• Four model types designed to t a wide range
of applications
• Easy installation - software detection/correction
of wiring errors
• Wide backlit LCD display for easy viewing
• Easy to use - four keys select all parameters
• Use for single or three-phase applications
• Not for use with grounded delta applications
• Modbus communication option available
GIMA Three Phase
Digital Panel Meters
Models & Parameters G100 G200 G300 G400
Phase Amps X X X X
Phase Volts X X X X
Line Volts X X X X
Per Phase PK X X X X
Per Phase kW X X X X
Per Phase kvar X X
Per Phase kVA X
3 Phase PF X X X X
3 Phase kW X X X X
3 Phase kvar X X
3 Phase kVA X
Frequency X X X X
KWh X X X
Capacitive kvarh X X
Inductive kvarh X X
Total kvarh X X
Import kvarh X
Current Demand X X X X
Voltage Demand X X X X
kW Demand X X
Peak Amps X
Peak Phase Volts X
Peak Current Demand X X X X
Peak Voltage Demand X X X X
Neutral Current X
The Specications & Dimensions are on the last pages

Accessories - Three-Phase Current Transformer
A three-phase terminal style current transformer must be
used with GIMA® three phase meters.
The current transformer is equipped with terminals to
permit easy connection to the GIMA units.
These terminals are #8-32 brass studs and come with a
atwasher, lockwasher and a regular nut (leads are not
provided).
Ordering Information
Catalog
Number
37026 50:5 ± 3% 2.0
37027 100:5 ± 1% 2.0
37028 150:5 ± 1% 4.0
37029 200:5 ± 1% 5.0
37030 300:5 ± 1% 10.0
Current
Ratio
Accuracy
@ 60 Hz
Burden VA
@ 60 Hz
GIMA Three Phase
Digital Panel Meters
Ordering Information -
GIMA can be congured by making an entry in each section below. Example: G100-1-3-1-0.
_____ _____ _____ _____
G
I I I I I
Basic Unit Power
Supply
Select From Each One Below Select From Each One Below
Basic Unit Voltage Input
100 GIMA 100 Meter 1 120/208V
200 GIMA 200 Meter 2 120/240V - Split Phase
300 GIMA 300 Meter 3 277/480V
400 GIMA 400 Meter 4 63/110V
Power Supply Current Input
1 115 VAC @ 45-65Hz 1 5 Amps @ 45-65 Hz
2 230 VAC @ 45-65 Hz
For other Voltage and Current Inputs
contact Simpson Electric Company
Voltage
Input
0 None
1 Modbus Communication *
* RS485/422 communications
Current
Input
Other
Other

GIMA Three Phase
Digital Panel Meters
Mounting Requirements
Panels should be .04 to .16 inches (1mm to 4mm) thick with a square cut-out of 3.62” x 3.62” (92mm x 92mm.)
A minimum depth of 2.83” (72mm) should be allowed behind the panel for the meter.
Remove the panel mounting clips and insert the meter into the cutout from the front of the panel.
Push the meter home.
Ensure the screws in each panel mount clip are fully retracted and insert the clips as shown in the diagram below.
Tighten the screws to secure the meter rmly in the panel. Do not overtighten.

Digital Panel Meters
Specications
INPUT
System 3-phase, 3 or 4 wire unbalanced load
Voltages 120/208, 120/240, 277/480, 63/110
Measurement Range 20% to 120%
Current 5 amp from external CTs Fully Isolated
Measurement Range 5% to 120%
Operating Frequency 45 to 65 Hz
Harmonics Up to the 30th harmonic
Input Loading
Voltage Less than 0.1VA per phase
Current Less than 0.1VA per phase
Overload
Voltage x2 for 2 seconds max.
Current x40 for .5 second max.
Auxiliary Supply
Standard 115V±15% 45-65Hz
Optional 230V±15% 45-65Hz
Display Custom backlit supertwist LCD 3 lines of .47”
General (12mm) digits plus .15” (3.8mm) legends
Update Rate Once/Second
GIMA Three Phase
ENVIRONMENTAL
Temperature 14°F to 149°F (-10°C to 65°C) operating
Humidity <75% RH non-condensing
Programming
CT Primary 5amp to 6500 amp
VT Primary 60v to 50,000v
Pulse Outputs 2
Function
Output No. 1 Wh (G200, G300 & G400 only)
Output No. 2 Total varh (G300 & G400 only)
Pulse Length 100ms to 20 seconds
Isolation 2.2KV (50V Output No. 1 to Output No. 2)
Scaling Settable 1, 10 or 100 pulse output rate

Accuracy
Parameter Spec Range Spec
Phase Current 5% to 120% lb ±0.2% lb (1% *Rdg) ±1 Digit
Neutral Current 5% to 120% lb ±0.6% lb (2% *Rdg) ±1 Digit
Phase Voltage 20% to 120% Vb ±0.2% Vb (1% *Rdg) ±1 Digit
Voltage LL 20% to 120% Vb ±0.3% Vb (1% *Rdg) ±1 Digit
Phase Watts 5% to 120% FS ±0.4% FS (1% *Rdg) ±1 Digit
Phase VA 5% to 120% FS ±0.6% FS (1.5% *Rdg) ±1 Digit
Phase var 5% to 120% FS ±0.8% FS (2% *Rdg) ±1 Digit
Phase PF ±0.2 Degrees
System Watts 5% to 120% FS ±0.6% FS (1% *Rdg) ±1 Digit
System VA 5% to 120% FS ±1% FS (1.5% *Rdg) ±1 Digit
System var 5% to 120% FS ±1.5% FS (2% *Rdg) ±1 Digit
System PF ±0.2 Degrees
Frequency 45Hz to 65Hz ±.05 Hz
GIMA Three Phase
Digital Panel Meters
Note: *Rdg = Reading
MECHANICAL
Bezel 3.79” x 3.79” (w/ .29” lip)
Depth 3.35”
Panel Cutout 3.62” x 3.62”
Weight 14 oz.