Do not install and use your portable air conditioner
unit before carefully reading this instruction guide.
Please retain this manual brochure for product
warranty and future reference
CAUTION
1. Do not use means to accelerate the defrosting
process or to clean, other than those
recommended by the manufacturer.
2. The appliance shall be stored in a room without
continuously operating ignition sources (for
example: open flames, an operating gas
appliance or an operating electric heater.)
3. Do not pierce or burn.
4. Be aware that refrigerants may not contain an
odour.
5. Appliance AMC-11P shall be installed, operated
and stored in a room with a floor area larger
than 12m
2
and AMC-14P larger than 13m2.
6. Servicing shall be performed only as
recommended by the manufacturer.
7. The appliance shall be stored in a wellventilated area where the room size
corresponds to the room area as specified for
operation.
8. All working procedure that affects safety means
shall only be carried by competent persons.
Page 3
9. " PLEASE MAKE SURE THE PRODUCT
VENTILATES ALL THE TIME "! Please make
sure the inlet and outlet ventilation is not
blocked at all times.
10. Operate this unit on a horizontal surface to
avoid water leakage.
11. Do not operate this unit in an explosive or
corrosive atmosphere.
12. Operate this unit in an ambient of 35 degree
centigrade or less.
13. The heating function of the unit should be operated
in an indoor ambient temperature between 7℃and
23℃
14. Clean air filter periodically to enjoy the most
efficient cooling.
15. When the unit is shut off, please wait at least
3.5 minutes before restarting this is to prevent
the compressor from being damaged.
16. This unit needs at least 7 Amps of electricity to
have its compressor operational. To avoid the
household electricity block out, please do not
use any extension cord for this unit.
17. This unit is for indoor cooling, heating and
Page 4
dehumidifying.
18. When turning on the unit, the fan will operate
but the compressor will start up after the
cooling alarm flashes for three minutes
● In heating function, the heating alarm will
flash for 3.5 minutes before the compressor
and fan start up.
19. When the supply cord is damaged, it must be
replaced by the manufacturer, its service
agent or similarly qualified persons in order to
avoid hazard.
20. In order to dispose the appliance safely, please
remove the batteries from the unit before
scrapping it.
21. This appliance can be used by children aged from 8
years and above and persons with reduced
physical,sensory or mental capabilities or lack of
experience and knowledge if they have been given
supervision or instruction concerning use of the
appliance in a safe way and understand the
hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall
not be made by children without supervision.
22. The air-conditioner can be connected only to a
supply with system impedance no more than
0.219Ω.In case necessary, please consult your
supply authority for system impedance
information.
23. The appliance shall be installed in accordance with
Page 5
national wiring regulations.
24. Do not operate your air conditioner in a wet room
such as a bathroom or laundry room. (Do not
suitable for the model with window kit)
Transportation, marking and storage for units
1. Transport of equipment containing flammable
refrigerants Compliance with the transport
regulations
2. Marking of equipment using signs
Compliance with local regulations
3. Disposal of equipment using flammable
refrigerants Compliance with national
regulations
4. Storage of equipment/appliances The storage
of equipment should be in accordance with
the manufacturer’s instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be
constructed such that mechanical damage to
the equipment inside the package will not
cause a leak of the refrigerant charge. The
maximum number of pieces of equipment
permitted to be stored together will be
determined by local regulations.
6. The appliance shall be stored so as to prevent
mechanical damage from occurring.
7. General work area All maintenance staff and
Page 6
others working in the local area shall be instructed on
the nature of work being carried out. Work in
confined spaces shall be avoided. The area
around the workspace shall be sectioned off.
Ensure that the conditions within the area have
been made safe by control of flammable material.
ATTENTION
For effective heating and cooling
functions, please ensure that the
following steps are undertaken:
1) Extend the exhaust hose to a
length of not more than
400mm. The exhaust hose
must be kept parallel and
must not be bent up or down.
2) A distance of 500mm
minimum must be kept
between the filter side of the
unit and wall or any other
obstacles”.
3) When this appliance starts to defrost, the word “DF”
will be displayed on the LED
Page 7
CONGRATULATIONS ON YOUR
SELECTION OF A QUALITY
PORTABLE AIR CONDITIONER
PORTABLE AIR CONDITIONER
This Air Conditioner has been designed and manufactured to the
highest standards of modern engineering.
Our product not only provides you a remote control to help user
operate all the functions easily and conveniently but also has below
benefits:
- Moves easily from room to room on easy glide castors
- No installation required-just plug into any household
power outlet
-Powerful refrigerated air system cools down the ambience
instantly whenever you want.
-Dehumidified and filtered air cycle improve breathing
environments effectively.
- Besides the remote control, your one touch electronic pad
also provides easy-identifying manual operation.
- 24 hour programmable timer that can be used with either the
air conditioning or dehumidification setting
- Unique sleep control function
- 220-240 Volt 50Hz operation
- 1.8 meter cord with plug
Page 8
UNPACKING INSTRUCTIONS
1. Place the unit in the correct upright position before unpacking.
2. Cut the two packing straps.
3. Slide the carton in an upwards motion and it will release from the base.
4. Grip the carry handles located on either sides of the unit and carefully lift until it
slides out of the foam base.
5. Remove the air outlet and take out the
exhaust hose as the picture.
6. Install the exhaust hose on the unit before
operating the unit.
CONTENTS
1 / Air conditioner unit
2 / Remote control
3 / Batteries
4/ Window Kit A
Page 9
NAME OF THE PARTS
1. Control panel
2. Remote control receiver
3. Adjustable air vent
4. Joint tube
5. Exhaust hose
6. Upside drain hole
7. Cool air inlet
8. Cool air filter
9. Hot air inlet
10. Hot air filter
11. Downside drain hole
Page 10
CONTROL PANEL & DESCRIPTION OF FUNCTION
˖
1. POWER KEY
Press to turn unit "ON" or "OFF".
2. FUNCTION
Press this key to select cooling, heating, or dehumidifying.
3. T EMP ER ATU RE R EG UL ATI ON KEY (UP)
During cooling function˖This key raises the preset temperature by 1ć each time it is
pressed and the maximum limit is 30ć.
During heating function˖
This key raises the preset temperature by 1ć each time it is
pressed and the maximum limit is 25ć.
4. TEMPERATURE REGULATION KEY (DOWN)
During cooling function˖This key lowers the preset temperature by 1ć each time it is
pressed and the minimum limit is 17ć.
During heating function˖This key lowers the preset temperature by 1ć each time and
the minimum limit is 15ć.
5. L.E.D. DISPLAY
The display indicates the current setting temperature or the timer setting. When the set
temperature or the timer is adjusted, the new setting is shown then the display returns the
current set temperature.
Ć The display is also used to show error codes should a fault occur, see ERROR
CODES.
Page 11
6. SPEED
Note: In heating function and dehumidifying function,ġthis key is invalid because
dehumidifying mode.
Press to select either LOW, MEDIUM, HIGH or AUTO fan speed.
If "AUTO" is selected,”HIGH” or "MEDIUM" or “LOW" will be
selected automatically according to the difference between setting temperature and
ambienttemperature.
the unit is defined to be high speed in heating mode and low speed in
7. PROGRAMMABLE
Programmable timer ON/OFF key.
TIMER-ON: The timer-on is used to turn on the unit automatically after the set time is
over.
1. Press the "TIMER" key at stand-by status to set the time you desired.
2. Once the set hour has come to an end, the unit will turn on automatically.
3. Press the "POWER" key before time out, the setting time will be canceled and the
unit will turn on.
4. You can set the function and fan speed while setting the timer.
TIMER-OFF: The timer-off is used to turn off the unit automatically after the setting
time is over.
1. Press the "TIMER" key at operating status to set the time you desired.
TIMER
2. Once the set hour has come to an end, the unit will turn off automatically.
3. Press the "POWER" key before the time out, the setting time will be canceled and
the unit will turn off.
8. SLEEP CONTROLFUNCTION
1. While in cooling mode, press the SLEEP key to set the temperature. It increases1 ć
after an hour and at most increases 2 ć after 2 hours.
Page 12
2. While in heating mode, press the SLEEP key to set the temperature. It decreases
1 ć after an hour and at most decreases 2 ć after 2 hours.
3. Press the SLEEP key again can cancel the setting.
9. ALARM
When the water tank is full,"E4" will be displayed on the display panel. To resume
operation, please remove the rubber cap of the drain hose to drain out the water firstly.
The E4 warning will disappear after draining, and then you can restart the unit by
pressing the POWER key.
Page 13
REMOTE CONTROL FUNCTION
1. POWER
2. FUNC
3. TIMER
4. AUTO
5. HI
6. MID
7. LOW
8. SLEEP
9. TEMP.
On/Off switch
Function “MODE” selector
Hourly programming
Automatic fan speed
High fan speed
Medium fan speed
Low fan speed
Night operation selector
Temperature selector
Page 14
NOTICE
This unit can evaporate the condensation and distribute through the exhaust hose
automatically.
1. When the unit is in the cooling function, it does not need the drain pipe installed.
Please make sure that the rubber cap is locked on drain hole, when the unit is
running.
2. When operating the heating function, the “ķ” rubber cap on drain hole should be
pulled out and install a proper drain pipe in order to improve the heating effect
3. When operating the dehumidifying function the “ķ” rubber cap on drain hose should
be pulled out and install a proper drain hose.
ƽ Please remove the air exhaust hose, connect a drain hose to the drain hole and
lead the water to the outside in order to intensify dehumidifying capacity.
Ć When the water tank is full,"E4" will be displayed on the display panel. Please
remove the rubber cap“ĸ” of the drain hole to drain out the water first. After the
drainage is completed, please restart the unit and then the unit can operate
normally.
MAINTENANCE
PLEASE DISCONNECT THE POWER CORD BEFORE CLEANING.
AIR FILTER
The air filter located on the left hand side of the unit can be removed,
simply by pulling the frame out
Page 15
CONDENSER/EVAPORATOR
Use a brush attachment with a vacuum cleaner.
Casing
Wipe with a damp cloth and polish with a soft cloth.
To remove the air filter, please follows the arrow direction and pull the
filter lightly, and then take out the filter for cleaning.
Page 16
POWER SUPPLY
ġ
(1) Confirm the correct power.
(2) Insert the plug into the outlet firmly In order to prevent any
dangerous leakage.
(3) Don’t pull power wire by force because it will cause damage to power
wire.
PLACE FOR USE
(1) Because the machine distributes hot air, please don’t place or
operate in a narrow place.
(2) In case of dangerous leak, don’t work the machine in a humid place.
(3) Don’ t place the machine in a sunlit corner otherwise the unit might
shut down due to the overheat and the color of the machine may
soon fade out.
HELPFUL HINTS
The unit is fitted with a special thermal cut off device.
Please ensure the unit is not placed against objects which will
obstruct air intake e.g. furniture or curtains as this will affect it's
performance dramatically.ġ
Page 17
EXHAUST HOSE INSTALLġ
ġ
1.Circumrotate the exhaust hose according to the direction as the arrowhead ķ
indicates and then the exhaust hose can be took out from the unit.
Circumrotate the exhaust hose according to the direction as the arrowhead ĸ
2.
indicates and then make it connect with the unit.
WINDOW KIT INSTALL
Install the Exhaust Hose and the Adjustable Window Slider Kit as
depicted in Fig.1 ˂ Fig.1a.
Page 18
How to enjoy heating function?
When operating heating function˖
Disassemble the outlet and the exhaust hose as arrow direction in Fig.01 and then
exchange the two subassemblies to install. The finished illustration is as Fig.03.
Page 19
TROUBLESHOOTING
1. Information on servicing
1) Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For repair to
the refrigerating system, the following precautions shall be complied with prior to
conducting work on the system.
2) Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk
of a flammable gas or vapour being present while the work is being performed.
3) Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and
during work, to ensure the technician is aware of potentially flammable
atmospheres. Ensure that the leak detection equipment being used is suitable for
use with flammable refrigerants, i.e. non-sparking, adequately sealed or
intrinsically safe.
4) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available to
hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
5) No ignition sources
No person carrying out work in relation to a refrigeration system which involves
exposing any pipe work that contains or has contained flammable refrigerant
shall use any sources of ignition in such a manner that it may lead to the risk of
fire or explosion. All possible ignition sources, including cigarette smoking,
should be kept sufficiently far away from the site of installation, repairing,
removing and disposal, during which flammable refrigerant can possibly be
released to the surrounding space. Prior to work taking place, the area
Page 20
around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
6) Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation shall
continue during the period that the work is carried out. The ventilation should
safely disperse any released refrigerant and preferably expel it externally into the
atmosphere.
7) Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose
and to the correct specification. At all times the manufacturer’s maintenance and
service guidelines shall be followed. If in doubt consult the manufacturer’s
technical department for assistance.
The following checks shall be applied to installations using flammable
refrigerants:
– The charge size is in accordance with the room size within which the refrigerant
containing parts are installed;
– The ventilation machinery and outlets are operating adequately and are not
obstructed;
– If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant;
– Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected;
– Refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
Page 21
8) Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the circuit
until it is satisfactorily dealt with. If the fault cannot be corrected immediately but
it is necessary to continue operation, an adequate temporary solution shall be
used. This shall be reported to the owner of the equipment so all parties are
advised.
Initial safety checks shall include:
• That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking;
• That there no live electrical components and wiring are exposed while charging,
recovering or purging the system;
• That there is continuity of earth bonding.
2. Repairs to sealed components
1) During repairs to sealed components, all electrical supplies shall be disconnected
from the equipment being worked upon prior to any removal of sealed covers, etc. If
it isabsolutely. necessary to have an electrical supply to equipment during servicing,
then a permanently operating form of leak detection shall be located at the most
critical point to warn of a potentially hazardous situation.
2) Particular attention shall be paid to the following to ensure that by working on
electrical components, the casing is not altered in such a way that the level of
protection is affected. This shall include damage to cables, excessive number of
connections, terminals not made to original specification, damage to seals, incorrect
fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer
serve the purpose of preventing the ingress of flammable atmospheres. Replacement
Page 22
parts shall be in accordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated
prior to working on them.
3. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that this will not exceed the permissible voltage and current permitted for
the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in
the presence of a flammable atmosphere. The test apparatus shall be at the correct
rating. Replace components only with parts specified by the manufacturer. Other
parts may result in the ignition of refrigerant in the atmosphere from a leak.
4. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects. The check shall
also take into account the effects of aging or continual vibration from sources such
as compressors or fans.
5. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching
for or detection of refrigerant leaks. A halide torch (or any other detector using a
naked flame) shall not be used.
6. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibration. (Detection equipment
shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a
potential source of ignition and is suitable for the refrigerant used. Leak detection
Page 23
equipment shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed and the appropriate percentage of gas (25 %
maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall
be recovered from the system, or isolated (by means of shut off valves) in a part of
the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged
through the system both before and during the brazing process.
7. Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other
purpose –conventional procedures shall be used. However, it is important that best
practice is followed since flammability is a consideration. The following procedure
shall be adhered to:
• Remove refrigerant;
• Purge the circuit with inert gas;
• Evacuate;
• Purge again with inert gas;
• Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The
system shall be “flushed” with OFN to render the unit safe. This process may need
to be repeated several times. Compressed air or oxygen shall not be used for this
task. Flushing shall be achieved by breaking the vacuum in the system with OFN
and continuing to fill until the working pressure is achieved, then venting to
atmosphere, and finally pulling down to a vacuum. This process shall be repeated
until no refrigerant is within the system. When the final OFN charge is used, the
Page 24
system shall be vented down to atmospheric pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe-work are to take
place. Ensure that the outlet for the vacuum pump is not close to any ignition
sources and there is ventilation available.
8. Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
– Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimise the
amount of refrigerant contained in them.
– Cylinders shall be kept upright.
– Ensure that the refrigeration system is earthed prior to charging the system with
refrigerant.
– Label the system when charging is complete (if not already).
– Extreme care shall be taken not to overfill the refrigeration system. Prior to
recharging the system it shall be pressure tested with OFN. The system shall be
leak tested on completion of charging but prior to commissioning. A follow up leak
test shall be carried out prior to leaving the site.
9. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely
familiar with the equipment and all its detail. It is recommended good practice that all
refrigerants are recovered safely. Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required prior to re-use of
reclaimed refrigerant. It is essential that electrical power is available before the task
is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
Page 25
• Mechanical handling equipment is available, if required, for handling refrigerant
cylinders;
• All personal protective equipment is available and being used correctly;
• The recovery process is supervised at all times by a competent person;
• Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed
from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer's
instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and all
isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless
it has been cleaned and checked.
10. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied
of refrigerant. The label shall be dated and signed. Ensure that there are labels on
the equipment stating the equipment contains flammable refrigerant.
11. Recovery
When removing refrigerant from a system, either for servicing or decommissioning,
it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge is available. All cylinders to be used
Page 26
are designated for the recovered refrigerant and labelled for that refrigerant (i.e.
special cylinders for the recovery of refrigerant). Cylinders shall be complete with
pressure relief valve and associated shut-off valves in good working order. Empty
recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions
concerning the equipment that is at hand and shall be suitable for the recovery of
flammable refrigerants. In addition, a set of calibrated weighing scales shall be
available and in good working order. Hoses shall be complete with leak-free
disconnect couplings and in good condition. Before using the recovery machine,
check that it is in satisfactory working order, has been properly maintained and that
any associated electrical components are sealed to prevent ignition in the event of
a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct
recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been
evacuated to an acceptable level to make certain that flammable refrigerant does
not remain within the lubricant. The evacuation process shall be carried out prior to
returning the compressor to the suppliers. Only electric heating to the compressor
body shall be employed to accelerate this process. When oil is drained from a
system, it shall be carried out safely.
Fuse parameters of the machine
Type: 5ET or SMT Voltage: 250V Current: 3.15 A
Page 27
TROUBLE SHOOTINGġġ
Problem
Cause
Trouble shooting
E1
Electrical short on both
temperature sensor and PCB
Contact an electrician for repair
E2
Electrical short of temperature
sensor copper tube and PCB
wiring
Contact an electrician for repair
E4
Indicates water tank full or
possibly the incorrect wiring of
plug
User needs to pull out the rubber stopper
which is located at the bottom of the unit,
to drain the water away. Check that the
plug has been wired correctly.
Page 28
ENERGY LABEL
Page 29
SPECIFICATIONġ
ġ ġ
Model
Power Source
Rated Power (EN60335)
ġġ
Cooling
Heating
1150 W
965 W
1535 W
1290 W
Cooling Capacity
Heating Capacity
Moisture Removed
Refrigerant
Allowable Pressure:
Suction
Discharge
Maximum Allowable Pressure
Dimensions (mm)
AMC-11P AMC-14P
220–240 V / 50 Hz
3000 W 4000 W
3000 W 4000 W
50 liters/day 70 liters/day
R290 / 0,23kg R290 / 0,27kg
0,6MPa (6Kgf/cm2)
300 (W) × 532 (D) × 760 (H)
2,5MPa (25Kgf/cm
4,0MPa (40Kgf/cm2)
2
)
Page 30
This marking indicates that this product should not
be disposed
with other household wastes
throughout the EU. To prevent possible hazards to
the environment or human health from uncontrolled
waste disposal, please recycle it to prove the
sustainable reuse of material resources. Please
ask return and collection systems or contact the
retailer where the product was purchased to return
your used device, they can recycle products safely.
INFORMATION CONCERNING USED REFRIGERANT
MEDIUM
Device is pre-filled with flammable R290 refrigerant. The
maintanance and the liquidation must be carried out by qualified
personel.
Type of refrigerant: R290 (CH3CH2CH3)
The quantity of the refrigerant: please see the unit label.
Hermetically sealed system.
The value GWP: 3
GWP = Global Warming Potential
In case of quality problem or other please contact your local
supplier or authorized service center.
Emergency number: 112
Page 31
PRODUCER
SINCLAIR CORPORATION Ltd.
1-4 Argyll St.
LONDON
W1F 7LD
United Kingdom
www.sinclair-world.com
The device was made in China (Made in China).
REPRESENTATIVE, SERVICE
SINCLAIR Global Group s.r.o.
Purkyňova 45
Brno
612 00
Czech republic
Phone - sales: +420 541 590 140
Phone - service: +420 541 590 150
Fax: +420 541 590 124
www.sinclair-solutions.com
info@sinclair-solutions.com
Page 32
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.