Sinclair ASF-12A, ASF-18A, ASF-30A, ASF-24A, ASF-36 Service Manual

...
Page 1
SERVICE MANUAL
ASF-12A,
ASF-18A, ASF-24A, ASF-30A
FLOOR & CEILING
SERIES
ASF-36, ASF-48A, AS-60A
Page 2
Page 3
Contents
Part 1 General information………………………………………………….2
Part 2 Indoor units……………………………………………………………5
Part 3 Outdoor units………………………………………………………..36
Part 4 Installation…………………...………………………………………64
Part 5 Control………………………………………………………………..72
Page 4
Part 1
General Information
1. Model names of units……………………..…………………………………3
2. External Appearance………………………………………………………...3
3. Nomenclature…………………………………………………………………4
4. Features………………………………………………………………………..4
2
Page 5
1. Model names of units
ASF-12A ASF-18A ASF-24A ASF-30A ASF-36A ASF-48A ASF-60A
2. External Appearance
2.1 Indoor units
2.2 Outdoor units
3
Page 6
3. Nomenclature
ASF – 24 A
Air Condition
Sinclair
Refrigerant A R410A
Cooling Capacity x 1000 [BTU/h]
Floor & Ceiling
4. Features
4.1. New design, more modern and elegant appearance;
4.2. Convenient installation;
4.3. Two direction auto swing (vertical & horizontal) and wide angle air flow;
4.4. Three level fan speed, more humanism design, meets different air-supply requirement;
4.5. Water proof by utilizing the absorbing plastic film on water collector;
4.6. Easy operation. Auto-restart function, remote control and optional wire control method;
4.7. Low noise level plus compact size;
4.8. Universal outdoor design
4
Page 7
Part 2
Indoor units
Ceiling & Floor Type…………………………………………………………6
5
Page 8
Ceiling & Floor Type
1. Features……………………………………………………………………………………………..7
2. Specification………………………………………………………………………………………..8
3. Dimensions………………………………………………………………………………………..14
4. Service space……………………………………………………………………………………..15
5. Piping diagrams…………………………………………………………………………………..16
6. Wiring diagrams…………………………………………………………………………………..17
7. Capacity Tables…………………………………………………………………………………...20
8. Air Velocity and Temperature Distributions………………………………………………….27
9. Electric Characteristics………………………………………………………………………….29
10. Sound Levels……………………………………………………………………………………...30
11. Exploded view…………………………………………………………………………………….32
6
Page 9
1. Features
1.1. New design, more modern and elegant appearance.
1.2. Convenient installation
--The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow
--It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting
1.3. Two direction auto swing (vertical & horizontal) and wide angle air flow
--Air flow directional control minimizes the air resistance and produces wilder air flow to vertical direction.
--The range of horizontal air discharge is widened which secures wider air flow distribution to provide more comfortable air circulation no matter where the unit is set up
1.4. Three level fan speed, more humanism design, meets different air-supply requirement.
1.5. Water proof by utilizing the absorbing plastic film on water collector
1.6. Easy operation. Auto-restart function, remote control and optional wire control method.
1.7. Low noise level plus compact size
--Shape of the blades has been improved to prevent noise caused by turbulence.
7
Page 10
2. Specification
Cooling & Heating
Model ASF-12A ASF-18A ASF-24A
Power supply Ph-V-Hz 1,220-240V,50Hz 1,220-240V,50Hz 1,220-240V,50Hz
Capacity Btu/h
12000 18000 24000
Capacity kW
3.5 5.4 7.1
Input W
1200 1900 2700
Rated current A
6.0 8.5 12.0
Cooling
EER Btu/W.h
10.0 9.7 8.9
Capacity Btu/h
13000 20500 27300
Capacity kW
3.8 6 8
Input W
1130 1850 2800
Rated current A
5.0 8.0 12.5
Heating
COP Btu/W.h
11. 6 11. 1 9.8
Moisture Removal L/h
1.2 1.8 2.4
Max. input consumption W
1500 2400 3300
Max. current A
7.0 11.5 14.5
Starting current A
26 36.8 61
Model
PA140X2C-4FT PA225X2CS-4KU PA290X3CS-4MU1
Type
ROTARY ROTARY ROTARY
Brand
TOSHIBA TOSHIBA TOSHIBA
Supplier
TOSHIBA (Guangdong) TOSHIBA (Guangdong) TOSHIBA (Guangdong)
Capacity Btu/h
11567 18834 24498
Input W
1145 1870 2430
Rated current(RLA) A
5.3 8.75 11.4
Locked rotor Amp(LRA) A
26 36.8 61
Thermal protector
INNER INNER INNER
Capacitor uF
35/370 μF/V 50/370 μF/V 50/400 μF/V
Compressor
Refrigerant oil ml
RB68AF/T68/Α68tf
480
ESTER OIL VG74 750 ESTER OIL CG74 950
Model
YSK25-6L YSK55-4L YSK55-4L
Input W
104/98 110/104/98 110/104/98
Capacitor uF
1.5uF/450V 2.5uF/450V 2.5uF/450V
Indoor fan
motor
Speed(hi/lo) r/min
1190/1000/890 1280/ 1190/1000 1280/ 1190/1000
Number of rows
2 3 3
Tube pitch(a) x row pitch(b) mm
25.4×22 25.4×22 25.4×22
Fin spacing mm
1.7 1.7 1.7
Fin type
Hydrophilic aluminum Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia. and type mm
Ф9.53 innergroove tube Ф9.53 innergroove tube Ф9.53 innergroove tube
Indoor coil
Coil length x height x width mm
804×254×44 804×254×66 804×254×66
Indoor air flow(Hi/Mid/Lo) m3/h
600/480/400 800/600/500 1000/900/700
8
Page 11
Indoor noise level (Hi/Mid/Lo) dB(A)
43/41/38 43/41/38 45/43/40
Dimension (WxHxD)(body) mm
995×660×198 995×660×198 995×660×198
Packing (WxHxD)(body) mm
1075×744×278 1075×744×278 1075×744×278
Indoor unit
Net/Gross weight(body) kg
29/35 30/37 30/37
Model
YDK24-6F YDK53-6K YDK53-6H
Input W
56 130 130
Capacitor uF
2.5uF/450V 2.5 uF/450V 3μF/450V
Outdoor fan
motor
Speed r/min
800 750 800
Number of rows
2 2 2
Tube pitch(a)x row pitch(b) mm
25.4 x22 25.4×22 25.4×22
Fin spacing mm
1.4 1.7 1.5
Fin type
Hydrophilic aluminum Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia. and type mm
φ9.53x0.35,Innergroove
tube
Ф9.53,Innergroove tube Ф9.53,innergroove tube
Coil length x height x width mm
651x559x44 775×660×44 850×810×44
Outdoor coil
Number of circuits
2 3 4
Outdoor air flow m3/h
2100 2400 3000
Outdoor noise level dB(A)
43 48 55
Dimension(WxHxD) mm
760×590×285 845×695×335 895×860×330
Packing (WxHxD) mm
887x655x355 970X770X395 1043X915X395
Outdoor
unit
Net/ Gross weight kg
44/48 57/62 68/70
Refrigerant type/Quantity g
R410A/1120 R410A/2050 R410A/2600
Design pressure (high side/low side) MPa
4.2/2.5 4.2/2.5 4.2/2.5
Liquid side mm(inch)
6.35 (1/4) 6.35 (1/4) 9.53 (3/8)
Gas side mm(inch)
12.7 (1/2) 12.7 (1/2) 16 (5/8)
Max. pipe length m
25 25 30
Refrigerant
piping
Max. difference in level m
15 15 15
Operation temp °C
17~30 17~30 17~30
Ambient temp °C
-7~45 -7~45 -7~45
Application area m
2
18~26 34~49 40~56
Qty’per 20’& 40’Fcl Pieces
63/138/155 49/104/126 44/94/101
9
Page 12
Model ASF-30A ASF-36A
Power supply Ph-V-Hz 1,220-240V,50Hz 3,380V,50Hz
Capacity Btu/h
30000 36000
Capacity kW
9.2 10.5
Input W
3750 3750
Rated current A
16.3 6.6
Cooling
EER Btu/W.h
8.0 9.6
Capacity Btu/h
32000 39000
Capacity kW
9.4 11.4
Input W
3500 3700
Rated current A
15.2 6.5
Heating
COP Btu/W.h
9.2 10.6
Moisture Removal L/h
3 3.8
Max. input consumption W
4620 4400
Max. current A
21 8.0
Starting current A
97 61
Model
C-SBN301H5D C-SBN303H8D
Type
SCROLL SCROLL
Brand
SANYO SANYO
Supplier
SANYO SANYO(Dalian)
Capacity Btu/h
33438 33438
Input W
3650 3650
Rated current(RLA) A
17.65 6.58
Locked rotor Amp(LRA) A
97 61
Thermal protector
INNER INNER
Capacitor uF
60uF/440V /
Compressor
Refrigerant oil ml
FV68S 1700 DAPHNE FV68S 1700
Model
YSK80-4A YSK80-4A
Input W
142/134/132 142/134/132
Capacitor uF
3.5uF/450V 3.5uF/450V
Indoor fan
motor
Speed(hi/lo) r/min
1310/1200/1000 1310/1200/1000
Number of rows
3 3
Tubepitch(a)x row pitch(b) mm
25.4×22 25.4×22
Fin spacing mm
1.7 1.7
Fin type
Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm
Ф9.53, inner groove tube Ф9.53, inner groove tube
Indoor coil
Coil length x height x width mm
905×203×66 905×203×66
Indoor air flow(Hi/Mid/Lo) m3/h
1400/1200/1000 1400/1200/1000
Indoor noise level (Hi/Mid/Lo) dB(A)
45/43/40 45/43/40
Dimension (WxHxD)(body) mm
1285×660×198 1285×660×198
Indoor unit
Packing (WxHxD)(body) mm
1365×744×278 1365×744×278
10
Page 13
Net/Gross weight(body) kg
34/42 34/42
Model
YDK250-6D YDK250-6D
Input W
307 307
Capacitor uF
10 uF/450V 10 uF/450V
Outdoor fan
motor
Speed r/min
740 740
Number of rows
2 2
Tube pitch(a)x row pitch(b) mm
25.4×22 25.4×22
Fin spacing mm
1.7 1.7
Fin type
unhydrophilic aluminium unhydrophilic aluminum
Tube outside dia.and type mm
Ф9.53, inner groove tube Ф9.53, inner groove tube
Coil length x height x width mm
955×915×44 955×915×44
Outdoor coil
Number of circuits
8 8
Outdoor air flow m3/h
5000 5000
Outdoor noise level dB(A)
57 57
Dimension(WxHxD) mm
990×960×360 990×960×360
Packing (WxHxD) mm
1120X1090X435 1120X1090X435
Outdoor unit
Net/ Gross weight kg
90/102 90/102
Refrigerant type/Quantity g
R410A 3450 R410A/3100
Design pressure (high side/low side) MPa
4.2/2.5 4.2/2.5
Liquid side mm(inch)
12.7 (1/2) 12.7 (1/2)
Gas side mm(inch)
19 (3/4) 19 (3/4)
Max. pipe length m
30 30
Refrigerant
piping
Max. difference in level m
20 20
Operation temp °C
17~30 17~30
Ambient temp °C
-7~45 -7~45
Application area m
2
60~85 60~85
Qty’per 20’& 40’Fcl Pieces
27/55/62 27/55/62
11
Page 14
Model ASF-48A ASF-60A
Power supply Ph-V-Hz 3,380V,50Hz 3,380V,50Hz
Capacity Btu/h
48000 60,000
Capacity kW
14 17
Input W
4700 6000
Rated current A
8.2 9.8
Cooling
EER Btu/W.h
10.2 10.0
Capacity Btu/h
52000 68,000
Capacity kW
15.2 20
Input W
4900 6000
Rated current A
8.6 9.8
Heating
COP Btu/W.h
10.6 11.4
Moisture Removal L/h
4.8 6
Max. input consumption W
5870 7500
Max. current A
10.7 12.8
Starting current A
66 67
Model -
C-SBN373H8D C-SBN453H8D
Type -
SCROLL SCROLL
Brand -
SANYO SANYO
Supplier -
SANYO(Dalian) SANYO(Dalian)
Capacity Btu/h
48109 55957
Input W
4750 5750
Rated current(RLA) A
8.22 9.77
Locked rotor Amp(LRA) A
66 67
Thermal protector
INNER INNER
Capacitor uF
/ /
Compressor
Refrigerant oil ml
DAPHNE FV68S 1700 DAPHNE FV68S 1700
Model
YSK59-4A YSK59-4A
Input W
118/108/101 118/108/101
Capacitor uF
2.5uF/450V 2.5uF/450V
Indoor fan
motor
Speed(hi/lo) r/min
820/695/620 820/695/620
Number of rows
3 3
Tube pitch(a)x row pitch(b) mm
25.4X22 25.4X22
Fin spacing mm
1.7 1.7
Fin type
Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia. and type mm
Ф9.53, inner groove tube Ф9.53, inner groove tube
Indoor coil
Coil length x height x width mm
1150x254x66 1150x254x66
Indoor air flow(Hi/Mid/Lo) m3/h
2000/1800/1600 2000/1800/1600
Indoor noise level (Hi/Mid/Lo) dB(A)
47/45/42 47/45/42
Dimension (WxHxD)(body) mm
1670×680×240 1670×680×240
Packing (WxHxD)(body) mm
1764×760×329 1764×760×329
Indoor unit
Net/Gross weight(body) kg
52/62 52/62
12
Page 15
Indoor units
21
Model
YDK65-6; YDK65-6F YDK65-6F; YDK65-6F
Input W
138+156 138+156
Capacitor uF
3.5×2 uF/450V 3.5×2 uF/450V
Outdoor fan
motor
Speed r/min
800 800
Number of rows
2 2
Tube pitch(a)x row pitch(b) mm
25.4×22 25.4×22
Fin spacing mm
1.8 1.8
Fin type
Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia. and type mm
Ф9.53, inner groove tube Ф9.53, inner groove tube
Coil length x height x width mm
715×1220×44 715×1220×44
Outdoor coil
Number of circuits
4 4
Outdoor air flow m3/h
6000 6000
Outdoor noise level dB(A)
58 58
Dimension(WxHxD) mm
940×1245×340 940×1245×340
Packing (WxHxD) mm
1058X1380X435 1058X1380X435
Outdoor unit
Net/ Gross weight kg
112/127 112/127
Refrigerant type/Quantity g
R410A/4000 R410A/4200
Design pressure (high side/low side) MPa
4.2/2.5 4.2/2.5
Liquid side mm(inch)
12.7 (1/2) 12.7 (1/2)
Gas side mm(inch)
19 (3/4) 19 (3/4)
Max. pipe length m
50 50
Refrigerant
piping
Max. difference in level m
30 30
Operation temp °C
17~30 17~30
Ambient temp °C
-7~45 -7~45
Application area m
2
80~105 95~120
Qty’per 20’& 40’Fcl Pieces
25/50/54 25/50/54
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB;
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are
from an anechoic room.
13
Page 16
3. Dimensions
3.1. ASF-12A ASF-18A ASF-24A
4-12 18 Overhanging hole
ˇÁ
Connecting point of refrigerant pipe
(gas side)
Drain point
Connecting point of refrigerant pipe
(Liquid side)
402
Strengthener
980
995
3.2. ASF-30A ASF-36A
4-12 18 Overhanging hole
ˇÁ
Connecting point of refrigerant pipe
(gas side)
Drain point
Connecting point of refrigerant pipe
(Liquid side)
402
Strengthener
980
1285
3.3. ASF-48A ASF-60A
4-12 18 Overhang ing hole×
Co nne cti n g po int of ref rig eran t pi pe
(gas si de)
Drain point
Co nne cti ng po int of ref rig erant pipe
(Li qui d s i de )
240
660
Strengthener
980
1610
14
Page 17
4. Service space
>600mm
>600mm
15
Page 18
5. Piping Diagrams
Remark: 1. For ASF-12A and ASF-18A, accumulator is not included.
2. For ASF-30A, ASF-36A and ASF-48A, check valve and auxiliary capillary is not included.
16
Page 19
6. Wiring Diagrams
6.1 ASF-12A
XT1
R T 2 XT1
XT2
R
T1
X P 1~ 4 X
S 1~ 4
C A P 1
FA
N 1
C N1-CN24
T4
XT2
K M 1
G M 1
FA N1
D IS P L A Y
B
O A R D
C A P1
T4
M N CONTROL BOA R D
CN15
C
N 10
C
N
16
C
N
1
CN2
CN
3
CN5
(W
H ITE )
XP1 XS1
XS3
XP3
Y/ G
IN D O O R
W IR IN G
A G R A M
C O N N E C TO R S
P I P E T E M P. S E N
S O
R
R
O O M TEM P. S E N S O R
5
- W A Y T E R M IN A L
P.C.B O A R D S OC K E T S
T R A N S F O R M E R
RL 8
C O M P R E S S O R
Y/ G
C N 12
KM 1
CODE
IN D O O R FA N
IN D O O R FA N C A P
PA RT N A M E
B
L
A
C
K
(
H
I
)
R
E
D
B
L
A
C
K
B
L
U
E
(
S
.
V
)
B
L
A
C
K
(
C
)
R
E
D
W
H
I
T
E
B
L
A
C
K
W
H
I
T
E
(
T
3
)
B
L
A
C
K
(
E
)
R
E
D
(
L
O
)
B
L
A
C
K
(
L
)
B
L
U
E
(
N
)
C N 13
435
(R
E D)
Y/ G
LN12(N)
C O N N E C TO R S
6
- W A Y T E R M INA L
G M 2
6.2 ASF-18A
X T1
RT2 XT1
XT2
RT1
X P1 ~4 X
S1~4
CAP 1
FA
N 1
T4
XT2
K M 1
GM1
FA N1
D IS PLA Y
B
O A R D
CAP1
T4
C N 15
C N 10
CN16
CN1
C
N
2
CN3
CN5
(W
H
ITE)
XP1 XS1
X S3
X
P3
Y/ G
P O WE R
WHITE
INDOOR
WIRING DIAGRAM
P. C . B O A R D SO CK E TS
R L 8
Y/ G
CN12
K M 1
C OD E
IN D O O R FAN CA P
PA R T N A M E
B
L
A
C
K
(
H
I
)
R
E
D
B
L
A
C
K
B
L
U
E
(
S
.
V
)
B
L
A
C
K
(
C
)
R
E
D
W
H
I
T
E
B
L
A
C
K
W
H
I
T
E
(
T
3
)
B
L
A
C
K
(
E
)
R
E
D
(
L
O
)
B
L
A
C
K
(
L
)
B
L
U
E
(
N
)
CN13
WHITE
435
(RE D )
Y/ G
LN1
2
(
N
)
GM2
17
AI
DI
RELAY FOR
PLUMB SWING MOTOR
LEVEL SWING MOTOR
WHITE
WHITE
TO OUTDOOR UNIT
TO OUTDOOR UNIT
POWER
MAIN CONTROL BOARD
TO OUTDOOR UNIT
TO OUTDOOR UNIT
CN1-CN24
TRANSFORMER
INDOOR FAN
CONNECTORS CONNECTORS
ROOM TEMP.SENSOR PIPE TEMP.SENSOR
5 - WAY TERMINAL 6 - WAY TERMINAL RELAY FOR
COMPRESSOR LEVEL SWING MOTOR
PLUMB SWING MOTOR
Page 20
6.3 ASF-24A
6.1.4. ASF-30A
18
Page 21
6.1.5. ASF-36A
6.1.6. ASF-48A ASF-60A
19
Page 22
7. Capacity Tables
Model: ASF-12A
Cooling OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 3.38 3.23 3.12 2.94 2.82 2.73 2.65
Sensitive capacity kW 2.70 2.59 2.49 2.35 2.26 2.19 2.12
21ºC D
15ºC W
Input kW. 0.76 0.86 0.97 1.08 1.19 1.30 1.40
Total capacity kW 3.70 3.54 3.41 3.22 3.09 2.99 2.90
Sensitive capacity kW 2.96 2.83 2.73 2.58 2.47 2.40 2.32
24ºC D
17ºC W
Input kW. 0.80 0.91 1.03 1.14 1.25 1.37 1.48
Total capacity kW 4.03 3.85 3.71
3.50
3.36 3.26 3.15
Sensitive capacity kW 3.22 3.08 2.97 2.80 2.69 2.60 2.52
27ºC D
19ºC W
Input kW. 0.84 0.96 1.08
1.20
1.32 1.44 1.56
Total capacity kW 4.63 4.43 4.27 4.03 3.86 3.74 3.62
Sensitive capacity kW 3.70 3.54 3.41 3.22 3.09 2.99 2.90
32ºC D
23ºC W
Input kW. 0.97 1.10 1.24 1.38 1.52 1.66 1.79
Heating OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW 6.56 5.24 4.37 3.93 3.71 3.28 3.06 2.84
15ºC
Input kW. 1.95 1.56 1.30 1.23 1.17 1.10 1.04 0.91
Capacity kW 6.16 4.92 4.10 3.69 3.49 3.08 2.87 2.67
18ºC
Input kW. 1.83 1.46 1.22 1.16 1.10 1.04 0.98 0.85
Capacity kW 5.70 4.56
3.80
3.42 3.23 2.85 2.66 2.47
20ºC
Input kW. 1.70 1.36
1.13
1.07 1.02 0.96 0.90 0.79
Capacity kW 5.24 4.20 3.50 3.15 2.97 2.62 2.45 2.27
22ºC
Input kW. 1.56 1.25 1.04 0.99 0.94 0.88 0.83 0.73
Capacity kW 4.56 3.65 3.04 2.74 2.58 2.28 2.13 1.98
27ºC
Input kW. 1.36 1.08 0.90 0.86 0.81 0.77 0.72 0.63
20
Page 23
Model: ASF-18A
Cooling OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 5.22 4.99 4.81 4.54 4.35 4.22 4.08
Sensitive capacity kW 4.17 3.99 3.85 3.63 3.48 3.37 3.27
21ºC D
15ºC W
Input kW. 1.20 1.37 1.54 1.71 1.88 2.05 2.22
Total capacity kW 5.71 5.46 5.27 4.97 4.77 4.62 4.47
Sensitive capacity kW 4.57 4.37 4.21 3.97 3.82 3.70 3.58
24ºC D
17ºC W
Input kW. 1.26 1.44 1.62 1.81 1.99 2.17 2.35
Total capacity kW 6.21 5.94 5.72
5.40
5.18 5.02 4.86
Sensitive capacity kW 4.97 4.75 4.58 4.32 4.15 4.02 3.89
27ºC D
19ºC W
Input kW. 1.33 1.52 1.71
1.90
2.09 2.28 2.47
Total capacity kW 7.14 6.83 6.58 6.21 5.96 5.78 5.59
Sensitive capacity kW 5.71 5.46 5.27 4.97 4.77 4.62 4.47
32ºC D
23ºC W
Input kW. 1.53 1.75 1.97 2.19 2.40 2.62 2.84
Heating OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW 10.35 8.28 6.90 6.21 5.87 5.18 4.83 4.49
15ºC
Input kW. 3.19 2.55 2.13 2.02 1.91 1.81 1.70 1.49
Capacity kW 9.72 7.78 6.48 5.83 5.51 4.86 4.54 4.21
18ºC
Input kW. 3.00 2.40 2.00 1.90 1.80 1.70 1.60 1.40
Capacity kW 9.00 7.20
6.00
5.40 5.10 4.50 4.20 3.90
20ºC
Input kW. 2.78 2.22
1.85
1.76 1.67 1.57 1.48 1.30
Capacity kW 8.28 6.62 5.52 4.97 4.69 4.14 3.86 3.59
22ºC
Input kW. 2.55 2.04 1.70 1.62 1.53 1.45 1.36 1.19
Capacity kW 7.20 5.76 4.80 4.32 4.08 3.60 3.36 3.12
27ºC
Input kW. 2.22 1.78 1.48 1.41 1.33 1.26 1.18 1.04
21
Page 24
Model: ASF-24A
Cooling OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 6.86 6.56 6.32 5.96 5.73 5.55 5.37
Sensitive capacity kW 5.49 5.25 5.06 4.77 4.58 4.44 4.29
21ºC D
15ºC W
Input kW. 1.70 1.94 2.19 2.43 2.67 2.92 3.16
Total capacity kW 7.51 7.19 6.92 6.53 6.27 6.07 5.88
Sensitive capacity kW 6.01 5.75 5.54 5.23 5.02 4.86 4.70
24ºC D
17ºC W
Input kW. 1.80 2.05 2.31 2.57 2.82 3.08 3.33
Total capacity kW 8.17 7.81 7.53
7.10
6.82 6.60 6.39
Sensitive capacity kW 6.53 6.25 6.02 5.68 5.45 5.28 5.11
27ºC D
19ºC W
Input kW. 1.89 2.16 2.43
2.70
2.97 3.24 3.51
Total capacity kW 9.39 8.98 8.65 8.17 7.84 7.59 7.35
Sensitive capacity kW 7.51 7.19 6.92 6.53 6.27 6.07 5.88
32ºC D
23ºC W
Input kW. 2.17 2.48 2.79 3.11 3.42 3.73 4.04
Heating OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW 13.80 11.04 9.20 8.28 7.82 6.90 6.44 5.98
15ºC
Input kW. 4.83 3.86 3.22 3.06 2.90 2.74 2.58 2.25
Capacity kW 12.96 10.37 8.64 7.78 7.34 6.48 6.05 5.62
18ºC
Input kW. 4.54 3.63 3.02 2.87 2.72 2.57 2.42 2.12
Capacity kW 12.00 9.60
8.00
7.20 6.80 6.00 5.60 5.20
20ºC
Input kW. 4.20 3.36
2.80
2.66 2.52 2.38 2.24 1.96
Capacity kW 11.04 8.83 7.36 6.62 6.26 5.52 5.15 4.78
22ºC
Input kW. 3.86 3.09 2.58 2.45 2.32 2.19 2.06 1.80
Capacity kW 9.60 7.68 6.40 5.76 5.44 4.80 4.48 4.16
27ºC
Input kW. 3.36 2.69 2.24 2.13 2.02 1.90 1.79 1.57
22
Page 25
Model: ASF-30A
Cooling OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 8.89 8.50 8.19 7.73 7.42 7.19 6.96
Sensitive capacity kW 7.11 6.80 6.55 6.18 5.94 5.75 5.56
21ºC D
15ºC W
Input kW. 2.36 2.70 3.04 3.38 3.71 4.05 4.39
Total capacity kW 9.73 9.31 8.97 8.46 8.13 7.87 7.62
Sensitive capacity kW 7.79 7.45 7.18 6.77 6.50 6.30 6.09
24ºC D
17ºC W
Input kW. 2.49 2.85 3.21 3.56 3.92 4.28 4.63
Total capacity kW 10.58 10.12 9.75
9.20
8.83 8.56 8.28
Sensitive capacity kW 8.46 8.10 7.80 7.36 7.07 6.84 6.62
27ºC D
19ºC W
Input kW. 2.63 3.00 3.38
3.75
4.13 4.50 4.88
Total capacity kW 12.17 11.64 11.21 10.58 10.16 9.84 9.52
Sensitive capacity kW 9.73 9.31 8.97 8.46 8.13 7.87 7.62
32ºC D
23ºC W
Input kW. 3.02 3.45 3.88 4.31 4.74 5.18 5.61
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW 16.22 12.97 10.81 9.73 9.19 8.11 7.57 7.03
15ºC
Input kW. 6.04 4.83 4.03 3.82 3.62 3.42 3.22 2.82
Capacity kW 15.23 12.18 10.15 9.14 8.63 7.61 7.11 6.60
18ºC
Input kW. 5.67 4.54 3.78 3.59 3.40 3.21 3.02 2.65
Capacity kW 14.10 11.28
9.40
8.46 7.99 7.05 6.58 6.11
20ºC
Input kW. 5.25 4.20
3.50
3.33 3.15 2.98 2.80 2.45
Capacity kW 12.97 10.38 8.65 7.78 7.35 6.49 6.05 5.62
22ºC
Input kW. 4.83 3.86 3.22 3.06 2.90 2.74 2.58 2.25
Capacity kW 11.28 9.02 7.52 6.77 6.39 5.64 5.26 4.89
27ºC
Input kW. 4.20 3.36 2.80 2.66 2.52 2.38 2.24 1.96
23
Page 26
Model: ASF-36A
Cooling OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 10.14 9.70 9.35 8.82 8.47 8.20 7.94
Sensitive capacity kW 8.11 7.76 7.48 7.06 6.77 6.56 6.35
21ºC D
15ºC W
Input kW. 2.36 2.70 3.04 3.38 3.71 4.05 4.39
Total capacity kW 11 .11 10.63 10.24 9.66 9.27 8.98 8.69
Sensitive capacity kW 8.89 8.50 8.19 7.73 7.42 7.19 6.96
24ºC D
17ºC W
Input kW. 2.49 2.85 3.21 3.56 3.92 4.28 4.63
Total capacity kW 12.08 11.55 11.13
10.50
10.08 9.77 9.45
Sensitive capacity kW 9.66 9.24 8.90 8.40 8.06 7.81 7.56
27ºC D
19ºC W
Input kW. 2.63 3.00 3.38
3.75
4.13 4.50 4.88
Total capacity kW 13.89 13.28 12.80 12.08 11.59 11.23 10.87
Sensitive capacity kW 11. 11 10.63 10.24 9.66 9.27 8.98 8.69
32ºC D
23ºC W
Input kW. 3.02 3.45 3.88 4.31 4.74 5.18 5.61
Heating OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW 19.67 15.73 13.11 11.80 11.14 9.83 9.18 8.52
15ºC
Input kW. 6.38 5.11 4.26 4.04 3.83 3.62 3.40 2.98
Capacity kW 18.47 14.77 12.31 11.08 10.47 9.23 8.62 8.00
18ºC
Input kW. 5.99 4.80 4.00 3.80 3.60 3.40 3.20 2.80
Capacity kW 17.10 13.68
11.40
10.26 9.69 8.55 7.98 7.41
20ºC
Input kW. 5.55 4.44
3.70
3.52 3.33 3.15 2.96 2.59
Capacity kW 15.73 12.59 10.49 9.44 8.91 7.87 7.34 6.82
22ºC
Input kW. 5.11 4.08 3.40 3.23 3.06 2.89 2.72 2.38
Capacity kW 13.68 10.94 9.12 8.21 7.75 6.84 6.38 5.93
27ºC
Input kW. 4.44 3.55 2.96 2.81 2.66 2.52 2.37 2.07
24
Page 27
Model: ASF-48A
Cooling OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 13.52 12.94 12.47 11.76 11.29 10.94 10.58
Sensitive capacity kW 10.82 10.35 9.97 9.41 9.03 8.75 8.47
21ºC D
15ºC W
Input kW. 2.96 3.38 3.81 4.23 4.65 5.08 5.50
Total capacity kW 14.81 14.17 13.65 12.88 12.36 11.98 11.59
Sensitive capacity kW 11.85 11.33 10.92 10.30 9.89 9.58 9.27
24ºC D
17ºC W
Input kW. 3.13 3.57 4.02 4.47 4.91 5.36 5.80
Total capacity kW 16.10 15.40 14.84
14.00
13.44 13.02 12.60
Sensitive capacity kW 12.88 12.32 11.87 11.20 10.75 10.42 10.08
27ºC D
19ºC W
Input kW. 3.29 3.76 4.23
4.70
5.17 5.64 6.11
Total capacity kW 18.52 17.71 17.07 16.10 15.46 14.97 14.49
Sensitive capacity kW 14.81 14.17 13.65 12.88 12.36 11.98 11.59
32ºC D
23ºC W
Input kW. 3.78 4.32 4.86 5.41 5.95 6.49 7.03
Heating OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW 26.22 20.98 17.48 15.73 14.86 13.11 12.24 11.36
15ºC
Input kW. 8.45 6.76 5.64 5.35 5.07 4.79 4.51 3.94
Capacity kW 24.62 19.70 16.42 14.77 13.95 12.31 11.49 10.67
18ºC
Input kW. 7.94 6.35 5.29 5.03 4.76 4.50 4.23 3.70
Capacity kW 22.80 18.24
15.20
13.68 12.92 11.40 10.64 9.88
20ºC
Input kW. 7.35 5.88
4.90
4.66 4.41 4.17 3.92 3.43
Capacity kW 20.98 16.78 13.98 12.59 11.89 10.49 9.79 9.09
22ºC
Input kW. 6.76 5.41 4.51 4.28 4.06 3.83 3.61 3.16
Capacity kW 18.24 14.59 12.16 10.94 10.34 9.12 8.51 7.90
27ºC
Input kW. 5.88 4.70 3.92 3.72 3.53 3.33 3.14 2.74
25
Page 28
Model: ASF-60A
Cooling OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 16.42 15.71 15.14 14.28 13.71 13.28 12.85
Sensitive capacity kW 13.14 12.57 12.11 11.42 10.97 10.62 10.28
21ºC D
15ºC W
Input kW. 3.78 4.32 4.86 5.40 5.94 6.48 7.02
Total capacity kW 17.99 17.20 16.58 15.64 15.01 14.55 14.08
Sensitive capacity kW 14.39 13.76 13.26 12.51 12.01 11.64 11.26
24ºC D
17ºC W
Input kW. 3.99 4.56 5.13 5.70 6.27 6.84 7.41
Total capacity kW 19.55 18.70 18.02
17.00
16.32 15.81 15.30
Sensitive capacity kW 15.64 14.96 14.42 13.60 13.06 12.65 12.24
27ºC D
19ºC W
Input kW. 4.20 4.80 5.40
6.00
6.60 7.20 7.80
Total capacity kW 22.48 21.51 20.72 19.55 18.77 18.18 17.60
Sensitive capacity kW 17.99 17.20 16.58 15.64 15.01 14.55 14.08
32ºC D
23ºC W
Input kW. 4.83 5.52 6.21 6.90 7.59 8.28 8.97
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW 34.50 27.60 23.00 20.70 19.55 17.25 16.10 14.95
15ºC
Input kW. 10.35 8.28 6.90 6.56 6.21 5.87 5.52 4.83
Capacity kW 32.40 25.92 21.60 19.44 18.36 16.20 15.12 14.04
18ºC
Input kW. 9.72 7.78 6.48 6.16 5.83 5.51 5.18 4.54
Capacity kW 30.00 24.00
20.00
18.00 17.00 15.00 14.00 13.00
20ºC
Input kW. 9.00 7.20
6.00
5.70 5.40 5.10 4.80 4.20
Capacity kW 27.60 22.08 18.40 16.56 15.64 13.80 12.88 11.96
22ºC
Input kW. 8.28 6.62 5.52 5.24 4.97 4.69 4.42 3.86
Capacity kW 24.00 19.20 16.00 14.40 13.60 12.00 11.20 10.40
27ºC
Input kW. 7.20 5.76 4.80 4.56 4.32 4.08 3.84 3.36
26
Page 29
8. Air Velocity and Temperature Distributions
Discharge angle 60° (CEILING)
Airflow velocity
Temperature
27
Page 30
Discharge angle 60°(FLOOR)
Airflow velocity
Temperature
28
Page 31
9. Electric Characteristics
Power supply Indoor fan motor
Model
Hz Voltage Power output FLA
ASF-12A 50 220~240 25 0.13
ASF-18A 50 220~240 55 0.355
ASF-24A 50 220~240 55 0.355
ASF-30A 50 220~240 80 0.475
ASF-36A 50 380 80 0.475
ASF-48A 50 380 59 0.34
ASF-60A 50 380 59 0.34
Symbols:
FLA: Full Load Amps.
29
Page 32
10. Sound Levels
Ceiling Floor
Low airflow
High airflow
12000 BTU/h 18000 BTU/h
Octave band center frequencyŁ ¨HzŁ ©
Sound pressure level dBŁ ¨0dB=0.0002¦ Ě barŁ ©
Audibility limits of continuous white sound
Octave band center frequenc
y
Ł ¨
HzŁ ©
Sound pressure level dBŁ ¨0dB=0.0002¦ Ě barŁ ©
Audibility limits of continuous white sound
Ceiling Floor
30
Page 33
24000 BTU/h 30000 BTU/h 36000 BTU/h
Sound pressure level dBŁ ¨0dB=0.0002¦ Ě ba rŁ ©
Octave band center frequencyŁ ¨HzŁ ©
Audibility lim its of continuous white sound
Sound pressure level dBŁ ¨0dB=0.0002¦
Ě
ba
r
Ł ©
Octave band center frequencyŁ ¨HzŁ ©
Audibilit y li m i ts o f continuous white sound
Ceiling Floor
48000 BTU/h 60000 BTU/h
Octave band center frequencyŁ ¨HzŁ ©
Sound pressure level dBŁ ¨0dB=0.0002¦ Ě barŁ ©
Audibility limits of continuous white sound
Octave band center frequencyŁ ¨HzŁ ©
Sound pressure level dBŁ ¨0dB=0.0002¦ Ě barŁ ©
Audibility limits of continuous white sound
Ceiling Floor
31
Page 34
11. Exploded view
11.1 ASF-12A ASF-18A ASF-24A
No. Part Name Quantity No. Part Name Quantity
1
A
ir inlet grille 1 20 Installation clamp 2
2 filter 2 21 Right holder,eva 1
3 Electric control assy 1 22 Base pan 1
3.1 Electric part box 1 23 Evaporator 1
3.2
Wire joint 1 23.1 Electric expansive valve 1
3.3 Wire jointROHS 1 23.2 Electric Expansion loop 1
3.4 Pipe Temperature Sensor Ass'y II 1 24 left holder, eva 1
3.5 Pipe Temperature Sensor Ass'y 1 25 left fixed board, eva 1
3.6
Transformer 1 26 left frame holder, eva 1
3.7 Main control PCB 1 27 left clapboard 1
3.8 Fan motor capacitor
1
28 right installation board 1
4
Cover for E-box 1 29 right clapboard 1
5
Panel Ass'y 1 30 middle beam 1
6
Display panel box 1 31 grille lock 1
7
Display PCB assy 1 32 fan motor 1
8
Manual button 1 33 grille strip 2
9
Sealing foam I for air out frame 1 34 grille strip screw 2
10
Sealing foam II for air out frame 2 35 Sroll-shell, down 2
11 Sealing foam III for air out frame 1 36 Sroll-shell, up 2
32
Page 35
12 Air-out frame assy 1 37 fan 2
13 Back clapboard 1 38 left fixing clamp for motor 1
14 wiry holder for water collector 1 39 right fixing clamp for motor 1
15 Collect water pan assy 1 40 Strenghten board for motor 1
16 plastic cover 1 41 left installation board 1
17
base pan frame assy 1 42 holder 1
18 Right frame holder, eva 1 43 Remote Controller 1
19 Right fixed board, eva 1
11.2 ASF-30A ASF-36A
33
Page 36
No. Part Name Quantity No. Part Name Quantity
1 Air inlet grille 1 21 Right holder,eva 1
2 filter 3 22 Base pan 1
3 E-Parts box ass'y 1 23 Evaporator 1
3.1 Electric part box 1 24 left holder, eva 1
3.2
Wire joint 1 25 left fixed board, eva 1
3.3 Wire joint 1 26 left frame holder, eva 1
3.4 Pipe temp. sensor ass'y 1 27 left clapboard 1
3.5 Room temp. sensor ass'y 1 28 right installation board 1
3.6
Transformer 1 29 right clapboard 1
3.7 Main control PCB 1 30 middle beam 1
3.8 Fan motor capacitor
1
31 grille lock 2
4
Cover for E-box 1 32 fan motor 1
5
Panel ass'y 1 33 grille strip 2
6
Display panel box 1 34 grille strip screw 2
7
Display board ass'y 1 35 Sroll-shell, down 3
8
Manual button 1 36 Sroll-shell, up 3
9
Sealing foam I for air out frame 1 37 fan 3
10
Sealing foam II for air out frame 3 38 left fixing clamp for motor 1
11 Sealing foam III for air out frame
1
39 right fixing clamp for motor 1
12 Air-out frame assy 1 40 Strenghten board for motor 1
13 Back clapboard 1 41 left installation board 1
14 wiry holder for water collector 1 42 Supporting board for bearing 1
15 Collect water pan assy 1 43 bearing underlay 1
16 plastic cover 1 44 Axis 1
17
base pan frame assy 1 45 Fixing board for bearing 1
18 Right frame holder, eva 1 46 Coupling 1
19 Right fixed board, eva 1 47 holder 1
20 Installation clamp 2 48 Remote Controller 1
34
Page 37
11.3 ASF-48A ASF-60A
No. Part Name Quantity No. Part Name Quantity
1 Air inlet grille 2 23 left sealing board 1
2 filter
4
24 left clapboard 1
3 left fixing clamp for motor 2 25 E-Parts box ass'y 1
4
right fixing clamp for motor 2 25.1 Wire joint 1
5
Strenghten board for motor 2
25.2
Wire joint 1
6
E-part box underlay 1 25.3 Pipe temp. sensor ass'y 1
7
Sroll-shell, down 4 25.4 Room temp. sensor ass'y 1
8
Sroll-shell, up 4 25.5 Transformer 1
9
fan 2
25.6
Main control PCB 1
10
fan motor 2 25.7 Fan motor capacitor 2
11 fan motor holder 2 25.8 Electric part box 1
12 right holder, filter 2 26 Cover for E-box 1
13 left holder, filter 2 27 Collect water pan ass'y 1
14 middle beam 1 28 cover 1
15 pipe fixed board 1 29 Display board ass'y 1
16 Sealing foam for collect pan 2 30 Display panel box 1
17
Installation clamp 2 31 Sealing foam I for air out frame 2
18 right clapboard 1 32 Air-out frame assy 1
19 right sealing board 1 33 Evaporator 1
20 right installation board 1 34 plastic cover 1
21 Base pan ass'y 1 35 holder 1
22 left installation board 1 36 Remote Controller 1
35
Page 38
Part 3
Outdoor Units
Outdoor Units………………………………………………………………..37
36
Page 39
Outdoor Units
1. Dimensions……………………………………………………………………………………..38
2. Service Space…………………………………………………………………………………..41
3. Wiring Diagrams……………………………………………………………………………….42
4. Field Wiring……………………………………………………………………………………..45
5. Electric Characteristics………………………………………………………………………46
6. Operation Limits……………………………………………………………………………….46
7. Sound Levels…………………………………………………………………………………..47
8. Exploded view………………………………………………………………………………….49
9. Troubleshooting……………………………………………………………………………….56
37
Page 40
1. Dimensions
1.1 ASF-12A
290
315
285
530
62
590
750
110
1.2. ASF-18A
12. 5
38
Page 41
1.3. ASF-24A
330
62
895
860
590
141
1.4. ASF-30A ASF-36A
39
Page 42
1.5. ASF-48A ASF-60A
40
Page 43
600mm
M10 bolt
4pieces per unit
41
2. Service Space
Capacity 60000 Btu/h
>30cm
>60cm
>
3
0
c
m
>
2
0
0
c
m
(Wall or obstacle)
Air inlet
Air outlet
Air inlet
Maintain channel
>
6
0
c
m
Obstacle
Fix with bolt
Deep foundation
Necessary width
Page 44
3. Wiring diagrams
3.1 Cooling & Heating
3.1.1. ASF-12A
3.1.2. ASF-18A
42
Page 45
3.1.3. ASF-24A
3.1.4. ASF-30A
1
2
4
5
RES
L312N
43
PART NAME
COMP. RUN CAP.
OUTDOOR FAN CAP. COMPRESSOR OUTDOOR FUN AC CONTACTOR PIPE TEMP. SENSOR CONNECTORS 5 - WAY TERMINAL
2-WAY TEMINAL
MIDDLE TEMINAL
4-WAY VALVE
2 - WAY TERMINAL
CODE
CAP1 CAP2
COMP FAN KM1 RT3 XS1, XP1 XT1 XT2 XT3 VALVE
CODE
HEATER
FAN
COMP
CAP1
CAP2
XT3
XT4
XT7, XT8
VALVE
K1
RT3
KM8
K2
CAP3
RELAY
RES
PART NAME
CRANK
OUTDOOR FAN
COMPRESSOR
COMPRESSOR RUN CAPACITOR
FAN CPACITOR
5-WAY TERMINAL
3-WAY TERMINAL
MIDDLE TERMINAL
REVERSING VALVE
GAS TEMP. SWITCH
PIPE TEMPERATURE SENSOR
AC CONTACTOR
HIGH PRESSURE SWITCH
STARTING RELAY
DISCHARGE RESISTANCE
STARTING CAPACITOR
WARNING: IF THE INDOOR UNIT IS T1&T2&DL
SERIES, PLEASE PUT THE LINES ON XT3 TO INDOOR UNIT
XT1'S CORRELATIVE PART!
Page 46
3.1.5. ASF-36A
3.1.6. ASF-48A
2
0
6
K1H- PRO
X
P
9
T5
2
0
8
2
0
3
FAN3
WHITE
BACK( HI)
BLUE
RED
YELLOW
S. V.
BLUE
Y
E
L
L
O
W
B
L
U
E
(
S
.
V
)
RED( L OW)
COMP
1 2 3
4
5
BLUE
RED YE LL OW
WHITE
BLUE( N)
HEAT
BLACK( L 1)
B
L
U
E
(
N
)
R
E
D
(
A
1
)
R
E
D
(
A
1
)
B
L
U
E
(
S
.
V
)
B
L
A
C
K
(
H
I
)
XT5
XT6
XT7
W
V
U
FAN4
CAP3
CAP4
C
O
L
D
M
O
D
U
L
E
XT2
XT1
BLACK( L 2 )
BLACK( L 1)
Y/ G
Y/ G
R
T
5
R
T
3
R
T
1
C
N
C
N
C
N
CN
CNCN
201
100
200
X
S
8
X
P
8
4
A
BCN
A1
1
2
3
4
5
6
21
22
KM1
A2
BLUE
RED
R
E
D
BLACK
BLACK
BLUE( N)
B
L
U
E
(
N
)
BLUE( N)
BLACK( L 3)
44
CODE
COMP
FAN3
CAP3
S.V.
KM1
HEAT
XT4
XT5-7
H-PRO
T201
RT3
XS8-9
XP8-9
CN100-208
K1
RT4
XT3
T5
PART NAME
COMPRESSOR
OUTDOOR FAN
FAN CAP.
4-WAY VALVE
AC CONTACTOR
CRANK
4-WAY TERMINAL
CONNECTOR
HIGH PRESSURE SWITCH
CURRENT DETECTOR
PIPE TEMP. SENSOR
CONNECTORS
CONNECTORS
P.C. BOARD SOCKETS
TEMP. PROTECT SWITCH
ROOM TEMP. SENSOR
5-WAY TERMINAL
TRANSFORMER
CODE
COMP
FAN3 FAN4
CAP3 CAP4
S.V
KM1
HEAT
H-PRO RT3 XS8-9 XP8-9 CN100-208 K1
RT4 XT1 T5 RT5
PART NAME
COMPRESSOR
OUTDOOR FAN
FAN CAP.
4-WAY VALUE AC CONTACTOR
CRANK HIGH PRESSURE SWITCH
PIPE TEMP. SENSOR CONNECTORS CONNECTORS P.C. BOARD SOCKETS TEMP. PROTECT SWITCH ROOM TEMP. SENSOR 5-WAY TERMINAL TRENSFORMER TEMP. SENSOR
TO INDOOR UNIT TO INDOOR UNIT
Page 47
4. Field Wiring
45
Page 48
5. Electric Characteristics
Power supply Compressor Outdoor fan motor
Model
Hz Voltage MSC RLA
Power output
FLA
ASF-12A 50 220~240 5.3 26 24 0.27
ASF-18A 50 220~240 8.75 36.8 53 0.61
ASF-24A 50 220~240 11.4 61 53 0.66
ASF-30A 50 220~240 17.65 97 250 1.38
ASF-36A 50 380 6.58 61 250 1.38
ASF-48A 50 380 8.22 66 65 0.7
ASF-60A 50 380 9.77 67 65 0.7
Symbols:
MSC: Max. Starting Current RLA: Rated Locked Current FLA: Full Load Amps.
6. Operation Limits
Ensure the operating temperature is in allowable range.
46
Page 49
7. Sound levels
1m
Microphone
12000 Btu/h 18000 Btu/h
47
Page 50
24000 Btu/h 30000 Btu/h & 36000 Btu/h
48000 Btu/h & 60000 Btu/h
48
Page 51
Cooling & Heating
8.1 ASF-12A
No. Part Name Quantity No. Part Name Quantity
1 Clamp for front net 6 15 Capacitor clamp 1
2 Front net 1 16 Wire joint,5p 1
3 Front clapboard
1
Wire joint, 2p 1
4 Propeller fan 1 17 Left supporter 1
5 Fan motor 1 18 Separating board 1
6 Holder for fan motor 1 19 Condenser 1
7 Chassis 1 20 Water collector 1
8 Compressor 1 21 Right clapboard 1
9 Installation plate for valves 1 22 Big handle 1
10
Gas pipe valve 1 23 Cover 1
4-way valve 1 24 Small handle 1
11 Liquid pipe valve 1 25 Rear net 1
12 Fan motor capacitor 1
26
Copper nut, TLM-C03 1
13 Installation board for E-parts 1
27
Copper nut, TLM-A01 1
14 Compressor capacitor 1 28 Pipe temp sensor ass'y 1
8. Exploded view
49
Page 52
No. Part Name Quantity No. Part Name Quantity
1 Clamp for front net 8 19 Wire joint 1
2 Front net 1 20 Separating board 1
3 Front clapboard 1 21 Installation board for E-parts 1
4 Propeller fan
1
22 Washer for wire joint 1
5 Fan motor 1 23 Clamp for wiring 1
6 Holder for fan motor 1 24 Compressor capacitor 1
7 Foam over holder for motor 1 25 Capacitor clamp 1
8 Cover 1 26 Chassis 1
9 Little handle 1 27 Front right clapboard 1
10 Condenser 1 28 Compressor 1
11 Support board for motor holder 1 29 Liquid valve assy 1
12 Left clapboard 1 30 Liquid pipe valve 1
13 Rear net 1 31 4-Ways valve assy 1
14 Rear right clapboard 1 Gas pipe valve 1
15 Big handle 1
32
Four-way Valve 1
16 Installation plate for valves 1 33 Copper nut, TLM-A01 1
17 Water collector 1 34 Copper nut, TLM-C03 1
18 Fan motor capacitor 1
8.2 ASF-18A
50
Page 53
No. Part Name Quantity No. Part Name Quantity
1 Front net 1 20
A
C contactor 1
2 Cabinet,Front 1 21 Capacitor,Fan Motor 1
3 Fan,Propeller
1
22 Wire Clamp 1
4 Fan Motor 1 Terminal Block,5p 1
5 Mount,Fan Motor 1
23
Terminal Block,2p 1
6 Topcap Ass'y 1 24 Compressor 1
7 Condenser Ass'y 1 25 Fixture,Segregator 1
8 Inlet Pipe for Condenser 1 4-way Valve 1
9 Outlet Pipe for Condenser 1
26
4-way Valve Solenoid 1
10 Rear Net 1 27 Liquid pipe valve 1
11 Support board,Back side 1 28 Capillary pipe 1
12 Handle 2 29 Gas pipe valve 1
13 Separating board 1 30 refrigerant Container 1
14 Base Pan Ass'y 1 31 Pipe temp. sensor assy 1
15 Cabinet,Front-Right 1 32 Support board, Left Side 1
16 Capacitor Clamp 1 33 Big handle 1
17 Capacitor, Compressor 1 34 Filter 1
Wiring Installation Panel 1 35 Small Handle 1
Washer for wire joint 1 36 Copper nut, TLM-B02 1
18
Terminal install board 1 37 Copper nut, TLM-D04 1
19 Terminal Block,2p 1
8.3 ASF-24A
51
Page 54
No. Part Name Quantity No. Part Name Quantity
1 Clamp for front net 10 20 Fan motor capacitor 1
2 Front net 1 21 Installation board for E-parts 1
3 Front clapboard 1 22 AC contactor 1
4 Propeller fan 1 23 Main control box 1
5 Fan motor 1 24 Wire joint for multiplexer 2
6 Holder for fan motor 1 25 Wire joint for multiplexer 1
7 Chassis 1 26 Washer for wire joint 1
8 Separating board 1 27 Wire clamp 1
9 Cover 1 28 Wire joint for power 1
Condenser I 1 29 Liquid valve assy 1
10
Condenser II 1 30 Liquid valve 1
11 Support board for motor holder 1 31 4-way valve assy 1
12 Left supporting bar 1 32 4-way Valve 1
13 Rear net 1 33 Gas valve 1
14 Rear right clapboard 1 34 Compressor 1
15 Big handle 1 35 Discharge temp sensor 1
16 Installation plate for valves 1 36 Front right clapboard 1
17 Pipe temp sensor 1 37 Copper nut, TLM-C03 1
18 Refrigerant container 1 38 Copper nut, TLM-E05 1
19 Container clamp 1
8.4 ASF-30S
52
Page 55
No. Part Name Quantity No. Part Name Quantity
1 Clamp for front net 10 20 Fan motor capacitor 1
2 Front net 2 21 Installation board for E-parts 1
3 Front clapboard 1 22 AC contactor 1
4 Propeller fan 1 23 Main control board,Outdoor unit 1
5 Fan motor 1 24 Wire joint for multiplexer 2
6 Holder for fan motor 1 25 Wire joint for multiplexer 1
7 Chassis 1 26 Washer for wire joint 1
8 Separating board 1 27 Wire clamp 1
9 Cover 1 28 Wire joint for power 1
Condenser I 1 29 Liquid valve assy 1
10
Condenser II 1 30 Liquid valve 1
11 Support board for motor holder 1 31 4-way valve assy 1
12 Left supporting bar 1 32 4-way valve 1
13 Rear net 1 33 Gas valve 1
14 Rear right clapboard 1 34 Compressor 1
15 Big handle 1 35 Discharge temp sensor 1
16 Installation plate for valves 1 36 Front right clapboard 1
17 Pipe temp sensor 1 37 Copper nut, TLM-C03 1
18 Refrigerant container 1 38 Copper nut, TLM-E05 1
19 Container clamp 1
8.5 ASF-36A
53
Page 56
No. Part Name Quantity No. Part Name Quantity
1 Front net 2 17 Capacitor,Fan Motor 2
2 Cabinet,Front 1 18 Terminal Block,2p 3
3 Fan,Propeller
2
19
A
C contactor 1
4
Fan Motor 2 20 Low Pressure Valve 1
5 Room temp. sensor,outdoor 1 21 PCB board,outdoor unit 1
6 Mount,Fan Motor 1 22 Terminal Block,3p 1
7 Topcap Ass'y 1 23 Wire joint for power 1
Condensator I 1 24 Compressor 1
8
Condensator II 1 25 Refrigerator Container 1
9 Left Side Cabinet 1 26 Fixture,Segregator 1
10 Supporter, Rear Cabinet 1 Four-way Valve 1
10 Supporter, Rear Cabinet 1
27
Four-way Valve Solenoid 1
11 Cabinet,Back side 1 28 Low Pressure Valve 1
12 Handle 2 29 Capillary Tube Ass'y 1
13 Plate,Sound-proof 1 30 Electric heat belt for comp 1
14 Base Pan Ass'y 1 31 Discharge temp controller 1
15 Cabinet,Front Side 1 32 Pipe temp. sensor 1
16 E-control box, assy 1
8.6 ASF-48A
54
Page 57
No. Part Name Quantity No. Part Name Quantity
1 Guard fan 2 17 Capacitor,Fan Motor 2
2 Cabinet,Front 1 18 Terminal Block,2p 3
3 Fan,Propeller
2
19
A
C contactor 1
4
Fan Motor 2 20 Low Pressure Valve . 1
5 Room temp. sensor,outdoor 1 21 PCB board,outdoor unit 1
6 Mount,Fan Motor 1 22 Terminal Block,4p 1
7 Topcap Ass'y 1 23 Wire joint for power 1
Condensator I 1 24 Compressor 1
8
Condensator II 1 25 Refrigerator Container 1
9 Left Side Cabinet 1 26 Fixture,Segregator 1
10 Supporter, Rear Cabinet 1 4-way Valve 1
10 Supporter, Rear Cabinet 1
27
4-way Valve Solenoid 1
11 Cabinet,Back side 1 28 Low Pressure Valve 1
12 Handle 2 29 Capillary Tube Ass'y 1
13 Plate,Sound-proof 1 30 Electric heat belt for comp 1
14 Base Pan Ass'y 1 31 Discharge temp controller 1
15 Cabinet,Front Side 1 32 Pipe temp. sensor 1
16 E-control box, assmy 1
8.7 ASF-60A
55
Page 58
9. Troubleshooting
9.1 Indoor unit’s LED indication of trouble
NO. Protection or Malfunction Operation
lamp
Timer lamp Defrosting
lamp
Auto
recover
1
Indoor temp. sensor abnormal
×
× Yes
2
Indoor heat exchanger sensor abnormal
× × Yes
3
Outdoor heat exchanger sensor abnormal
× ×
Ye s
4
Outdoor abnormal   
Ye s
5
EEPROM abnormal
× No
×——Extinguish ; ——Flash at 5Hz
9.2 LEDs’ for the indication of outdoor trouble
MOU-36HN1, MOU-48HN1, MOU-60HN1 380-415V, 3 phase
Type Contents LED1 LED2 LED3
Protection Phase sequence Flash Off Off
Protection Overload of current Off Off Flash
Protection Lack of phase Flash Off Off
Protection Protection of pressure Flash Flash Off
Protection Open-circuit and short-circuit trouble of T3 Off Flash Flash
Protection Open-circuit and short-circuit trouble of T4 Off Flash Off
Protection High temperature protection of condenser Flash Flash Flash
56
Page 59
Phase sequence error
Change the order of two of the wires to power supply.
If the problem can not be solved, the outdoor PCB is defective
Switch on the unit again.
9.2.2 Overload of current
Check the current, normally The max. current for MOU-36HN2 is 9.4 A The max. current for MOU-48HN2 is 10.9A The max. current for MOU-60HN2 is 13.2A Is the current in rated range?
Overload of current
No
Yes
Possible reason
1. Outdoor fan is defective
2. The compressor is defective
3. Refrigerant is over charged
4. Air enter the refrigerant system
5. Heat exchanger is too dirty
The outdoor PCB is defective
9.2.1 Phase sequence error:
57
Page 60
Lack of phase
Check the power supply, is it 3 phase,
Yes
Check the connection between power supply and terminal,
Yes
Outdoor PCB is defective
9.2.3 Lack of phase
58
Page 61
Protection of pressure or temp.
Yes
Is it k1 or K2 open ?
Is temp. protective switch K1
Yes
Is pressure protective switch K2
Yes
Possible reason
1. The wires is loose to K1
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is defective
5. Outdoor unit is bad ventilation
6. Refrigerant is leakage
Possible reason
1. The wires is loose to K2
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is defective
5. Outdoor unit is bad ventilation
6. Refrigerant is two much
9.2.4 Protection of pressure or temp.
59
Page 62
No
Repair connector
Yes
Indoor PCB is defective.
Is it the resistance is normal?
Check the resistance of the temp. sensor according to Annex 1
Is connection to connector of temp. sensor good?
Yes
No
Replace the sensor
9.2.6 Open-circuit and short-circuit trouble of T4
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
No
Yes
Replace the sensor
Indoor PCB is defective.
Is it the resistance is normal?
Is connection to connector of temp. sensor good?
9.2.5 Open-circuit and short-circuit trouble of T3
60
Page 63
9.2.7 High temperature protection of condenser
Check the resistance of the temp. sensor according to Annex 1, is it normal?
High temperature protection of condenser
No
Yes
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
Replace the sensor
61
Page 64
If any the following abnormal conditions occur, turn off the power supply immediately. Please contact our dealer.
Indicator lamps flash rapidly, after your disconnecting and connecting the unit, the situation is the same. Fuse or circuit breaker work frequently. Foreign matter or water has fallen into the unit. Remote controller is disabled or the switch is out of hand.
TROUBLES
Any other unusual conditioner is observed. If any of the following conditions occur, check your unit and resolve corresponding problems referring to given remediation. If the trouble can't be settled contact our dealer.
Trouble Cause Solutions
Power failure. Wait for the comeback of power
Power switch is open. Switch on the power
Fuse of power switch may have blown. Replace the fuse
Batteries of remote controller are exhausted. Replace the batteries
Unit does not start
The time is not start-up time you have set. Wait or cancel the time set.
Temperature is not set correctly. Set the temperature properly.
Door or window is open. Close door and window.
Air filter is blocked with dust or dirtiness. Clean the air filter.
Inlet/outlet of indoor/outdoor units are
blocked.
Clear all blockages.
Inlet/outlet of indoor/outdoor units are
blocked.
Clear the blockage, then restart your operation.
Air flowing normally with low cooling(heating) effect
Be in 3 minutes protection of compressor Wait
NOTE: Do not replace electric wire or repair the air conditioner by yourself to avoid possible danger.
9.4 Troubles and solutions concerning the remote controller
Please make the following check before asking for repair or maintenance.
Trouble Cause Solutions
Check if the mode display on the LCD is AUTO
The lndoor Unit will select fan speed automatically when AUTO mode is selected.
CAN NOT CHANGE THE FAN SPEED SETTING
Check if the mode display on the LCD is DRY
The lndoor Unit will select fan speed automatically when the unit is on DRY mode.
The transmission symbol does not flash
Symptom Checking items Cause Press ON/OFF button, the remote controlling signals can not be transmitted
Check if the remote controller has run out of power
When the battery was out, transmission signals can not be sent
9.3 Troubles and Solutions
62
Page 65
Temperature display disappear
Symptom Checking items Cause Temperature Display does not light.
Check if the mode display on the LCD is FAN ONLY
You can not set the temperature when the unit is on FAN ONLY mode.
The Display Goes Off
Symptom Checking items Cause The indication on the display disappears after a lapse of time.
Check whether the timer operation has come to an end when the OFF TIMER is indicated on the display.
The air conditioner operation stops since the set time elapsed.
The ON TIMER indicators go off after a lapse of certain time.
Check whether the timer operation is started when the ON TIMER is indicated on the display.
When the time set to start the air conditioner is reached, the air conditioner will automatically start and the appropriate indicator will go off.
The Signal Receiving Tone does Not Sound
Symptom Checking items Cause No receiving tone sounds from the indoor unit even when the ON/OFF button is pushed.
Check whether the signal transmitter of the remote controller is properly directed to the receiver of the indoor unit when the ON/OFF button is pushed.
Direct the signal transmitter of the remote controller to the receiver of the indoor unit, and then repeatly push the ON/OFF button twice.
Buttons on the remote controller don't work.
Press Reset button.
63
Page 66
Part 4
Installation
Installation……………………………………………………………………65
64
Page 67
1. Refrigerant pipe installation
1.1. Measure the necessary length of the connecting pipe, and make it by the following way. a. Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
CAUTIONS:
z Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds z With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Tubing size Torque
6.35 1420~1720N.cm(144~176kgf.cm)
9.52 3270~3990N.cm(333~407kgf.cm)
12.7 4950~6030N.cm(504~616kgf.cm) 16 6180~7540N.cm(630~770kgf.cm) 19 9720~11860N.cm(990~12106kgf.cm)
b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection. c. Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
1.2. Locate The Pipe a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover. b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation. c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.
1.3. Connect the pipes.
1.4. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow.
1.5. Be sure of no leakage by checking it with leak detector or soap water.
1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage.
65
Page 68
2. Vacuum dry and leakage checking
2.1. Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water (steam temperature) is 100°C. Use vacuum pump to make the pressure in the pipe near vacuum state, the boiling point of water falls relatively. When it falls under outdoor temperature, the moisture in the pipe will be vaporized.
2.2. Vacuum dry procedure There are two methods of vacuum dry due to different construction environment: common vacuum dry, special vacuum dry. a) Common vacuum dry procedure z Vacuum dry (for the first time)---connect the all-purpose detector to the inlet of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the vacuum pump should be below -755mmHg) z If the pump can’t achieve below -755mmHg after pumping 2 hours, moisture or leakage point will still exist
in the pipe. At this time, it should be pumped 1 hour more.
z If the pump can’t achieve -755mmHg after pumping 3 hours, please check if there are some leakage
points.
z Vacuum placement test: place 1 hour when it achieves -755mmHg, pass if the vacuum watch shows no
rising. If it rises, it shows there’s moisture or leakage point.
z Vacuuming from liquid pipe and gas pipe at the same time. z Sketch map of common vacuum dry procedure.
66
Page 69
b) Special vacuum dry procedure
z This vacuum dry method is used in the following conditions: There’s moisture when flushing the refrigerant pipe. Rainwater may enter into the pipe. z Vacuum dry for the first time ······ 2h pumping
c) Vacuum destroy for the second time ······ Fill nitrogen to 0.5Kgf/cm2
Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method can’t dry thoroughly. So, please pay more attention to prevent water entering and forming condensation water.
d) Vacuum dry for the second time······1h pumping
Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat
procedure c) and d). e) Vacuum placing test ······ 1h f) Sketch map of special vacuum dry procedure
3. Additional charge
3.1. When the length of the one-way pipe is less than 5m, additional refrigerant charge after vacuuming is unnecessary.
3.2. When the length of one-way pipe is over 5m, the additional charge quantity is as follows (unit in gram): Calculation method
Refrigerant Liquid diameter (mm) Unit amount (g/m) Formula
Φ6.35 30 (L-5)×30 Φ9.53 65 (L-5)×65
R410A
Φ12.7 90 (L-5)×90
Remark: 1-The additional refrigerant charge is simply related with the liquid pipe diameter.
2-In the up formula, “L” means total length of liquid pipe(unit: m).
67
Page 70
4. Water drainage
4.1. Gradient and Supporting
4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble.
4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop stand.
Diameter Distance between the prop stands Hard PVC pipe 25~40mm 1.5~2m
4.1.3. Precautions a) The diameter of drainpipe should meet the drainage requirement at least. b) The drainpipe should be heat-insulated to prevent atomization. c) Drainpipe should be installed before installing indoor unit. After powering on, there is some water in
water-receiver plate. Please check if the drain pump can operate correctly. d) All connection should be firm. e) Wipe color on PVC pipe to note connection. f) Climbing, horizontal and bending conditions are prohibited. g) The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe. h) Heat-insulation should be done well to prevent condensation. i) Indoor units with different drainage type can’t share one convergent drainpipe.
4.2 Drainpipe Trap
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap.
4.2.2. Every indoor unit needs one drainpipe trap.
4.2.3. A plug should be designed to do cleaning.
Pl u g
5 0 c
m 5
0
c
m
68
Page 71
4.3 Upwards drainage(drain pump)
4.3.1. To ensure the gradient 1/100, the drainpipe can be lifted to 340mm. After upwards, place downwards, or
it will cause malfunction to drain pump.
4.4 Convergent drainage
4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong.
4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.
4.4.3. Selecting the diameter Number of connecting indoor unitsCalculate drainage volumeSelect the diameter Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr)
Allowed volume(lean 1/100) (l/ hr) I.D. (mm) Thick
Hard QV≤14
Φ
25
3.0
Hard 14< QV 88
Φ
30
3.5
Hard 88< QV≤175
Φ
40
4.0
Hard 175< QV≤334
Φ
50
4.5
Hard 334< Q
V
6.0
Φ
80
4.5 Drainage test Drainage without drain pump – After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly.
69
Page 72
5. Insulation work
5.1 Insulation material and thickness
5.1.1. Insulation material Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70 in the high-pressure side, no less than 120 in the low-pressure side(For the cooling type machine, no requirements at the low-pressure side.) Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120) Cooling only type---- Polyethylene foam (withstand above 100)
5.1.2. Thickness choice for insulation material Insulation material thickness is as follows:
Pipe diameter (mm) Adiabatic material thickness
Φ6.4—Φ25.4 10mm
Refrigerant pipe
Φ28.6—Φ38.1 15mm
Drainage pipe
Inner diameterΦ20—Φ32 6mm
5.2 Refrigerant pipe insulation
5.2.1. Work Procedure a) Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated. b) When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated
5.2.2. Insulation for non-jointing parts and non-connection parts
wrong right
Gas pipe and liquid pipe should
not be put together to
insulate
Insulate the gas pipe
(cooling only)
Insulate the gas pipe
and
liquid pipe
70
Page 73
For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes.
5.2.3. Insulate for the jointing area, expanding area and the flange area a) Insulate for the jointing area, expanding area and the flange area should be done after checking leakage
of the pipes
b) Make sure there’s no clearance in the joining part of the accessorial insulation material and local
preparative insulation material.
5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part.
5.4 Note
5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test
5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually.
5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit
71
Page 74
Part 5
Control
Control………………………………………………………………………..73
72
Page 75
1 Remote controller
There’s one model R05-BG/E.
The below is R05-BG/E remote controller.
1
Mo de set t ing
5
ON/OFF
7
Horiz swing
9
Tim e sett in g
6
Air dire cti on setting
8
Vert. swing
11
Time OFF
10
Time ON
Ad jus t
2
Fan s peed se ttin g
4
Adjust
1
3
Co ol/heat
Lock
Reset
15
13
12
14
Confirm b utton
16
E conomic operation
TIME ON
TI M E OF F
CLOCK
SWIN G
A IR DI RE CTI ON
OK
ECO
SW I N G
MOD E
FAN SPEED
M
AUTO
COOL
DRY
HEAT
FAN
TE M P
SET
SET
Visual photo
MODEL AND SPECIFICATION
Model R05/BGE Rated voltage 3.0V(2 pieces of LR03 7# batteries) Min voltage for sending signal of CPU 2.4V
8m~11m
Effective receiving distance Operation condition -5~60OC
73
Page 76
BUTTONS AND FUNCTION
MODE: Once pressing, running mode will be selected in the following sequence:
AUTO
COOL DRY HEAT FAN
NOTE: No heating mode for cool only type unit.
FAN SPEED: Fan speed will be selected in following sequence once pressing this button:
AUTO
LOW MED
HIGH
Adjust
: Decrease the set temp. Keeping pressing will decrease the temp with 1°C per 0.5s.
Adjust
: Increase the set temp. Keeping pressing will increase the temp with 1°C per 0.5s.
ON/OFF: For turning on or turning off the air conditioner. AIR DIRECTION: Activate swing function of air deflector. Once pressing, air deflector will turn 6°. For normal
operation and better cooling and heating effect, deflector will not turn to the degree which is the state of deflector when the unit is turned off.( Only available when remote controller is used with corresponding unit.) HORIZ SWING: Activate or turn off horizontal swing function. (Only available when remote controller is used with corresponding unit.) VERT SWING: Activate or turn off vertical swing function. (Only available when remote controller is used with corresponding unit.) CLOCK: Display the current time. (12:00 is displayed when resetting or electrifying for the first time.) Press CLOCK for 5s, icon indicating hour will flash with 0.5s. Press it again; icon indicating minute will flash with 0.5s.
and are used to adjust the figure. Setting or modification is effective only by pressing OK button to make confirmation. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting. TIME OFF: For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjust the figure to 0.00 will cancel time ON setting. RESET (inner located): Press this button with a needle of 1mm to cancel the current setting and reset remote controller.
LOCK (inner located): Press this button with a needle of 1mm to lock or unlock the current setting. OK: Used to confirm the time setting and modification. COOL/HEAT (inner located): Press this button with a needle of 1mm to shift mode between COOL only and
COOL&HEAT. During setting, background light will be lightened. Factory default mode is COOL&HEAT. ECO: Activate or turn off economic operation mode. It is suggested to turn on this function when sleeping. (Only available when remote controller is used with corresponding unit.)
74
Page 77
2. Wire controller
2.1 KJR-01B/dP(T)
General constant wire controller is available for cooling&heating type as default Its function of Mid-speed Fan can be adjusted by the dial switch (Sw1) in the main panel of wire controller, which is shown as follows:
1 ON 2 ON
1 ON 2 OFF
1 OFF 2 ON
1 OFF 2 OFF
Mid-speed Fan cooling&heating
Mid-speed Fan cooling only
No mid-speed Fan cooling&heating
No mid-speed Fan cooling only
Customers can adjust it according to the model and their requirement. It is necessary to re-electrify after adjustment.
75
Page 78
2.2 KJR-10B/dP(T)
76
Page 79
3. Central controller
3.1 Preparation
Network function is reserved in R410A U series indoor PCB. To realize network control, the following components are required: U series indoor & outdoor units; CCM01/E (Central Control Monitor); NIM01/E (Network interface module); Network software set (including a software CD, aconverter, a softdog).
3.2. Wiring diagram
77
Page 80
3.3 NIM Address setting
Every air-conditioner in network has its unique address to distinguish each other. Address code of air-conditioner in LAN is set by code switch(S1/S2) on NIM, and the set range is 0-63.
S1 S2 Address Code
00 ~ 15
16 ~ 31
32 ~ 47
48 ~ 63
3.4 CCM Address setting
The PC or gateway can connect to a maximum of 16 CCM. Every CCM works as one network area and be distinguished by setting code switch. The setting range is 0-15.
78
Loading...