Set temp display
Display set temp valueits range is 16~30
5 Run mode display
auto mode cool mode dry mode
fresh fan mode fan mode
heat mode(only cool and heat unit)
6 Indoor temp display Display surrounding temp indoor
7 Outdoor temp display Display surrounding temp outdoor
8 Frost display When unit frosts ,it display
9 Sleep display Display sleep at Sleep mode
10 Swing display When setting swing function, it displays,
11 Error display When unit error, error code display
Page 39
U-MATCH AIR CONDITIONERS CONTROL
38
4.3 Dimension
4.4 Installation
1. First select an installation position. According to the size of the communication line of the
wire controller, leave a recess or a embedded wire hole to bury the communication line.
2. If the communication line between the wire controller (85×85×20) and the indoor unit is
surface-mounted, use 1# PVC pipe and make matching recess in the wall (refer to Figure 6);
If concealed installation is adopted, 1# PVC pipe can be used (Refer to Figure 7).
3. No matter if surface mounting or concealed mounting is selected, it is required to drill 2 holes
(in the same level) which distance shall be the same as the distance (60mm) of installation
holes in the bottom plate of the wire controller. Then insert a wood plug into each hole. Fix
the bottom plate of the wire controller to the wall by using the two holes. Plug the
communication line onto the control panel. Lastly install the panel of the wire controller.
Caution:
During the installation of the bottom plate of the wire controller, pay attention to the direction
of the bottom plate. The plate’s side with two notches must be at the lower position, and otherwise
the panel of the wire controller cannot be correctly installed.
Page 40
U-MATCH AIR CONDITIONERS CONTROL
39
PVC pipe
Fig6Surface Mounting of Cable Fig7Concealed mounting of Cable
1 324
Fig 8 Schematic Diagram of Installation
No. Name
1 Wall Surface
2 Bottom Plate of Wire Controller
3 Screw M4X10
4 Panel of Wire Controller
Caution:
1. The communication distance between the main board and the wire controller can be as far as
20m (The standard distance is 8m).
2. The wire controller shall not be installed in a place where there is water drop or large amount
of water vapor.
Page 41
U-MATCH AIR CONDITIONERS CONTROL
40
5 CENTRALIZED CONTROLLER
5.1 Centralized Controller-not with week timer
5.1.1 Function
Centralized Controller-not with week timer only control on-off function of every units. Up to 16 sets of units
can be controlled simultaneously by the centralized controller-not with week timer.
5.1.2 Operation View
NO. Name Function description
1 ON button Press the button to set start unit
2 OFF button Press the button to set close unit
3 LCD display Display unit information
4 LED LED indication
5 Increasing / Decreasing button Press buttons select the unit
5.1.3 Display View
Display unit address value in the net.
Page 42
U-MATCH AIR CONDITIONERS CONTROL
41
5.1.4 Dimensions
5.2 Centralized Controller-week timer
5.2.1 Function
Centralized Control and Week Timer Functions: The centralized controller and the weekly
timer are integrated in the same wire controller. The system has both the centralized control and
the week timing functions. Up to 16 sets of units can be controlled simultaneously by the
centralized controller (weekly timer). The weekly timer has the function of invalidating the lower
unit. The weekly timing function is able to realized four timing ON/OFF periods for any unit
every day, so as to achieve fully automatic operation. No timing control can be set for holidays.
On and off of every duct type unit can be done through the Timer On / Off of this WEEKLY TIMERit can not set other functions except on-off function of units.
Page 43
U-MATCH AIR CONDITIONERS CONTROL
42
5.2.2 Operation View
NO. Name Function description
1 ENTER button
when “enter” is pressed the setting is validate.
2 Increasing button
Press “” and selected the unit or a certain day in one week or specific value.
Press “” can set week part of time.
3 Decreasing button
Press “
” and selected the unit or a certain day in one week or specific
value. Press “ ” can set week part of time.
4
CANCEL/DELETE
button
short-press “cancel/delete” to back to default page or last process, long-press
cancel/delete” to cancel timer of a certain time period in a certain day
5
SINGLLE/GROUP
button
short-press “single/group” to enter single control setting. “SINGLE”
displayed. long-press “single/group” to enter group control setting.
GROUP” displayed
6
TIMER/TIME
button
Short-press “timer/time” to enter timer setting.
Long-press “timer/time” under default page can begin time setting.
7 On/off button Control unit run or stop
8 LCD display Display unit information
Page 44
U-MATCH AIR CONDITIONERS CONTROL
43
5.2.3 Display View
NO. Name Function description
1 unit’s no. displays Display unit’s numbers
2 Group control displays when group controls, it will display
3 Single control displays when single unit controls, it will display
4 Timer time in week displays Display time in week
5 Timer displays Display time
6 timer state displays
“on”: when set unit on, “on” will display;
“off”: when set unit off, “off” will display;
7 timer on time displays Display starts time
8 on control displays When set unit or group on, it will display,
9 off control displays When set unit or group off, it will display,
10 present time in week display Display present time of week.
11 present time in Hr:Min displays Display time of hour and minute now
12 timer off time displays Display over time
13 timer period displays Set to different time segment
Note
Please read corresponding manual of weekly timer controller to be familiar with it.
Page 45
U-MATCH AIR CONDITIONERS CONTROL
44
5.2.4 Dimensions
Page 46
U-MATCH AIR CONDITIONERS CONTROL
45
5.3 Field Setting
The centralized controller displays code of various units: unit code is determined by the
position (on the back of the manual operator) of the toggle switch of the manual operator on each
flue pipe air conditioner. Toggling values are corresponding to the 4-1 feet from the right to left of
the toggle switch. “ON” stands for “0”, and conversely, “OFF” stands for “1”
Example 1: to get “0111”, which represents the serial number “8”, you can put foot 1, 2 and 3
of the toggle switch to the opposite of “ON” and foot 4 to “ON”.
Example 2: to get “1010”, which represents the serial number “11”, you can put foot 2 and 4
of the toggle switch to the opposite of “ON” and foot 1 and 3 to “ON”.
Position Serial No. Position Serial No. Position Serial No. Position Serial No.
0000 1 0100 5 1000 9 1100 13
0001 2 0101 6 1001 10 1101 14
0010 3 0110 7 1010 11 1110 15
0011 4 0111 8 1011 12 1111 16
As shown in the following diagram:
机组编码:1
0000
机组编码:2 0001
机组编码:3 0010
机组编码:4 0011
机组编码:5
0100
机组编码:6 0101
机组编码:7 0110
机组编码:8 0111
机组编码:9
1000
机组编码:10
1001
机组编码:11
1010
机组编码:12
1011
机组编码:13
1100
机组编码:14
1101
机组编码:15
1110
机组编码:16
1111
Unit code:1
Unit code:2
Unit code:3
Unit code:4
Unit code:5
Unit code:6
Unit code:7
Unit code:8
Unit code:9
Unit code:10
Unit code:11
Unit code:12
Unit code:13
Unit code:14
Unit code:15
Unit code:16
Page 47
U-MATCH AIR CONDITIONERS CONTROL
46
5.4 Control Wiring Design
16 Units in Max
Week timer
Wired remote controller
LCD LCD LC
Wired remote controlle
Telephone wire box Telephone wire box Telephone wire box
Twisted-wire with crystal joint
Longest distance 1200m
Corresponding relation between code switch and sequence of unit (Note:Putting code switch to ON means 0.)
AC-L AC-N
Power supply
P S P S P S P S
0000 1 0010 5 0001 9 0011 13
1000 2 1010 6 1001 10 1011 14
0100 3 0110 7 0101 11 0111 15
1100 4 1110 8 1101 12 1111 16
Page 48
GREE COMMERCIAL AIR CONDITION U-MATCH AIR CONDITIONERS
47
INSTALLATION
Page 49
U-MATCH AIR CONDITIONERS INSTALLATION
48
INSTALLATION
1 INDOOR UNIT INSTALLATION
1.1 Installation of Duct Type
1.1.1 Before Installation
When the unit arrives, please check if any damage due to transport is existent. If any hurt is found on the
surface or inside, please declare to the transport company or the manufacturer in writing.
Upon receipt of the unit, the unit and accessories shall be checked in accordance with the packing list. Before
acceptance, it must be confirmed that the model is correct and the unit is in good shape and specification and
quantity of accessories are right.
Correct handling route and method shall be decided to prevent damage to the unit. For protecting the unit and
ensuring its safety, carrying the unit with its package is recommended. If such carrying method is difficult
under particular conditions, the canton shall not be removed to avoid looseness or falling during handling
Confirm the foundation is secure. When the unit is installed on the metal part of a building, electrical
insulation must be in compliance with relevant standards.
Confirm the installation position is away from storage zone of inflammable and explosive substances, or
otherwise leakage of inflammable and explosive substances may lead to explosion or a fire.
1.1.2 Installation Site
Ensure the top hanging piece has strong strength to withstand the weight of the unit.
The drainage pipe has convenient flow of water. There is no obstacle blocking the air intake and exhaust outlet, so as to ensure sound air circulation. The installation spaces required by the drawing must be ensured, so as to provide enough space for the
service and maintenance.
The installation site must be far away from heat source, leakage of inflammable gas or smoke.
The indoor unit is of ceiling mount (indoor unit is hidden inside the ceiling).
The indoor and outdoor units, the power cable and the connecting electrical lines must be at least 1 meter
from any TV set or radio. This is to avoid image interference or noise of the TV set or radio. (Even if the
distance is 1 meter, noise can also exist if there is strong electric wave.)
1.1.3 Caution for Installation
1
Ceiling installation mode is applicable to units indoors. The suspender on the ceiling must have sufficient
intensity to bear the weight of the unit.
2
Rubber cushion pads (thickness ≥20mm) and flexible rubber connectors must be used in the installation of
units to meet noise and vibration prevention requirements.
3Insert a M10 expansion bolt into the hole. Drive a nail into the bolt. Refer to the profile dimensions drawing
of the indoor unit for the distance between the holes. Refer to Figure 1 for the installation of the expansion
bolt
as Figure 1-1-1 shows.
Page 50
U-MATCH AIR CONDITIONERS INSTALLATION
49
Figure 1-1-1 Figure 1-1-2
Figure 1-1-3
4Install the hanger onto the indoor unit as Figure 1-1-2 and Figure 1-1-3 shows. 5Install the indoor unit at the ceiling as Figure 1-1-5shows.
Air Supply
Air Intake
Nut
Hanger
Screw
mm
I Enlargement
I
Figure 1-1-5
6Precautions for unfavorable installation:
The preparation of all pipes (connecting pipes and drainage pipes) and cables (connecting lines of wire
controller, indoor unit and outdoor unit) must be ready before the installation, so as to achieve smooth
installation.
Drill an opening on the ceiling. Maybe it is required to support the ceiling to ensure the evenness of it and
avoid the vibration of it. Consult with the user or a construction company for details.
In case the strength of ceiling is not enough, use angle iron sections to set up a beam support. Place the unit
at the beam and fix it.
Page 51
U-MATCH AIR CONDITIONERS INSTALLATION
50
7 Level detection of indoor unit
After installation of indoor unit, level detection for the complete unit must be done to ensure
levelness, as shown in Fig. 1-1-6.
Air Supply
Air Intake
i
Condensate Drainpipe
Level Instrument
Condensate Drainpipe
Enlarged View
As the inside of the unit is in the negative pressure status, it is required to set up a backwater elbow. The requirements is: A=B
P/10+20(mm)
P is the absolute pressure inside the unit.
The unit of the pressure is Pa.
Figure 1-1-6
1.1.4 Dimension Data
EHVXLWIRU$6'8$$6'8$$6'8$
Page 52
U-MATCH AIR CONDITIONERS INSTALLATION
51
Figure 1-1-7
suit for: ASDU-24A, ASDU-36A, ASDU-42A, ASDU-48A, ASDU-60A
Dimension Data Duct Unit
Model A B C D E F G H I J ASDU-09A ASDU-12A ASDU-18A
932 430 738 894 1012 736 738 125 207 266
ASDU-24A
1101 515 820 1159 1270 530 1002 160 235 268
ASDU-36A ASDU-42A A
SDU-48A
ASDU-60A
1015 788 820 1115 1226 815 979 160 261 330
290
1011
748
820
1115
1226
775
979
160
231 220
Unitmm
856
571
515
790
913
680
750
100
172
Page 53
U-MATCH AIR CONDITIONERS INSTALLATION
52
List of Accessories for Installation of Indoor Unit
Designation and shape Qty Description
Operation and installation instructions 1
Heat insulating material for large
connector
1 For air pipe connector of indoor unit
Heat insulating material for small
connector
1
For refrigerant pipe connector of indoor
unit
Heat insulation material for drain pipe 2
For packing condensate pipe and rubber
plug
Nut with washer M8 8 For fixing the hanging hook
Nut with washer M10 4
Nut and spring washer 4
Four sets, for hoisting the unit on the ceiling
Hanging hook 4 For hoisting the unit on the ceiling
Wire binding tie 4or 8
4 for a two-horsepower unit, 8 for other
unit.
Wire controller 1
Remote controller 1
Battery 2
Bellow
0
2 or 4
0 for a 2-powerhorse unit, 2 for a 2.5
3
horsepower unit
4 for a 45 horsepower
unit.
Power cable
1
2
2 for a 4
5 horsepower unit and 1 for other
unit.
Connecting cable
2
3
3 for a 45 horsepower unit and 2 for other
unit.
1.1.5 Installation Clearance Data
only for 24 and above models
Indoor Unit Figure 1-1-8
Nut with washer
Nut spring washer
Page 54
U-MATCH AIR CONDITIONERS INSTALLATION
53
1.1.6 Drain Piping Work
1Installation of Drainage Pipeline A drainage outlet is located at both the left and right sides of the indoor unit. After selecting one drainage
outlet, the other outlet shall be blocked by rubber plug. Bundle the blocked outlet with string to avoid
l1eakage, and also use thermal insulation materials to wrap the blocked outlet.
When shipped out from factory, both the Drainage outlets are blocked by rubber plugs. When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline at the side of
the unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When carrying out
connection, place the end of the PVC pipeline into the drainage hole. Use flexible drainage tube and tighten
it with thread loop. Never use adhesive to connect the drainage hole and the flexible drainage tube. (As
shown in Figure 1-1-9)
When the laid drainage pipe is used for multiple units, the common pipe shall be about 100mm lower than
the drainage outlet of each set of unit. A pipe with thicker wall shall be used for such purpose.
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-1-9
2
Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system.
During the test, check if the water correctly flows through the pipelines. Carefully observe the joints to
ensure that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating
the ceiling.
3
Matters of Attention
The joint of Drainage Pipeline must not have leakage.
The Drainage Pipeline shall be installed with an inclining angel of 510°, so as to facilitate the drainage of
condensate. The joints of the Drainage Pipeline must be covered by thermal insulation materials to avoid
generation of exterior condensate. (As shown in Figure 1-1-10)
Page 55
U-MATCH AIR CONDITIONERS INSTALLATION
54
Insulating layer of condensate pipe
Pipe cover
Figure 1-1-10
1.1.7 Installation of air pipes and openings
Caution:
The air supply pipe, the air intake pipe and the fresh air pipe must be covered with a layer of thermal
insulation, so as to avoid thermal leakage and condensation. Firstly apply liquid nail on the pipes, then attach
the thermal insulation cotton with a layer of tinfoil. Use the liquid nail cover to fix it. Lastly use tinfoil
adhesive tape to carefully seal the joints; other good thermal insulation materials can also be used.
The air supply pipes and the air intake pipes shall be fixed to the prefabricated boards of the ceiling by using
iron supports. The joints of the pipes must be sealed by glue so as to avoid leakage.
The design and installation of air pipes must be in conformity with the relevant state engineering criteria. The edge of the air intake pipe must be at least 150mm away from the wall. The air intake must be covered
with filter.
Silencing and shock absorption shall be considered in the design and installation of the air pipes. Additionally,
the noise source must be far away from where people stay. The air intake shall not be located above the place
where users stay (offices and rest places, etc.).
Page 56
U-MATCH AIR CONDITIONERS INSTALLATION
55
1
Installation of air supply duct
Installation of rectangular air duct, as shown in Figure 1-1-11
Return air
Return air
Supply air
Figure 1-1-11
No. Designation No. Designation
1 Hanger rod 5 Filter screen
2 Return duct 6 Main air supply duct
3 Canvas duct 7 Air outlet
4 Return air inlet
Installation of circular duct, as shown in Figure 1-1-12
Figure 1-1-12
Page 57
U-MATCH AIR CONDITIONERS INSTALLATION
56
No. Designation No. Designation
1 Hanger rod 6 Transition duct
2 Air return duct 7 Air supply duct
3 Canvas duct 8 Air diffuser
4 Return air shutter 9 Connector of air diffuser
5 Air outlet
Note:
The above two diagrams show how back return air inlets are installed. Lower return air inlets shall be used
according to actual installation demands. The installation method is similar to the back return air inlets. Among all
air outlets, at least one keeps open. If circular duct is in use, air shall be supplied to rooms through circular flexible
insulating duct. Air supply duct and return duct shall be heat insulated.
2Installation of fresh air duct (only limited to excessive pressure units with refrigerating output
over 6000W)
The fresh air battle, as shown in Figure 1-1-13(a), must be removed for mounting the fresh
air duct. If the fresh air duct is not in use, gaps around the battle shall be sealed by sponge.
Circular flanges are mounted for convenient connection of the fresh air duct, as shown in
Figure 1-1-14(b)
Ducts and circular flanges must be sealed and insulated sufficiently. Fresh air must be filtered air.
(a) (b)
Figure 1-1-13
3
Installation of air return duct
Square flanges at ex-factory shall be defaulted to installation at the back and the air return cover plate shall
be mounted at the lower, as shown in figure 1-1-14.
Figure 1-1-14
Round air duct
Page 58
U-MATCH AIR CONDITIONERS INSTALLATION
57
If lower air return is demanded, the square flange and the air return cover plate should be exchanged in their
respective position.
The air return duct shall be connected to the air return inlet on the indoor unit with rivets, and the other end
of the air return duct is connected to an air return window. To freely adjust the height, a section of canvas
duct can be fabricated and reinforced by
8# iron wires in the folding shape. A proper installation method
shall be selected by taking into overall consideration of building and maintenance conditions.
No. Designation No. Designation
1 Air return window (with filter screen) 4 Indoor unit
2 canvas duct 5 Air supply duct
3 Air return duct 6 Check grating
Figure 1-1-15
4Installation of circular air supply outlet
(indoor unit)
(indoor unit)
(round supply air outlet)
(Connect firmly after hole matched )
(round supply air outlet)
(Connect firmly after hole matched )
(Duct unit whose cooling capacity is 10000W-12000W)
(Installation sketch for round supply air outlet)
(Duct unit whose cooling capacity is 6500W-8000W)
(sponge)
(Sealing board)
Figure 1-1-16
Page 59
Page 60
U-MATCH AIR CONDITIONERS INSTALLATION
58
1.2 Installation of Ceiling Type
1.2.1 Before Installation
When the unit arrives, please check if any damage due to transport is existent. If any hurt is found on the
surface or inside, please declare to the transport company or the manufacturer in writing.
When the unit arrives, please check if any damage due to transport is existent. If any hurt is found on the
surface or inside, please declare to the transport company or the manufacturer in writing.
Correct handling route and method shall be decided to prevent damage to the unit. For protecting the unit and
ensuring its safety, carrying the unit with its package is recommended. If such carrying method is difficult
under particular conditions, the canton shall not be removed to avoid looseness or falling during handling.
Confirm the foundation is secure. When the unit is installed on the metal part of a building, electrical
insulation must be in compliance with relevant standards.
Confirm the installation position is away from storage zone of inflammable and explosive substances, or
otherwise leakage of inflammable and explosive substances may lead to explosion or a fire.
1.2.2 Installation Site
Such a place where cool air can be distributed throughout the room. Such a place where condensation water is easily drained out. Such a place that can handle the weight of indoor unit. Such a place which has easy access for maintenance. Such a place where is permitting easy connection with the outdoor unit. Such a place where is 1m or more away from other electric appliances such as television, audio device, etc. Avoid a location where there is heat source, high humidity or inflammable gas. Do not use the unit in the immediate surroundings of a laundry, a bath, a shower or a swimming pool.
Be sure that the installation conforms to the installation dimension diagram.
The space around the unit is adequate for ventilation
1.2.3 Caution for Installation
Adjust the distance from the unit to the ceiling slab beforehand (Refer to Figure 1-2-1). Fix the hanger bracket to the suspension bolt (Refer to Figure 1-2-2). Make sure that extended suspension bolt from the ceiling stays inside the arrowed position. Readjust the
hanger bracket when it is outside the arrowed position. (Refer to Figure 1-2-3)
Suspension bolt stays inside the cap of indoor unit .Never remove the cap. Lift the unit and slide forward unit
the dent. (Refer to Figure 1-2-4)
Screw tightly both hanger bracket setting bolts (M8) (Refer to Figure 1-2-2) Screw tightly both hanger bracket fixing bolts (M6) to prevent the movement of the indoor unit. (Refer to
Figure 1-2-2)
Adjust the height by turning the nut with a spanner. Insert the spanner from the hanger bracket opening.
(Refer to Figure 1-2-5)
Page 61
U-MATCH AIR CONDITIONERS INSTALLATION
59
Hanger bracket Figure 1-2-1 Figure 1-2-2
Figure 1-2-3 Hanger bracket Figure 1-2-4
In case of hanging:
It is possible to install using inward facing hanger bracket by not removing the brackets from the
indoor unit. (Refer to Figure 1-2-6) Be sure to use only the specified accessories and parts for
installation work.
Figure 1-2-5 Figure 1-2-6
Page 62
U-MATCH AIR CONDITIONERS INSTALLATION
60
1.2.4 Dimension Data
Figure 1-2-7
Unit: mm
Model A B C D E
ASFU-09A ASFU-12A ASFU-18A
836 238 745 695 260
ASFU-24A
1300 188 1202 600 260
ASFU-36A ASFU-42A ASFU-48A
1590 238 1491 695 260
Page 63
U-MATCH AIR CONDITIONERS INSTALLATION
61
1.2.5 Installation Clearance Data
Figure 1-2-8
1.2.6 Drain Piping Work
1Installation of Drainage Pipeline
A Drainage outlet is located at both the left and right sides of the indoor unit. After selecting one Drainage
outlet, the other outlet shall be blocked by rubber plug. Bundle the blocked outlet with string to avoid
leakage, and also use thermal insulation materials to wrap the blocked outlet.
When shipped out from factory, both the Drainage outlets are blocked by rubber plugs.
When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline at the side of
the unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When carrying out
connection, place the end of the PVC pipeline into the drainage hole. Use flexible drainage tube and tighten
it with thread loop. Never use adhesive to connect the drainage hole and the flexible drainage tube. (As
shown in Figure 1-2-9)
When the laid drainage pipe is used for multiple units, the common pipe shall be about 100mm lower than
the drainage outlet of each set of unit. A pipe with thicker wall shall be used for such purpose.
Page 64
U-MATCH AIR CONDITIONERS INSTALLATION
62
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-2-9
2Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system. During the test, check if the water correctly flows through the pipelines. Carefully observe the joints to
ensure that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating
the ceiling.
3Matters of Attention
The drain pipe outlet direction can be chosen from either the right rear or right.
The diameter of the drain pipe should be equal to or greater than the diameter of the connecting pipe. (Vinyl
tube; pipe size: 20mm; outer dimension: 26mm)
Keep the drain pipe short and incline downwards at a gradient of at least 1/100 to prevent air pockets. (Refer
to Figure 1-2-10)
Figure 1-2-10
No folding of drain hose inside the indoor unit. (Refer to Figure 1-2-11) Confirm that smooth drainage is achieved after the piping work. Pour 600 cc of water into the drain pan from
the air outlet for confirming drainage. (Refer to Figure 1-2-12)
Page 65
U-MATCH AIR CONDITIONERS INSTALLATION
63
Figure 1-2-11 Figure 1-2-12
1.3 Installation of Cassette Type
1.3.1 Before Installation
When the unit arrives, please check if any damage due to transport is existent. If any hurt is found on the
surface or inside, please declare to the transport company or the manufacturer in writing.
Upon receipt of the unit, the unit and accessories shall be checked in accordance with the packing list. Before
acceptance, it must be confirmed that the model is correct and the unit is in good shape and specification and
quantity of accessories are right.
Correct handling route and method shall be decided to prevent damage to the unit. For protecting the unit and
ensuring its safety, carrying the unit with its package is recommended. If such carrying method is difficult
under particular conditions, the canton shall not be removed to avoid looseness or falling during handling.
Confirm the foundation is secure. When the unit is installed on the metal part of a building, electrical
insulation must be in compliance with relevant standards.
Confirm the installation position is away from storage zone of inflammable and explosive substances, or
otherwise leakage of inflammable and explosive substances may lead to explosion or a fire.
1.3.2 Installation Site
Obstruct should put away from the intake or outlet vent of the indoor unit so that the airflow can be blown
though all the room.
Make sure that the installation had accord with the requirement of the schematic diagram of installation
spaces.
Select the place where can stand 4 times of the weight of the indoor unit and would not increase the
operating noise and oscillate.
The horizontally of the installation place should be guaranteed. Select the place where is easy to drain out the condensate water, and connect with outdoor unit. Make sure that there are enough space for care and maintenance. Make sure that the weight between the
indoor unit and ground is above 2300mm.
When installing the steeve bolt, check if the install place can stand the weight 4 times of the unit’s. If not,
reinforce before installation. (Refer to the install cardboard and find where should be reinforced) The
appliance shall not be installed in laundry.
Page 66
U-MATCH AIR CONDITIONERS INSTALLATION
64
Cautions:
There will be lots of lampblack and dust stick on the acentric, heat exchanger and water pump in dining room and
kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal operation of the
water pump.
The following treatment should be taken under this circumstance:
Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the indraft of
the lampblack by the air conditioner.
Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air
conditioner.
1.3.3 Caution for Installation
1Important notice:
To guarantee the good performance, the unit must be installed by professional personnel according with this
instruction.
Please contact the local Gree special nominated repair department before installation. Any malfunction
caused by the unit that is installed by the department that is not special nominated by Gree would not deal
with on time by the inconvenience of the business contact.
2Dimension of ceiling opening and location of the hoisting screw (M10)
(Hanging bolt position)
15-3/4"(400mm)
(□650mm)(Grille measurement)
□25-15/32"(650mm)
Hanging bolt position
23-27/32"(606mm)
2-19/32"(66mm)
17-5/16"(440mm)
ASCU-12A, ASCU-18A
Figure 1-3-1
Page 67
U-MATCH AIR CONDITIONERS INSTALLATION
65
pe piantergirefR
)4(X
ewcrng sistoiH
)
dsorwer scngitsi honeewte bspaG
0(68
)
t unirndoo I
0(84
)
gnng openiileiC
0(89
)
dsarboacefrud setarcoeD
950(
)
sdare bocafd surtearcoeD
0(95
)
ingpeng oilinCe
(0*89
)
itnuordon I
(840
)
sdo rwe scrngtisi honeetw bepsGa
0(78
ASCU-24A, ASCU-36A, ASCU-42A, ASCU-48A
Figure 1-3-2
The drilling of holes in the ceiling must be done by the professional personnel.
Figure 1-3-3
Cautions:
The dimension for the ceiling openings with * marks can be as large as 910mm. But the overlapping sections of the
ceiling and the decorated surface boards should be maintained at no less than 20mm.
Page 68
U-MATCH AIR CONDITIONERS INSTALLATION
66
3Main body of hoisting air conditioner
Bolt attachment
Bolt(attachment
[Fix the install cardboard]
Center of the ceiling
opening
Bolt of one of the angle of outlet pipe is fix on the angle of the drainage slot
Install cardboard
Nut (supplied at scene)
Gasket (attachment)
Tighten (double nuts)
Hoisting stand
[Fix the hoisting stand firmly]
Insert
Gasket anchor board (attachment)
[Fix the gasket firmly]
Water lever
Polyethylene pipe
Figure 1-3-4
The primary step for install the indoor unit.
When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper
and lower of the hoisting stand to fix it. The use of gasket anchor board can prevent gasket break
off.
Use install cardboard
Please refer to the install cardboard about the dimension of ceiling opening.
The central mark of the ceiling opening is marked on the install cardboard.
Install the install cardboard on the unit by bolt (3 piece), and fix the angle of the drainage
pipe at the outlet vent by bolt.
Adjust the unit to the suitable install place. Check if the unit is horizontal.
Inner drainage pump and bobber switch are included in the indoor unit, check if 4 angle of
every unit are horizontal by water lever. (If the unit is slant toward the opposite of the coagulate
water flow, there may be malfunction of the bobber switch and lead water drop.)
Backout the gasket anchor board used to prevent gasket break off and tighten the nut on it. Backout the install cardboard.
Cautions:
Please do tighten the nuts and bolts to prevent air conditioner break off.
Page 69
U-MATCH AIR CONDITIONERS INSTALLATION
67
1.3.4 Dimension Data
ASCU-12A, ASCU-18A
Figure 1-3-5-1
Item
Model
A B C D E F
ASCU-12A ASCU-18A
710 650 400 606 160 230
ASCU-24A, ASCU-36A, ASCU-42A, ASCU-48A
Figure 1-3-5-2
Page 70
U-MATCH AIR CONDITIONERS INSTALLATION
68
Figure 1-3-2
Item
Model
A B C D E F G
ASCU-24A
950 890 840 780 680 160 240
ASCU-36A ASCU-42A ASCU-48A
950 890 840 780 680 160 320
1.3.5 Installation Clearance Data
≥1500
≥1500
≥1800
H
>20
Unit:mm
Figure 1-3-6
Models H(mm)
ASCU-12A ASCU-18A
250
ASCU-24A
260
ASCU-36A ASCU-42A ASCU-48A
340
1.3.6 Drain Piping Work
1Installation of Drainage Pipeline When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline
at the side of the unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When
Page 71
U-MATCH AIR CONDITIONERS INSTALLATION
69
carrying out connection, place the end of the PVC pipeline into the drainage hole. Use
flexible drainage tube and tighten it with thread loop. Never use adhesive to connect the
drainage hole and the flexible drainage tube. (As shown in Figure 1-3-7)
When the laid drainage pipe is used for multiple units, the common pipe shall be about
100mm lower than the drainage outlet of each set of unit. A pipe with thicker wall shall be
used for such purpose.
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-3-7
2Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system. During the test, check if the water correctly flows through the pipelines. Carefully observe
the joints to ensure that there is no leakage. If the unit is to be installed in a new house, carry
out testing before decorating the ceiling.
3Matters of Attention The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The
diameter of polythene pipe: Outer diameter 25mm Surface thickness ≥1.5mm)
Drain hose should be short and drooping gradient should at less 1/100 to prevent the
formation of air bubble.
If drain hose cannot has enough drooping gradient, drain raising pipe should be added. To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m.
(As shown in Figure 1-3-8)
1-1.5m
(Correct) 1/100 or more gradient
× (wrong)
Figure 1-3-8
The install height of the drain raising pipe should less than 280mm. The drain raising pipe should form a right angle with the unit, and distance to unit should not
Page 72
U-MATCH AIR CONDITIONERS INSTALLATION
70
beyond 300mm. (As shown in Figure 1-3-9)
Celling
1-1.5m
Hanger bracket
Below
1120mm
Above 280mm
200mm
Drainage raising pipe
Drainage hose (attachment)
Cassette type unit
with in 300mm
Clamp(attachment)
Figure 1-3-9
The slant gradient of the attached drain hose should be within 75mm so that the drain hole
doesn’t has to endure the unnecessary outside force. (As shown in Figure 1-3-10)
Drain hose(attachment)
.
Below75mm
Below500mm
Figure 1-3-10
Please install the drain hose according to the following process if several drain hoses join
together. (As shown in Figure 1-3-11)
T-tie in join drain hose
Above100mm
.
The specs of the selected join drain hose should fits the running capacity of the unit.
Figure 1-3-11
Check the smoothness of drain after installation. Check the drain state by immiting 600cc water slowly from the outlet vent or test hole. (As
shown in Figure 1-3-12)
Check the drain in the state of refrigerating after installation of the electric circuit.
Page 73
U-MATCH AIR CONDITIONERS INSTALLATION
71
Test hole cover
Drain hose
< Immiting water from the rest hole>
Above100mm
.
Drain vent for repair use (plastic stopper is included) (drain the water in waterspout by this outlet vent)
[Way of immiting]
Test hole
<Immiting water from the outlet vent terminal>
Plastic water pot (The length of the pipe should be about 100mm.)
Figure 1-3-12
1.3.7 Installation of panel
1Set the panel to the indoor unit body by matching the position of the swing flap motor of the
decoration panel to the piping position of the panel to the piping position of the indoor unit as
shown in Figure 1-3-13.
Figure 1-3-13
Page 74
U-MATCH AIR CONDITIONERS INSTALLATION
72
Hang the latch, which is located on the opposite side of the swing flap motor on the panel,
temporarily to the book of the indoor unit. (2 Positions)
Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be
careful not to let the swing motor lead wire get caught in the sealing material.)
Screw all 4 hexagon head screws located right beneath the latches in approximately
15mm.(Panel will rise)
Adjust the panel by turning it to the arrowed direction in Fig.4 so that the ceiling opening is
completely covered.
Tighten the screws until the thickness of the sealing material between the panel and the
indoor unit body is reduced to 5~8 mm.
2Precautions: Improper screwing of the screws may cause the troubles shown in Figure 1-3-14.
Figure 1-3-14
If gap is still left between the ceiling and the panel after screwing the screws, readjust the
height of the indoor unit body (Refer to Figure 1-3-15)
Figure 1-3-15
After fixing be sure no gap left between the ceiling and the panel 3Wiring of the decoration panel. Connect the joints for swing flap motor lead wire (at 2 places) installed on the panel (Refer to
Figure 1-3-16)
Page 75
U-MATCH AIR CONDITIONERS INSTALLATION
73
Figure 1-3-16
2 OUTDOOR UNIT INSTALLATION
2.1 Before Installation
When the unit arrives, please check if any damage due to transport is existent. If any hurt is
found on the surface or inside, please declare to the transport company or the manufacturer in
writing.
Upon receipt of the unit, the unit and accessories shall be checked in accordance with the
packing list. Before acceptance, it must be confirmed that the model is correct and the unit is
in good shape and specification and quantity of accessories are right.
Correct handling route and method shall be decided to prevent damage to the unit. For
protecting the unit and ensuring its safety, carrying the unit with its package is recommended.
If such carrying method is difficult under particular conditions, the canton shall not be
removed to avoid looseness or falling during handling.
Confirm the foundation is secure. When the unit is installed on the metal part of a building,
electrical insulation must be in compliance with relevant standards.
Confirm the installation position is away from storage zone of inflammable and explosive
substances, or otherwise leakage of inflammable and explosive substances may lead to
explosion or a fire.
2.2 Installation Site
To ensure the unit in proper function, selection of installation location must be in accordance
with following principles:
Outdoor unit shall be installed so that the air discharged by outdoor unit will not r eturn and
that sufficient space for repair shall be provided around the unit.
The installation site must have good ventilation, so that the outdoor unit can take in and
exhaust enough air. Ensure that there is no obstacle for the air intake and exhaust of the
outdoor unit. If there is any obstacle blocking the air intake or exhaust, remove it.
Place of installation shall be strong enough to support the weight of outdoor unit, and it shall
be able to insulate noise and prevent vibration. Ensure that the wind and noise from the unit
will not affect your neighbors.
Avoid direct sunshine over the unit. It is better to set up a sun shield as the protection.
Page 76
U-MATCH AIR CONDITIONERS INSTALLATION
74
Place of installation must be able to drain the rainwater and defrosting water. Place of installation must ensure the unit will not be buried under snow or subject to the
influence of rubbish or oil fog.
The installation site must be at a place where the air exhaust outlet does not face strong wind. Outdoor unit should be hoisted through indicated hoisting holes. During hoisting, special
attention must be paid to the unit to prevent collision into its sheet metal parts to avoid rust.
Rubber cushion or spring shock absorber shall be used for outdoor unit to avoid excessive
noise and vibration.
Rubber cushion or spring shock absorber shall be used for outdoor unit to avoid excessive
noise and vibration.
Only professional personnel are allowed for unit installation.
2.3 Caution for Installation
Installation of outdoor unit shall not allow discharged air to return, and sufficient
maintenance space shall be left around the unit.
Installation position must be well-ventilated, enabling the unit to absorb and discharge
enough air. Inlet and outlet must be free of obstruction. Any obstacle blocking air going in
and out must be removed.
When outdoor unit is mounted on the secure floor such as concrete, bolts and nuts in M10
can used for fixing the unit. Uprightness or levelness of the unit must be ensured.
Outdoor unit should be hoisted through indicated hoisting holes. During hoisting, special
attention must be paid to the unit to prevent collision into its sheet metal parts to avoid rust.
Rubber cushion or spring shock absorber shall be used for outdoor unit to avoid excessive
noise and vibration. Uprightness or levelness must be ensured.
In installation of drain pipe, the connector of the drain pipe shall be inserted into a drain hole
on the chassis of the outdoor unit. And then a drain pipe shall be connected to the drain
connector. (If the drain connector is used, installing height of the outdoor unit shall be at least
5cm).
If pipe is put through wall, a wall pipe must be used. Installation dimension must be in line with requirements by the instructions. Outdoor unit
must be fixed on the mounting position.
Only professional personnel are allowed for unit installation
Page 77
U-MATCH AIR CONDITIONERS INSTALLATION
75
2.4 Dimension Data
B
Figure 2-4-1
Unit
mm
Model A B C D E
ASGE-09A
ASGE-12A
ASGE-18A
820 320 540 540 286
ASGE-24A 1018 412 695 572 378
ASGE-36A
1018 412 840 572 378
ASGE-42A
ASGE-48A
ASGE-60A
1032 412 1250 572 378
Page 78
U-MATCH AIR CONDITIONERS INSTALLATION
76
2.5 Installation Clearance Data
Figure 2-5-1
3 REFRIGERATION PIPING WORK
3.1 Refrigeration Piping Work Procedures
1Connecting pipelines Connection pipes must be in accordance with the following requirements: the basic principle
--- keeping dry, clean and no leakage inside.
Figure 3-1-1
Align copper pipe flare with the center of screwed connector and tighten fully the nut of the
flare by hand.
Page 79
U-MATCH AIR CONDITIONERS INSTALLATION
77
Tighten the flare nut with a torque spanner until the torque spanner makes a click, as shown
in Figure 3-1-1. Moment needed for tightening a nut is shown in Tab. 3-1-1.
Figure 3-1-2
Form 3-1-1 the tightening torque needed for tightening nut
Pipe diameter Tightening torque
1/4
15-30 (N·m)
3/8
35-40 (N·m)
5/8
60-65 (N·m)
1/2
45-50 (N·m)
3/4 70-75 N·m)
Curvature of piping shall not be too small, or otherwise piping may be broken. So installation
personnel should use a pipe bender to bend pipes.
Upward or longitudinal welding joint method is usually applied to the welding of pipelines.
The welding method that mouth of pipe is downward (face-down welding) should be avoided
as far as possible, because such method is prone to welding defects and even would cause
leakage, as shown in Figure 3-1-3.
Figure 3-1-3
Uninsulated connecting pipes and connectors should be packed with sponge and tied with
plastic adhesive tapes.
Page 80
U-MATCH AIR CONDITIONERS INSTALLATION
78
2Vacuum-pumping and leak detection
Dismantle the bonnet of refrigerant valve and air valve. Align with the center of piping and adequately tighten nuts of connecting pipes by hand Tighten the nuts with a spanner. Remove the one way valve cap of air valve. Unscrew the spool of refrigerant valve for 1/4 turn with a socket head wrench, and at the
same time push up the spool of air valve with a screwdriver to let air give off.
Air exhaust continues for 15 seconds until coolant gas appears, immediately shut off one way
valve and tighten the valve cap.
Totally open the spool of refrigerant valve and air value (as shown in Figure 3-1-4)
Figure 3-1-4
Tighten the valve caps and use soapy water or a leak detector to check any leakage on indoor
unit, outdoor unit and connection parts of pipes.
Caution
If conditions are allowed, a vacuum pump shall be used for drawing off air inside the system at a
valve. Method for creation of vacuum by using a vacuum pump is as follows:
Take out the nut cover of the inlet for refrigerant. Connect the tube of the vacuum watch with the vacuum pump, having the low-pressure end
linking to the inlet for refrigerant. (As shown in Figure 3-1-5)
Page 81
U-MATCH AIR CONDITIONERS INSTALLATION
79
Figure 3-1-5
Starting the vacuum pump, when the indicator turns to-1 bar, closing the low pressure handle
and stopping vacuumize. Keep for 15 minutes, ensuring the pressure of the vacuum watch
remains.
Take out the valve cover of the gas valve together with the liquid valve. Loosing the cord of liquid valve until the pressure rise to 0 bar. Dismantle the tube from the cover of the inlet for refrigerant then, tighten the cover. Loose the valve cord of the gas valve as well as the liquid valve entirely. Tighten the valve cover of the gas valve and liquid valve so as to check whether leakage
occurred.
3) Installation of Protective Layer of Connecting Pipe
To avoid generation of condensate on the connecting pipe and avoid leakage, the big pipe and
the small pipe of the connecting pipe must be covered by thermal insulation materials, be
bundled by adhesive tape, and be isolated from air.
The joint connecting to the indoor unit must be wrapped by thermal insulation material.
There shall be no gap between the connecting pipe joint and the wall of the indoor unit. Refer
to Figure 3-1-6.
Figure 3-1-6 Figure 3-1-7
Page 82
U-MATCH AIR CONDITIONERS INSTALLATION
80
Use adhesive tape to bundle the connecting pipe and the cables together. To prevent
condensate from overflowing out from the drainage pipe, separate the drainage pipe firm the
connecting pipe and the cables.
Use thermal insulation tape to wrap the pipes from the bottom of the outdoor unit until the
upper end of the pipe where the pipe enters the wall. When wrapping thermal insulation tape,
the later circle of tape must cover half of the front circle of tape (Figure 3-1-7).
Wrapped pipe must be fixed to wall using pipe clamps.
Caution:
After the pipes are wrapped by protective materials, never bend the pipes to form very small
angle, and otherwise the pipes may crack or break.
Do not wrap the protective tape too tight, otherwise the efficiency of thermal insulation may
be decreased. Ensure that the condensate drainage flexible tube is separate from the bundled
pipes.
After the protective work is completed and the pipes are wrapped, use seal material to block
the hole in the wall, so as to prevent rain and wind from entering the room.
3.2 Caution in Connecting Pipes
Arrangement of connecting pipes shall be performed according to sit conditions with reference to
the following principles.
Try to shorten the length of connecting pipes, within 5m for the better. Try to reduce height difference between indoor unit and outdoor unit. Try to reduce number of joint bends of connecting pipes. If the length of connecting pipes is more than 20m, adequacy of lubricant of the system must
be checked; and if necessary, add more lubricant properly.
Filling amount of refrigerant in the system is matched to a 7m connecting pipe. If the
connecting pipe is needed to lengthen, appropriate amount of refrigerant should be added.
How much refrigerant should be added for every meter extension refers to the following table.
Allowable maximum pipe length is 30m.
If height difference between indoor unit and outdoor unit exceeds 10m in installation of air
conditioner, an oil return bend must be mounted at an interval of 6m.
If heights of indoor unit and outdoor unit are different, pipes should be laid out with reference
to Figure 3-2-1.
Refrigerant pipe (thin)
- - - - - - Air pipe (large)
Page 83
U-MATCH AIR CONDITIONERS INSTALLATION
81
Figure 3-2-1
3.3 Specification of Connection Pipe
External Diameter
Maximum
Length
of Connection
Pipe
Maximum Difference
in Height between
Outdoor and Indoor
Unit
Additional
Charge
of
Refrigerant
Model
Gas Pipe Liquid Pipe
(m) (m) (g/m)
ASGE-09A
φ3/8
ASGE-12A
ASGE-18A
φ1/2
φ1/4
20 15 15
ASGE-24A
φ5/8
φ3/8
30 15 60
ASGE-36A
ASGE-42A
ASGE-48A
ASGE-60A
φ3/4
φ1/2
50 30 120
Refrigerant pipes
Air pipe
Outdoor unit
Oil loop of air pipe
Oil loop of air pipe
An oil loop is arranged at an
interval of 4-6m.
indoor unit
Page 84
U-MATCH AIR CONDITIONERS INSTALLATION
82
4 ELECTRIC WIRING WORK
4.1 Wiring Principle
4.1.1General
Perform wiring of the power supply in conformance with the regulations of the local electric
company.
For the control wires connecting indoor units, and between indoor and outdoor units, use of
double-core shield wires is recommended to prevent noise trouble.
Be sure to set the earth leakage breaker and the switches to the power supply section of the
indoor unit.
Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for
each outdoor unit.
Store wiring system for control and refrigerant piping system in the same line. Arrange the cables so that the electric wires do not come to contact with high-temperature
part of the refrigerant pipe; otherwise coating melts and an accident may be caused.
Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish. Installation should be conducted by National Wiring Regulation. The rated voltage and exclusive power supply must be adopted for the air conditioners. The power cable should be reliable and fixed, in order to avoid the wiring terminal be
suffered from force. And do not drag the power cable forcibly.
The wire diameter of power cable should be large enough, if power cable and connection
wire be damaged, it should be replaced by the exclusive cable.
All electric installation must be done by professional personnel according to local law,
regulation and this manual.
It should be reliably earthed, and it should be connected to the special earth device, the
installation work should be operated by the professional.
The creepage protect switch and air switch must be installed. Air switch should have the thermal dropout and magnetic dropout function, in order to avoid
the short circuit and overload.
The on spot connection should refer to the circuit diagram, which is stuck on the unit body. The unit should be reliably earth, if it is improperly earthed that may cause electric shock or
fire.
Air conditioner is the “I” class electric appliance, thus please do conduct reliable grounding
measure.
The yellow-green two-color wiring of air conditioner is grounding wire and cannot be used
for other purposes. It cannot be cut off and be fixed by screw, otherwise it would cause
electric shock.
The user must offer the reliable grounding terminal. Please don’t connect the grounding wire
to the following places:
Page 85
U-MATCH AIR CONDITIONERS INSTALLATION
83
① Water pipe; ② Gas pipe; ③ Blowing pipe; ④ Other places that professional personnel consider them unreliable.
4.1.2 Connection of electric wires with the terminal
1Caution
Before installing the electrical equipment, please pay attention to the following matters which
have been specially pointed out by our designers:
Check to see if the power supply used conforms to the rated power supply specified on the
nameplate.
The capacity of the power supply must be large enough. The section area of fitting line in the
room shall be larger than 2.5mm2.
The lines must be installed by professional personnel. An electricity leakage protection switch and an air switch with gap between electrode heads
larger than 3 mm shall be installed in the fixed line.
2Connection of single wire
Use wire stripper to strip the insulation layer (25mm long) from the end of the single wire. Remove the screw at the terminal board of the air-conditioning unit. User pliers to bend the end of the single wire so that a loop matching the screw size is formed. Put the screw through the loop of the single wire and fix the loop at the terminal board. 3Connection of multiple twisted wires Use wire stripper to strip the insulation layer (10mm long) from the end of the multiple
twisted wires.
Remove the screw at the terminal board of the air-conditioning unit. Use crimping pliers to connect a terminal (matching the size of the screw) at the end of the
multiple twisted wires.
Put the screw through the terminal of the multiple twisted wires and fix the terminal at the
terminal board.
War nin g:
If the power supply flexible line or the signal line of the equipment is damaged, only use
special flexible line to replace it.
Before connecting lines, read the voltages of the relevant parts on the nameplate. Then carry
out line connection according to the schematic diagram.
Page 86
U-MATCH AIR CONDITIONERS INSTALLATION
84
The air-conditioning unit shall have special power supply line which shall be equipped with
electricity leakage switch and air switch, so as to deal with overload conditions.
The air-conditioning unit must have grounding to avoid hazard owing to insulation failure. All fitting lines must use crimp terminals or single wire. If multiple twisted wires are
connected to terminal board, arc may arise.
All line connections must conform to the schematic diagram of lines. Wrong connection may
cause abnormal operation or damage of the air-conditioning unit.
Do not let any cable contact the refrigerant pipe, the compressor and moving parts such as
fan.
Do not change the internal line connections inside the air-conditioning unit. The
manufacturer shall not be liable for any loss or abnormal operation arising from wrong line
connections.
4.1.3 Power Cable Connection
1) Air-conditioning unit with single-phase power supply
Remove the front-side panel of the outdoor unit. Pass the cable though rubber ring. Connect the power supply cable to the “L, N” terminals and the grounding screw. Use cable fastener to bundle and fix the cable.
2) Air-conditioning unit with 3-phase power supply
Remove the front-side panel of the outdoor unit. Attach rubber ring to the cable-cross hole of the outdoor unit. Pass the cable though rubber ring. Connect the power cable to the terminal and earthing screws marked “L1, L2, L3 & N”. Use cable fastener to bundle and fix the cable.
Caution:
For air-conditioner with auxiliary heater, it is required to connect the power cable to the “L1,
L2 L3”terminals and the grounding screw.
4.1.4 Connection of Signal Line of Wire Controller
Caution:
Take great care when carrying out the following connections, so as to avoid malfunction of
the air-conditioning unit because of electromagnetic interference.
The signal line of the wire controller must be separated from the power line and the
connecting line between the indoor unit and the outdoor unit.
◆ In case the unit is installed in a place vulnerable by electromagnetic interference, it is
better to use shielded cable or double-twisted cable as the signal line of the wire controller.
Open the cover of the electric box of the indoor unit. Pull the signal cable of the wire controller through the rubber ring.
Page 87
U-MATCH AIR CONDITIONERS INSTALLATION
85
Plug the signal line of the wire controller onto the 4-bit pin socket at the circuit board of the
indoor unit.
Use cable fastener to bundle and fix the signal cable of the wire controller.
4.1.5Connection of wires Remove the board on the right side of outdoor unit and put through the wire running hole on
the outdoor unit and put on a rubber ring.
Remove wire holders and connect the power cord to the terminal and fix it. Secure the power connecting cord and signal control cable with wire holders and then connect
corresponding adapters.
Check if wires are fixed properly. Fit on the front side board.
Page 88
U-MATCH AIR CONDITIONERS INSTALLATION
86
4.2 Electric Wiring Design
4.2.1 ASGE-09A WK+ASDU-09A, ASGE-12A WK+ASDU-12A, ASGE-18A WK+ASDU-18A, ASGE-24A WK+ASDU-24A,
ASGE-36A WK+ASDU-36A, ASGE-42A WK+ASDU-42A, ASGE-48A WK+ASDU-48A, ASGE-60A WK+ASDU-60A
Power220-240V ~50HZ Power220-240V ~50HZ
Power380-415V 3N~50HZ Power220-240V ~50HZ
Page 89
U-MATCH AIR CONDITIONERS INSTALLATION
87
4.2.2 ASGE-09A WK+ASFU-09A, ASGE-12A WK+ASFU-12A,
ASGE-18A WK+ASFU-18A, ASGE-24A WK+ ASFU-24A,
ASGE-36A WK+ASFU-36A, ASGE-42A WK+ASFU-42A,
ASGE-48A WK+ASFU-48A, ASGE-60A WK+ASFU-60A
Power380-415V 3N~50HZ Power220-240V ~50HZ
Power220-240V ~50HZ Power220-240V ~50HZ
Page 90
U-MATCH AIR CONDITIONERS INSTALLATION
88
4.2.3 ASGE-09A WK+ASCU-09A, ASGE-12A WK+ ASCU-12A,
ASGE-18A WK+ASCU-18A, ASGE-24A WK+ ASCU-24A,
ASGE-36A WK+ASCU-36A, ASGE-42A WK+ASCU-42A,
ASGE-48A WK+ASCU-48A, ASGE-60A WK+ASCU-60A
Power220-240V ~50HZ
Power380-415V 3N~50HZ Power220-240V ~50HZ
Power220-240V ~50HZ Power220-240V ~50HZ
Page 91
Model: ASFU-60A
Page 92
4.3.1 Outdoor
Capability of Air Swith
Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm2) (mm2)
ASGE-09A WK
220-240, 1, 50
16 2,5 2.5
ASGE-12A WK
220-240, 1, 50
16 2,5 2.5
ASGE-18A WK
220-240, 1, 50
20 4.0 4.0
ASGE-24A WK
220-240, 1, 50
25 4.0 4.0
ASGE-36A WK
380-415, 3, 50
16 2,5 2.5
ASGE-42A WK
380-415, 3, 50
20 4.0 4.0
ASGE-48A WK
380-415, 3, 50
25 4.0 4.0
ASGE-60A WK
380-415, 3, 50
25 4.0 4.0
• Duct Type
Capability of Air Swith
Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm2) (mm2)
ASDU-09A
220-240, 1, 50
6 1.0 1.0
ASDU-12A
220-240, 1, 50
6 1.0 1.0
ASDU-18A
220-240, 1, 50
6 1.0 1.0
ASDU-24A
220-240, 1, 50
6 1.0 1.0
ASDU-36A
220-240, 1, 50
10 1.5 1.5
ASDU-42A
220-240, 1, 50
10 1.5 1.5
ASDU-48A
220-240, 1, 50
10 1.5 1.5
ASDU-60A
220-240, 1, 50
10 1.5 1.5
Ceiling Type
Capability of Air Swith
Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm2) (mm2)
ASFU-09A
220-240, 1, 50
6 1.0 1.0
ASFU-12A
220-240, 1, 50
6 1.0 1.0
ASFU-18A
220-240, 1, 50
6 1.0 1.0
ASFU-24A
220-240, 1, 50
6 1.0 1.0
ASFU-36A
220-240, 1, 50
6 1.0 1.0
ASFU-42A
220-240, 1, 50
6 1.0 1.0
ASFU-48A
220-240, 1, 50
6 1.0 1.0
Cassette Type
Capability of Air Swith
Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm2) (mm2)
ASCU-12A
220-240, 1, 50
6 1.0 1.0
ASCU-18A
220-240, 1, 50
6 1.0 1.0
ASCU-24A
220-240, 1, 50
6 1.0 1.0
ASCU-36A
220-240, 1, 50
6 1.0 1.0
ASCU-42A
220-240, 1, 50
6 1.0 1.0
ASCU-48A
220-240, 1, 50
6 1.0 1.0
Model
Power Supply
(V, Ph, Hz)
4.3.2 Indoor Unit
4.3 Specification of Power Supply Wire and Air Switch
Model
Power Supply
(V, Ph, Hz)
Model
Power Supply
(V, Ph, Hz)
Model
Power Supply
(V, Ph, Hz)
Page 93
GREE COMMERCIAL AIR CONDITION U-MATCH AIR CONDITIONERS
91
MAINTENANCE
Page 94
U-MATCH AIR CONDITIONERS MAINTENANCE
92
MAINTENANCE
1 TROUBLE TABLE
Trouble
Code
Trouble Name
Origin of
Trouble Signal
Control Description
E0 Pump Failure Pump
If water full protection continues for 2 hours and fails to restore,
it is believed that the water pump is at fault and all loads are shut
off and fail to restore automatically.
E1
Compressor High
Pressure Protection
High voltage switch
When high voltage protection is detected for continuous 3
seconds, all loads are shut off (except for the four way valve), all
buttons and remote control signals except for power-on or
power-off are shielded and fail to restore automatically, the unit
should be powered off and on, or failure should be removed after
power supply is restored.
E2
Indoor Frost-Proof
Protection
Evaporator of indoor
unit
Thermal bulb
When the unit has been running for refrigeration or
dehumidification for a period of time and evaporator thermal
bulb is detected to be lower than -2
, the unit will report a fault
and stops the compressor and the outdoor unit. The unit will
begin to operate after temperature is
10 and the compressor
keeps outage for 3 minutes.
E3
Compressor Low
Pressure Protection
Low voltage switch
When the unit is started or at standby (detection will begin 3
minutes after the compressor is started up) and detected
b
reakdown of the low voltage switch for continuous 30 seconds,
a fault is reported. The unit can be restored automatically after
the first 2 reported faults within 30 minutes. The third reported
fault and so on can not be restored automatically.
E4
Compressor Exhaust High
Temperature Protection
Discharge thermal
bulb
After the compressor is started, if discharge temperature is
detected to be more than or equal to 130 degree for continuous
30 seconds, E4 will be displayed, all loads (except for the four
way valve) will be shut off, the compressor will stop for 3
minutes and the complete system will restore after discharge
temperature is lower than 90 degree. If such fault is reported for
successive three times, the protection can not be restored itself.
E5
Compressor
Overheat
Compressor
After the compressor is started, if the overload switch of the
compressor is detected to shut off, the fault is reported. All loads
(except for the four way valve) are shut off, the fault is displayed,
and the compressor will stop for 3 minutes. If the fault is
removed, the compressor can be restarted to run. If successive
three compressor overload protection faults are detected within
Page 95
U-MATCH AIR CONDITIONERS MAINTENANCE
93
Trouble
Code
Trouble Name
Origin of
Trouble Signal
Control Description
30 minutes, the unit can not be restored itself and the buzzer will
give out an alarm. Push the ON/OFF button to shut off the unit.
And then push ON/OFF button again, if high voltage protection
disappears, operation will restore, or otherwise, the fault is
displayed.
E6
Communications
Failure
Communication
When outdoor unit is energized and fails to receive data of indoor
unit within 30 seconds, an indoor unit communication fault is
reported. The compressor and the outdoor unit will be shut off,
and the four way valve will be stopped 2 minutes after the
compressor outage in heating state.
If indoor unit fails to receive information of outdoor unit, a
communication fault is reported. The indoor unit is shut off and
an indicator is twinkling. If the display board fails to receive
information of outdoor unit, a communication fault is determined
and displayed and the unit does not actuate. After communication
b
ecomes normal, the system can restore to the previous running
state itself.
E8
Indoor Fan
Protection
Indoor unit
If fan overload protection is detected for continuous 3 seconds,
relevant compressor and fan shall be shut off immediately and a
fault code E8 is displayed, and at the same time, the buzzer gives
out an alarm. Push the ON/OFF key, if the fault disappears, clear
the fault display and push the ON/OFF key for restarting the
system.
E9
Full Water
Protection
Liquid level switch
Water full is detected for continuous 8 seconds after the system is
powered on, the water full protection is initiated and the indicator
is twinkling (or E9 is displayed). Under refrigeration and
dehumidification mode, the outdoor fan and the compressor are
shut off and the indoor fan stops after 1 minute delay; under
heating mode, he outdoor fan and the compressor are shut off, the
four way valve keeps at the previous status, and the indoor fan
stops after 1 minute delay; under air supply mode, the load o
f
indoor unit remains.
F0
Failure of Indoor Room
Sensor at Air Intake
Indoor environment
Thermal bulb
Open-circuit or short-circuit of the indoor environment thermal
b
ulb is detected for continuous 5 seconds, indoor environment
temperature will be set compulsively at 24 degree, the system
does not take any measure, and only the indicator is twinkling or
fault code F0 is displayed. After the fault is removed, the system
can restore operation by itself. Under air supply mode, only the
Page 96
U-MATCH AIR CONDITIONERS MAINTENANCE
94
Trouble
Code
Trouble Name
Origin of
Trouble Signal
Control Description
fault is displayed and the indoor fan is running normally. The
fault display disappears when the fault is removed.
F1
Failure of Evaporator
Temp. Sensor
Indoor evaporator
thermal bulb
Open-circuit or short-circuit of evaporator thermal bulb is
detected for continuous 5 seconds, under refrigeration and
dehumidification mode, the system will be shut off; and under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F1 is displayed. The
system can restore by itself and display fault elimination after the
fault is removed. Under air supply mode, only the fault is
displayed and the indoor unit is running normally. The fault
display disappears when the fault is removed.
F2
Failure of Condenser
Temp. Sensor
Outdoor condenser
thermal bulb
Open-circuit or short-circuit of condenser thermal bulb is
detected for continuous 5 seconds, under refrigeration and
dehumidification mode, the system will be shut off; and under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F2 is displayed. The
system can restore by itself and display fault elimination after the
fault is removed. Under air supply mode, only the fault is
displayed and the indoor unit is running normally. The fault
display disappears when the fault is removed.
For other types of refrigeration machines except for air duct
machine, condenser thermal bulb is not detected.
F3
Failure of Outdoor
Ambient Sensor
Outdoor environment
thermal bulb
Open-circuit or short-circuit of outdoor environment thermal
b
ulb is detected for continuous 5 seconds, under refrigeration and
dehumidification mode, the system will be shut off; and under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F3 is displayed. The
system can restore by itself and display fault elimination after the
fault is removed. Under air supply mode, only the fault is
displayed and the indoor unit is running normally. The fault
display disappears when the fault is removed.
F4
Failure of Exhaust
Temp. Sensor
Discharge thermal
bulb
After the compressor is started, open-circuit of discharge thermal
bulb is detected for continuous 5 seconds. Under refrigeration
and dehumidification mode, all loads will be shut off. Under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F4 is displayed. And
the buzzer gives out an alarm. After the fault is removed, the
system will restore by itself and clear the fault code.
Page 97
U-MATCH AIR CONDITIONERS MAINTENANCE
95
Trouble
Code
Trouble Name
Origin of
Trouble Signal
Control Description
If discharge thermal bulb is short circuited, under refrigeration
and dehumidification mode, all loads will be shut off. Under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F4 is displayed. And
the buzzer gives out an alarm. After the fault is removed, the
system will restore by itself and clear the fault code.
F5
Failure of Indoor
Room Sensor at
Wire Controller
Line controller
Open-circuit or short-circuit of line controller thermal bulb is
detected for continuous 5 seconds, indoor environment
temperature will be set compulsively at 24 degree, the system
does not take any measure, and only the indicator is twinkling or
fault code F0 is displayed. After the fault is removed, the system
can restore operation by itself. Under air supply mode, only the
fault is displayed and the indoor fan is running normally. The
fault display disappears when the fault is removed.
2Cassette Type Indoor Unit’s Error Indicating
LED No error Flash times
every two seconds
Error description
once the indoor ambient temperature sensor error twice the evaporator temperature sensor error three times the condenser temperature senor error four times the outdoor ambient temperature senor error
yellow: Timing
indicating lamp
It goes on as per the
set time, And it
flashes when the
temperature sensor
error occurs
five times the discharge air temperature sensor error
twice Defrosting
three times high pressure protection
four times the low pressure protection
five times Overload protection
green
Compressor
indicating lamp
It goes on/off as the
compressor is turned
on/off. And it
flashes when
defrosting or the
compressor error
occurs
six times Discharge high temperature protection
twice the water overflow protection three times the anti-freezing error
red Running
indicating lamp
It goes on/off as the
unit is turned on/off,
And it flashes when
the indoor unit error
occurs
four times Anti-high temperature protection
Page 98
MAINTENANCE
102
3 WIRING DIADRAM
3.1 Wiring Diagram-Outdoor Units
1ǃASGE-09A WK
WITH FUNCTION OF LOW TEMP. COOLING:
WITHOUT FUNCTION OF LOW TEMP. COOLING:
ASGE-09A
Page 99
MAINTENANCE
103
2ǃASGE-12A WK
WITH FUNCTION OF LOW TEMP. COOLING:
ASGE-12A: WITHOUT FUNCTION OF LOW TEMP. COOLING:
Page 100
MAINTENANCE
104
3ǃASGE-18A WK
WITH FUNCTION OF LOW TEMP. COOLING:
ASGE-18A: WITHOUT FUNCTION OF LOW TEMP. COOLING:
Loading...