Simpson Electric S662 Instruction Manual

S662
Digital Preset Totalizer & Batch Counter
Operation Manual
SIMPSON ELECTRIC COMPANY
520 Simpson Avenue, Lac du Flambeau, WI 54538-0099
(715) 588-3311 FAX (715) 588-3326
Printed in U.S.A. Part No. 06-116547 Edition 8, 06/07
!
To the best of our knowledge and at the time written, the information contained in this document is technically correct and the procedures accurate and adequate to operate this
Menu
Category
Parameter
Name
Choices /
Format
Description Tech
Note
instrument in compliance with its original advertised specifications.
Notes and Safety Information
This Instruction Manual contains warning headings that alert the user to check for hazard­ous conditions. These appear throughout this manual where applicable, and are defined below. To ensure the safety of operating performance of this instrument, these instruc­tions must be adhered to.
Caution, refer to accompanying documents.
Caution, risk of electric shock.
Technical Assistance
SIMPSON ELECTRIC COMPANY offers assistance Monday through Friday 8:00 am to 4:30 pm Central Time by contacting Technical Support or Customer Service at (715) 588-3311. Internet: http://www.simpsonelectric.com
rESEt SEtuP
End
ArESEt diSAbLE*
At SP1 At SP2 At SP3 At SP4 AFtoP1 AFtoP2
rStbtn EnAbLE*
disAbLE
PonrSt no*
YES
Auto Reset Mode
Selects when an auto reset function is to occur. Disabled, at a setpoint or after output times out. See also the RSTP1 parameter in the Setpnt Setup category
Reset Button Enable or disable front panel reset button.
Power On Reset Select
whether count reset event will occur at power-up.
Exit Programming
4.7
4.8
4.8
Warranty and Returns
SIMPSON ELECTRIC COMPANY warrants each instrument and other articles manu­factured by it to be free from defects in material and workmanship under normal use and service, its obligation under this warranty being limited to making good at its factory or other article of equipment which shall within one (1) year after delivery of such instru­ment or other article of equipment to the original purchaser be returned intact to it, or to one of its authorized service centers, with transportation charges prepaid, and which its examination shall disclose to its satisfaction to have been thus defective; this warranty being expressly in lieu of all other warranties expressed or implied and of all other obli­gations or liabilities on its part, and SIMPSON ELECTRIC COMPANY neither assumes nor authorizes any other persons to assume for it any other liability in connection with the sales of its products.
This warranty shall not apply to any instrument or other article of equipment which shall have been repaired or altered outside the SIMPSON ELECTRIC COMPANY factory or
Menu
* = factory default settings
authorized service centers, nor which has been subject to misuse, negligence or accident, incorrect wiring by others, or installation or use not in accord with instructions furnished by the manufacturer.
Under the normal field usage there is no need to remove the front bezel of this product. The front bezel of this product should only be removed by a qualified technician.
1 38
Menu
Category
Parameter
Name
Choices /
Format
Contents
Description Tech
1 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Note
1.1 General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SEtPnt SEtuP
dELAY 010.00*
untiL2 Reset*
SP1 SP2 SP3 SP4 RstP 1
SP1 000010 *
Delay 2
Output 2 delay time.
Appears only if Output 2
mode set to timed.
Until 2
Output 2 latched until parameter. Appears only
if M m ode2 = latch and SRC2 = Count1.
SP1
Set point #1 Low.
Values: -99999 to 99999.
Decimal point will appear according to the current
Output 1 Source
setting.
4.5
4.5
4.6
1.2 Part Number Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.3 Option Module Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2 Hardware Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1 Panel Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Removing / Installing Option Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 120/240 VAC Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4 Standard Input Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.5 Quadrature Input Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.6 Excitation Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7 Single and Dual Relay Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3 Display & Keypad Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.1 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Display Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3 What the Keys Do in Display Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4 What the Keys Do in the Programming Mode. . . . . . . . . . . . . . . . . . . . . . . . . .16
3.5 Special Start-Up Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Menu
Category
Parameter
Name
rStP 1 000000*
rStP 2 000000*
Choices /
Format
Description Tech
Count 1 Preset Value
Count 1 value is set to this when an Auto or Manual Reset event occurs. Values:
-99999 to 999999. Decimal point will appear according to the user-programmed
Count DP 1 position.
Count 2 Preset Value
Count 2 value is set to this when an Auto or Manual Reset event occurs. Values:
-99999 to 999999. Decimal point will appear according to the user-programmed
Count DP 2 position.
Note
4.6
4.6
4 Counter Operations and Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.1 Password and Security Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2 A/B Channel Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 Count 1 Scaling and Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 Count 2 (Batch) Scaling and Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.5 Output Control Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.6 Set Point Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.7 Auto Reset Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.8 Miscellaneous Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Appendix A: Technical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
A.1 Functional Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
A.2 Electrical, Environmental and Mechanical Specifications. . . . . . . . . . . . . . . . .28
Appendix B: Programming Quick Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
* = factory default settings
37 2
1 Product Description
Menu
Parameter
Choices /
Description Tech
1.1 General Description
The S662 preset totalizer & batch counter fits a 1/8 DIN standard cutout and is perfect for tight spaces, extending only 3.24” (82mm) behind the panel. The unit is UL listed. The unit is for indoor use at altitudes up to 2000m, temperatures between 0° and 40°C, and installation category III, pollution degree 2.
Category
Name
Format
SP2 000020*
SP3 000030*
SP2
Set point #1 High.
Values:-99999 to
999999. Decimal point will appear according to the current Output 1
Source setting.
SP3
Set point #2 Low.
Values: -99999 to
999999. Decimal point will appear according to the current Output 2
Source setting.
Note
4.6
4.6
The counter is powered from 120 or 220 VAC. The nonvolatile EEPROM retains all pro­gramming and count information when power is removed or interrupted.
Display scaling, preset values and all menu functions are easily programmed from the front panel, following easy-to-use word prompts. Front panel reset disable and password lockout protection features guard against unauthorized or accidental changes.
The counter accepts count rates up to 20 kHz and pulses from different types of sensors, including Quadrature, CMOS or TTL circuits and PNP or NPN devices.
The optional field-replaceable single/dual relay, DC module enhances the counter from a passive display device to an integral control element for your application. Outputs may be controlled by Count or Batch values with independent reset operations. The counter has latching, boundary or timed 0.01 to 599.99 seconds) output modes. An optional 12 VDC (100mA) excitation output module can provide power for external sensors.
SP4 000040*
* = factory default settings
SP4
Set point #2 High.
Values: -99999 to
999999. Decimal point will appear according to the current Output 2
Source setting.
4.6
1.2 Part Number Identification
The following matrix indicates the configuration of your S662 counter.
Basic Unit
S662
Power Supply
120 VAC 240 VAC
1 2
Input
Standard
Quadrature
Output
1 2
One relay
Two Relays
None
0 1 2
Excitation
None 12VDC
0 1
Other
None
3 36
0
Menu
Parameter
Choices /
Description Tech
1.3 Option Module Summary
Category
Name
Format
SrC 2 Count1*
Count2
bAtrSt no*
YES
tiMmEd<— LAtCHEd<— SP3=Lo<—
—>At SP3 —>AtSP3* —>SP4=Hi
Output 2 Source
Select which Display value to be used for Output 2 comparisons / matchpoints. See also
SP3 and SP4.
Output 2 Batch Reset
When output activates, perform Count 2 Reset as well.
Output 2 Bindings
Reminder message indicates which and how the set points are used for comparison. Which message is displayed
Note
4.5
4.5
4.5
1
Input Excitation Power
2
4
Supply
5
Output
Figure 1. Option Module Slots (Rear View)
The S662 is modular product which uses field configuring slide-in modules. The mod­ules slide easily into the rear of the counter.
depends on the Output 2 Mode or Source
selected.
* = factory default settings
Table 1 describes available option modules for the S662.
Table 1. Option Module Summary
Module
slot
1 Input Standard Input Module
1 Input Quadrature Input Module
2 Ext 45064 12 VDC Excitation Module
4 Power 120 VAC Power Module
4 Power 240 VAC Power Module
Type P/N Description
See
Section
2.4
2.5
2.6
2.3
2.3
5 Output 45062 Dual Relay Module
5 Output 45063 Single Relay Module
35 4
2.7
2.7
2 Hardware Setup
Menu
Parameter
Choices /
Description Tech
2.1 Panel Installation
The S662 1/8 DIN counter requires a standard 1/8 DIN panel cutout of 1.77” (45mm) high by 3.62” (92mm) wide. To install the counter into a panel cutout, remove the clips from the side of the counter. Slide the counter through your panel cutout, then slide the mounting clips back on. Press evenly to ensure a proper fit.
3.62"
92mm
3.24"
82mm
1.77"
45mm
1.74"
44mm
.52"
13.2 mm
%
RESET
ENTER
3.93"
99.8 mm
2.04"
51.8mm
Category
Name
tiMmEd<— LAtCHED<— SP1=Lo <—
Format
—>At SP1 —>AtSP1* —>SP2=Hi
dELAY1 010.00*
untiL1 ReseT*
SP1 SP2 SP3 SP4 rStP1
Output 1 Bindings
Reminder message indicates which and how the set points are used for comparison. Which message is displayed depends on the Output 1 Mode or Source selected.
Delay 1
Output 1 delay time.
Appears only if Output 1 mode set to timed.
Until 1
Output 1 latched until parameter. Appears only
if MmodE1 = LAtCH and SrC1 = Count1.
Note
4.5
4.5
4.5
Figure 2. Counter and Panel Cut-Out Dimensions
oPut 2 SEtuP
MmodE2 diSAbL
tiMmEd LAtCH* bound
* = factory default settings
Output 2 Mode
Set the mode of operation for Output 2. Can be disabled, timed, latched or boundary mode.
4.5
Figure 3. Panel Mounting Clips
5 34
Menu
!
Parameter
Choices /
Description Tech
2.2 Removing / Installing Option Modules
Category
oPut 1 SEtuP
Name
M m odE1 diSAbLE
SrC 1 Count1*
bAtrSt no*
Format
tiMmEd LAtCH* bound
Count2
YES
Output 1 Mode
Set the mode of operation for Output 1. Can be disabled, timed, latched or boundary mode.
Output 1 Source
Select which Display value to be used for Output 1 comparisons / matchpoints. See also
SP1 and SP2.
Batch Reset
When output activates,
Note
4.5
4.5
4.5
Shut power off before removing or installing any option modules
1. Remove module from case by inserting a screwdriver into tab slot opening at top of input module. Apply pressure to release module from case. Repeat procedure for tab located on underside of module and then slide module away from the case.
2. Refer to appropriate sections to configure switches or jumpers for proper operation. Table 1 can be used to identify modules and their associated detail paragraph.
3. Install module by carefully aligning module edges with slots in case and pressing forward until tabs (on top and bottom) engage.
perform Count 2 Reset as well. Appears only if SrC 1 = Count2.
* = factory default settings
Figure 4. Removing Option Module
33 6
2.3 120/240 VAC Power Module
!
!
Remove power before wiring option modules.
Menu
Category
Parameter
Name
Choices /
Format
Description Tech
Note
Denotes module
!
position 4 at rear of counter
from standard 50/60 Hz line power. The power module will be configured as 120 VAC or 240 VAC per markings on the back panel. Ensure the input rating of the supply
The AC power module allows the S662 to be operated
VAC
VAC
Power Supply 120 VAC or 240 VAC power connection
matches your line voltage. The power supply module has provisions for a hard-wire Primary (Count 1) Reset. This control can be a switch, relay contact or solid state device. Actuation is immediate upon an active Low for at least
RESET
COMMON
POWER
Figure 5. AC Power Module
Remote Reset Active low 0.2V performs primary reset
2.5ms to this terminal. The reset circuit is independent of the power circuit.
NOTE: A fusible link is not provided on this module. A ½ Amp Time Delay fuse, Bussman MDL ½ or simi­lar, is recommended.
Never connect AC mains (hot or neutral) to the Reset or Common terminals!
2.4 Standard Input Module
Count 2 SEtuP
M m odE duAL*
bAtCH
Batch Mode
Display value 2 (Count
4.4
2) mode. Defines the counting mode for batch count.
PrESCL 1.0*
0.1
0.01
Count 2 Prescale
Set prescaling multiplier
for Display Value 2.
4.4
0.001
SCALE 2 01.0000*
Count 2 Scale
4.4
Set Display Value 2 (Count 2) scaling multiplier.
Values: -9.9999 to
99.9999.
dP 2 000000*
000000.
00000.0
0000.00
000.000
00.0000
Count 2 DP
Display Value 2 Decimal Point location. Affects appearance of RstP2 and any associated Set
Point parameters.
4.4
Figure 6. Standard Input Module
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
Denotes module
position 1 at rear
of counter
Primary Input
Connect the input
signal to A input
and common
Count2 Reset
Active low
resets Batch count
and alarms
Secondary Input Direction Control or count pulse input
0.00000
* = factory default settings
7 32
Menu
Category
Parameter
Name
Choices /
Format
Description Tech-
Note
DIP Switch (Shown for TTL Factory Settings)
inPut SEtuP
Count 1 SEtuP
A CHAn uP*
doW n quad r quad
b CHAn dir*
uP doW n
SCALE1 01.0000*
Chan A Mode
Select count mode of A channel.
Chan B Mode
Select count mode for B channel. Note: if A channel set to quad or Rquad, this item is not accessible.
Count 1 Scale
Set Display Value 1 scaling multiplier.
Values: -9.9999 to
99.9999
4.2
4.2
4.3
FUNCTION
B Bias Off=Hi On=Lo B Freq Off=Hi On=Lo B Off= Sink On= Source A Bias Off=Hi On=Lo A Freq Off=Hi On=Lo A Off= Sink On= Source
Dipswitch Legend
CHANNEL
1 2 3 4 5 6
1 2 3 4 5 6
= ON = OFF
Note: Refer to specifications for DIP switch function electrical characteristics
Figure 7. Standard Input Module Default Settings
DIP switch SW1, figure 7, is used to set up the counter to conform to the electrical char­acteristics of the sensor or signal being detected. Switch positions 1-3 configure channel B, while switches 4-6 configure channel A. These switches select bias (threshold volt-
dP 1 000000 *
000000.
00000.0
0000.00
000.000
00.0000
0.00000
* = factory default settings
Count 1 DP Display Value 1 (Count1) Decimal Point location. Affects appearance of RstP1 and any associated Set Point parameters.
4.3
ages), low pass filter (enable/disable) and sensor type (Sink or Source).
Refer to the documentation that accompanied the sensor for related information. The sensor can most likely be matched to one of the typical switch settings shown in figure 8 and figure 8a.
Note: The input boards are designed so that selecting sourcing or sinking is based on the type of sensor that is being used. If a PNP (sinking) sensor is being used, set the input board for sinking also (switches 3 and 6 = OFF).
If channel B is not used, default settings for switch positions 1 through 3 should be se­lected. Default settings are provided in Table 2.
The input module also provides for a user input signal. On the S662, this input serves as the secondary channel (Batch) hard-wired reset. This may be used to reset the batch count while preserving the primary count. The S662 can accept inputs from many different sensors. The A and B channels may be configured independently as shown in Table 2. Figures 8 and 8a have examples of some typical sensors and the wiring connections that would be used.
31 8
Table 2. Standard Input Module DIP Switch Settings(* = Factory Default Setting)
+
Single / Dual Relay Modules
1 B Channel Bias: OFF = Hi* VLT = 5.0 V VUT = 7.0V (+/- 10%) ON = Low VLT = 1.6 V VUT = 3.6V (+/- 10%)
2 B Channel Frequency: OFF = Hi* (low pass filter disabled) ON = Lo (low pass filter enabled)
3 B Channel Sensor: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
4 A Channel Bias: OFF = Hi VLT = 5.0 V VUT = 7.0V (+/- 10%) ON = Low* VLT = 1.6 V VUT = 3.6V (+/-10%)
5 A Channel Frequency: OFF = Hi* (low pass filter disabled) ON = Lo (low pass filter enabled)
6 A Channel Sensor Type: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
Contact Rating
Mechanical Life
5 Amps 250 VAC
1,000,000 cycles
Isolated 12V Excitation Module
Exitation Output
Exitation Isolation
100 mA at 12 VDC ±5%
1500 V
Appendix B: Programming Quick Reference
If you are unfamiliar with navigating menus in the S662, see section 3. Each pa­rameter is listed in the order of appearance in the menu system. Refer to the para­graph indicated in the Tech Note column for technical details on a particular param­eter.
Tip: Photocopy these pages to mark settings on.
HIGH FREQUENCY
ON
1 2 3 4 5 6
LOW BIAS LOW FREQUENCY SOURCING
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
HIGH BIAS
SINKING
OUTPUT
COMMON
ON
1 2 3 4 5 6
LOW BIAS LOW FREQUENCY SOURCING
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
ISO+12V
ISOCOM
EXCITATION
NPN SENSOR
__
---
ON
1 2 3 4 5 6
HIGH FREQUENCY
+
_
HIGH BIAS
SINKING
LOW BIAS LOW FREQUENCY SOURCING
A INPUT
COMMON
USER INPUT
B INPUT
ISO+12V
ISOCOM
COMMON
INPUT
EXCITATION
PNP SENSOR
__
---
HIGH FREQUENCY
HIGH BIAS
SINKING
+
_
DRY CONTACT
Figure 8. Sensor Connection Examples Figure 8a Sensor Input Example
Menu
Category
Parameter
Name
Choices /
Format
PASS 000
ACCESS<—
—>dEniEd
CHPASS 000*
Description Tech
Password Entry and
Verification
Password Fail
Appears if incorrect password entered
Password Change
Appears if correct password entered
000 = Password protection disabled 001-099 = Secures all parameters
Note
4.1
4.1
4.1
2.5 Quadrature Input Module
The Quadrature / Universal Input Module has two operational modes: Quadrature mode and Standard mode. Quadrature mode is selected by positioning JP1 and JP2 on pins 1 and 2. Standard mode is selected by placing JP1 and JP2 on pins 2 and 3 (see Figure 10 for details). The Quadrature mode supports a wide range of encoders including the Simp­son SE series.
9 30
100-999 = Enable
SPs/ResPos access in display mode
* = factory default settings
Standard input module
While in Standard mode, this module works similarly to the Standard Input module, with
Input Channels
Count edge
Input Sources
Input Impedance
A & B channels
User Channel
Low pass filter
Max voltage
A, B and User
High to low transition (A and B channels)
Switch contact, CMOS or TTL logics, PNP or NPN devices
Sinking: 10K, 5% Res. Pull-up to (9.0 - 16 VDC) ±10% Sourcing: 5.1K, 5% Res. Pull-down to common
Input Thresholds
Low Bias mode:VLT = 1.6V ±10% VUT = 3.6V ±10% High Bias mode:VLT = 5.0V ±10% VUT = 7.0V ±10%
VLT = 0.2V (min) VUT = 3.0V (max)
Frequency < 200Hz (0 to 10V input square wave at 50% duty cycle)
A, B and User channels 30VDC maximum sustained
the added capability to selectively invert A, B, and User input signals.
The Input module also provides for a User input signal. On the S662 this input serves as the secondary channel (Batch) hard-wired reset. This may be used, for example, to reset the batch count while preserving the primary count.
In both modes, the state of the User input signal can be selected as active high or active low. DIP switch SW1 configures the counter to match the specifications of the accom­panying sensor. When shipped from the factory, the counter is set for X1 quadrature, as shown in Figure 10 and Table 3: witch settings for SW1 positions 1 through 3. Default settings are provided in Table 3.
Denotes module
position 1 at rear
of counter
A INPUT
Primary Input
COMMON
or
Quadrature A
NOTE: If B channel is not going to be used,
Quadrature input module
Input Channels
User-selectable input polarity. A and B channel
Input Inversion
Operation modes
Input Sources
Input Impedance
A, B and User
polarity selective in standard mode only.
Standard, Quadrature X1 and Quadrature X4
Switch contact, CMOS or TTL logics, PNP or NPN devices quadrature (single-ended) encoders
Sinking: 10K, 5% Res. Pull-up to (9.0 - 16 VDC) ±10% Sourcing: 5.1K, 5% Res. Pull-down to common
Input Thresholds
USER INPUT
B INPUT
COMMON
INPUT
Count2 Reset
Active low
Resets Batch count
and alarms
Secondary Input or Quadrature B
Quadrature
Count
12 3
JP2
use the default
Figure 9. Quadrature / Universal Input Module
Dipswitch Legend
12 3
JP1
B Bias Off=Hi On=Lo
B Freq Off=Hi On=Lo
B Off= Sink On= Source
A Freq Off=Hi On=Lo
A Off= Sink On= Source
A Bias Off=Hi On=Lo
B Edge Off= On=
A Edge Off= On=
User pol Off= On=
Quadr Off=X4 On=X1
= ON = OFF
A & B channels
User Channel
Low pass filter
Max voltage
Low Bias mode:VLT = 1.6V ±10%VUT = 3.6V ±10% High Bias mode:VLT = 5.0V ±10% VUT = 7.0V ±10%
VLT = 0.9V (min) VUT = 3.15V (max)
Frequency < 200Hz (0 to 10V input square wave at
50% duty cycle)
A, B and User channels 30VDC maximum sustained
29 10
Standard
Count
Note: To Enable standard count Mode move both jumpers down one pin
1 2 3 4 5 6 7 8 9 10
SW1
Dip Switch:
Shown in
Quadrature Mode
(Factory Defualt)
Figure 10. Quadrature Input Module Default Settings
Table 3. Quadrature Module DIP Switch and Jumper Settings
JP1/2: Count Mode Selector
A.2 Electrical, Environmental and Mechanical
Jumpered 1-2 = Quadrature mode Jumpered 2-3 = Standard counter mode SW1: 10 Position DIP Switch * = Factory Default setting
1 B Channel Bias: OFF = Hi* VLT = 5.0V VUT = 7.0V (+/- 10%) ON = Low VLT = 1.6V VUT = 3.6V (+/- 10%)
2 B Channel Frequency: OFF = Hi* (low pass filter disabled) ON = Low (low pass filter enabled)
3 B Channel Sensor: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
4 A Channel Bias: OFF = Hi* VLT = 5.0 V VUT = 7.0V (+/- 10%) ON = Low VLT = 1.6 V VUT = 3.6V (+/- 10%)
Power Requirements
Power Consumption
Reset Input Signal
Storage
Temperature
Operating
Temperature
Relative Humidity
Bezel
AC Supply: 120 or 240 VAC, ±10%
3VA
Active Low: 0.2 VDC = active
-10 to 60°C
0 to 40°C
0 to 80% for temperatures less than 32°C, decreasing linearly to 50% at 40°C. (Non­condensing)
3.93" x 2.04" x 0.52" (99.8 x 51.8 x 13.3mm)
5 A Channel Frequency: OFF = Hi* (low pass filter disabled) ON = Lo (low pass filter enabled)
6 A Channel Sensor Type: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
7 B Channel Count Edge: OFF = Rising (standard count mode only) ON = Falling*
8 A Channel Count Edge: OFF = Rising (standard count mode only) ON = Falling*
9 User Input Polarity: OFF = High/open circuit = Inhibit Count ON* = Low/closed circuit = Inhibit Count
Panel Cutout
Case Depth
Weight
3.62" x 1.77" (92 x 45 mm) 1/8 DIN
3.24" (82mm)
9.0 oz. (255.1g)
10 Quadrature Mode: OFF = X4 (quadrature mode only) ON = X1*
11 28
4) The display will flash between Ponrst and the default no. When the display shows no, press .
5) Use the arrow keys to select either no or yes. Press when the correct mode is se-
ENTER
ENTER
lected.
6) The display will now show end. If you are finished programming the S662, press .
ENTER
If not, use the arrow keys to back up to the necessary parameter.
Appendix A: Technical Specifications A.1 Functional Specifications
2.6 Excitation Module
PHASE A-WHITE
PHASE B-GREEN
QUADRATURE ENCODER
A INPUT
COMMON
+
USER INPUT
Count modes supported
Batch modes supported
Count Inputs
Miscellaneous inputs
Count range (internal)
Maximum count rate
Min pulse width
Count/Direction, Add-Add, Add-Subtract, Subtract-Subtract, Quadrature and Reverse Quadrature, Rate, and Batch
Dual mode: Primary and Secondary counts share common input, but with independent scaling and resets. Batch mode: Secondarey Count incremented when Primarey Count Auto Reset occurs.
2: Channel A (Primary) and Channel B (Secondary / Dir
control)
2: Reset (Count Reset) and User (Count Inhibit).
-2,147,483,648 to +2,147,483,648
20 Khz (Standard and Quadrature X1 modes)
5 Khz (Quadrature X4 mode)
5 uS (Standard mode)
COMMON (BLACK)
POSITIVE-RED
B INPUT
COMMON
INPUT
QUADRATURE INPUT CARD
ISO+12V
ISOCOM
EXCITATION
EXCITATION
CARD
+
__
---
_
Figure 11. Wiring Encoder w/ Excitation Supply
12 VDC Excitation Module The Excitation Module can supply 12 VDC at up to 100 mA for external sensors or en­coders. This excitation is isolated from the counter internal logic supply. When using sensors or encoders that do not have a signal return or imply a signal return that is in common with the supply voltage, a common attachment that ties the excitation supply to the logic input common may be required. Examples of this appear in figures 8, 8a, 11 and 12.
Display Digits
Display Decimal Point
Display LEDs
Display Range
Output channels
Output modes
Delay times
Output Response time
Multi-tasking Operation
6-digit, 7-segment with leading zero blanking
User-programmable
Red 0.56" (14.2mm), high efficiency
- 99,999 to + 999,999 (Independent of decimal position)
2, with front panel indicator for each
Disabled, Timed, Latching, and Boundary
0.01 to 599.99 sec -2.5 ms/+15ms
Latched and timed modes: < 5ms Boundary mode: < 15 ms Batch: <15 ms
Count and output control maintained while in programming mode.
27 12
MODEL S.E. QUADRATURE ENCODER
Figure 12. Wiring Encoder with External Supply
CHANNEL A-WHITE
CHANNEL B-GREEN
POSITIVE (RED)
EXTERNAL POWER SUPPLY
DENOTES MODULE POSTION 1 AT REAR OF COUNTER
A INPUT
COMMON
+
USER INPUT
B INPUT
COMMON
+
COMMON (BLACK)
INPUT
QUADRATURE INPUT CARD
Denotes module position 2 at rear of counter
Mode Description
Only a front panel or external reset event will
diSAbL
reset count.
ISO+12V
+
__
---
ISOCOM
EXCITATION
_
Figure 12. Excitation Module
2.7 Single and Dual Relay Modules
12 VDC, 100 mA max
At SP#
event occurs.
Auto Reset occurs after Output 1 times-out
When the selected set point is encountered, reset
AFtoP1
(Output 1 must be in timed mode).
Auto Reset occurs after Output 2 times-out
AFtoP2
(Output 2 must be in timed mode).
1) To access the Auto Reset Mode, enter the Programming Mode, and press until the reset setup menu category is reached.
2) Press to continue to the Parameter Name areset. The display will flash between areset and the default value of disabl. When the display shows disabl, press .
3) Use the arrow keys to scroll through the available options. Press when the cor-
ENTER
ENTER
ENTER
rect mode is selected to accept mode and proceed to the next parameter name, Reset Button.
rStbtn
(Reset Button)
The Reset Button Inhibit feature disables the front panel reset button . This can be used to prevent accidental resets, especially useful when using the counter as a sequencer. The external (rear panel) hardware reset input is not affected by this setting.
Figure 14. Single Relay Figure 15. Dual Relay
The Single and Dual Relay modules can activate circuit loads of up to 5 amps at 250 VAC. A Form C configuration allows use of normally-open (NO) and normally-closed (NC) circuit action. Only the output 1 channel is implemented in the single relay module.
PonrSt
(Power ON RESET)
When the Power ON RESET is set to YES, the counter will always use the Reset Position value as its initial display/count. With this setting, when an unexpected power loss occurs, the existing count will be lost.
When this function is set to NO, the existing count will be retained after a power loss.
4.8 Miscellaneous Controls
1) To access the Miscellaneous Controls, enter the Programming Mode, and press until the reset setup menu category is reached.
2) Press , and then to continue to the Parameter Name rstbtn. The display will flash between rstbtn and the default value of enable. When the display shows en­able, press .
3) Use the arrow keys to select either Enable or Disable. Press when the correct
ENTER
ENTER
ENTER
mode is selected to accept selection and proceed to the next parameter name, Power On Reset.
13 26
The SP1 and SP3 parameters are used as Latched or Timed “trigger” values. When a Boundary Output is selected, SP1 and SP3 become the low boundary values.
The SP2 and SP4 parameters are used as high boundary value or ‘turn-off’ values when
3 Display & Keypad Controls
3.1 Display
used with other alarm types (i.e. latched until SP4). The values for all set points are -99999 to 999999. The decimal point will appear accord­ing to the current decimal point setting.
Set Point Parameters
1) To set the Set Point parameters, enter the Programming Mode, and press until the setpnt setup menu category is reached.
2) Press to continue to the Parameter Name sp 1. The display will flash between sp 1 and the default value of 000010. When the display shows 000010, press .
3) Use the arrow keys to enter the correct value of the flashing digit. Use the key to advance to the next digit. Press when the correct set point is selected to
ENTER
ENTER
RESET
RESET
accept value and proceed to the next parameter, SP 2.
4) Repeat these steps for SP 2, SP 3, and SP 4. The counter will proceed to the next parameter, Reset Position.
Reset Position
1) To access the Reset Position parameter, enter the Programming Mode, and press quntil the setpnt setup menu category is reached.
2) Press and then to continue to the Parameter Name rstp 1. The display will
ENTER
Output Status
Indicators
4 Button Keypad
Figure 16. Display and Keypad Layout
6-Digit 0.56” high red LED Display.
2 Output Status Indicators; “1” and “2.”
Units Window for supplied label or legend.
Numeric & Message Display
Units Window
flash between rstp 1 and the default value of 000000. When the display shows 000000, press .
3) Use the arrow keys to enter the correct value of the flashing digit. Use the key to advance to the next digit. Press when the correct position is selected to ac-
ENTER
RESET
ENTER
cept value and proceed to the next parameter name, Count 2 Reset Value. Continue as above for the reset value for count 2. When finished, the counter will proceed to the next menu category, Auto Reset Mode (Reset Setup).
4.7 Auto Reset Operations (Reset Setup)
The S662 has the capability to perform a Count Reset event based upon various condi­tions. When Auto Reset occurs, the outputs will return to the deactivated status and the displayed count will return to the value stored in the Reset Position (rstpos) function. This feature is used in cut-to-length or other applications where an automatic repetitive cycle is established.
4-Button Keypad with tactile response.
If Count 2 Mode is set to Batch, Count 2 will be increased by one (1) whenever an Auto Reset occurs. A Batch Reset may link to an output condition. See section 4.5 for details.
25 14
3.2 Display Error Messages
NOTE: The outputs for this counter activate regardless of count direction in all
Table 4. Display Error Messages
Display Description Action Required
Cycle power to the
counter, if the error
remains, return
counter to factory for
repair.
Reset Counter
Reset Counter
Reset Counter
Reset Counter
PAdErr
999999 or
-99999
(Flashing)
E1
(Outputs
deactivate, count
stops)
E2
(Outputs
deactivate, count
stops)
E3
(Outputs
deactivate, count
stops)
The Keypad is disabled or a key is stuck in the ON position
The displayed count is too large for the counter to display. Since the internal count buffer is much larger than the display, the counter will maintain accurate count and control well beyond the display value.
Raw Count Overflow: The number of count pulses has exceeded the counter’s maximum internal value (2,147,483,648 or
-2,147,483,648)
Math Overflow: A large scale factor in combination with large raw count has exceeded the counter's maximum internal
value (+2,147,483,648 or -2,147,483,648)
Watchdog Fault: The counter did not experience an orderly power-down. This can happen by exceeding the maximum allowable count speed for a sustained period of time.
count modes. Output 1 Mode
1) To set the Output Control modes, enter the Programming Mode, and press until the oput 1 setup menu category is reached.
2) Press to continue to the Parameter Name mmode1. The display will flash be­tween mmode1 and the default value of latch. When the display shows latch, press
3) Use the arrow keys to select the correct mode. Press when the correct mode is
ENTER
ENTER
ENTER
selected to accept value and proceed to the next parameter, Output 1 Source.
Output 1 Source
1) After entering the output mode, the display will flash between src 1 and the default value count1. When the display shows count1, press .
ENTER
2) Use the arrow keys to select the display value to be used for Output 1 comparisons and match points. Press when the correct source is selected to accept the value
ENTER
and proceed to the next parameter, Batch Reset.
Batch Reset
1) After entering the output 1 source, the display will flash between batrst and the de­fault value no. When the display shows no, press .
ENTER
2) Use the arrow keys to choose whether when the output activates, the counter will perform a Count 2 reset as well. When the selection is made, press to accept
ENTER
selection and proceed to the next parameter, Output 1 Bindings.
Output 1 Bindings
Which message is display under this parameter depends on the Output 1 Mode selected.
1) After entering the Batch Reset, the display will flash between three choices, de-
3.3 What the Keys Do in Display Mode
Key Keypad behavior
If current Display Value is Count 1, resets Count
RESET
or
ENTER
Hold and
ENTER
Press
1 to RstP 1 parameter. If current Display value is Count 2, resets Count 2 to RstP 2 parameter. This
action may be disabled (see section 4.7).
Allows quick access to all the set points and
RstPos (Reset Position). This feature can be
disabled by using a password (see section 4.1).
Select current Display Value (Count 1 or Count 2).
Access the Programming Menu.
pending on the mode previously selected. This is a reminder message only. Press
ENTER
to proceed to the next parameter. See Appendix B for which options correspond with which parameters.
Output 2
1) After entering the Output 1 parameters, the counter will proceed to the Output 2 Setup. Follow the above instructions for the second output, using Appendix B as a guide, if necessary.
2) When all selections are entered and accepted into counter memory, counter will proceed to next menu category, Set Point Setup.
4.6 Set Point Parameters (Set Point Setup)
The S662 has four set point parameters and a special value referred to as Reset Position. The Reset Position can be referred to as Count Reset Value. SP1 and SP2 are used only with Output 1, and SP3 and SP4 are used only with Output 2.
15 24
4.5 Output Control Modes (Output Setup)
The S662 supports two independent output channels with four modes of operation: disabled, timed, latched and boundary.
3.4 What the Keys Do in the Programming Mode
Key Keypad behavior
Output Type Description
Disabled Output
The output channel is inactive.
The timed mode activates an output when a set point or ‘trigger’ condition is reached. Once active, the output is held until a specified delay period. The delay may be between 0.01 and 599.99 seconds.
Timed Output
The output will activate when the specified value is encountered (SP1 for output 1, SP3 for output 2). If a timing period is in progress, a new trigger does not occur. This is referred to as a non-retriggereable timer. A RESET will cancel the timed output.
The latch mode activates an output when a ‘trigger’ or set point is reached.
The output will activate when the value is
Latch Output
encountered (SP1 for output 1, SP3 for output 2). Once activated, the output is held and can be deactivated only when the specified Latched Until condition is met. The Latched Until conditions can be seen in Table 8.
RESET
or
ENTER
Press and hold for four seconds to exit the programming mode.
The up and down keys navigate through the available menu functions. The menu ‘wraps around’ when the bottom or top of the menu is reached.
1) Enter the current menu or parameter to
view/edit.
2) Write the change to the counter memory and move to the next function.
Setup Menu Function Menu Option Menu
CHPASS 000
INPUT SETUP
COUNT SETUP
other setup menus
ENTER
ENTER
A CHAN UP
B CHAN DOWN
ENTER
ENTER
000
down quad
rquad
dir
down
up
up
ENTER
ENTER
ENTER
Boundary Output
Latch Until Description
Reset
SP#
RstPos
The Boundary mode differs from the other output types in that it allows the counter to have an output activate/deactivate automatically within a specified
range.
Boundary mode activates an output when the count is between the specified low and high set points (SP1/SP2 for output 1, SP3/SP4 for output 2.)
Table 8. Latch Until
A front panel or external reset event is required to deactivate the output.
Output deactivated when set point is encountered.
Output deactivated when reset position is encountered.
END
ENTER
Return to
Display Mode
Figure 17. Programming Menu Structure
In the Programming Mode, the S662 will return to Display Mode automatically if a key is not pressed within 120 seconds (2 minutes). The menu is comprised of three levels: Setup Menu, Function View and Option Edit. Figure 17 illustrates the three levels of the menu system. Password Entry Entry (Pass) and changing of the password (Chpass) are similar to edit-
ing a numerical parameter. See Numerical Value below. If the pass­word has been set to a value other than “000,” entry of the proper pass­word is required to access the remainder of the menu.
Setup Menu At the first level of the menu, the keys navigate up or down through the
available Menu Categories.
Function Menu The second level of the menu contains the function or software param-
eters that need to be configured for the counter to operate properly.
Option Menu Contains either Choice Lists or Numerical Values for configuring the
functions of the counter.
23 16
Choice List A choice list allows selection from a fixed number of options. A Choice
3) Use the arrow keys to scroll through the choices. Press when the correct batch
ENTER
List is found in the Options section of the menu. The list is made up of the available options for the function that is being edited. Example: Menu is Input Setup Menu, the Function is A Channel, the Choice List is up, down, quad, and squad. (See Table 6)
Key Keypad behavior
The up and down keys scroll through the
ENTER
available choices in the Choice list.
Saves the current choice as new parameter setting and steps to next parameter or category.
Numerical Value A numerical entry allows the changing of set point values, scale values, etc.
Key Keypad behavior
RESET
Selects the next digit to the left of the current
flashing digit for editing.
mode is selected to accept value and proceed to the next menu category, Count 2 Prescale.
Prescale
The S662 counter allows for prescaling of display values. Prescaling allows the counter to display a more accurate number than its 6-digit capacity might otherwise allow. Gen­erally speaking, the smaller the scale value, the more accurate the count will be. The S662 has four prescale values, 1.0 (default), 0.1, 0.01, and 0.001.
An example of this application is as follows: A 600 pulse-per-revolution encoder is used to measure cable before it is cut to the proper length. There is a wheel (one foot in circumference) attached to the encoder, in direct contact with the cable. The user wants to see the counter display feet to 1/100’ accuracy (to two decimal points).
With the default prescale of 1.0, one rotation of the wheel would be displayed on the counter as 00.0016’. However, by using a prescale of 0.01, the resolution has been mul­tiplied by 100, allowing the counter to display 0.16667, increasing the accuracy of the
The up and down keys increment or decrement the flashing digit. Some parameters support
or
ENTER
negative numbers. In these cases, the most significant digit can be made negative by incrementing it between "9" and "0."
Saves the values as the new setting for the
function in memory and advances to the next function of the menu automatically.
3.5 Special Start-Up Modes
There are two start-up modes for the S662 counter. The default start-up mode will be used every time the counter is powered up by the user. There is one alternate start-up mode that will allow the operator to return the counter software functions to factory de­fault settings.
The alternate start-up modes can only be accessed by pressing and holding certain keys during the power up sequence.
Press and hold both keys on the face of the counter
Apply power while holding keys
Key Keypad behavior
Returns parameters to factory defaults. Resets password to 000, and all user scaling, operation modes and set points to factory defaults. Display will show freset.
ENTER
and
RESET
counter and allowing more accurate cutting.
1) To access the prescale parameters, enter the Programming Mode, and press until the count2 setup menu category is reached.
2) Press to continue to the Parameter Name prescl. The display will flash between prescl and the default value of 1.0. When the display shows 1.0, press .
3) Use the arrow keys to scroll through the choices. Press when correct prescale is
ENTER
ENTER
ENTER
selected to accept the value and proceed to the next parameter, Count 2 Scale.
Scale 2
1) To access the user-defined scaling parameter, enter the Programming Mode, and press until the count2 setup menu category is reached. Press .
ENTER
2) Press to continue to the Parameter Name scale2. The display will flash between scale2 and the default value of 01.0000. When the display shows 01.0000, press
3) Use the arrow keys to enter the correct value of the flashing digit. Use the key to advance to the next digit. Press when the correct scale is selected to accept
ENTER
RESET
ENTER
value and proceed to the next parameter, Count 2 DP.
DP 2
1) To set the Decimal Point position, enter the Programming Mode, and press until the count2 setup menu is reached.
2) Press , and then to continue to the Parameter Name dp 2. The display will flash between dp 2 and the default 000000. When the display shows 000000, press
3) Use the arrow keys to scroll through the choices. Press when the correct deci-
ENTER
ENTER
ENTER
mal place is selected to accept value and proceed to the next menu category, Output 1 Mode setup.
17 22
2) Press to continue to the Parameter Name scale1. The display will flash between
ENTER
4 Programming Operations and Parameters
scale1 and the default value of 01.0000. When the display shows scale1, press
3) Use the arrow keys to enter the correct value of the flashing digit. Use the key to advance to the next digit. Press when the correct scale is selected to accept value
ENTER
RESET
ENTER
and proceed to the next parameter, DP 1.
To calculate the scaling parameter, use the following scale formula:
Display = Multiplier (Pulse x Prescale x Scale x Decimal Point)
If the scale value isn’t known, use the following formula:
DISPLAY X Dp
SCALE =
MULT. (PULSE X PRESCALE)
For the example we used, the scale value is:
1.00
SCALE =
= 0.1667
1 (600) X 0.01
Decimal Point Position
1) To set the Decimal Point position, enter the Programming Mode, and press q until the count1 setup menu is reached.
2) Press to continue to the Parameter Name dp 1. The display will flash between dp 1 and the default 000000. When the display shows 000000, press .
3) Use the arrow keys to scroll through the choices. Press when the correct decimal
ENTER
ENTER
ENTER
This section details the initial programming options of the S662, presuming all defaults are in place.
If you are already familiar with the S662 programming, see Appendix B for the Program­ming Quick Reference Guide.
To enter the Programming Mode, hold and press p .
To return to the Display Mode, press and hold for four seconds when counter is not in
ENTER
RESET
an option menu.
4.1 Password and Security Controls
The security feature helps prevent accidental changes to counter settings.
The password value determines the counter’s security level, as shown in Table 5.
If you have forgotten the password, see section 3.5; Special Start-Up Modes.
place is selected to accept value and proceed to the next menu category, Count 2 Setup.
4.4 Count 2 (Batch) Scaling and Display (Count 2 Setup)
Count 2 operation may be controlled in one of two ways: Dual mode and Batch Mode.
Dual Mode
In Dual Mode, the Count 2 is increased or decreased at the same time Count 1 is in­creased or decreased. The counter operates like two independent counters sharing the same input signal. Each “counter” has independent scaling and reset controls.
Batch Mode
In Batch Mode, Count 2 is increased whenever an Auto Reset occurs on Count 1. The Auto Reset parameters (see section 4.7) must be configured for the application.
The Count 2 display value is independent of the Count 1 display value. The secondary “channel” in the S662 has its own scaling values and decimal position. The Scale 2 mul­tiplier and Decimal Point 2 locations operate similar to that for Count 1. In addition, a
1) After entering the Programming Mode, the first field is Password. a) If no password has been assigned, the counter will flash between chpass, for
“Change Password” and the default value, 000.
b) To change the password, press when the display shows 000. Use the arrow keys
ENTER
to change the flashing digit to the desired number.
c) Press to advance to the next digit. Press to accept the password to counter
RESET
ENTER
memory and press it again to advance to the next parameter, Input Setup.
Table 5. Password Values
Password Value Level of Security
No Security - Default setting
000
001 - 099
Allows full access to the Programming Menu and
Quick Access to set points is enabled.
Fully secure
The Programming Menu is secured by password
and Quick Access to set points is disabled.
Count 2 Prescale is available. This allows a large accumulating raw count to be reduced to a much smaller (display-able) number.
1) To set the Batch Mode, enter the Programming Mode, and press until the count2 setup menu is reached.
2) Press to continue to the Parameter Name mmode. The display will flash be­tween mode and the default dual. When the display shows dual, press .
ENTER
ENTER
21 18
100 - 999
Quick Access Only
Programming Menu is secured by password,
Quick Access to set points via up and down keys
enabled.
2) If a password is already in the counter, the display will flash between pass, for “En-
Table 7. Count Behavior with B Channel Set as Direction Control
ter Password,” and the default value, 000.
a) When the display shows 000, press . Use the arrow keys to change the flashing
digit to the desired number. Press to advance to the next digit.
b) Press to enter the password as shown. If an incorrect password is entered, access
ENTER
ENTER
RESET
denied will flash on the display. Press an arrow key to return to the pass display.
c) After entering the correct password, the counter will return to chpass. Press to
ENTER
change password, or press the key to continue to the Input Setup menu category.
4.2 A/B Channel Options (Input Setup)
The next category in the Programming Mode is the “Input Setup.” Here you can adjust the A and B channels to the appropriate count modes.
The A channel input may be selected as an Up, Down, Quadrature or Reverse Quadra­ture* input.
As an Up channel, pulses applied to the A input are added to the display. In Down mode,
A Channel Setting State at B Input Resulting Count
UP UP UP
UP DOWN DOWN
DOWN UP DOWN
DOWN DOWN UP
When A channel has been set to either Quadrature or Reverse Quadrature settings, the B channel internally behaves as a direction control.
2) To set the B channel: a) In the Input Setup area, after entering the A Chan value, the display will flash be-
tween b chan and the counter’s default (dir). b) When the display shows dir, press . c) Use the arrow keys to change the value, then press to accept the selection and
ENTER
ENTER
proceed to the next menu category, Count Setup.
subtraction occurs. Note that when using Quadrature inputs, appropriate hardware (jump­er) settings may be needed. The Reverse Quadrature input allows the user to reverse the count direction of the encoder in software instead of having to rewire/remount the encod­er.
Table 6. Channel A Selection
A CHAN Direction B CHAN
UP Up User defined
DOWN Down User defined
QUAD Up Not Available
R QUAD Down Not Available
1) To set the A Channel value: a) When the display flashes input setup, press . The display will change to a chan. b) Press again to proceed to the choice list. Scroll through up, down, quad, and r
ENTER
ENTER
NOTE: The B channel will not show in the menu when Quadrature or Reverse Quadrature has been selected for the A Channel input.
4.3 Count 1 Scaling and Display (Count 1 Setup)
Scale
The S662 counter allows for scaling of display values. Scaling allows the counter to dis­play a more accurate number than its 6-digit capacity might otherwise allow.
Generally speaking, the smaller the scale value, the more accurate the count will be. The S662 has four prescale values, 1.0 (default), 0.1, 0.01, and 0.001.
An example of this application is as follows: A 600 pulse-per-revolution encoder is used to measure cable before it is cut to the proper length. There is a wheel (one foot in circumference) attached to the encoder, in direct contact with the cable. The user wants to see the counter display feet to 1/100’ accuracy
quad using the arrow keys.
c) When the selection is complete, press to accept the selection to counter memory
ENTER
and proceed to the next parameter, Chan B Mode.
The B channel may be set as Up, Down or Direction. In the direction mode, the B chan­nel is no longer a count source, but controls the count direction of the A channel input. This state control works as an ‘exclusive-or’ with the channel A direction. Thus, if B input is in the ‘Down’ state and A channel is set to Down, pulses at the A input will in­crement count.
19 20
(to two decimal points).
With the default scale of 01.0000, one rotation of the wheel would be displayed on the counter as 00.0016’. However, by using a prescale of 0.01, the resolution has been mul­tiplied by 100, allowing the counter to display 0.16667, increasing the accuracy of the counter and allowing more accurate cutting.
1) To access the user-defined scaling parameter, enter the Programming Mode, and
press q until the count 1 setup menu category is reached.
Loading...