Sinclair ASF-60AN, ASC-60AN Service Manual

Page 1
SERVICE MANUAL
ASF-60AN, ASC-60AN
ON/OFF SERIES
Page 2
Page 3
External Appearance
External Appearance
Indoor Units
Super-slim 4-way Cassette
Ceiling & floor type
Outdoor Units
Double fan outdoor unit
1
Page 4
Features
Features
High quality coils:
The coil is constructed of advanced inner grooved copper tube and aluminum fins.
Anti-rust, 500 hours salt spray test.
Low operation sound level: Well-known stable and quiet running fan motor.
Well-known compressor.
Compact design: Smaller dimension and larger stuffing capacity.
Universal outdoor unit design.
Optional air outlet grille: plastic type and wire type.
Wire type Plastic type Plastic type
Optional low temperature cooling module.
R410A environment friendly refrigerant.
2
Page 5
ASC-60AN
V- Ph-Hz 220~240-1-50
V- Ph-Hz 380~415-3-50
Capacity Btu/h 51000
Input
W 6030
Current
A 10,41
EER
W/W 2,48
Capacity Btu/h 58000
Input
W 6410
Current
A 11,07
COP
W/W 2,65
Model WZDK124-38G
Qty 1
Input w 124(Output)
Capacitor uF /
Speed(hi/mi/lo) r/min 770/610/540
m
3
/h
2100/1800/1600
dB(A) 55/50/47
/
Dimension (W x Dx H)(body) mm 840x840x287
Packing (W x Dx H)(body) mm 900x900x292
Dimension (W x Dx H)(panel) mm 950x950x55
Packing (W x Dx H)(panel) mm 1035x1035x90
Net/Gross weight(body) kg 28.3/32.5
Net/Gross weight(panel) kg 5/8
MPa 4.2/1.5
mm ODĭ32
Refrigerant piping Liquid side/ Gas side mm ĭ9.52/ĭ19(3/8"/3/4")
Standard
Remote-RG51C/E
17~30
Cooling
17~32
Heating
0~30
Controller
Room temperature
Operation temperature
Cooling
Heating
Indoor fan motor
Indoor air flow (Hi/Med/Lo)
Sound level (sound pressure)
Remarks:1.The above design and specifications are subject to change
Throttle type
Indoor unit
Design pressure
Drainage water pipe dia.
Model
Power supply (outdoor )
Power supply (indoor )
Page 6
ASF-60AN
V- Ph-Hz
220~240-1-50
V- Ph-Hz
380~415-3-50
Capacity Btu/h
52000
Input
W
5370
Current
A
9.27
EER
W/W
2.84
Capacity Btu/h
57100
Input
W
5400
Current
A
9.32
COP
W/W
3.1
Model WZDK90-38GS-W
Qty 2
Input W 90(Output)
Capacitor uF /
Speed(Hi/Med/Lo) r/min
1320/1200/1120
Number of rows
3
Tube pitch(a)x row pitch(b) mm 21x13.37
Fin spacing mm 1,3
Fin type Hydrophilic aluminium
Tube outside dia.and type mm Ɏ7,Inner grooved tube
Coil length x height x width mm 1300x294x40.11
Number of circuits
8
m3/h
2550/2150/1850
dB(A)
55/52/50
/
Dimension (WxDxH) mm 1650x675x235
Packing (WxDxH) mm 1725x755x313
Net/Gross weight kg
40/46
MPa
4.2/1.5
mm ODĭ25
Refrigerant piping Liquid side/Gas side mm(inch) ĭ9.52/ĭ19(3/8"/3/4")
Standard Remote-RG51Q1/BGE
17~30
Cooling
17~32
Heating
0~30
Remarks:1.The above design and specifications are subject to change
Throttle type
Indoor unit
Design pressure
Drainage water pipe diameter
Controller
Room temperature
Operation temperature
Cooling
Heating
Indoor fan motor
Indoor coil
Indoor air flow(Hi/Med/Lo)
Indoor noise level (sound pressure)(Hi/Med/Lo)
Model
Power supply (outdoor )
Power supply (indoor )
Page 7
ASF-60AN, ASC-60AN
OUTDOOR UNIT
V-ph-Hz 380~415-3-50
W 7000
A 19
Model C-SBN453H8D
Type Scroll
Brand Sanyo
Capacity Btu/h 55957
Input W 5750
Rated current(RLA) A 9,77
Locked rotor Amp(LRA) A 67
Thermal protector position Internal
Capacitor ȝF /
Refrigerant oil ml 1700
Model YDK90-6D
Qty 2
Input W 142/127
Capacitor ȝF 5UF/450V
Speed r/min 880/810
Number of rows
1,6
Tube pitch(a)* row pitch(b) mm 22x19.05
Fin spacing mm 1.5
Fin type Hydrophilic aluminium
Tube outside dia.and type mm Ɏ7.94,inner grooved tube
Coil length * height * width mm 995×1320×19.05+593x1320x19.05
Number of circuits
10
m3/h
7500
dB(A) 63
Capillary
Dimension(WxDxH) mm 938x392x1369
Packing(WxDxH) mm 1095x495x1505
Net/Gross weight kg 111.1/125.4
Type R410A
Charged volume kg 3.5
MPa 4.2/1.5
Liquid side/ Gas side mm(inch) ĭ9.52/ĭ19(3/8"/3/4")
Max. pipe length m 50
Max. difference in level m 25
Cooling
18~43
Heating
-724
Remarks:1.Theabovedesignandspecificationsaresubjecttochangewithoutpriornoticeforproductimprovement.
Ambient temperature
Outdoor noise level (sound pressure)
Throttle type
Outdoor unit
Refrigerant type/Quantity
Design pressure
Refrigerant piping
Outdoor fan motor
Outdoor coil
Outdoor air flow (Max.)
Model
Power supply
Max. input consumption
Max. input current
Compressor
Page 8
Indoor Units
Indoor Units
Super-slim Cassette Type ..................................................4
Ceiling & Floor Type ...........................................................17
3
Page 9
Super-slim Cassette Type
Super-slim Cassette Type
1.Features ......................................................................5
2.Dimensions .................................................................9
3.Service Space ............................................................. 10
4.Wiring Diagrams .........................................................11
5.Electric Characteristics ............................................. 12
6.Sound Levels .............................................................. 13
7.Accessories ................................................................14
8.The Specification of Power ....................................... 15
9.Field Wiring ................................................................. 16
4
Page 10
Features
1. Features
1.1 Overview
¾ Compact design, super slim body size, less space requiring in installation ¾ Each louver can be separately controlled, more comfort air blowing is possible. ¾ Auto-lifting panel design, more convenient to clean and maintain the filter. (optional)
Old Cassette New Slim Cassette Reduction
60K 840*300*840 840*287*840 4%Ļ
1.2
Fresh air intake function
¾ Fresh air fulfills air quality more healthy and comfortable. ¾ Ventilation motor is optional to increase the effect of fresh air.
5
Page 11
Features
1.3 Optional ionizer generator
¾ Ionizer generator is optional to get refreshing air to your room.
¾ Ionizer can be switched on or off by remote controller.
When pressing the Clean Air button on the remote controller, Ionizer will work and the indicator light on display board will shine.
New air-intake
IIoonniizzeerr ggeenneerraattoorr
ccoonnnneeccttoorr
VVeennttiillaattiioonn mmoottoorr
ccoonnnneeccttoorr
6
Page 12
Features
1.4 External air duct design
¾ Reserve external air duct, more flexible for the air supply.
1.5
Built-in draining pump
¾ Due to the improvement of structure, more convenient to repair or replace the draining pump.
¾ Built-in draining pump to make sure condensed water drain out reliably.
Draining Pump
7
Page 13
Features
1.6 Terminals for alarm lamp and long-distance on-off controller connection are standard
¾ Reserve terminals for the connection of alarm lamp and long-distance on-off controller, more human
control.
1.7 Optional touch screen wired controller
¾ Touch screen wired controller is optional, with error code indication function. Better
man-machine conversation interface.
¾ Undated structure design, 4-way wire layout design, no raised part at backside, more convenient to
place the wires and install the device.
Alarm lamp
Long-distance on-off controller
8
Page 14
Dimensions
2. Dimensions
Model A H
ASC-60AN
287 >317
9
Page 15
Service Space
3. Service Space
>1000mm
>1000mm
> 1000mm
> 1000mm
10
Page 16
Wiring Diagrams
4. Wiring Diagrams
ASC-60AN
11
Page 17
Field Wiring
5. Electric Characteristics
Model
Indoor Unit Power Supply
Hz Voltage Min Max MFA
ASC-60AN 50 220-240V 198V 254V 16
Note:
MFA: Max. Fuse Amps. (A)
12
Page 18
Sound Levels
6. Sound Levels
P
Microphone
Model
Noise level dB(A)
H M L
ASC-60AN 55 50 47
13
Page 19
Field Wiring
7. Accessories
INSTALLATION FITTINGS
Name Shape Quantity
Installation paper board
1
Bolt M5 4
Tubing & Fittings Soundproof / insulation sheath
2
Drainpipe Fittings
Out-let pipe
1
Out-let pipe sheath
1
Out-let pipe clasp 1
Remote controller & Its Frame
Remote controller & Its Frame
1
Remote controller holder 1
Mounting screw(ST2.9×10-C-H) 2
Remote controller manual 1
Alkaline dry batteries (AM4)
2
Others
Owner's manual
1
Installation manual 1
Network wires
1
Installation accessory (The product you have might not be provided the following accessories
Expansible hook
4
Installation hook
4
Orifice
1
14
Page 20
The Specification of Power
8. The Specification of Power
Model
ASC-60AN
INDOOR UNIT POWER
Phase 1-phase
Frequency and Voltage 220-240V, 50Hz
POWER WIRING (mm2) 3×1.0
Circuit Breaker/ Fuse (A) 20/16
OUTDOOR UNIT POWER
Phase 3-phase
Frequency and Voltage 380-415V, 50Hz
POWER WIRING (mm2) 5×2.5
Circuit Breaker/ Fuse (A) 25/20
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
3×0.2
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
15
Page 21
Field Wiring
9. Field Wiring
ASC-60AN
16
Page 22
Ceiling & Floor Type
Ceiling & Floor Type
1. Features ...........................................................................18
2. Dimensions ......................................................................19
3. Service Space ..................................................................20
4. Wiring Diagrams ............................................................. 21
5. Electric Characteristics .................................................. 22
6. Sound Levels ...................................................................22
7. Accessories ..................................................................... 23
8. The Specification of Power ............................................23
9. Field Wiring .....................................................................24
17
Page 23
Features
1. Features
1.1. New design, more modern and elegant appearance.
1.2. Convenient installation
--The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow
--It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting.
1.3. Two direction auto swing (vertical & horizontal) and wide angle air flow,
--Air flow directional control minimizes the air resistance and produces wilder air flow to vertical direction.
--The range of horizontal air discharge is widened which secures wider air flow distribution to provide more comfortable air circulation no matter where the unit is set up
1.4. Three level fan speed, more humanism design, meets different air-supply requirement.
1.5. New foam drain pan with plastic-spraying inner surface
1.6. Easy operation.
1.7. Remote control and optional wired control method.
18
Page 24
Dimensions
2. Dimensions
Capacity (Btu/h)
A B C D E
ASF-60AN 1650 675 235 1565 220
19
Page 25
Service Space
3. Service Space
20
Page 26
Wiring Diagrams
4. Wiring Diagrams
ASF-60AN
21
Page 27
Electric Characteristics
5. Electric Characteristics
Model
Indoor Units Power Supply
Hz Voltage Min. Max. MFA
ASF-60AN 50 220-240V 198V 254V 16
Remark:
MFA: Max. Fuse Amps. (A)
6. Sound Levels
Microphone
1m
1m
Air outlet side
1.5m
1m
Microphone
Ceiling Floor
Model
Noise level dB(A)
H M L
ASF-60AN
56
53 51
22
Page 28
Accessories
7. Accessories
Remote controller & Its holder
1. Remote controller
1
2. Remote controller holder 1
3. Mounting screw (ST2.9×10-C-H) 2
4. Alkaline dry batteries (AM4) 2
Others
5. Owner's manual
1
6. Installation manual
1
7. Remote controller manual
1
8. The Specification of Power
Model
ASF-60AN
INDOOR UNIT POWER
Phase 1-phase
Frequency and Voltage 220-240V, 50Hz
POWER WIRING (mm2) 3×1.0
Circuit Breaker/ Fuse (A) 20/16
OUTDOOR UNIT POWER
Phase 3-phase
Frequency and Voltage 380-415V, 50Hz
POWER WIRING (mm2) 5×2.5
Circuit Breaker/ Fuse (A) 25/20
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
3×0.2
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
23
Page 29
Field Wiring
9. Field Wiring
ASF-60AN
24
Page 30
Outdoor Units
Outdoor Units
1. Dimensions ................................................................................................26
2. Service Space ............................................................................................27
3. Piping Diagrams ........................................................................................28
4. Wiring Diagrams ........................................................................................29
5. Electric Characteristics .............................................................................30
6. Operation Limits ........................................................................................31
7. Sound Levels .............................................................................................32
25
Page 31
Dimensions
1. Dimensions
Model
Unitφmm
A B C D E F H
938 633.5 404 448 370 392 1369
ASF-60AN, ASC-60AN
26
Page 32
Service Space
2. Service Space
More than 60cm
More than 30cm
More than 60cm
More than 200cm
Air inlet
Air inlet
More than 30cm
Air outlet
(Wall or obstacle)
Maintain channel
27
Page 33
Piping Diagrams
3. Piping Diagrams
ASF-60AN, ASC-60AN
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
Compressor
2-WAY VALVE
3-WAY VALVE
4-WAY VALVE
COOLING
HEATING
T2 Evaporator temp. sensor
T1 Room temp. sensor
T3 Condenser temp. sensor
Accumulator
High pressure switch
T4 Ambient temp. sensor
Low pressure
switch
INDOOR OUTDOOR
CHECK VALVE (Heating Model only)
CAPILIARY TUBE
28
Page 34
Wiring Diagrams
4. Wiring Diagrams
ASF-60AN, ASC-60AN
29
Page 35
Electric Characteristics
5. Electric Characteristics
Model
Outdoor Unit
Hz Voltage Min. Max.
ASF-60AN,ASC-60AN 50 380~415V 342V 435V
30
Page 36
Operation Limits
6. Operation Limits
Temperature
Mode
Cooling operation Heating operation
Room temperature 17đЊ32đ
Outdoor temperature
18đЊ43đ
-7đЊ24đ
    







Indoor temperature(ć WB)
Outdoor temperature(ć DB)
STD
Cooling

 







With Low
Ambient
Cooling System
   



Indoor temperature(ć WB)
Outdoor temperature(ć DB)
Heating







STD
31
Page 37
Sound Levels
7. Sound Levels
Microphone
Outdoor Unit
H
1.0m
Note: H= 0.5 × height of outdoor unit
Model Noise level dB(A)
ASF-60AN,ASC-60AN 63
32
Page 38
Installation
Installation
1. Installation Procedure ...............................................................................34
2. Location selection .....................................................................................35
3. Indoor unit installation ..............................................................................36
4. Outdoor unit installation (Side Discharge Unit) ......................................43
5. Refrigerant pipe installation .....................................................................44
6. Drainage pipe installation .........................................................................45
7. Vacuum Drying and Leakage Checking ..................................................49
8. Additional refrigerant charge ...................................................................50
9. Engineering of insulation ......................................................................... 51
10. Engineering of electrical wiring .............................................................52
11. Test operation .........................................................................................52
33
Page 39
Insulation Work
1. Installation Procedure
Vacuum drying and leakage checking
Additional refrigerant charge
Insulation the joint part of refrigerant pipe
Wiring connection and electric safety checking
Test operation
Refrigerant pipe
installation and insulation
Drainage pipe installation
and insulation
Indoor unit installation
location selection
Outdoor unit installation
location selection
Indoor unit installation Outdoor unit installation
Refrigerant pipe
installation and insulation
Drainage pipe installation
and insulation
34
Page 40
Location selection
2. Location selection
2.1 Indoor unit location selection
¾ The place shall easily support the indoor unit’s weight. ¾ The place can ensure the indoor unit installation and inspection. ¾ The place can ensure the indoor unit horizontally installed. ¾ The place shall allow easy water drainage. ¾ The place shall easily connect with the outdoor unit. ¾ The place where air circulation in the room should be good. ¾ There should not be any heat source or steam near the unit. ¾ There should not be any oil gas near the unit ¾ There should not be any corrosive gas near the unit ¾ There should not be any salty air neat the unit ¾ There should not be strong electromagnetic wave near the unit ¾ There should not be inflammable materials or gas near the unit ¾ There should not be strong voltage vibration.
2.2 Outdoor unit location selection
¾ The place shall easily support the outdoor unit’s weight. ¾ Locate the outdoor unit as close to indoor unit as possible ¾ The piping length and height drop can not exceed the allowable value. ¾ The place where the noise, vibration and outlet air do not disturb the neighbors. ¾ There is enough room for installation and maintenance. ¾ The air outlet and the air inlet are not impeded, and not face the strong wind. ¾ It is easy to install the connecting pipes and cables. ¾ There is no danger of fire due to leakage of inflammable gas. ¾ It should be a dry and well ventilation place ¾ The support should be flat and horizontal ¾ Do not install the outdoor unit in a dirty or severely polluted place, so as to avoid blockage of the heat
exchanger in the outdoor unit.
¾ If is built over the unit to prevent direct sunlight, rain exposure, direct strong wend, snow and other scraps
accumulation, make sure that heat radiation from the condenser is not restricted.
More than 30cm
More than 60cm
More than 200cm
More than 30cm
More than 60cm
(Service space
Fe
n
c
e
o
r
o
b
s
t
a
c
l
e
s
35
Page 41
Indoor unit installation
3.3 Super-slim cassette indoor unit installation
3.3.1 Service space for indoor unit
Model A H Remark
ASC-60AN
287 >317 R410A Cooling / Cooling & Heating
3.3.2 Bolt pitch
3.3.3 Install the pendant bolt
Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings).
3. Indoor unit inst
36
Page 42
Insulation Work
3.3.4 Install the main body
Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body. Use a leveling instrument to make sure the levelness of the main body is within f1e.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even. The body's lower part should sink into the ceiling for 10~12 mm. In general, L is half of the screw length of the installation hook.
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.
37
Page 43
Indoor unit installation
3.3.5 Install the panel
Remove the grille
Remove the 4 corner covers.
Hang the panel to the hooks on the mainbody. If the panel is with auto-lift grille, please watch the ropes lifing the grille, DO NOT make the ropes enwinded or blocked.
38
Page 44
Insulation Work
Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate water.
Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively.
Install the 4 corner covers back.
Note: The panel shall be installed after the wiring connected.
39
Page 45
Indoor unit installation
3.4 Ceiling & floor indoor unit installation
3.4.1 Service space for indoor unit
3.4.2 Bolt pitch
ķ Ceiling installation
Capacity (Btu/h)
D E
ASF-60AN 1565 220
ĸ Wall-mounted installation
40
Page 46
Insulation Work
3.4.3 Install the pendant bolt
ķ Ceiling installation Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings).
ĸ Wall-mounted installation Install the tapping screws onto the wall.(Refer to picture below)
3.4.4 Install the main body
ķ Ceiling installation (The only installation method for the unit with drain pump) Remove the side board and the grille.
41
Page 47
Indoor unit installation
Locate the hanging arm on the hanging screw bolt. Prepare the mounting bolts on the unit.
Put the side panels and grilles back.
ĸ Wall-mounted installation Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit. (The bottom of body can touch with floor or suspended, but the body must install vertically.)
42
Page 48
Insulation Work
4. Outdoor unit installation (Side Discharge Unit)
4.1 Service space for outdoor unit
4.2 Bolt pitch
Model B C D
ASF-60AN, ASC-60AN 633.5 404 448
4.3 Install the Unit
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling. Never hold the inlet of the outdoor unit to prevent it from deforming.
43
Page 49
Refrigerant pipe installation
Do not touch the fan with hands or other objects. Do not lean it more than 45, and do not lay it sidelong. Make concrete foundation according to the specifications of the outdoor units. Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind.
5. Refrigerant pipe installation
5.1 Maximum pipe length and height drop
Considering the allowable pipe length and height drop to decide the installation position. Make sure the distance and height drop between indoor and outdoor unit not exceeded the date in the following table.
Model Max. Length Max. Elevation
45,000Btu/h~60,000Btu/h 50m 25m
5.2 The procedure of connecting pipes
5.2.1 Choose the pipe size according to the specification table.
5.2.2 Confirm the cross way of the pipes.
5.2.3 Measure the necessary pipe length.
5.2.4 Cut the selected pipe with pipe cutter
¾ Make the section flat and smooth.
90
Lean
Crude
Burr
o
5.2.5 Insulate the copper pipe
¾ Before test operation, the joint parts should not be heat insulated.
5.2.6 Flare the pipe
¾ Insert a flare nut into the pipe before flaring the pipe ¾ According to the following table to flare the pipe
44
Page 50
Insulation Work
Pipe diameter
Flare dimension A (mm)
Flare shape
Min Max
1/4" (6.35) 8.3 8.7
R0.4~0.8
A
4
5
°
90e
4
-
+
3/8" (9.52) 12.0 12.4
1/2" (12.7) 15.4 15.8
5/8" (15.9) 18.6 19.1
3/4" (19) 22.9 23.3
¾ After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or
exogenous impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pipes so that it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
5.2.10 Set the wall conduit
5.2.11 Set the supporter for the pipe.
5.2.12 Locate the pipe and fix it by supporter
¾ For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m. ¾ For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners.
¾ Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the
bellmouthing, and too small torque may cause leakage. Refer the following table for different pipe connection.
Pipe Diameter
Torque Sketch map
(kgf.cm) (N.cm)
1/4" (6.35) 144~176 1420~1720
3/8" (9.52) 333~407 3270~3990
1/2" (12.7) 504~616 4950~6030
5/8" (15.9) 630~770 6180~7540
3/4" (19) 990~1210 9270~11860
6. Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
¾ Ensure at least 1/100 slope of the drainage pipe ¾ Adopt suitable pipe diameter ¾ Adopt nearby condensate water discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeline route and elevation
¾ Before installing condensate water pipeline, determine its route and elevation to avoid intersection with
other pipelines and ensure slope is straight.
45
Page 51
Drainage pipe installation
6.2.2 Drainage pipe selection
¾ The drainage pipe diameter shall not small than the drain hose of indoor unit ¾ According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu) Water flowrate (l/h)
12 2.4
18 4
24 6
30 7
36 8
42 10
48 12
60 14
According to the above table to calculate the total water flowrate for the confluence pipe selection. For horizontal drainage pipe (The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
Slope 1/50 Slope 1/100
PVC25 20 39 27
For branch pipe
PVC32 25 70 50
PVC40 31 125 88
Could be used for confluence pipe
PVC50 40 247 175
PVC63 51 473 334
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe (The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h) Remark
PVC25 20 220
For branch pipe
PVC32 25 410
PVC40 31 730
Could be used for confluence pipe
PVC50 40 1440
PVC63 51 2760
PVC75 67 5710
PVC90 77 8280
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
6.2.3 Individual design of drainage pipe system
¾ The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
¾ The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
¾ In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
¾
Each vertical pipe shall be equipped with not less than two hangers.
¾ Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
46
Page 52
Insulation Work
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
¾ The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
¾ The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
¾
If the indoor unit has high extra static pressure and without water pump to elevate the condensate water, such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow or blow water phenomena.
Indoorunit
More than 50mm
More than 25mm
Plug
Water storage pipe
6.2.7 Lifting pipe setting of indoor unit with water pump
¾ The length of lifting pipe should not exceed the pump head of indoor unit water pump.
Pump head of big four way cassette: 750mm Pump head of compact four way cassette: 500mm
¾ The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong
operation of water level switch.
¾ Refer the following picture for installation reference.
47
Page 53
Drainage pipe installation
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipeİ150mm
B: Lift height
İthe pump head of water pump
Down incline pipe
B
6.2.8 Blowhole setting
¾ For the concentrated drainage pipe system, there should design a blowhole at the highest point of main
pipe to ensure the condensate water discharge smoothly.
¾ The air outlet shall face down to prevent dirt entering pipe. ¾ Each indoor unit of the system should be installed it. ¾ The installation should be considering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
6.2.9 The end of drainage pipe shall not contact with ground directly.
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage pump.
48
Page 54
Insulation Work
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe whether the water can discharge through the transparent hard pipe at drainage outlet.
(In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by turning down power supply and eliminating accumulated water.
Note: Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering parts.
7. Vacuum Drying and Leakage Checking
7.1 Purpose of vacuum drying
¾ Eliminating moisture in system to prevent the phenomena of ice-blockage and copper oxidation.
Ice-blockage shall cause abnormal operation of system, while copper oxide shall damage compressor.
¾ Eliminating the non-condensable gas (air) in system to prevent the components oxidizing, pressure
fluctuation and bad heat exchange during the operation of system.
7.2 Selection of vacuum pump
¾ The ultimate vacuum degree of vacuum pump shall be -756mmHg or above. ¾ Precision of vacuum pump shall reach 0.02mmHg or above.
7.3 Operation procedure for vacuum drying
Due to different construction environment, two kinds of vacuum drying ways could be chosen, namely ordinary vacuum drying and special vacuum drying.
7.3.1 Ordinary vacuum drying
49
Page 55
Additional refrigerant charge
1. When conduct first vacuum drying, connect pressure gauge to the infusing mouth of gas pipe and liquid
pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached
-755mmHg).
2 If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates
that there is moisture or leakage in pipeline system and need to go on with drying for half an hour.
3 If the vacuum degree of vacuum pump still could not reach -755mmHg after 1.5 hours of drying, check
whether there is leakage source.
4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that there is moisture or leak source.
7.3.2 Special vacuum drying
The special vacuum drying method shall be adopted when:
1. Finding moisture during flushing refrigerant pipe.
2. Conducting construction on rainy day, because rain water might penetrated into pipeline.
3. Construction period is long, and rain water might penetrated into pipeline.
4. Rain water might penetrate into pipeline during construction.
Procedures of special vacuum drying are as follows:
1. Vacuum drying for 1 hour.
2. Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could achieve the effect of vacuum drying, but this method could not achieve drying thoroughly when there is too much moisture. Therefore, special attention shall be drawn to prevent the entering of water and the formation of condensate water.
3. Vacuum drying again for half an hour.
If the pressure reached -755mmHg, start to pressure leakage test. If it cannot reached the value, repeat vacuum damage and vacuum drying again for 1 hour.
4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that there is moisture or leak source.
8. Additional refrigerant charge
¾ After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
¾ The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following formula to calculate the charge volume.
Diameter of liquid pipe (mm) ĭ6.35 ĭ9.52 ĭ12.7
Formula V=11g/m×(L-5) V=30g/m×(L-5) V=60g/m×(L-5)
V:
Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
¾ Refrigerant may only be charged after performed the vacuum drying process. ¾ Always use gloves and glasses to protect your hands and eyes during the charge work. ¾
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
¾ Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and manifold gauge should be exhausted.
¾ After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
50
Page 56
Insulation Work
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe ĺ insulation (except joint section) ĺ flare the pipe ĺ piping layout and connectionĺ vacuum drying ĺ insulate the joint parts
9.1.2 Purpose of refrigerant pipe insulation
¾ During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwise it shall debase the performance of unit and burn compressor.
¾ Gas pipe temperature is very low during cooling. If insulation is not enough, it shall form dew and cause
leakage.
¾ Temperature of gas pipe is very high (generally 50-100ć) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
¾
The burning performance should over 120ć
¾ According to the local law to choose insulation materials ¾ The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thicker accordingly.
9.1.4 Installation highlights of insulation construction
¾
Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner.
Liquid pipe Insulation meterial
Gas pipe
¾ The insulation material at the joint pipe shall be 5~10cm longer than the gap of the insulation material. ¾ The insulation material at the joint pipe shall be inserted into the gap of the insulation material. ¾ The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly.
¾ The linking part should be use glue to paste together ¾ Be sure not bind the insulation material over-tight, it may extrude out the air in the material to cause bad
insulation and cause easy aging of the material.
9.2 Insulation of drainage pipe
9.2.1 Operational procedure of refrigerant pipe insulation
Select the suitable pipe ĺ insulation (except joint section) ĺ piping layout and connectionĺ drainage testĺ insulate the joint parts
9.2.2 Purpose of drainage pipe insulation
The temperature of condensate drainage water is very low. If insulation is not enough, it shall form dew and cause leakage to damage the house decoration.
51
Page 57
Engineering of electrical wiring
9.2.3 Insulation material selection for drainage pipe
¾
The insulation material should be flame retardant material, the flame retardancy of the material should
be selected according to the local law.
¾ Thickness of insulation layer is usually above 10mm. ¾ Use specific glue to paste the seam of insulation material, and then bind with adhesive tape. The width
of tape shall not be less than 5cm. Make sure it is firm and avoid dew.
9.2.4 Installation and highlights of insulation construction
¾
The single pipe should be insulated before connecting to another pipe, the joint part should be insulated
after the drainage test.
¾ There should be no insulation gap between the insulation material.
10. Engineering of electrical wiring
10.1 Highlights of electrical wiring installation
¾ All field wiring construction should be finished by qualified electrician. ¾ Air conditioning equipment should be grounded according to the local electrical regulations. ¾ Current leakage protection switch should be installed. ¾ Do not connect the power wire to the terminal of signal wire. ¾ When power wire is parallel with signal wire, put wires to their own wire tube and remain at least 300mm
gap.
¾ According to table in indoor part named “the specification of the power” to choose the wiring, make sure
the selected wiring not small than the date showing in the table.
¾ Select different colors for different wire according to relevant regulations. ¾ Do not use metal wire tube at the place with acid or alkali corrosion, adopt plastic wire tube to replace it. ¾ There must be not wire connect joint in the wire tube If joint is a must, set a connection box at the place. ¾ The wiring with different voltage should not be in one wire tube. ¾ Ensure that the color of the wires of outdoor and the terminal No. are same as those of indoor unit
respectively.
11. Test operation
11.1 The test operation must be carried out after the entire installation has been
completed.
11.2 Please confirm the following points before the test operation.
¾ The indoor unit and outdoor unit are installed properly. ¾ Tubing and wiring are correctly completed. ¾ The refrigerant pipe system is leakage-checked. ¾ The drainage is unimpeded. ¾ The ground wiring is connected correctly. ¾ The length of the tubing and the added stow capacity of the refrigerant have been recorded. ¾ The power voltage fits the rated voltage of the air conditioner. ¾ There is no obstacle at the outlet and inlet of the outdoor and indoor units. ¾ The gas-side and liquid-side stop values are both opened. ¾ The air conditioner is pre-heated by turning on the power.
11.3 Test operation
Set the air conditioner under the mode of "COOLING" by remote controller, and check the following points.
Indoor unit
¾
Whether the switch on the remote controller works well.
¾ Whether the buttons on the remote controller works well. ¾ Whether the air flow louver moves normally. ¾ Whether the room temperature is adjusted well.
52
Page 58
Insulation Work
¾ Whether the indicator lights normally. ¾ Whether the temporary buttons works well. ¾ Whether the drainage is normal. ¾ Whether there is vibration or abnormal noise during operation.
Outdoor unit
¾
Whether there is vibration or abnormal noise during operation.
¾ Whether the generated wind, noise, or condensed of by the air conditioner have influenced your
neighborhood.
¾ Whether any of the refrigerant is leaked.
 
53
Page 59
Electrical Control
Electrical Control System
1. Electrical Control Function ...................................................................55
2. Troubleshooting ....................................................................................64
3. Controller ............................................................................................. 79
54
Page 60
Electrical Control Function
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature
T2: Coil temperature of evaporator
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 Time delay at restart for compressor.
1.2.2 Sensor protection at open circuit and breaking disconnection.
1.2.3 Phase check function
If the phase sequence is detected wrong or lack of 1 or 2 phase, the unit won’t start and there is error code
displayed on outdoor PCB.
1.2.4 Over-current protection
When compressor is running, if the current is over twice of the rated for 3 seconds, the compressor will stop and an error code will be displayed on the outdoor PCB. If the current becomes normal, the indoor sends signal to the outdoor, the outdoor will display normally.
1.2.5 Fan Speed is out of control
When Indoor fan speed keeps too low (less than 300RPM) for 50s, the unit will stop and the LED will display
the failure.
55
Page 61
Electrical Control Function
1.3 Operation Modes and Functions
1.3.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/(med)/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
27
T1
26
High
Low
24
Medium
1.3.2 Cooling Mode
1.3.2.1 Compressor running rules
Once the compressor starts up, it will follow the below rules:
When indoor room temp.T1 is lower than Ts, the compressor and outdoor fan will shut off. When T1 is higher
than Ts+1, the compressor and outdoor fan will start up.
Ts+1
T1
Ts
On
Off
1.3.2.2 Outdoor fan running rules
For double-fan outdoor units:
Fan(above): The outdoor fan runs all the time.
Fan(below):
33
T3
On
Off
30
56
Page 62
Electrical Control Function
1.3.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto.
The auto fan:
4
T1-Ts
3
High
Low
1
Medium
1.3.2.4 Low evaporator coil temperature T2 protection
For Duct:
TE6
T2
On
Off
TE5
When the evaporator coil temp.T2 keeps lower than TE5 for Time0, the compressor and outdoor fan will shut
off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
For Ceiling & Floor, super-slim cassette type:
AC will enter T2 protection if any of the following conditions is satisfied.
Condition 1:
TE6
T2
On
Off
TE5
When the evaporator coil temp.T2 keeps lower than TE5 for 30 minutes, the compressor and outdoor fan will
shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
57
Page 63
Electrical Control Function
Condition 2:
TE6
T2
On
Off
TE5-2
When the evaporator coil temp.T2 keeps lower than TE5-2 for 20 minutes, the compressor and outdoor fan
will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
Condition 3:
TE6
T2
On
Off
TE5-4
When the evaporator coil temp.T2 keeps lower than TE5-4 for 8 minutes, the compressor and outdoor fan
will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
1.3.2.5 Condenser high temperature T3 protection
For Duct & super-slim cassette type:
T3
TE12
Off
On
TE13
When T3TE12 for Time1, the compressor will shut off. When T3
ψTE13,the compressor will restart.
58
Page 64
Electrical Control Function
For Ceiling & Floor:
T3
TE10
Off
On
TE11
When T3TE10, the compressor will shut off. When T3
ψTE11,the compressor will restart.
1.3.3 Heating Mode
1.3.3.1 Compressor running rules:
For Duct & super-slim cassette type: Once the compressor starts up, it keeps running 7 minutes,
For Ceiling & Floor
: Once the compressor starts up, it keeps running HEATFTIM minutes,
then it will follow the below rules:
When indoor room temp.T1 is higher than Tgap0, the compressor and outdoor fan will shut off. When T1 is
lower than Tgap0-1, the compressor and outdoor fan will start up.
Tgap0
T1-TS
On
Off
Tgap0-1
For Ceiling & Floor:Tgap0
= setting temperature-compensation.
1.3.3.2 Outdoor fan running rules:
Fan(below): The outdoor fan runs all the time.
Fan(above):
18
T4
Off
On
16
1.3.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function
has the priority.
59
Page 65
Electrical Control Function
Auto fan action:
For Duct & super-slim cassette type:
For Ceiling & Floor: setting temperature-compensation.=4
qC
3
T1-Ts
2
High
Low
Medium
1
For Ceiling & Floor: setting temperature-compensation.=1qC
0
T1-Ts
-1
High
Low
Medium
-2
1.3.3.4 Defrosting modeφ
z Condition of defrosting:
AC will enter defrosting mode if any of the following items is satisfied.
A: T3< TE19 and the compressor keeps running over 45 minutes. Meanwhile T3
ψTE17 for 3minutes.
B: After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2 protection
cumulates up to 90 minutes.
z Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal
heating mode.
A: T3 rises to be higher than TE18.
B: The machine has run for 10 minutes in defrosting.
C: Turn to other modes or off.
z Defrosting actionφ
60
Page 66
Electrical Control Function
1.3.3.5 High evaporator coil temp.T2 protection:
For Duct and Super-slim Cassette:
For Ceiling & Floor:
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
đ.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ǻT (ǻT =T1-Ts).
Setting defrosting time
45S 45S Compressor
4 way valve 40S 40S Outdoor fan
Indoor fan
10S
Compressor off Outdoor fan off
TE9
Compressor on Outdoor fan off
TE8 TE10
Compressor on Outdoor fan on
TE11
TE7
TE8
TE9
Compressor off
Outdoor fan off
Compressor and Outdoor fan off
Compressor and Outdoor fan on
Compressor and Outdoor fan on
61
Page 67
Electrical Control Function
For Duct and Super-slim Cassette:
ǻT=T1-Ts Running mode
ǻTϊ2đ
Cooling
-1ǻT2đ
Fan-only
ǻT<-1đ
Heating
For Ceiling & Floor:
ǻT=T1-Ts Running mode
ǻTϊ2đ
Cooling
-1<ǻT2đ
Fan-only
ǻT-1đ
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
1.3.5 Drying mode
1.3.5.1 The indoor fan will keep running at low speed.
1.3.5.2 All protections are active and the same as that in cooling mode.
1.3.5.3 The louver operates the same as in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 It is valid in cooling, heating and auto mode.
1.3.7.2. Turning off, changing mode or setting fan speed will cancel economy function.
1.3.7.3 Operation process in sleep mode is as follow:
62
Page 68
Electrical Control Function
After pressing ECONOMIC or SLEEP button on the controller, the machine will go into economy mode.
When cooling, the setting temperature rises 1
đ(be lower than 30đ) every hour, 2 hours later the setting
temperature stops rising.
For heat pump models, when they are in heating, the setting temperature reduces 1
đ(be higher than 17đ)
every hour, 2 hours later the setting temperature stops reducing.
1.3.7.4 In this mode, the fan speed is forced into AUTO mode.
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes
when power returns.
1.3.9 Drain pump control(For duct & cassete)
1.3.9.1 Water level check
The water lever will be checked every 5 seconds, if the feedback signal is abnormal, it will be considered as
drain water full by the control system.
1.3.9.2 Drain pump control
If there is no water full error, the drain pump will be on when the unit is in cooling mode (including
auto-cooling and forced cooling) and dry mode. It will be off when the unit is in heating mode, fan only mode
or off state (if the pump is on before the unit is off, it will delay 3 minutes to be off).
If there is a water full error, the drain pump will be on when the error occurs. Afterwards:
If the error disappears in 3 minutes, the drain pump will work as normal state. (if it is necessary to turn off the
pump, it will be off in 1 minute delay.)
If the error is still there in 3 minutes, the drain pump will be off as well as the AC unit. The error can be
cleared only when the power of the unit is cut off.
63
Page 69
Troubleshooting
2. Troubleshooting
2.1 Display board
2.1.2 Icon explanation on indoor display board (Super-slim 4-way cassette).
2.1.4 Display board of
G[ZUROLZOTMVGTKRUL]G_IGYYKZZK
2.1.5 Icon explanation on indoor display board(Ceiling & Floor)
64
Page 70
Troubleshooting
2.2. Self-diagnosis
Indoor unit’s LED indication
For Super-slim 4-way Cassette
NO. Malfunction
Running
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
Display(digital
tube)
1
Communication malfunction between indoor and outdoor units
ƿ X ƿ X E1
2
Open or short circuit of T1 temperature sensor
X ƿ X X E2
3
Open or short circuit of T2 temperature sensor
ƿ X X X E3
4
Open or short circuit of T3 temperature sensor
X X ƿ X E4
5 Outdoor unit malfunction ƿ ƿ ƿ ƿ E6
6 Indoor EEPROM malfunction ƿ ƿ X X E7
7 Full-water malfunction X X X ƿ E8
8 Indoor fan speed is out of control X ƿ X ƿ Eb
9 Protection of low pressure ƿ ƿ ƿ X Ed
10
Communication malfunction between main PCB and up-down panel PCB
ƿ X ƿ ƿ F0
11
Up-down panel malfunction X ƿ ƿ ƿ F1
12
Up-down panel is not closed X O ƿ ƿ F2
O (on) X(off) ƿ(flash at 5Hz)
65
Page 71
Troubleshooting
For Ceiling & Floor
NO. Malfunction
Running
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
1
Communication malfunction between indoor and outdoor units
ƿ X ƿ X
2 Open or short circuit of T1 temperature sensor X ƿ X X
3 Open or short circuit of T2 temperature sensor ƿ X X X
4 Open or short circuit of T3 temperature sensor X X ƿ X
5 Outdoor unit malfunction ƿ ƿ ƿ ƿ
6 Indoor EEPROM malfunction ƿ ƿ X X
7 Full-water malfunction X X X ƿ
8 Indoor fan speed is out of control X ƿ X ƿ
9 Protection of low pressure ƿ ƿ ƿ X
LEDs’ for the indication of outdoor trouble
Type Contents LED2(Green) LED3(Yellow) LED4(Red)
Normal Normal running O X X
Normal Normal standby X O X
Trouble Phase sequence error X ƿ X
Trouble Lack of phase X X ƿ
Trouble Open-circuit and short-circuit trouble of T3 X X O
Trouble Open-circuit and short-circuit trouble of T4 ƿ X X
Trouble
Temperature protection of compressor
discharge
O X O
Trouble Protection of high pressure ƿ ƿ X
Trouble Protection of low pressure ƿ X ƿ
Trouble Overload of current X ƿ O
Trouble High temperature protection of condenser ƿ ƿ O
Trouble Fan selection error ƿ ƿ ƿ
O(light) X(off) ƿ(flash at 1Hz)
Note:
1. T3: Outdoor condenser temperature sensor
2. T4: Outdoor ambient temperature sensor
66
Page 72
Troubleshooting
2.3. Solving steps for typical malfunction
(1) For indoor unit
a. Communication malfunction between indoor and outdoor units(E1)
No
Power off, then turn on the unit 5 seconds later(reconnect the power wire).Is the error still displaying after several minutes?
Check whether the signal wire is shield cable or whether the shield cable is earthing?
Adopt shield cable/Shield cable earthing.
Check whether the wire is correct polarity? P to P, Q to Q, E to E?
No
Yes
Correct the connection.
No
Check if there’s any interference. Such as too many lamps, power transformers? Or the signal wire is too long?
Yes
Remove interference. Increase the capacity of anti­interference
Yes
Check whether the signal wire is broken?
Yes
Replace the signal wire.
Yes
Check whether the signal wires insert on PCB well?
Pull out and insert back.
No
No
Replace indoor PCB, is the error distinguished?
Yes
Replace the outdoor PCB.
No
67
Page 73
Troubleshooting
b. Open or short circuit of temperature sensorδE2θE3, E4ε
Check the connections
between temperature sensor and PCB. Are
the connections good?
Correct the connections.No
Yes
Yes Replace indoor or outdoor PCB.
Replace the sensor
Check the resistance value
of the sensor via Appendix 1
Is it normal?
No
68
Page 74
Troubleshooting
c. Outdoor unit malfunction(E6)
Whether the outdoor main board has error
display
Refer to corresponding solving stepsYes
No
No Check whether the power is on
Replace outdoor main
board
Yes
Whether the outdoor
unit is power on
Check whether the
communication wire
between the indoor and
outdoor unit is
connected correctly
Yes
Connect the wiring well or
replace the communication wire
No
Replace the indoor PCB Trouble is solved
check if the errors
happen again?
Yes
No
Outdoor unit malfunction
69
Page 75
Troubleshooting
d. Indoor EEPROM malfunction(E7)
If the EEPROM chip
is welded on PCB,
replace the PCB directly. Otherwise, check whether the
EEPROM chip
plugged in PCB well?
Yes
No
Yes
Insert the EEPROM well
Replace the indoor PCB.
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
e. Full-water malfunction(E8)
If the water-level switch
is inserted well?
No Insert the water-level switch well
If the water-level switch
is broken?
Yes Replace the water-level switch
If the water pump is
normal?
No
Replace the water pump
Yes
No
Yes
Check PCB board or replace the indoor main PCB
70
Page 76
Troubleshooting
f. Indoor fan speed has been out of control(Eb)
71
Page 77
Troubleshooting
Index 1:
1.Indoor DC fan motor(control chip is inside fan motor)
Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan motor must have problems and need to be replaced.
NO. Color
1 Red 2 --­3 Black 4 White 5 Yellow 6 Blue
Index2:
1. DC fan motor(control chip is inside fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must have problems and need to be replaced.
DC motor voltage input and output
NO. Color Signal
V
oltage
1 Red Vs/Vm 140~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 13.5~16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 15V
72
Page 78
Troubleshooting
For the super-slim cassette with up-down panel
a. Communication error between indoor unit and up-down panel b. Up-down panel is defective
73
Page 79
Troubleshooting
c Up-down panel is not closed
74
Page 80
Troubleshooting
Lack of phase
Check the power supply, is it 3 phase,
-
Check the connection between power supply and terminal,
is the voltage in outdoor terminal is 3 phase, 380-415V?
Outdoor PCB is defective
Yes
Yes
(2) For the outdoor unit
a. Phase sequence error:
b. Lack of phase
Phase sequence error
Change the order of two of the wires to power supply.
Switch on the unit again.
If the problem cannot be solved, the outdoor PCB is defective
75
Page 81
Troubleshooting
Protection of pressure or temp.
Is it K1 or K2 open ?
Is temp. protective switch K1 close
Possible reason
1. The wires is loose to K1
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is leakage
Is pressure protective switch K2 close
Yes
Yes Yes
Possible reason
1. The wires is loose to K2
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor motor or fan blade is defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is too much
c. Overload of current
d. Protection of pressure or temp.
Overload of current
Check the current, normally
Is the current in rated range?
The outdoor PCB is defective
Possible reason
1. Outdoor fan is defective
2. The compressor is defective
3. Refrigerant is over charged
4. Air enter the refrigerant system
Yes
No
76
Page 82
Troubleshooting
e. High temperature protection of condenser
High temperature protection of condenser
Check the resistance of the temp. sensor
according to
Appendix 1, is it normal?
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
Replace the sensor
No
Yes
77
Page 83
Troubleshooting
Appendix 1 Temperature Sensor Resistance Value Table (ć--K)
ć
K Ohm
ć
K Ohm
ć
K Ohm
ć
K Ohm
-20
115.266
20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5000 62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.2190 25 10.000 65 1.96532 105 0.54448
-14 79.3110 26 9.55074 66 1.89627 106 0.52912
-13 74.5360 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.48600
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44.0000 36 6.13059 76 1.34105 116 0.40060
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.21330 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.57050 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.32390
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.87950 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.27770
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.9180 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231
78
Page 84
Controller
3. Controller
3.1 Wireless Remote Controller
3.1.1 RG51Q1/BGE
The R51Q1/BGE wireless remote controller is standard for Four-way cassette type and the Ceiling& floor
type.
General Function for wireless remote controller:
Model RG51Q1/BGE
Rated voltage 3.0V(2pieces of LR03 7ί batteries)
Min voltage for sending signal of CPU 2.4V
Effective receiving distance 8m~11m
Operation condition -5~60ć
79
Page 85
Controller
Buttons and functions
1. Adjust
: Decrease the set temp. Keeping pressing will decrease the temp with 1ć per 0.5s.
2. Adjust
: Increase the set temp. Keeping pressing will increase the temp with 1ć per 0.5s.
3. MODE: Once pressing, running mode will be selected in the following sequence:
AUTO COOL DRY
HEAT
FAN
NOTE: No heating mode for cool only type unit.
4. VERT SWING:
Used to stop or start horizontal louver movement or set the desired up/down air flow direction. The louver changes 6 degree in angle for each press. If keep pushing more than 2 seconds, the louver will swing up and down automatically.
5. HORIZ SWING: Used to stop or start vertical louver movement.
6. AIR DIRECTION: Used to set the desired up/down air flow direction. The louver changes 6 degree in
angle for each press.
7. ON/OFF: For turning on or turning off the air conditioner.
8. FAN SPEED: Fan speed will be selected in following sequence once pressing this button:
AUTO LOW MED
HIGH
9. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set
time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting.
10. ECO: Activate or turn off economic operation mode. It is suggested to turn on this function when sleeping.
(Only available when remote controller is used with corresponding unit.)
11. TIME OFF:
For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the
set time exceeds 10 hours, pressing the button will increase the time by 1 hour.
Adjust the figure to 0.00 will cancel time ON setting.
12. C/H (inner located): Press this button with a needle of 1mm to shift the mode between Cooling only and
Cooling & Heating according to the feature of the machine.
13.RESET (inner located): Press this button with a needle of 1mm to cancel the current setting and reset
remote controller.
80
Page 86
Controller
3.1.2 RG51C/E
Remote Controller Specifications
Model RG51C/E
Rated Voltage 3.0V
Lowest Voltage of CPU Emitting Signal 2.0V
Reaching Distance 8m (when using 3.0 voltage, it can get 11m)
Environment Temperature Range -5ćЊ60ć
Introduction of Function Buttons on the Remote Controller
ADJUST
AU TO COOL
DRY HE AT
FAN HIGH
MED LOW
MODE
SWING
FAN SPEED
TIMER ON
ECO
ON/OFF
TIMER OFF
RESET LOC K
2
1
4
5
3
7
8
9
10
11
SET TEMPERATURE( C)
12
Adju st
Mod e settin g
Adj ust
ON/ OFF
TIMER ON
TIME R O F F
L ock
Econom ic ope rat ion
Fan speed se tt ing
SWING
AI R DIRECTION
Res et
13
1. Adjust
: Decrease the set temp. Keeping pressing will decrease the temp with 1ć per 0.5s.
2. Adjust : Increase the set temp. Keeping pressing will increase the temp with 1ć per 0.5s.
3. MODE: Once pressing, running mode will be selected in the following sequence:
AUTO COOL DRY
HEAT
FAN
NOTE: No heating mode for cool only type unit.
4. VERT SWING:
Used to stop or start horizontal louver movement. The louver will swing up and down
automatically if push this button.
AIR DIRECTION: Used to set the desired up/down air flow direction. The louver changes 6 degree in
angle for each press.
5. HORIZ SWING: Used to stop or start vertical louver movement.
6. FAN SPEED+ MODE: Press the Mode and Fan speed button simultaneously for 2 seconds. The remote
81
Page 87
Controller
controls into faceplate setting state and the LCD shows F2.Press the TEMPUP( ) to control the faceplate up and press the TEMP DOWN(
) to control the faceplate down. Press any button to exit the faceplate
setting state, then the LCD back to the normal display.
7. ON/OFF: For turning on or turning off the air conditioner.
8. FAN SPEED: Fan speed will be selected in following sequence once pressing this button:
AUTO LOW MED
HIGH
9. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set
time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting.
10. ECO: Select this function during the sleeping time. It can maintain the most comfortable temperature
and save energy. This function is available on COOL, HEAT or AUTO mode only .
NOTE: While the unit is running under Energy-saving mode, it would be cancelled if press MODE, FAN SPEED or ON/OFF button.
11. TIME OFF: For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the
set time exceeds 10 hours, pressing the button will increase the time by 1 hour.
Adjust the figure to 0.00 will cancel time ON setting.
12. LOCK (inner located): Push this button to lock in all the current settings, and the remote controller will
not accept any operation except that of the LOCK. Use the LOCK mode when you want to prevent settings
from being changed accidentally. Press the LOCK button again to cancel the LOCK function. A lock symbol will appear on the remote controller display when the lock function is activated.
13.RESET (inner located): Once the recessed RESET button is pressed, all of the current settings will be
cancelled and the controller will return to the initial settings..
82
Page 88
Controller
3.2 Wired Remote Controller (OPTIONAL)
KJR-10B
Name and functions of buttons on the wire controller
1 mode selection button:
It is used to select mode, push the button one time, then the operation modes will change
In turn as follows:
AUTO COOL DRY
HEAT
FAN
Remark: no heating mode if wire controller is set as the cool only.
2 Timer on button:
Push the button to set TIMER ON, each time you push the button the time moves forward by o.5 hours.
When the set time is over 10 hours, each time you push the button the time moves forward by 1 hour. If
want to cancel the TIMER ON, then adjust the time of TIMER ON as 0.0
3 Timer off button:
Push the button to set TIMER OFF, each time you push the button the time moves forward by o.5 hours.
When the set time is over 10 hours, each time you push the button the time moves forward by 1 hour. If
want to cancel the TIMER OFF, then adjust the time of TIMER OFF as 0.0
4 CLOCK button:
Normally display the clock set currently (display 12:00 for the first electrifying or resetting). When push
the button for 4 seconds, the hour part on the clock display flashes every 0.5 seconds, then push button
and to adjust hour; push the button CLOCK again, the minute part flashes every 0.5 seconds, then push
and button to adjust minute. When set clock or alter clock setting, must push the confirm button to
complete the setting
83
Page 89
Controller
Name and function of LCD on the wire
controller
1 Mode select button (MODE):
Press MODE button to select “COOL”, “DRY” , "HEAT", or "FAN ONLY" mode.(HEAT is invalid for
COOL ONLY wire controller.)
AUTO COOL DRY
HEAT
FAN
2 Fan speed button (FAN SPEED)
Press FAN SPEED to select fan speed from "AUTO", "LOW"," MED" , and "HIGH”. NOTE: some air
conditioners have no MED fan speed, and then the MED is regarded as HIGH.
3 Economical operation displays:
Press ECONOMICAL to display economical operation, if press ECONOMICAL again then the display
disappears
4 Lock display
Press LOCK to display the icon of LOCK. Press the button again then the icon of LOCK disappears. In
the mode of LOCK, all the buttons are invalid except for LOCK button.
5 CLOCK display.
Usually display the clock set currently. Press the button CLOCK for 4 seconds, the HOUR part will flash,
press button Ÿ and ź to adjust HOUR. Press the button CLOCK again, the minute part flash, press
buttonŸ orź to adjust MINUTE. After clock set or clock operation, it must press CONFIRM to complete
the set.
6 TIMER ON/OFF display:
Display ON at the state of TIMER ON adjustment or after only set the TIMER ON; Display OFF at the
state of TIMER OFF adjustment or after only set the TIMER OFF; Display ON/OFF if simultaneously set
the mode of TIMER ON and TIMER OFF.
7 Temperature display area:
Usually display the set temperature. Press the buttons of and to set temperature, at the mode of FAN,
there is no figure display in the area.
84
Page 90
Controller
Remark:
The wired controller will reset to factory setting with auto mode, auto fan and 24đ setting temperature when
the air conditioner restarts after power failure. And this may cause inconsistent displays on the wired controller and on the air conditioner. You need to readjust the running status through the wired controller.
Installation
Installation Notice:
When the air conditioner needs the constant frequency wire Controller, be sure adding a Wire Joint with 5
terminal named A, B, C, D, E in indoor unit, and fixing a infrared emitter whose anode and cathode
connecting with A and B near the receiver in the Indoor Unit Switch Board, then connecting the terminal +5v,
GND, Run in the Switch Board to C,D,E respectively.
NOTE
Never turn screws too tightly, or else the cover would be dented or the Liquid Crystal breaks.
Please leave enough long cable for maintenance of the Wire Controller Board.
85
Page 91
MODEL:ASC60ANintdoor
Page 92
No Description PartCode Actualization QtyPriceCode
1 Panel assembly 201109990017 1 BG
1.1 Louver motor 202400100007 2 AM
1.2 Display box assembly 203342890005 1 AV
1.3 Panel assembly P0000449603 1 AZ
1.3.1 Cover assembly of installation plate P0000449698 4 AD
1.3.2 Air inlet grille assembly P0000449689 1 AL
1.3.2.1 Air filter 201109901903 1 AL
1.3.3 Transmission framework P0000449696 2 AF
1.3.3.1 Louver P0000449731 2 AD
2 Cover 201142790001 1 AC
3 Foam tray assembly for condenser water 202242790002 1 BA
4 Evaporator fixing hanger 201242990039 2 AD
5 Evaporator assembly 201542990027 1 BS
5.1 Output pipe assembly 201642990041 1 AV
5.2 Copper nut 201600320004 1 AC
5.3 Input pipe assembly 201642990006 1 AT
5.3.1 Copper nut 201600320001 1 AC
6 Base foam assembly 202242990004 1 AU
7 Board assembly III 201242990035 1 AN
8 Board assembly I 201242990034 1 AM
9 Chassis assembly 201242590012 1 AX
10 Board assembly II 201242990037 1 AN
11 Board assembly Ⅳ 201242990036 1 AM
12 Eva
p
orator fixing board 201242790011 1
A
D
MODEL:ASC60ANintdoor
12
Evaporator fixing board
201242790011
1
AD
13 Pipe fixing board assembly 201142790002 1 AD
14 Asynchronous motor 202400300529 1 BF
15 Fan assembly 201100100846 1 AZ
16 Ventilation assembly 201142990003 1 AU
17 Electronic control box assembly 203342990019 1 BF
17.1 Electronic control box 201242590004 1 AG
17.2 Insulation plate 201142590002 1 AF
17.3 Main control board assembly 201342990007 1 BC
17.4 Wire joint 202301450125 1 AE
17.4 Wire joint 202301450116 1 AD
17.6 Ambient temperature sensor assembly 202440120100 1 AD
17.7 Reactance 202301000950 1 AR
18 Cover of electronic control box I 201242590023 1 AD
19 Remote controller 203355091508 1 AT
20 Pipe temperature sensor 202301300111 1 AD
21 Water level sensor assembly 202301310051 1 AM
22 Water Pump installation bracket assembly 201242990003 1 AF
23 Drain pump 202400600203 1 AZ
24 Pump rubber washer 202742000002 3 AC
25 Drain pipe 202856001093 1 AG
25 Drain pipe 202742590002 1 AG
26 Water pipe 201142500032 1 AD
Thedataaresubjecttochangewithoutnotice.
Page 93
Model: ASF-60AN indoor
Page 94
No Description PartCode Actualization Qty PriceCode
1 Air inlet grille assembly II 201144790014 1 AK
1.1 Air filter I 201144790023 1 AD
2 Air inlet grille assembly I 201144790015 2 AL
2.1 Air filter II 201144790024 1 AD
3 Top cover assembly 201244790048 1 AZ
4 Display installation box 201144790016 1 AP
5 Display board assembly 201344790040 1 AR
6 Evaporator assembly 201544790142 1 BS
6.1 Pipe temperature sensor assembly 202301300111 1 AD
6.2 Input pipe assembly 201644790189 1 AT
6.2.1 Copper nut 201600320001 1 AC
6.3 Output pipe assembly 201644790185 1 AV
6.4 Evaporator 201544790139 1 BQ
6.5 Copper nut 201600320004 1 AC
7 Water collector 202244790001 1 AY
7.1 Louver motor 202400200100 1 AH
8 Insulated axis 201132590888 2 AF
9 Volute shell (above) 201144690032 4 AK
10 Fan motor fixing board 201252490002 2 AD
11 Centrifugal fan 201144690083 4 AM
12 Fan motor axes clamp (right) 201280200006 2 AE
13 Fan motor axes clamp (left) 201280200005 2 AE
14 Asynchronous motor 202400300070 2 BE
15 Volute shell
(
below
)
20114469003
3
4
A
L
MODEL:ASF60ANintdoor
15
Volute shell (below)
201144690033
4
AL
16 Right cover 201144790017 1 AN
17 Right hook 201244790033 2 AC
18 Supporter of louver 201144790018 2 AD
19 Louver 201144790006 1 AH
20 Louver motor 202400200162 1 AN
21 Left hook 201244790034 2 AC
22 Left cover 201144790019 1 AM
23 Remote controller 203355091492 1 AT
24 Cover of electronic control box 201244490048 1 AE
25 Electronic control box assembly 203344690026 1 BF
25.1 Electronic control box 201244790050 1 AK
25.2 Wire joint 202301450042 1 AD
25.2 Wire joint 202301450125 1 AE
25.3 Main control board assembly 201344690017 1 BD
25.5 Ambient temperature sensor assembly 202301310072 1 AD
25.7 Reactor 202301000950 1 AR
27 Pipe clamp board 201244790047 1 AE
28 Chassis assembly 201244690053 1 BD
29 Electronic control box assembly 203319900796 2 BC
29.1 Electronic control box 201270590340 1 AH
29.2 Inverter control board assembly 201319903060 1 BA
29.3 Radiator 202301900138 1 AQ
Thedataaresubjecttochangewithoutnotice.
Page 95
MODEL:ASC60AN,ASF60ANoutdoor
Page 96
No Description PartCode Actualization Qty PriceCode
1 Ambient temperature sensor assembly 202440220061 1 AD
2 Rear net 201175690001 1 AR
3 Condenser assembly 201575790151 1 CK
3.1 Condenser assembly 201575790152 1 BW
3.1 Condenser assembly 201575790153 1 BW
3.2 Input pipe assembly 201675890900 1 AV
3.3 Fluted pipe assembly 201675890890 1 AW
4 Pipe temperature sensor assembly 202450200331 1 AE
5 Big Handle assembly 201157390007 1 AF
6 Rear right clapboard assembly 201248700199 1 AZ
7 Handle 201148700009 2 AD
8 Water collector 201148790000 1 AE
9 Front clapboard assembly 201248700204 1 AZ
10 Valve plate 201248790014 1 AE
11 Chassis 201248700285 1 BA
12 Partition board assembly 201275690068 1 AW
13 Accumulator cylinder 201601000636 1 AY
14 Fix clamp of segregator 201248700067 1 AC
15 Left clapboard 201275690067 1 AL
16 Air outlet grille 201148100116 2 AP
17 Front panel 201248700201 1 AX
18 Axial flow fan 201100300045 2 AQ
19 Fan motor 202400401375 2 BB
20 Supporter assembly of fan motor 201248700197 1 AY
21 Support Board 201248300231 1 AD
22 Su
pp
orting bar 201275690066 1
A
F
MODEL:ASC60AN,ASF60ANoutdoor
pp g
23 Top cover assembly 201248300242 1 AT
24 Compressor C-SB453H8A 201400710560 1 CR
25 Discharge pipe assembly 201675890952 1 AW
25.1 Pressure switch 202301820020 1 AS
25.2 Muffler 201601000041 1 AK
26 4-way valve assembly 201675790946 1 BD
26.1 4-way valve 201600600166 1 BA
26.2 Gas valve 201600720425 1 AS
27 Liquid valve assembly 201675790987 1 AX
27.1 Liquid valve 201600740704 1 AR
28 Electronic control box assembly 2033757A0156 1 BE
28.1 Installation plate of electric parts 201248700194 1 AK
28.2 Main control board assembly 201348890013 1 AX
28.3 Wire joint 202301450003 1 AF
28.3 Wire joint 202301450121 1 AD
28.3 Wire joint 202301450117 3 AD
28.4 Fan motor capacitor 202401100505 2 AG
28.7 AC contactor 202300850045 1 AV
28.8 Transformer 202300900161 1 AK
29 Copper nut 201600320001 1 AC
30 Crankcase electric heater 202403101716 1 AR
31 Discharge temperature sensor assembly 202301610500 1 AH
32 Suction pipe assembly 201675790991 1 AU
32.1 Pressure switch 202301800118 1 AP
Thedataaresubjecttochangewithoutnotice.
Loading...