Simpson Electric S661 Instruction Manual

Page 1
S661
Rate Counter
Operation Manual
SIMPSON ELECTRIC COMPANY
520 Simpson Avenue, Lac du Flambeau, WI 54538-0099
(715) 588-3311 FAX (715) 588-3326
Printed in U.S.A. Part No. 06-116546 Edition 8, 06/07
Page 2
!
To the best of our knowledge and at the time written, the information contained in this document is technically correct and the procedures accurate and adequate to operate
Menu
Category
Parameter
Name
Choices /
Format
Description Tech
Note
this instrument in compliance with its original advertised specifications.
Notes and Safety Information
This Instruction Manual contains warning headings that alert the user to check for hazardous conditions. These appear throughout this manual where applicable, and are defined below. To ensure the safety of operating performance of this instrument, these instructions must be adhered to.
Caution, refer to accompanying documents.
Caution, risk of electric shock.
Technical Assistance
SIMPSON ELECTRIC COMPANY offers assistance Monday through Friday 8:00 am to 4:30 pm Central Time by contacting Technical Support or Customer Service at (715) 588-3311. Internet: http://www.simpsonelectric.com
rESEt SEtuP
SP3 000030*
SP4 000040*
rStbtn EnAbLE*
diSAbL
SP3
Set point #2 Low.
Values: -99999 to
999999. Decimal point will appear according to the current DP setting.
SP4
Set point #2 High.
Values: -99999 to
999999. Decimal point will appear according to the current DP setting.
Reset Button
Enable or disable front panel reset button.
4.5
4.5
4.6
Warranty and Returns
SIMPSON ELECTRIC COMPANY warrants each instrument and other articles manu­factured by it to be free from defects in material and workmanship under normal use and service, its obligation under this warranty being limited to making good at its fac­tory or other article of equipment which shall within one (1) year after delivery of such instrument or other article of equipment to the original purchaser be returned intact to it, or to one of its authorized service centers, with transportation charges prepaid, and which its examination shall disclose to its satisfaction to have been thus defective; this warranty being expressly in lieu of all other warranties expressed or implied and of all other obligations or liabilities on its part, and SIMPSON ELECTRIC COMPANY neither assumes nor authorizes any other persons to assume for it any other liability in con­nection with the sales of its products.
This warranty shall not apply to any instrument or other article of equipment which shall have been repaired or altered outside the SIMPSON ELECTRIC COMPANY fac­tory or authorized service centers, nor which has been subject to misuse, negligence or accident, incorrect wiring by others, or installation or use not in accord with instruc-
END
Exit Programming Menu
* = factory default settings
tions furnished by the manufacturer.
Under the normal field usage there is no need to remove the front bezel of this prod­uct. The front bezel of this product should only be removed by a qualified technician.
1 38
Page 3
Menu
Category
Parameter
Name
Choices /
Format
Description
Tech
Contents
1 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Note
1.1 General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SEtPnt SEtuP
dELAY 2 010.00*
SP1 000010*
SP2 000020 *
Delay 2
Output 2 delay time.
Appears only if Output 2
mode set to timed.
SP1
Set point #1 Low. Values:
-99999 to 999999. Decimal point will appear according to the current
DP setting.
SP2
Set point #1 High. Values:
-99999 to 999999. Decimal point will appear according to the current
DP setting.
4.4
4.5
4.5
1.2 Part Number Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Option Module Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Hardware Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Panel Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Removing / Installing Option Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 120/240 VAC Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Standard Input Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.5 Quadrature Input Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6 Excitation Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.7 Single and Dual Relay Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3 Display & Keypad Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2 Display Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 What the Keys Do in Display Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.4 What the Keys Do in the Programming Mode. . . . . . . . . . . . . . . . . . . . . 18
3.5 Special Start-Up Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
* = factory default settings
4 Counter Operations and Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.1 Password and Security Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.2 A/B Channel Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.3 Rate (Frequency) Scaling and Display. . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.4 Output Control Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.5 Set Point Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.6 Miscellaneous Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Appendix A: Technical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
A.1 Functional Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
A.2 Electrical, Environmental and Mechanical Specifications. . . . . . . . . . . . 31
Appendix B: Programming Quick Reference. . . . . . . . . . . . . . . . . . . . . . . . . . 33
37 2
Page 4
1 Product Description
Menu
Parameter
Choices /
Description Tech
1.1 General Description
The S661 rate counter fits a 1/8 DIN standard cutout and is perfect for tight spaces, extending only 3.24” (82mm) behind the panel. The unit is UL listed. The unit is for in­door use at altitudes up to 2000m, temperatures between 0° and 40°C and installation category III, pollution degree 2.
Category
oPut 2 SEtuP
Name
SP1=Lo<—
dELAY1 010.00*
MmodE2 diSAbL
Format
—>SP2=hi
timMEd LAtCH* bound
Output 1 Bindings
Reminder message indicates which and how
the set points are used for comparison.
Delay 1
Output 1 delay time.
Appears only if Output 1
mode set to timed.
Output 2 Mode
Set the mode of operation
for Output 2. Can be disabled, timed, latched or boundary mode.
Note
4.4
4.4
4.4
The counter is powered from 120 or 240 VAC. The nonvolatile EEPROM retains all programming and count information when power is removed or interrupted.
Display scaling, preset values and all menu functions are easily programmed from the front panel, following easy-to-use word prompts. Front panel reset disable and pass­word lockout protection features guard against unauthorized or accidental changes.
The counter accepts count rates up to 30 kHz and pulses from different types of sen­sors, including Quadrature, CMOS or TTL circuits and PNP or NPN devices.
The optional, field-replaceable single/dual relay module enhances the counter from a passive display device to an integral control element for your application. The counter has latching, boundary or timed (0.01 to 599.99 seconds) output modes.
An optional 12 VDC (100mA) excitation output module can provide power for external sensors.
SP3=Lo<—
—>SP4=Hi
* = factory default settings
Output 2 Bindings
Reminder message indicates which and how
the set points are used for comparison.
4.4
3 36
Page 5
Menu
Parameter
Choices /
Description Tech
1.2 Part Number Identification
Category
Name
Format
dP 000000*
000000.
00000.0
0000.00
000.000
00.0000
0.00000
oFFSEt 000000*
DP
Display Value 2 (Rate) Decimal Point location.
Affects appearance of Offset and Set Point parameters.
Offset
Set Display Value 2 (Rate) scaling offset.
Values: -99999 to
999999. A decimal point
will appear according to
the user-programmedDP
Note
4.3
4.3
The following matrix indicates the configuration of your S661 counter.
Basic Unit
S661
Power Supply
120 VAC 240 VAC
1 2
Input
Standard
Quadrature
Output
1 2
One relay
Two Relays
None
0 1 2
Excitation
None 12VDC
0 1
Other
None
1.3 Option Module Summary
0
oPut 1 SEtuP
MmodE 1 diSAbL
timMEd LAtCH* bound
* = factory default settings
position.
Output 1 Mode
Set the mode of operation for Output 1. Can be disabled, timed, latched or boundary mode.
4.4
1
Input Excitation Power
2
4
Supply
5
Output
Figure 1. Option Module Slots (Rear View)
The S661 is a modular product which uses field configuring slide-in modules. The modules slide easily into the rear of the counter.
Figure 1 displays the functional assignments for each module position.
35 4
Page 6
Table 1 describes available option modules for the S661.
Menu
Parameter
Choices /
Description Tech
Table 1. Option Module Summary
Module
slot
1 Input Standard Input Module
1 Input Quadrature Input Module
2 Ext 45064 12 VDC Excitation Module
4 Power 120 VAC Power Module
4 Power 240 VAC Power Module
5 Output 45062 Dual Relay Module
Type P/N Description
See
Section
2.4
2.5
2.6
2.3
2.3
2.7
Category
inPut SEtuP
rAtE SEtuP
Name
Format
A CHAn uP*
doWn quAd r quAd
b CHAn dir*
uP doWn
MmodE MmSEC*
SEC Mmin
Chan A Mode
Select count mode of A
channel.
Chan B Mode
Select count mode for B
channel.
Note: If A channel set to
Quad or Rquad, this item
is not accessible.
Rate Mode
Defines the prescaling
and sampling interval for
Note
4.2
4.2
4.3
5 Output 45063 Single Relay Module
2.7
Hr
SCALE 00.0000*
* = factory default settings
frequency computation
Scale
Set Display Value (Rate)
scaling multiplier.
Values: -9.9999 to 9.9999
4.3
5 34
Page 7
Appendix B: Programming Quick Reference
2 Hardware Setup
If you are unfamiliar with navigating menus in the S661 see section 3. Each param­eter is listed in the order of appearance in the menu system. Refer to the paragraph indicated in the Tech Note column for technical details on a particular parameter.
Tip: Photocopy these pages to mark settings on.
Menu
Category
Parameter
Name
Choices /
Format
PASS 000
Description Tech
Password Entry and
Note
4.1
Verification
ACCESS<—
—>dEniEd
Password Fail
4.1
Appears if incorrect
password entered
CHPASS 000*
Password Change
4.1
Appears if correct
2.1 Panel Installation
The S661 1/8 DIN counter requires a standard 1/8 DIN panel cutout of 1.77” (45mm) high by 3.62” (92mm) wide. To install the counter into a panel cutout, remove the clips from the side of the counter. Slide the counter through your panel cutout, then slide the mounting clips back on. Press evenly to ensure a proper fit.
3.62"
92mm
3.24"
82mm
1.77"
45mm
1.74"
44mm
2.04"
51.8mm
password entered
000 = Password protection disabled 001-099 = Secures all parameters 100-999 = Enables SPs/ResPos access in
display mode
* = factory default settings
ENTER
3.93"
.52"
13.2 mm
%
RESET
99.8 mm
Figure 2. Counter and Panel Cut-Out Dimensions
Figure 3. Panel Mounting Clips
33 6
Page 8
2.2 Removing / Installing Option Modules
!
Quadrature input module
Shut power off before removing or installing any option modules
1. Remove module from case by inserting a screwdriver into tab slot opening at top of input module. Apply pressure to release module from case. Repeat proce­dure for tab located on underside of module and then slide module away from the case.
2. Refer to appropriate sections to configure switch or jumpers for proper operation. Table 1 can be used to identify modules and their associated detail paragraph.
3. Install module by carefully aligning module edges with slots in case and pressing forward until tabs (on top and bottom) engage.
Input Channels
Input Inversion
Operation modes
Input Sources
Input Impedance
A & B channels
A, B and User
User-selectable input polarity. A and B channel polarity
selective in standard mode only.
Standard, Quadrature X1 and Quadrature X4
Switch contact, CMOS or TTL logics, PNP or NPN devices quadrature (single-ended) encoders
Sinking: 10K, 5% Res. Pull-up to (9.0 - 16 VDC) ±10% Sourcing: 5.1K, 5% Res. Pull-down to common
Input Thresholds
Low Bias mode:VLT = 1.6V ±10%VUT = 3.6V ±10% High Bias mode:VLT = 5.0V ±10% VUT = 7.0V ±10%
User Channel
Low pass
filter
Max voltage
VLT = 0.9V (min) VUT = 3.15V (max)
Frequency < 200Hz (0 to 10V input square wave at
50% duty cycle)
A, B and User channels 30VDC maximum sustained
Single / Dual Relay Modules
Contact Rating
Mechanical Life
5 Amps 250 VAC
1,000,000 cycles
Isolated 12V Excitation Module
Exitation Output
Exitation Isolation
100 mA at 12 VDC ±5%
1500 V
Figure 4. Removing Option Module
7 32
Page 9
A.2 Electrical, Environmental and Mechanical Specifications
!
!
2.3 120/240 VAC Power Module
Power Requirements
Power Consumption
Reset Input Signal
Storage Temperature
Operating Temperature
Relative Humidity
Bezel
Panel Cutout
Case Depth
AC Supply: 120 or 240 VAC, ±10%
3VA
Active Low: 0.2 VDC = active
-10 to 60°C
0 to 40°C
0 to 80% for temperatures less than 32°C, decreasing linearly to 50% at 40°C. (Non-
condensing)
3.93" x 2.04" x 0.52" (99.8 x 51.8 x 13.3mm)
3.62" x 1.77" (92 x 45 mm) 1/8 DIN
3.24" (82mm)
Remove power before wiring option modules.
Denotes module
!
position 4 at rear of counter
The AC power module allows the S661 to be operated from standard 50/60 Hz line power. The power module will be configured as 120 VAC or 240 VAC per markings on the
VAC
VAC
Power Supply 120 VAC or 240 VAC power connection
back panel. Ensure the input rating of the supply matches your line voltage. The power supply module has provisions for a hard-wire Alarm Reset. This control can be a switch, relay contact or solid state device. Actuation is immediate upon an active Low for at least 2.5ms to this terminal. The
RESET
COMMON
POWER
Remote Reset Active low 0.2V performs primary reset
reset circuit is independent of the power circuit.
Figure 5. AC Power Module
Weight
Standard input module
Input Channels
Count edge
Input Sources
Input Impedance
A & B channels
User Channel
Low pass filter
Max voltage
9.0 oz. (255.1g)
A, B and User
High to low transition (A and B channels)
Switch contact, CMOS or TTL logics, PNP or NPN devices
Sinking: 10K, 5% Res. Pull-up to (9.0 - 16 VDC) ±10% Sourcing: 5.1K, 5% Res. Pull-down to common
Input Thresholds
Low Bias mode:VLT = 1.6V ±10% VUT = 3.6V ±10% High Bias mode:VLT = 5.0V ±10% VUT = 7.0V ±10%
VLT = 0.2V (min) VUT = 3.0V (max)
Frequency < 200Hz (0 to 10V input square wave at 50% duty cycle)
A, B and User channels 30VDC maximum sustained
NOTE: A fusible link is not provided on this module. A ½ Amp Time Delay fuse, Bussman MDL ½, or similar, is required.
Never connect AC mains (hot or neutral) to the Reset or Common terimnals!
2.4 Standard Input Module
Denotes module
position 1 at rear
of counter
Figure 6. Standard Input Module
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
Primary Input
Connect the input
signal to A input
and common
Display Hold
Active Low
'Freezes' Display Value
Secondary Input Direction Control or
31 8
Page 10
DIP Switch (Shown for TTL Factory Settings)
Appendix A: Technical Specifications A.1 Functional Specifications
FUNCTION
B Bias Off=Hi On=Lo B Freq Off=Hi On=Lo B Off= Sink On= Source A Bias Off=Hi On=Lo A Freq Off=Hi On=Lo A Off= Sink On= Source
Dipswitch Legend
= ON = OFF
CHANNEL
1 2 3 4 5 6
1 2 3 4 5 6
Note: Refer to specifications for DIP switch function electrical characteristics
Figure 7. Standard Input Module Default Settings
DIP switch SW1, figure 7, is used to set up the counter to conform to the electrical characteristics of the sensor or signal being detected. Switch positions 1-3 config­ure channel B, while switches 4-6 configure channel A. These switches select bias (threshold voltages), low pass filter (enable/disable) and sensor type (Sink or Source).
Refer to the documentation that accompanied the sensor for related information. The
Count modes supported
Count Inputs
Miscellaneous inputs
Maximum count rate
Min pulse width
Rate modes suported
Frequency accuracy
(instantaneous)
Frequency vs
temperature
Frequency vs time
(aging)
Count/Direction, Add-Add, Add-Subtract, Subtract-Subtract, Quadrature, Batch, and Rate
2: Channel A (Primary) and Channel B (Secondary/Dir control)
2: Reset (Alarm Reset) and User (Display Hold)
30 Khz (Standard and Quadrature X1 modes)
7.5 Khz (Quadrature X4 mode)
2 uS (Standard mode)
See Table 8
> ± 0.02% of reading
+ 0.0001% of reading per °C
± 0.002% of reading per year
sensor can most likely be matched to one of the typical switch settings shown in figure 8 and figure 8a.
Note: The input boards are designed so that selecting sourcing or sinking is based on the type of sensor that is being used. If a PNP (sinking) sensor is be­ing used, set the input board for sinking also (switched 3 and 6 = OFF).
If channel B is not used, default settings for switch positions 1 through 3 should be se­lected. Default settings are provided in Table 2.
The input module also provides for a user input signal. On the S661, this input per­forms a Display Hold. While active, the rate value shown on the display is “frozen.” Internal measurements and output controls continue to operate.
Display Digits
Display Decimal Point
Display LEDs
Display Range
Output channels
Output modes
Delay times
Output Response time
Multi-tasking Operation
6-digit, 7-segment with leading zero blanking
User-programmable
Red 0.56" (14.2mm), high efficiency
- 99,999 to + 999,999 (Independent of decimal position)
2, with front panel indicator for each
Disabled, Timed, Latching and Boundary
0.01 to 599.99 sec tol: -2.5 ms/+15ms
Within 10 ms of reading update (see rate modes)
Count and output control maintained while in Programming mode.
9 30
Page 11
Set Point Parameters
+
1) To set the Set Point parameters, enter the Programming Mode, and press un­til the setpnt setup menu category is reached.
2) Press to continue to the Parameter Name sp 1. The display will flash between sp 1 and the default value of 000010. When the display shows 000010, press
3) Use the arrow keys to enter the correct value of the flashing digit. Use the key to advance to the next digit. Press when the correct set point is select-
ENTER
ENTER
RESET
ENTER
ed to accept value and proceed to the next parameter, SP 2.
4) Repeat these steps for SP 2, SP 3, and SP 4. The counter will proceed to the next menu category, Reset Setup.
The S661 can accept inputs from many different sensors. The A and B channels may be configured independently as shown in Table 2. Figures 8 and 8a have examples of some typical sensors and the wiring connections that would be used.
Table 2. Standard Input Module DIP Switch Settings
* = Factory Default setting 1 B Channel Bias: OFF = Hi* VLT = 5.0 V VUT = 7.0V (+/- 10%) ON = Low VLT = 1.6 V VUT = 3.6V (+/- 10%)
2 B Channel Frequency: OFF = Hi* (low pass filter disabled)
4.6 Miscellaneous Controls
1) To access the Miscellaneous Controls, enter the Programming Mode, and press
until the reset setup menu category is reached.
2) Press to continue to the Parameter Name rstbtn. The display will flash be­tween rstbtn and the default value of enable. When the display shows enable, press
3) Use the arrow keys to select either Enable or Disable. Press when the cor­rect mode is selected to accept selection.
4) The display will now show end. If you are finished programming the S661, press
If not, press the arrow keys to back up to the necessary parameter.
ENTER
ENTER
ENTER
rStbtn
(Reset Button)
ENTER
The Reset button Inhibit feature disables the front panel reset button. This can be used to prevent accidental resets. The external (rear panel) hardware reset input is not affected by this setting.
ON = Lo (low pass filter enabled)
3 B Channel Sensor: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
4 A Channel Bias: OFF = Hi VLT = 5.0 V VUT = 7.0V (+/- 10%) ON = Low* VLT = 1.6 V VUT = 3.6V (+/-10%)
5 A Channel Frequency: OFF = Hi* (low pass filter disabled) ON = Lo (low pass filter enabled)
6 A Channel Sensor Type: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
ON
1 2 3 4 5 6
LOW BIAS LOW FREQUENCY SOURCING
A INPUT
COMMON
HIGH FREQUENCY
HIGH BIAS
SINKING
ON
1 2 3 4 5 6
LOW BIAS LOW FREQUENCY SOURCING
A INPUT
COMMON
HIGH FREQUENCY
HIGH BIAS
SINKING
USER INPUT
B INPUT
ISO+12V
ISOCOM
COMMON
INPUT
EXCITATION
PNP SENSOR
__
---
+
_
OUTPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
ISO+12V
ISOCOM
EXCITATION
NPN SENSOR
__
---
+
_
Figure 8. Sensor Connection Examples
29 10
Page 12
HIGH FREQUENCY
HIGH BIAS
SINKING
DRY CONTACT
ON
1 2 3 4 5 6
LOW BIAS LOW FREQUENCY SOURCING
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
Latch Until Description
A front panel or external reset event is required
Reset
to deactivate the output.
Output deactivated when set point is
SP#
encountered.
Output deactivated when reset position is
RstPos
encountered.
Table 10. Latch Until
NOTE: The outputs for this counter activate regardless of count direction in all count modes.
Figure 8a. Sensor Input example
2.5 Quadrature Input Module
The Quadrature / Universal Input Module has two operational modes: Quadrature mode and Standard mode. Quadrature mode is selected by positioning JP1 and JP2 on pins 1 and 2. Standard mode is selected by placing JP1 and JP2 on pins 2 and 3 (see Figure 10 for details). The Quadrature mode supports a wide range of encoders including the Simpson SE series.
While in Standard mode, this module works similarly to the Standard Input module, with the added capability to selectively invert A, B, and User input signals. The Input module also provides for a User input signal. On the S661 this input serves as a Dis­play Hold. While active, the rate value shown on the display is “frozen.” Internal mea­surements and output controls continue to operate.
NOTE: If B channel is not going to be used, use the default switch settings for
1) To set the Output Control modes, enter the Programming Mode, and press until the oput 1 setup menu category is reached.
2) Press to continue to the Parameter Name mmode1. The display will flash
ENTER
between mmode1 and the default value of latch. When the display shows latch, press
3) Use the arrow keys to select the correct mode. Press when the correct mode
ENTER
ENTER
is selected to accept value, and to the next parameter, Output 1 Bindings. Other choices may appear, depending on which Output 1 Mode is selected. See Ap­pendix B for which options correspond to which parameters.
4) Press until oput 2 setup is displayed to make similar selections for Output 2
ENTER
Mode.
5) When all selections are entered and accepted into counter memory, counter will proceed to next menu category, Set Point Setup.
4.5 Set Point Parameters (Set Point Setup)
The S661 has four set point parameters and an Offset Value.
SW1 positions 1 through 3. Default settings are provided in Table 3.
11 28
SP1 and SP2 are used only with Output 1, and SP3 and SP4 are used only with Out­put 2.
The SP1 and SP3 parameters are used as Latched or Timed “trigger” values. When a Boundary Output is selected, SP1 and SP3 become the low boundary value.
The SP2 and SP4 parameters are used as high boundary value or ‘turn-off’ values when used with other alarm types (i.e. latched until SP4).
The values for all set points are -99999 to 999999. The decimal point will appear ac­cording to the current decimal point setting.
Page 13
4.4 Output Control Modes
The S661 supports two independent output channels with four modes of operation: disabled, timed, latched and boundary.
Output Type Description
Disabled Output
The output channel is inactive.
In both modes, the state of the User input signal can be selected as active high or ac­tive low. DIP switch SW1 configures the counter to match the specifications of the ac­companying sensor. When shipped from the factory, the counter is set for X1 quadra­ture, as shown in Figure 10 and Table 3:
Denotes module
position 1 at rear
of counter
Timed Output
Latch Output
Boundary Output
The timed mode activates an output when a set point or ‘trigger’ condition is reached. Once active, the output is held for a specified delay period. The delay may be between 0.01 and 599.99 seconds.
The output will activate when the specified value is
encountered (SP1 for output 1, SP3 for output 2). If a timing period is in progress, a new trigger does not occur. This is referred to as a non­retriggereable timer.
A RESET will cancel the timed output.
The latch mode activates an output when a ‘trigger’
or set point is reached.
The output will activate when the value is encountered (SP1 for output 1, SP3 for output 2).
Once activated, the output is held and can be
deactivated only when the specified Latched Until
condition is met. The Latched Until conditions can be seen in Table 10.
The Boundary mode differs from the other output
types in that it allows the counter to have an output
activate/deactivate automatically within a specified range.
Boundary mode activates an output when the
count is between the specified low and high set points (SP1/SP2 for output 1, SP3/SP4 for output
2.)
Figure 9. Quadrature / Universal Input Module
12 3
JP2
Note: To Enable standard count Mode move both jumpers down one pin
Quadrature
Count
Standard
Count
12 3
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
JP1
B Bias Off=Hi On=Lo
B Freq Off=Hi On=Lo
B Off= Sink On= Source
A Freq Off=Hi On=Lo
A Bias Off=Hi On=Lo
1 2 3 4 5 6 7 8 9 10
Dip Switch:
Shown in
Quadrature Mode
(Factory Defualt)
Primary Input
or
Quadrature A
Display Hold
Freezes
Displayed value
Secondary Input or Quadrature B
A Off= Sink On= Source
B Edge Off= On=
A Edge Off= On=
User pol Off= On=
Quadr Off=X4 On=X1
SW1
Dipswitch Legend
= ON = OFF
Figure 10. Quadrature Input Module Default Settings
27 12
Page 14
Table 3. Quadrature Module DIP Switch and Jumper Settings
Rate Offset
1) To set the Rate Offset, enter the Programming Mode, and press until the rate JP1/2: Count Mode Selector Jumpered 1-2 = Quadrature mode** Jumpered 2-3 = Standard counter mode SW1: 10 Position DIP Switch * = Factory Default setting
1 B Channel Bias: OFF = Hi* VLT = 5.0V VUT = 7.0V (+/- 10%) ON = Low VLT = 1.6V VUT = 3.6V (+/- 10%)
2 B Channel Frequency: OFF = Hi* (low pass filter disabled) ON = Low (low pass filter enabled)
3 B Channel Sensor: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
4 A Channel Bias: OFF = Hi* VLT = 5.0 V VUT = 7.0V (+/- 10%) ON = Low VLT = 1.6 V VUT = 3.6V (+/- 10%)
setup menu is reached.
2) Press to continue to the Parameter Name offset. The display will flash be-
tween offset and the default 000000. When the display shows 000000, press .
3) Use the arrow keys to select the correct value for the flashing digit, press to
ENTER
ENTER
RESET
advance to the next digit.
3) When the correct value is displayed, press to accept and proceed to next
ENTER
menu category, Output 1 Mode.
Examples for Rate Mode, Rate Scale, Rate Decimal Point Position and Rate Offset are on following pages:
Description Value Formula Value
Pulses per second
seen at input
Mode 2 = x1 sec/Hz sec Mode
10000 Input Frequency
5 A Channel Frequency: OFF = Hi* (low pass filter disabled) ON = Lo (low pass filter enabled)
6 A Channel Sensor Type: OFF = Sinking* (internal pull-up enabled) ON = Source (internal pull-down enabled)
7 B Channel Count Edge: OFF = Rising (standard count mode only) ON = Falling*
8 A Channel Count Edge: OFF = Rising (standard count mode only) ON = Falling*
9 User Input Polarity: OFF = High/open circuit = Inhibit Count ON* = Low/closed circuit = Inhibit Count
10 Quadrature Mode: OFF = X4 (quadrature mode only) ON = X1*
User-entered
.5000 Scale
Multiplier
User-entered
100.00 Offset
additive value
Decimal Position 0000.00 DP
Table 9. Rate Example The input frequency can be linearly scaled using the Scaling Multiplier, Offset and Decimal Point. The rate channel has an offset value as well. To illustrate, the follow­ing example will be used:
1) Multiply Input Frequency by implied Mode multiplier 10000 x 1= 10000
2) Multiply by user-specified Scale:
3) Discard all digits to right of decimal place: (If number is larger than six digits, it will not fit in the display) 5000
4) Apply the user-specified DP location:
50.00
5) Add user-specified Offset location:
250.00 - 100.00 = 150.00 (That is what will be seen of the display) The following notation may be used to describe this behavior: Display = INT [Fint x Scale] DP + Offset
13 26
Page 15
4.3 Rate (Frequency) Scaling and Display (Rate Setup)
One of four rate modes may be selected to best accommodate input frequencies
2.6 Excitation Module
ranging from 0.00278 Hz to 30 kHz. Select the rate mode according to Table 8.
Range
(implied scale)
mSec
(Hz ÷ 1000)
Sec
(Hz x 1)
Min
(Hz x 60)
Hr
(Hz x 3600)
Typical Update
Period
1.0 sec 1 Hz 30 KHz
0.5 sec 2 Hz 30 KHz
3 sec
90 sec 40 Counts/Hr 3.0M Counts/Hr
Min. Input
Frequency
20
Counts/Min
Max. Input Frequency
1.2M
Counts/Min
Comments / Typical Application
1/1000 Hz resolution / High precision measurement of power line frequency
1 Hz resolution / Typical Setting for most
applications
Use when measuring ‘units per Minute'
Measures ‘units per Hour'. Also for very low
frequencies.
Table 8. Rate Mode Selection Rate can also be displayed as a signed entity and will be negative according to the direction state (see section 4.2). When B channel is configured for up or down count input, the rate is the sum of the frequencies at A and B with the polarity of rate deter­mined by the A channel up/down mode.
QUADRATURE ENCODER
Figure 11. Wiring Encoder w/ Excitation Supply
PHASE A-WHITE
PHASE B-GREEN
+
12 VDC Excitation Module
COMMON (BLACK)
POSITIVE-RED
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
QUADRATURE INPUT CARD
ISO+12V
ISOCOM
EXCITATION
EXCITATION
CARD
+
__
---
_
1) To set the rate mode, enter the Programming Mode and press until the rate
setup menu category is reached.
2) Press to continue to the parameter name rmmode. The display will flash be-
ENTER
tween rmmode and the default setting sec. When the display shows sec, press
.
ENTER
3) Use the arrow keys to scroll through the choices (mm sec, sec, mmin, hr). Press when the correct mode is selected to accept mode and proceed to next pa-
ENTER
rameter, Scale.
Rate Scale
1) At scale, the display will flash between rscale and the default 01.0000, when the
display shows 01.0000, press .
2) Use the arrow keys to select the correct value for the flashing digit, press to
ENTER
RESET
advance to the next digit.
3) When the correct value is displayed, press to accept and proceed to next pa-
ENTER
rameter, Rate DP.
Rate Decimal Point Position
1) To set the Decimal Point position, enter the Programming Mode, and press
until the rate setup menu is reached.
2) Press to continue to the Parameter Name rat dp. The display will flash be-
tween rat dp and the default 000000. When the display shows 000000, press .
3) Use the arrow keys to scroll through the choices. Press when the correct deci-
ENTER
ENTER
ENTER
mal place is selected to accept value and proceed to the next parameter name,
The Excitation Module can supply 12 VDC at up to 100 mA for external sensors or en­coders. This excitation is isolated from the counter internal logic supply. When using sensors or encoders that do not have a signal return or imply a signal return that is in common with the supply voltage, a common attachment that ties the excitation supply to the logic input common may be required. Examples of this appear in figures 8, 8a, 11 and 12.
DENOTES MODULE POSTION 1 AT REAR OF COUNTER
MODEL S.E. QUADRATURE ENCODER
CHANNEL A-WHITE
CHANNEL B-GREEN
POSITIVE (RED)
EXTERNAL POWER SUPPLY
+
+
COMMON (BLACK)
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
QUADRATURE INPUT CARD
Figure 12. Wiring Encoder with External Supply
Rate Offset.
25 14
Page 16
Denotes module position 2 at rear of counter
1) To set the A Channel value: a) When the display flashes input setup, press . The display will change to
ENTER
a chan.
b) Press again to proceed to the choice list. Scroll through up, down, quad,
ENTER
and r quad using the arrow keys.
c) When the selection is complete, press to accept the selection to counter
ENTER
memory, and press again to proceed to the next parameter, Chan B Mode.
The B channel may be set as Up, Down or Direction. In the direction mode, the B channel is no longer a count source, but controls the count direction of the A channel
ISO+12V
+
__
---
ISOCOM
EXCITATION
_
Figure 13. Excitation Module
2.7 Single and Dual Relay Modules
12 VDC, 100 mA max
input. This state control works as an ‘exclusive-or’ with the channel A direction. Thus, if B input is in the ‘Down’ state and A channel is set to Down, pulses at the A input will increment count.
A Channel Setting State at B Input Resulting Count
UP UP UP
UP DOWN DOWN
DOWN UP DOWN
DOWN DOWN UP
Table 7. Count Behavior with B Channel Set as Direction Control
When A channel has been set to either Quadrature or Reverse Quadrature settings, the B channel internally behaves as a direction control.
Figure 14. Single Relay Figure 15. Dual Relay
The Single and Dual Relay modules can activate circuit loads of up to 5 amps at 250 VAC. A Form C configuration allows use of normally-open (NO) and normally-closed (NC) circuit action.
Only the output 1 channel is implemented in the single relay module.
15 24
2) To set the B channel: a) In the Input Setup area, after entering the A Chan value, the display will
flash between b chan and the counter’s default (dir). b) When the display shows dir, press . c) Use the arrow keys to change the value, then press to accept the selec-
ENTER
ENTER
tion and proceed to the next menu category, Count Setup.
NOTE: The B channel will not show in the menu when Quadrature or Reverse Quadrature has been selected for the A Channel input.
Page 17
2) If a password is already in the counter, the display will flash between pass, for “Enter Password,” and the default value, 000.
3 Display & Keypad Controls
a) When the display shows 000, press . Use the arrow keys to change the
flashing digit to the desired number. Press to advance to the next digit.
b) Press to enter the password as shown. If an incorrect password is en-
ENTER
ENTER
RESET
tered, access denied will flash on the display. Press an arrow key to return to the pass display.
c) After entering the correct password, the counter will return to chpass.
Press to change password, or press the key to continue to the Input
ENTER
Setup menu category.
4.2 A/B Channel Options (Input Setup)
The next category in the Programming Mode is the “Input Setup.” Here you can adjust the A and B channels to the appropriate count modes.
The A channel input may be selected as an Up, Down, Quadrature or Reverse Quadrature* input.
3.1 Display
Numeric & Message Display
Output Status
Indicators
Units Window
4 Button Keypad
Figure 16. Display and Keypad Layout
6-digit 0.56” high red LED display.
2 Output Status Indicators; “1” and “2.”
As an Up channel, pulses applied to the A input are added to the display. In Down mode, subtraction occurs. Note that when using Quadrature inputs, appropriate hard­ware (jumper) settings may be needed.
* The Reverse Quadrature input allows the user to reverse the count direction of the encoder in software instead of having to rewire/remount the encoder.
Table 6. Channel A Selection
A CHAN Direction B CHAN
UP Up User defined
DOWN Down User defined
QUAD Up Not Available
Units Window for supplied label or legend.
4-Button keypad with tactile response.
R QUAD Down Not Available
23 16
Page 18
3.2 Display Error Messages
Table 4. Display Error Messages
Display Description Action Required
4.1 Password and Security Controls
The security feature helps prevent accidental changes to counter settings.
The password value determines the counter’s security level, as shown in Table 5.
PAdErr
999999 or
-99999
(Flashing)
E1
(Outputs
deactivate, count
stops)
E2
(Outputs
deactivate, count
stops)
E3
(Outputs
deactivate, count
stops)
The Keypad is disabled or a key is stuck in the ON position
The displayed count is too large for the counter to display. Since the internal count
buffer is much larger than the display, the
counter will maintain accurate count and control well beyond the display value.
Raw Count Overflow: The number of count pulses has exceeded the counter’s maximum internal value (2,147,483,648 or
-2,147,483,648)
Math Overflow: A large scale factor in
combination with large raw count has exceeded the counter's maximum internal value (+2,147,483,648 or -2,147,483,648)
Watchdog Fault: The counter did not experience an orderly power-down. This can
happen by exceeding the maximum
allowable count speed for a sustained period of time.
Cycle power to the
counter, if the error
remains, return
counter to factory for
repair.
Reset Counter
Reset Counter
Reset Counter
Reset Counter
If you have forgotten the password, see section 3.5; Special Start-Up Modes.
1) After entering the Programming Mode, the first field is Password.
a) If no password has been assigned, the counter will flash between chpass,
for “Change Password,” and the default value, 000.
b) To change the password, press when the display shows 000. Use the
ENTER
arrow keys to change the flashing digit to the desired number.
c) Press to advance to the next digit. Press to accept the password to
RESET
ENTER
counter memory and press it again to advance to the next parameter, Input Setup.
Table 5. Password Values
Password Value Level of Security
No Security - Default setting
000
001 - 099
Allows full access to the Programming Menu and
Quick Access to set points is enabled.
Fully secure
The Programming Menu is secured by password
and Quick Access to set points is disabled.
100 - 999
Programming Menu is secured by password,
Quick Access to set points via up and down keys
17 22
Quick Access Only
enabled.
Page 19
3.5 Special Start-Up Modes
There are two start-up modes for the S661 counter. The default start-up mode will be used every time the counter is powered up by the user. There is one alternate start-
3.3 What the Keys Do in Display Mode
Key Keypad behavior
up mode that will allow the operator to return the counter software functions to factory default settings.
The alternate start-up modes can only be accessed by pressing and holding certain keys during the power up sequence.
Press and hold both keys on the face of the counter
Apply power while holding keys
Key Keypad behavior
Returns parameters to factory defaults. Resets
ENTER
and
RESET
password to 000, and all user scaling, operation modes and set points to factory defaults. The display will show freset.
4 Counter Operations and Parameters
This section details the programming options of the S661, presuming all defaults are in place.
If you are already familiar with the S661 programming, see Appendix B for the Pro­gramming Quick Reference Guide.
To enter the Programming Mode, hold and press .
ENTER
Allows quick access to all the set points. This
or
Hold and
Press
ENTER
feature can be disabled by using a password (see
section 4.1).
Access the Programming Menu.
3.4 What the Keys Do in the Programming Mode
Key Keypad behavior
RESET
or
ENTER
Press and hold for four seconds to exit the programming mode.
The up and down keys navigate through the available menu functions. The menu ‘wraps around’ when the bottom or top of the menu is
reached.
1) Enter the current menu or parameter to view/edit.
2) Write the change to the counter memory and
move to the next function.
To return to the Display Mode, press and hold for four seconds.
RESET
21 18
Page 20
Setup Menu Function Menu Option Menu
Choice List A Choice list allows one to select from a fixed number of options. A
CHPASS 000
INPUT SETUP
COUNT SETUP
other setup menus
END
ENTER
ENTER
ENTER
A CHAN UP
B CHAN DOWN
Return to
Display Mode
ENTER
ENTER
000
up down quad
rquad
dir
up down
ENTER
ENTER
ENTER
Choice List is found in the Options section of the menu. This list is made up of the available options for the function that is being ed­ited. Example: Menu is Input Setup Menu, the Function is A Chan­nel, the Choice List is up, down, quad and rquad (see Table 6).
Key Keypad behavior
The up and down keys scroll through the
ENTER
available choices in the Choice list.
Saves the current choice as new parameter setting and steps to next parameter or category.
Numerical Value A numerical entry allows the changing of set point values, scale
values, etc.
Key Keypad behavior
Figure 17. Programming Menu Structure
In the Programming Mode, the S661 will return to Display Mode automatically if a key is not pressed within 120 seconds (2 minutes). The menu is comprised of three lev­els: Setup Menu, Function Menu and Option Edit Menu. Figure 17 illustrates the three levels of the menu system.
Password Entry Entry (Pass) and changing of the password (Chpass) are similar to
editing a numerical parameter. See Numerical Value below. If the password has been set to a value other than “000,” entry of the prop­er password is required to access the remainder of the menu.
Setup Menu At the first level of the menu, the arrow keys navigate up or down
through the available Menu selections.
Function Menu The second level of the menu contains the functions or software pa-
rameters that need to be configured for the counter to operate prop­erly
Option Menu Contains either Choice Lists or Numerical Values for configuring the
RESET
or
ENTER
Selects the next digit to the left of the current flashing digit for editing.
The up and down keys increment or decrement the flashing digit. Some parameters support negative numbers. In these cases, the most significant digit can be made negative by incrementing it past "9."
Saves the values as the new setting for the function in memory and advances to the next function of the menu automatically.
counter