520 Simpson Avenue, Lac du Flambeau, WI 54538-0099
Printed in U.S.A. Part No. 06-116545 Edition 14, 06/07
SIMPSON ELECTRIC COMPANY
(715) 588-3311 FAX (715) 3326
Page 2
About this Manual
To the best of our knowledge and at the time written, the information contained in this document
is technically correct and the procedures accurate and adequate to operate this instrument in
compliance with its original advertised specifications.
Notes and Safety Information
This Instruction Manual contains warning headings that alert the user to check for hazardous
conditions. These appear throughout this manual where applicable, and are defined below. To
ensure the safety of operating performance of this instrument, these instructions must be
adhered to.
Warning, refer to accompanying documents.
!
Caution, risk of electric shock.
Technical Assistance
SIMPSON ELECTRIC COMPANY offers assistance Monday through Friday 8:00 am to 4:30 pm
Central Time by contacting Technical Support or Customer Service at (715) 588-3311.
Internet: http://www.simpsonelectric.com
Warranty and Returns
SIMPSON ELECTRIC COMPANY warrants each instrument and other articles manufactured by
it to be free from defects in material and workmanship under normal use and service, its
obligation under this warranty being limited to making good at its factory or other article of
equipment which shall within one (1) year after delivery of such instrument or other article of
equipment to the original purchaser be returned intact to it, or to one of its authorized service
centers, with transportation charges prepaid, and which its examination shall disclose to its
satisfaction to have been thus defective; this warranty being expressly in lieu of all other
warranties expressed or implied and of all other obligations or liabilities on its part, and SIMPSON
ELECTRIC COMPANY neither assumes nor authorizes any other persons to assume for it any
other liability in connection with the sales of its products.
uneM
yrogetaC
4PS040000*
retemaraP
emaN
/seciohC
tamroF
4PS
noitpircseDhceT
etoN
5.4
.hgiH2#tniopteS
seulaV:
.999999ot99999-
raeppalliwtnioplamiceD
tnerrucehtotgnidrocca
D.gnittes
P
SoPtSr000000*
noitisoPteseR
5.4
sihtottessieulavtnuoC
launaMrootuAnanehw
.sruccotneveteseR
seulaVot
99999-:
tnioplamiceD.999999
otgnidroccaraeppalliw
demmargorp-resueht
PD.noitisop
tESEr
PutES
tESErALbASid*
1PStA
edoMteseRotuA
otuananehwstceleS
2PStA
3PStA
4PStA
1PotFA
2PotFA
basiD
.tuosemittuptuoretfa
ehtoslaeeSSOPTSR
ehtniretemaraptnpteS
6.4
.ruccootsinoitcnufteser
rotnioptesatadel
puteS.yrogetac
This warranty shall not apply to any instrument or other article of equipment which shall have
been repaired or altered outside the SIMPSON ELECTRIC COMPANY factory or authorized
service centers, nor which has been subject to misuse, negligence or accident, incorrect wiring
by others, or installation or use not in accord with instructions furnished by the manufacturer.
Under the normal field usage there is no need to remove the front bezel of this product. The front
bezel of this product should only be removed by a qualified technician.
The S660 preset counter fits a 1/8 DIN standard cutout and is perfect for tight spaces, extending
only 3.24" (82mm) behind the panel. The unit is UL listed. The unit is for indoor use at altitudes
up to 2000m, temperatures between 0° and 40°C, and installation category III, pollution degree
2.
The counter is powered from 120 or 240 VAC. The nonvolatile EEPROM retains all programming
and count information when power is removed or interrupted.
Display scaling, preset values and all menu functions are easily programmed from the front
panel, following easy-to-use word prompts. Front Panel Reset Disable and Password Lockout
Protection features guard against unauthorized or accidental changes.
The counter accepts count rates up to 20 KHz and pulses from different types of sensors,
including Quadrature, CMOS or TTL circuits and PNP or NPN devices.
The optional, field-replaceable, single/dual relay module enhances the counter from a passive
display device to an integral control element for your application. Outputs may be controlled by
count values with independent reset operation. The counter has latching, boundary or timed
(0.01 to 599.99 seconds) alarm output modes. An optional 12 VDC (100mA) excitation output
module can provide power for external sensors.
Basic Unit
S660
Power Supply
120 VAC
240 VAC
1
2
Standard
Quadrature
Input
Output
None
One relay
Two Relays
0
1
2
1
2
Excitation
None
12VDC
0
1
Other
None
0
uneM
yrogetaC
Pd000000*
1TuPo
PutES
retemaraP
emaN
1EdoMmbasiD*
/seciohC
tamroF
PD
.000000
0.00000
00.0000
itacol
000.000
0000.00
00000.0
tniopteS.sretemarap
demmit
hctaL
dnuob
noitpircseDhceT
eulaVyalpsiD1
stceffA.no
foecnaraeppasoPtsR
detaicossaynadna
ed
oM1tuptuOteS
,demit,delbasid
etoN
3.4
tnioPlamiceD)tnuoC(
4.4
noitarepofoedomeht
ebnaC.1tuptuOrof
yradnuobrodehctal
.edom
dEMmit—<
dEHCtAL
oL=1PS—<
>—1PStA
—<
>—1PStA*
>—ih=2PS
sgnidniB1tuptuO
4.4
egassemrednimeR
dnahcihwsetacidni
erastnioptesehtwoh
.no
sirapmocrofdesu
siegassemhcihW
sideyalpsid
ehtybdenimreted
1tuptuOedoM
.detceles
uneM
yrogetaC
-temaraP
emaNre
1YALEd00.010*
seciohC
tamroF/
1yaleD
noitpircseDhceT
etoN
4.4
.emityaled1tuptuO
fiylnosraeppA1tuptuO
.demitottesedom
1LitnutESEr*
1PS
2PS
3PS
1litnU
litnudehctal1tuptuO
.retemarapfiylnosraeppA
1edomM=hctal.
4.4
4PS
SoPtSr
2tuPo
PutES
2EdoMmLbASid*
dEmMit
HCtAL
edoM2tuptuO
ebnaC.2tuptuOrof
dnuob
4.4
noitarepofoedomehtteS
rodehctal,demit,delbasid
.edomyradnuob
* = factory default settings
1
InputExcitationPower
2
4
Supply
Figure 1. Option Module Slots (Rear View)
3
5
Output
32
Page 5
Appendix B: Programming Quick Reference
1.2Part Number Identification
If you are unfamiliar with navigating menus in the S660, see section 3. Each parameter is listed
in the order of appearance in the menu system. Refer to the paragraph indicated in the Tech
Note column for technical details on a particular parameter.
uneM
yrogetaC
Tip: Photocopy these pages to mark settings on.
retemaraP
emaN
/seciohC
tamroF
SSAP000
noitpircseDhceT
dnayrtnEdrowssaP
etoN
1.4
noitacifireV
SSECCA—<
>—dEinEd
liaFdrowssaP
1.4
tcerrocnifisraeppA
wssap
SSAPHC000 *
deretnedro
egnahCdrowssaP
1.4
tcerrocfisraeppA
deretnedrowssap
drowssaP=000
delbasidnoitcetorp
S=990-100
llaseruce
sretemarap
elbanE=999-001
soPseR/sPSnissecca
edomyalpsid
uneM
yrogetaC
PutEStuPninAHCAPu *
retemaraP
emaN
/seciohC
tamroF
nwod
dAuq
.lennahcA
noitpircseDhceT
edoMAnahC
etoN
2.4
foedomtnuoctceleS
dAuqr
nAHCbrid *
Pu
edoMBnahC
edomtnuoctceleS
nwod
.lennahcB
2.4
rof
teslennahcAfI:etoN
siht,dauqRrodauQot
.elbisseccatonsimeti
tnuoC
LCSErP0.1
PutES
*
1.0
10.0
elacs-erP
gnilacs-erpteS
.reilpitlum
3.4
100.0
ELACS0000.10*
elacS
3.4
eulaVyalpsiDteS
.reilpitlumgnilacs
eulaVot9999.9-:
s
.9999.99
The following matrix indicates the configuration of your S660 counter.
1.3Option Module Summary
The S660 is a modular product that uses field configuring slide-in modules. The modules slide
easily into the rear of the counter.
Figure 1 displays the functional assignments for each module position.
Table 1 describes available option modules for the S660.
Table 1. Option Module Summary
eludoM
tols
1tupnIeludoMtupnIdradnatS
1tupnIeludoMtupnIerutardauQ
2txE46054eludoMnoitaticxECDV21
4rewoPelu
4rewoPeludoMrewoPCAV042
5tuptuO26054eludoMyaleRlauD
5tuptuO36054eludoMyaleRelgniS
epyTN/PnoitpircseDnoitceSeeS
doMrewoPCAV021
4.2
5.2
6.2
3.2
3.2
7.2
7.2
= factory default settings
31
4
Page 6
2 Hardware Setup
Quadrature input module
2.1Panel Installation
The S660 1/8 DIN counter requires a standard 1/8 DIN panel cutout of 1.77" (45mm) high by
3.62" (92mm) wide. To install the counter into a panel cutout, remove the clips from the side of
the counter. Slide the counter through your panel cutout, then slide the mounting clips back on.
Press evenly to ensure a proper fit.
Figure 2. Counter and Panel Cut-Out Dimensions
slennahCtupnI
noisrevnItupnI
noitarepO
sedom
secruoStupnI
tupnI
ecnadepmI
slennahcB&A
lennahCresU
retlifssapwoL
egatlovxaM
Single / Dual Relay Modules
gnitaRtcatnoC
efiLlacinahceM
resUdnaB,A
lennahcBdnaA.ytiraloptupnielbatceles-resU
.ylnoedomdradnatsnievitcelesytiralop
4XerutardauQdna1XerutardauQ,dradnatS
NPNroPNP,scigolLTTroSOMC,tcatnochctiwS
sredocne)dedne-elgnis(erutardauqsecived
%01±)CDV61-0.9(otpu-lluP.seR%5,K01:gnikniS
nommocotnwod-lluP.seR%5,K1.5:gnicruoS
sdlohserhTtupnI
%01±V6.3=TUV%01±V6.1=TLV:edomsaiBwoL
%01±V0.7=TUV%01±V0.5=TLV:edomsaiBhgiH
)xam(V51.3=TUV)nim(V9.0=TLV
taevawerauqstupniV01ot0(zH002<ycneuqerF
)elcycytud%05
deniatsusmumixamCDV03slennahcresUdnaB,A
CAV052spmA5
selcyc000,000,1
1.77"
45mm
3.62"
92mm
1.74"
44mm
RESET
%
.52"
13.2 mm
Figure 3. Panel Mounting Clips
5
3.93"
99.8 mm
3.24"
82mm
ENTER
2.04"
51.8mm
Isolated 12V Excitation Module
tuptuOnoitatixE
noitalosInoitatixE
%5±CDV21taAm001
V0051
30
Page 7
A.2Electrical, Environmental and Mechanical Specifications
Shut power off before removing or installing any option modules
1.Remove module from case by inserting a screwdriver into tab slot opening at top of
input module. Apply pressure to release module from case. Repeat procedure for tab
located on underside of module and then slide module away from the case.
2.Refer to appropriate sections to configure switches or jumpers for proper operation.
Table 1 can be used to identify modules and their associated detail paragraph.
3.Install module by carefully aligning module edges with slots in case and pressing
forward until tabs (on top and bottom) engage.
Figure 4. Removing Option Module
29
6
Page 8
2.3120/240 VAC Power Module
!
Figure 5. AC Power Module
NOTE: A fusible link is not provided on this module. A ½ Amp Time Delay fuse, Bussman
MDL ½, or similar is required.
Remove power before wiring option modules.
Denotes module
VAC
VAC
!
position 4 at rear
of counter
Power Supply
120 VAC or 240
VAC power
connection
The AC power module allows the S660 to be operated from standard
50/60 Hz line power. The power module will be configured as 120
VAC or 240 VAC per markings on the back panel. Ensure the input
rating of the supply matches your line voltage. The power supply
module has provisions for a hard-wire Count Reset. This control can
be a switch, relay contact or solid state device. Actuation is immediate upon an active Low for at least 2.5ms to this terminal. The reset
Remote Reset
RESET
Active low 0.2V
COMMON
POWER
!
performs primary
reset
Never connect AC mains (hot or neutral) to the
Reset or Common terminals!
circuit is independent of the power circuit.
2.4Standard Input Module
Denotes module
position 1 at rear
of counter
A INPUT
COMMON
USER
INPUT
B INPUT
Primary Input
Connect the input
signal to A input
and common
Inhibit
Active low
stops counting
Appendix A: Technical Specifications
A.1Functional Specifications
sedomtnuoC
detroppus
stupnItnuoC
suoenallecsiM
stupni
egnartnuoC
)lanretni(
htdiweslupniM
stigiDyalpsiD
lamiceDyalpsiD
tnioP
sDELyalpsiD
egnaRyalpsiD
slennahctuptuO
sedomtuptuO
semityaleD
tuptuO
esnopseR
emit
gniksat-itluM
noitarepO
auQ
.)tibihnI
etartnuocmumixaM
5.0deR
,tcartbuS-ddA,ddA-ddA,noitceriD/tnuoC
esreveRdnaerutardauQ,tcartbuS-tcartbuS
erutard
BlennahCdna)yramirP(AlennahC:2
)lortnocriD/yradnoceS(
seRtnuoC(teseR:2
tnuoC(resUdna)te
846,384,741,2+ot846,384,741,2-
utardauQdnadradnatS(zhK02
)sedom1Xer
)edom4XerutardauQ(zhK5
)edomdradnatS(Su5
gniknalborezgnidaelhtiwtnemges-7,tigid-6
elbammargorp-resU
ycneiciffehgih,)mm2.41("6
999,999+ot999,99-
)noitisoplamicedfotnednepednI(
hcaerofrotacidnilenaptnorfhtiw,2
yradnuoBdna,gnihctaL,demiT,delbasiD
sm51+/sm5.2-ces99.995ot10.0
sm5<:sedomdemitdnadehctaL
sm51<:edomyradnuoB
ptuodnatnuoC
nielihwdeniatniamlortnoctu
.edomgnimmargorp
Figure 6. Standard Input Module
COMMON
INPUT
Secondary Input
Direction Control or
count pulse input
7
28
Page 9
4.7Miscellaneous Controls
ntbtSr
)nottuBteseR(
yllaicepse,steserlatnediccatneverp
r(lanretxe
.gnittessihtybdetceffa
tSrnoP
)TESERNOrewoP(
eRehtesusyawlalliwretnuoc
w
.tsoleblliwtnuocgnitsixe
1)To access the Miscellaneous Controls, enter the Programming Mode, and press
until the reset setup menu category is reached.
2)Press and then to continue to the Parameter Name rstbtn. The display will
ENTER
flash between rstbtn and the default value of enable. When the display shows
enable, press .
3)Use the arrow keys to select either Enable or Disable. Press when the correct
mode is selected to accept selection and proceed to the next parameter name,
ENTER
ENTER
Power On Reset.
4)The display will flash between Ponrst and the default no. When the display shows no,
ENTER
press .
5)Use the arrow keys to select either no or yes. Press when the correct mode is
ENTER
selected.
6)The display will now show end. If you are finished programming the S660, press
. If not, use the arrow keys to back up to the necessary parameter.
B Bias Off=Hi On=Lo
B Freq Off=Hi On=Lo
B Off= Sink On= Source
A Bias Off=Hi On=Lo
A Freq Off=Hi On=Lo
A Off= Sink On= Source
= ON
= OFF
1 2 3 4 5 6
CHANNEL
Dipswitch Legend
Note: Refer to specifications
for DIP switch function
electrical characteristics
Figure 7. Standard Input Module Default Settings
DIP switch SW1, figure 7, is used to set up the counter to conform to the electrical characteristics
of the sensor or signal being detected. Switch positions 1-3 configure channel B, while switches
4-6 configure channel A. These switches select bias (threshold voltages), low pass filter (enable/
disable) and sensor type (Sink or Source).
Refer to the documentation that accompanied the sensor for related information. The sensor
can most likely be matched to one of the typical switch settings shown in figure 8 and figure 8a.
Note: The input boards are designed so that selecting sourcing or sinking is based on the
type of sensor that is being used. If a PNP (sinking) sensor is being used, set the input
board for sinking also (switches 3 and 6 = OFF).
27
If channel B is not used, default settings for switch positions 1 through 3 should be selected.
Default settings are provided in Table 2.
The Input module also provides for a user input signal. On the S660, this input serves as a count
enable/disable control. Connecting User to Common will disable counting.
The S660 can accept inputs from many different sensors. The A and B channels may be
configured independently as shown in Table 2. Figures 8 and 8a have examples of some typical
sensors and the wiring connections that would be used.
Table 2. Standard Input Module DIP Switch Settings
* = Factory Default setting
1 B Channel Bias:OFF = Hi*VLT = 5.0 V VUT = 7.0V (+/- 10%)
ON = LowVLT = 1.6 V VUT = 3.6V (+/- 10%)
2 B Channel Frequency: OFF = Hi*(low pass filter disabled)
ON = Lo(low pass filter enabled)
3 B Channel Sensor:OFF = Sinking*(internal pull-up enabled)
ON = Source (internal pull-down enabled)
4 A Channel Bias:OFF = HiVLT = 5.0 V VUT = 7.0V (+/- 10%)
ON = Low*VLT = 1.6 V VUT = 3.6V (+/-10%)
8
Page 10
+
5 A Channel Frequency: OFF = Hi*(low pass filter disabled)
ON = Lo(low pass filter enabled)
6 A Channel Sensor Type:OFF = Sinking* (internal pull-up enabled)
ON = Source (internal pull-down enabled)
ON
HIGH BIAS
HIGH FREQUENCY
SINKING
OUTPUT
COMMON
ON
1 2 3 4 5 6
LOW BIAS
LOW FREQUENCY
SOURCING
A INPUT
COMMON
USER
INPUT
B INPUT
ISO+12V
ISOCOM
COMMON
EXCITATION
INPUT
NPN SENSOR
HIGH FREQUENCY
+
__
---
_
HIGH BIAS
SINKING
1 2 3 4 5 6
LOW BIAS
LOW FREQUENCY
SOURCING
A INPUT
COMMON
USER
INPUT
B INPUT
COMMON
INPUT
PNP SENSOR
ISO+12V
ISOCOM
EXCITATION
4.6Auto Reset Operations (Reset Setup)
The S660 has the capability to perform a Count Reset event based upon various conditions.
When Auto Reset occurs, the outputs will return to the deactivated status and the displayed
count will return to the value stored in the Reset Position (rstpos) function. This feature is used
in cut-to-length or other applications where an automatic repetitive cycle is established.
There are seven options for the Auto Reset Mode: Disabled, at one of four set points, or after an
output times out.
edoMnoitpircseD
LbASid
#PStA
1PotFA
+
__
---
_
2PotFA
.tnuocteser
sehtnehW
.sruccotneveteser
.)edomdemitniebtsum1tuptuO(
.)edomdemitniebtsum2tuptuO(
1)To access the Auto Reset Mode, enter the Programming Mode, and press until the
reset setup menu category is reached.
2)Press to continue to the Parameter Name areset. The display will flash between
ENTER
areset and the default value of disabl. When the display shows disabl, press
3)Use the arrow keys to scroll through the available options. Press when the
ENTER
correct mode is selected to accept mode and proceed to the next parameter name,
Reset Button.
lliwtneveteserlanretxerolenaptnorfaylnO
,deretnuocnesitnioptesdetcele
tuo-semit1tuptuOretfasruccoteseRotuA
uo-semit2tuptuOretfasruccoteseRotuA
t
ENTER
Figure 8. Sensor Connection Examples
HIGH BIAS
HIGH FREQUENCY
SINKING
ON
1 2 3 4 5 6
LOW BIAS
LOW FREQUENCY
SOURCING
A INPUT
COMMON
USER INPUT
B INPUT
COMMON
INPUT
DRY CONTACT
Figure 8a. Sensor Input example
9
26
Page 11
4.5Set Point Parameters (Set Point Setup)
The S660 has four set point parameters and a special value referred to as Reset Position.
The Reset Position can be referred to as Count Reset Value.
SP1 and SP2 are used only with Output 1, and SP3 and SP4 are used only with Output 2.
The SP1 and SP3 parameters are used as Latched or Timed “trigger” values. When a Boundary
Output is selected, SP1 and SP3 become the low boundary values.
The SP2 and SP4 parameters are used as high boundary value or ‘turn-off’ values when used
with other alarm types (i.e. latched until SP4).
The values for all set points are -99999 to 999999. The decimal point will appear according to
the current decimal point setting.
Set Point Parameters
1)To set the Set Point parameters, enter the Programming Mode, and press
until the setpnt setup menu category is reached.
2)Press to continue to the Parameter Name sp 1. The display will flash between sp
3)Use the arrow keys to enter the correct value of the flashing digit. Use the key
ENTER
1 and the default value of 000010. When the display shows 000010, press .
to advance to the next digit. Press when the correct set point is selected
ENTER
ENTER
RESET
to accept value and proceed to the next parameter, SP 2.
4)Repeat these steps for SP 2, SP 3, and SP 4. The counter will proceed to the next
parameter, Reset Position.
Reset Position
1)To access the Reset Position parameter, enter the Programming Mode, and press
until the setpnt setup menu category is reached.
2)Press and then to continue to the Parameter rstpos. The display will flash
ENTER
between rstpos and the default value of 000000. When the display shows 000000,
ENTER
press .
3)Use the arrow keys to enter the correct value of the flashing digit. Use the key
to advance to the next digit. Press when the correct position is selected to
ENTER
RESET
accept value and proceed to the next menu category, Reset Setup.
2.5Quadrature Input Module
The Quadrature / Universal Input Module has two operational modes: Quadrature mode and
Standard mode. Quadrature Mode is selected by positioning JP1 and JP2 on pins 1 and 2.
Standard Mode is selected by placing JP1 and JP2 on pins 2 and 3 (see Figure 10 for details).
The Quadrature mode supports a wide range of encoders including the Simpson SE series.
While in Standard Mode, this module works similarly to the Standard Input module. In addition
to the quadrature signal, the quadrature card allows a technician to select a rising or falling edge
trigger for the count input signal. The technician is also able to determine the polarity of the user
input.
The Input module also provides for a User input signal. On the S660, this input serves as a
Count Enable/Disable.
NOTE: If B channel is not going to be used, use the default switch settings for SW1
positions 1 through 3. Default settings are provided in Table 3.
In both modes, the state of the user input signal can be selected as active high or active low.
DIP switch SW1 configures the counter to match the specifications of the accompanying sensor.
When shipped from the factory, the counter is set for X1 quadrature, as shown in Figure 10 and
Table 3:
2 B Channel Frequency: OFF = Hi*(low pass filter disabled)
ON = Low(low pass filter enabled)
3 B Channel Sensor:OFF = Sinking*(internal pull-up enabled)
ON = Source (internal pull-down enabled)
4 A Channel Bias:OFF = Hi*VLT = 5.0 V VUT = 7.0V (+/- 10%)
ON = LowVLT = 1.6 V VUT = 3.6V (+/- 10%)
5 A Channel Frequency: OFF = Hi*(low pass filter disabled)
ON = Lo(low pass filter enabled)
6 A Channel Sensor Type:OFF=Sinking* (internal pull-up enabled)
ON = Source (internal pull-down enabled)
7 B Channel Count Edge:OFF=Rising(standard count mode only)
ON = Falling*
8 A Channel Count Edge:OFF=Rising(standard count mode only)
ON = Falling*
Table 8. Latch Until
litnUhctaLnoitpircseD
teseR
#PS
soPtsR
itcaedtuptuO
.deretnuocne
.deretnuocne
.tuptuoehtetavitcaedot
sitnioptesnehwdetav
deriuqersitneveteserlanretxerolenaptnorfA
sinoitisoptesernehwdetavitcaedtuptuO
NOTE:The outputs for this counter activate regardless of count direction in all count
modes.
1)To set the Output Control modes, enter the Programming Mode, and press until
the oput 1 setup menu category is reached.
2)Press to continue to the Parameter mmode1. The display will flash between
3)Use the arrow keys to select the correct mode. Presswhen the correct
ENTER
mmode1 and the default value of latch. When the display shows latch, press .
ENTER
ENTER
mode is selected to accept value, and proceed to the next parameter, Output 1
Bindings. Other choices may appear, depending on which Output 1 Mode is selected. See Appendix B for which options correspond to which parameters and make
selections accordingly.
4)Press until oput 2 setup is displayed to make similar selections for Output 2 Mode.
ENTER
Again, use Appendix B to make proper selections for subsequent parameters.
5)When all selections are entered and accepted into counter memory, counter will
proceed to next menu category, Set Point Setup.
9 User Input Polarity:OFF = High/open circuit = Inhibit Count
ON* = Low/closed circuit =Inhibit Count
10 Quadrature Mode:OFF = X4(quadrature mode only)
ON = X1*
2.6Excitation Module
Figure 11. Wiring Encoder w/ Excitation Supply
MODEL S.E.
QUADRATURE
ENCODER
12 VDC Excitation Module
CHANNEL A-WHITE
CHANNEL B-GREEN
+
POSITIVE (RED)
+
COMMON
(BLACK)
11
DENOTES MODULE POSTION 1
AT REAR OF COUNTER
QUADRATURE
INPUT CARD
A INPUT
COMMON
USER
INPUT
B INPUT
COMMON
INPUT
24
Page 13
EXCITATION
ISO+12V
ISOCOM
+
_
__
---
12 VDC, 100 mA max
Denotes module
position 2 at rear of
counter
4.4Output Control Modes (Output Setup)
The S660 supports two independent output channels with four modes of operation: disabled,
timed, latched and boundary.
epyTtuptuOnoitpircseD
tuptuOdelbasiD
tehT
.evitcanisilennahctuptuoehT
eht,evitcaecnO.dehcaersinoitidnoc’reggirt‘ro
99.995dna10.0neewtebebyam
.sdnoces
yaledehT.doirepyaleddeificepsarofdlehsituptuo
The Excitation Module can supply 12 VDC at up to 100 mA for external sensors or encoders.
This excitation is isolated from the counter internal logic supply. When using sensors or encoders that do not have a signal return or imply a signal return that is in common with the supply
voltage, a common attachment that ties the excitation supply to the logic input common may be
required. Examples of this appear in figures 8, 8a, 11 and 12.
The Single and Dual Relay modules can activate circuit loads of up to 5 amps at 250 VAC. A
Form C configuration allows use of normally-open (NO) and normally-closed (NC) circuit action.
action.
Only the output 1 channel is implemented in the single relay module.
3 Display & Keypad Controls
counter and allowing more accurate cutting.
1)To access the prescale parameters, enter the Programming Mode, and press
until the count setup menu category is reached.
2)Press to continue to the Parameter Name prescl. The display will flash
between prescl and the default value of 1.0. When the display shows 1.0, press
ENTER
ENTER
.
3)Use the arrow keys to scroll through the choices. Presswhen correct
ENTER
prescale is selected to accept the value and proceed to the next parameter, Scale.
User-defined Scale
The S660 also allows for a user-defined scaling multiplier.
1)To access the user-defined scaling parameter, enter the Programming Mode, and
press until the count setup menu category is reached. Press .
ENTER
2)Press to continue to the Parameter Name scale. The display will flash between
scale and the default value of 01.0000. When the display shows 01.0000, press
ENTER
.
3)Use the arrow keys to enter the correct value of the flashing digit. Use the
key to advance to the next digit. Press when the correct scale is
ENTER
RESET
selected to accept value and proceed to the next parameter, Decimal Point.
To calculate the scaling parameter, use the following scale formula:
Display = Multiplier (Pulse x Prescale x Scale x Decimal Point)
If the scale value isn’t known, use the following formula:
For the example we used, the scale value is:
SCALE =
SCALE == 0.1667
DISPLAY x DP
MULT. (PULSE x PRESCALE)
1.00
1 (600 x 0.01)
Decimal Point Position
1)To set the Decimal Point position, enter the Programming Mode, and press
until the count setup menu is reached. Press .
ENTER
2)Press to continue to the Parameter Name dp. The display will flash between dp and
the default 000000. When the display shows 000000, press .
3)Use the arrow keys to scroll through the choices. Presswhen the correct deci-
ENTER
ENTER
mal place is selected to accept value and proceed to the next menu category, Output
1 Setup.
3.1Display
Figure 16. Display and Keypad Layout
•6-Digit 0.56" high red LED Display.
•2 Output Status Indicators; “1” and “2.”
•Units Window for supplied label or legend.
•4-Button Keypad with tactile response.
13
22
Page 15
The B channel may be set as Up, Down or Direction. In the direction mode, the B channel is no
longer a count source, but controls the count direction of the A channel input. This state control
works as an ‘exclusive-or’ with the channel A direction. Thus, if B input is in the ‘Down’ state and
A channel is set to Down, pulses at the A input will increment count.
3.2Display Error Messages
Table 4. Display Error Messages
Table 7. Count Behavior with B Channel Set as Direction Control
gnitteSlennahCAtupnIBtaetatStnuoCgnitluseR
PUPUPU
PUNWODNWOD
NWODPUNWOD
NWODNWODPU
When A channel has been set to either Quadrature or Reverse Quadrature settings, the B
channel internally behaves as a direction control.
2)To set the B channel:
a)In the Input Setup area, after entering the A Chan value, the display will flash
between b chan and the counter’s default (dir).
b)When the display shows dir, press.
c)Use the arrow keys to change the value, then press to accept the selection
ENTER
ENTER
and proceed to the next menu category, Count Setup.
NOTE:The B channel will not show in the menu when Quadrature or Reverse Quadrature has been selected for the A Channel input.
4.3Scaling and Decimal Point Position
(Count Setup)
Prescale
The S660 counter allows for prescaling of display values. Prescaling allows the counter to
display a more accurate number than its 6-digit capacity might otherwise allow by making the
positive count the most significant digit.
Generally speaking, the smaller the scale value, the more accurate the count will be. The S660
has four prescale values, 1.0 (default), 0.1, 0.01, and 0.001.
An example of this application is as follows:
A 600 pulse-per-revolution encoder is used to measure cable before it is cut to the proper length.
There is a wheel (one foot in circumference) attached to the encoder, in direct contact with the
cable. The user wants to see the counter display feet to 1/100' accuracy (to two decimal points).
With the default prescale of 1.0, one rotation of the wheel would be displayed on the counter as
00.0016'. (1/600, where 1 is the number of feet as shown by wheel rotation and 600 is the
number of pulses per revolution.) However, by using a prescale of 0.01, the resolution has been
multiplied by 100, allowing the counter to display 0.16667, increasing the accuracy of the
21
14
Page 16
3.3What the Keys Do in Display Mode
4.2A/B Channel Options (Input Setup)
yeKroivahebdapyeK
ENTER
ro
RESET
sserP
SoPtSrebnacerutaefsihT.)noitisoPteseR(
dnadloH
ottnuocsteseRSoPtSrsihT.)noitisoPteseR(
3.4What the Keys Do in the Programming Mode
yeKroivahebdapyeK
RESET
ro
ENTER
hT
.dehcaer
.tide/weiv
.edomgnimmargorp
errucehtretnE)1
.noitcnuftxenehtotevom
The next category in the Programming Mode is the “Input Setup.” Here you can adjust the A and
B channels to the appropriate count modes.
.)7.4noitcesees(delbasidebyamnoitca
tesehtllaotsseccakciuqswollA
dnastniop
The A channel input may be selected as an Up, Down, Quadrature or Reverse Quadrature*
input.
As an Up channel, pulses applied to the A input are added to the display. In Down mode,
.)1.4noitcesees(drowssapagnisuybdelbasid
subtraction occurs. Note that when using Quadrature inputs, appropriate hardware (jumper)
settings may be needed.
.uneMgnimmargorPehtsseccA
* The Reverse Quadrature input allows the user to reverse the count direction of the encoder in
software instead of having to rewire/remount the encoder.
Table 6. Channel A Selection
NAHCAnoitceriDNAHCB
PUpUdenifedresU
NWODnwoDdenifedresU
DAUQpUelbaliavAtoN
DAUQRnwoDelbaliavAtoN
1)To set the A Channel value:
a)When the display flashes input setup, press. The display will change to a chan.
ehttixeotsdnocesruofrofdlohdnasserP
ehthguorhtetagivansyeknwoddnapue
sparw‘unemehT.snoitcnufunemelbaliava
siunemehtfopotromottobehtnehw’dnuora
otretemaraprounemtn
dnayromemretnuocehtotegnahcehtetirW)2
b)Press again to proceed to the choice list. Scroll through up, down, quad, and
c)When the selection is complete, pressto accept the selection to counter memory
ENTER
r quad using the arrow keys.
and proceed to the next parameter, Chan B Mode.
ENTER
ENTER
15
20
Page 17
Table 5. Password Values
eulaVdrowssaPytiruceSfoleveL
000
990-100
999-001
dna
seccA
otsseccAkciuQ
erucesylluF
gnittestluafeD-ytiruceSoN
ylnOsseccAkciuQ
dnauneMgnimmargorPehtotsseccallufswollA
.delbanesistnioptes
drowssapybderucessiuneMgnimmargorPehT
.delbasidsistnioptesotsseccAkciuQ
kciuQ,drowssapybderucessiuneMgnimmargorP
2)If a password is already in the counter, the display will flash between pass, for “Enter
Password,” and the default value, 000.
a)When the display shows 000, press. Use the arrow keys to change the
ENTER
flashing digit to the desired number.
RESET
Press to advance to the next digit.
b)Pressto enter the password as shown. If an incorrect password is en-
ENTER
tered, access denied will flash on the display. Press an arrow key to return to the
pass display.
c)After entering the correct password, the counter will return to chpass. Press to
change the password, or press thekey to continue to the Input Setup menu
ENTER
category.
Setup MenuFunction MenuOption Menu
000000
000
000000
upup
up
upup
downdown
down
downdown
quadquad
quad
quadquad
r quadr quad
r quad
r quadr quad
dirdir
dir
dirdir
upup
up
upup
downdown
down
downdown
ENTER
ENTER
ENTER
inPutinPut
inPut
inPutinPut
SEtuPSEtuP
SEtuP
SEtuPSEtuP
endend
end
endend
ENTER
ENTER
ENTER
A CHAnA CHAn
A CHAn
A CHAnA CHAn
uPuP
uP
uPuP
b CHAnb CHAn
b CHAn
b CHAnb CHAn
dirdir
dir
dirdir
Return to
Display Mode
ENTER
ENTER
CHPASSCHPASS
CHPASS
CHPASSCHPASS
000000
000
000000
.delbanesyeknwoddnapuaivstnioptesots
CountSEtuPCountSEtuP
CountSEtuP
CountSEtuPCountSEtuP
other setup menus
Figure 17. Programming Menu Structure
In the Programming Mode, the S660 will return to Display Mode automatically if a key is not
pressed within 120 seconds (2 minutes). The menu is comprised of three levels: Setup Menu,
Function Menu and Option Edit Menu. Figure 17 illustrates the three levels of the menu
system.
Password Entry Entry (Pass) and changing of the password (Chpass) are similar to editing a
numerical parameter. See Numerical Value below. If the password has
been set to a value other than “000,” entry of the proper password is
required to access the remainder of the menu.
Setup MenuAt the first level of the menu, the arrow keys navigate up or down through
the available Menu selections.
Function Menu The second level of the menu contains the functions or software param-
eters that need to be configured for the counter to operate properly.
Option MenuContains either Choice Lists or Numerical Values for configuring the func-
tions of the counter.
19
Choice ListA choice list allows selection from a fixed number of options. A Choice List
is found in the Options section of the menu. The list is made up of the
available options for the function that is being edited. Example: Menu is
Input Setup Menu, the Function is A Channel, the Choice List is up, down,
quad, and rquad. (See Table 6)
Numerical Value A numerical entry allows the changing of set point values, scale values,
16
Page 18
yeKroivahebdapyeK
ro
ENTER
ctnerrucehtsevaS
ehthguorhtllorcssyeknwoddnapuehT
.tsileciohCehtniseciohcelbaliava
retemarapwensaecioh
.yrogetacroretemaraptxenotspetsdnagnittes
etc.
yeKroivahebdapyeK
RESET
ro
ENTER
.gnitideroftigidgnihsalf
isyeknwoddnapuehT
edamebnactigidtnacifingis
".0"dna"9"neewtebtignitnemercni
ecnavdadnayromemninoitcnuf
.yllacitamotuaunemehtfonoitcnuf
ybevitagen
ehtrofgnitteswenehtsaseulavehtsevaS
3.5 Special Start up Modes
There are two start-up modes for the S660 counter. The default start-up mode will be used every
time the counter is powered up by the user. There is one alternate start-up mode that will allow
the operator to return the counter software functions to factory default settings.
The alternate start-up modes can only be accessed by pressing and holding certain keys during
the power up sequence.
•Press and hold both keys on the face of the counter
•Apply power while holding keys
4 Programming Operations and Parameters
This section details the initial programming options of the S660, presuming all defaults are in
place.
If you are already familiar with the S660 programming, see Appendix B for the Programming
Quick Reference Guide.