Simpson Electric G100, G200, G300, G400 Operation Manual

GIMA
Multi-Function
Electricity Meter
OPERATOR’S MANUAL
Technical Assistance
Simpson Electric Company offers assistance Monday through Friday, 8:00am to 4:30pm Central Time. To receive assistance contact Technical Support at (715) 588-3311 or contact us through our web site at www. simpsonelectric.com.
Warranty and Returns
Simpson Electric Company warrants each instrument and other articles manufactured by it to be free from defects in material and workmanship under normal use and service, it’s obligation under this warranty being limited to making good at its factory said instrument or other article of equipment which shall within one (1) year after delivery of such instrument or other article of equipment to the original purchaser be returned intact to it, or to one of its authorized service centers, with transportation charges prepaid, and which its examination shall disclose to its satisfaction to have been thus defective; this warranty being expressly in lieu of all other warranties expressed or implied and of all other obligations or liability on its part, and Simpson Electric Company neither assumes nor authorizes any other persons to assume for it any other liability in connection with the sales of its products.
This warranty shall not apply to any instrument or other article of equipment which shall have been repaired or altered outside the Simpson Electric Company factory or authorized service centers, nor which has been subject to misuse, negligence or accident, incorrect wiring by others, or installation or use no in accord with instructions furnished by the manufacturer.
This instrument is designed to prevent accidental shock to the operator when properly used. However, no engineering design can render safe an instrument which is used carelessly. Therefore, this manual must be read carefully and completely before making any measurements. Failure to follow directions can result in a serious or fatal accident.
2
Table Of Contents
1. SAFETY ........................................................................................ 4
1.1 W
1.2 M
2. METER OPERATION...................................................................... 5
2.1 M
2.2 P
2.3 D
3. DISPLAY PAGES ............................................................................ 8
3.1 P
3.2 C
3.3 V
3.4 P
3.5 R
3.6 S
3.7 M
3.8 D
3.9 I
ARNING SYMBOLS ............................................................................. 4
AINTENANCE ..................................................................................... 4
EASUREMENTS .................................................................................. 5
2.1.1 Balance Current Measurements ........................................... 5
2.1.2 Time Averaged Amps/Volts (T-Avg) ..................................... 6
2.1.3 Maximum Demand Power (MD)............................................ 6
OWER UP ........................................................................................ 7
ISPLAY PAGES ................................................................................... 7
OWER UP ........................................................................................ 8
URRENT MENU ...............................................................................8-9
OLTAGE MENU .............................................................................10-11
OWER MENU (METER TYPES 1-4) ..................................................11-14
ESET OF ENERGY REGISTERS ............................................................ 16
CROLLING MENU (METER TYPES 1-4) ................................................. 16
ETER TYPE DISPLAY MENUS .........................................................17-18
ISPLAY SCALING .............................................................................. 19
3.8.1 Voltage Scaling ................................................................... 19
3.8.2 Current Scaling ................................................................... 19
3.8.3 Power Scaling (W, VA, var)................................................. 19
3.8.4 Energy Registers (Wh, VAh, varh) ...................................... 19
3.8.5 Miscellaneous ..................................................................... 19
SOLATED PULSE OUTPUTS .................................................................. 20
4. INSTALLATION ............................................................................ 21
4.1 P
4.2 CT C
4.3 V
4.4 A
4.5 C
ANEL MOUNTING .............................................................................. 21
ONNECTIONS ............................................................................. 22
OLTAGE CONNECTIONS ...................................................................... 22
UXILIARY MAINS SUPPLY (L & N) ....................................................... 22
ONNECTION SCHEMATICS.............................................................. 23-25
5. METER SETUP ........................................................................ 26-28
5.1 P
ROGRAMMING MENU ......................................................................... 28
6. OPTIONS ...................................................................................... 28
6.1 I
NTERNAL MODBUS COMMUNICATIONS ................................................... 28
7. SPECIFICATION ......................................................................29-30
3
1. Safety
1.1 Warning Symbols
This manual provides details of safe installation and operation of the meter. Safety may be impaired if the instructions are not followed. Labels on individual meters give details of equipment ratings for safe operation. Take time to examine all labels on the meter and to read this manual before commencing installation.
CAUTION WARNING
Refer to Operating Manual Danger Risk of Electric Shock
Figure 1-1 Safety Symbols
WARNING
The meter contains no user serviceable parts. Installation and
commissioning should be carried out by qualifi ed personnel
1.2 Maintenance
The equipment should be maintained in good working order. Damage to the product should be repaired by the manufacturer. The meter may be cleaned by wiping lightly with a soft cloth. No solvents or cleaning agents should be used. All inputs and supplies must be isolated before cleaning any part of the equipment.
4
2. Meter Operation
2.1 Measurements
The GIMA makes use of a high speed micro-processor and an Analogue to Digital converter to monitor input signals from three independent phases. Each phase voltage, current and power (kW) are measured directly and a number of other parameters derived from these in software. The measurement process is continuous with all six signals scanned simultaneously at high speed. Unlike many other sampling systems, which sample one phase after another, this ensures that all input cycles are detected. Distorted input waveforms, with harmonics to the 30th are therefore detected accurately.
Derived parameters are calculated and displayed once a second, scaled by user programmed constants for current and voltage transformers.
Instantaneous power parameters are integrated over long time periods providing a number of energy registers. System frequency is detected by digital processing of the phase 1 voltage signal.
2.1.1 Balance Current Measurements
The rms. value of the instantaneous sum of the three phase currents is available on some GIMA meter types. The total current
in a three phase system may be represented as :
I
I
LEAK
I
n
Note: In 3 phase 3 wire systems the GIMA must be wired using 3 current transformers as shown in fi g. 4-3 for balance current measurement to be made.
represents any current leaving the system (e.g. Leakage to earth)
represents current in the neutral (4 wire systems only)
= I1 + I2 + I3= I
bal
LEAK
+ I
n
5
2.1.2 Time Averaged Amps/Volts (T-Avg)
Average values of volts and Amps are calculated over a user programmable time period (10 - 2500 seconds). The displays show the averages for the most recent time period ending at the time the display was last updated. The average period is continuously updated as time progresses.
The largest value of each T-Avg parameter is recorded, saved to non-volatile memory and displayed as Pk hold T-Avg. These peak values may be reset by the user.
Each Average-Period is split into 10 sub-periods. The average values of volts and amps are measured during each sub-period and stored in an array. The latest sub-period values replace the oldest in the array as time progresses. The T-Avg values are calculated as the mean of each corresponding array. The display is updated with the latest T-Avg parameters at the end of each sub-period (ever y Average-Period/10 seconds).
2.1.3 Maximum Demand Power (MD)
Average values of kW, kVA and kvar (if fi tted) are calculated over a user programmable time period (1 - 60 minutes). The displays show the averages for the most recent time period ending at the time the display was last updated. The demand period is continuously updated as time progresses. These parameters are referred to as Maximum Demand Powers.
The largest value of each MD parameter is recorded, saved to non­volatile memory and displayed as Pk hold MD. These peak values may be reset by the user.
Each MD-Period is split into 30 sub-periods. The average power values are measured during each sub-period and stored in an array. The latest sub-period values replace the oldest in the array as time progresses. The MD powers are calculated as the mean of each corresponding array. The display is updated with the latest MD values at the end of each sub-period (every MD-Period/30 seconds).
6
2.2 Power Up
On power up the GIMA shows the meter type and software issue. The example below shows a GIMA 300 with software issue 1.10.
CUBE
T - 4
SOFT 1.10
2.3 Display Pages
To select current measurements press the AMP key repeatedly until the desired page is displayed. The number of pages available is dependant on meter type.
To select voltage measurements press the until the desired page is displayed. The number of pages available is dependant on meter type.
To select power/energy measurements press the repeatedly until the desired page is displayed. The number of pages available is dependant on meter type.
Automatically scrolling pages showing PF, Volts & Amps on each phase are obtained by pressing SCROLL Display pages available on the full range of GIMA meters are shown below followed by tables showing those available on each standard meter type.
VOLT key repeatedly
POWER key
7
3. Display Pages
Measured data is displayed on the LCD updated every second unless otherwise stated. Display Pages are organized in four Standard Menus as follows:
3.1 Power Up
The following screen is shown when auxiliary power is fi rst supplied.
3.2 Current Menu
Press the AMP key to select from the available Current Menu pages.
Phase Amps
All Meter Types
Phase 1 true rms amps
Phase 2 true rms amps.
Phase 3 true rms amps.
This display is updated every second.
Peak Hold Phase Amps
G300 & G400 Only
The maximum value of displayed phase amps. These are stored in non-volatile memory when the meter loses auxiliary power
Press AMPS and VOLTS to reset all three peaks to zero.
8
System and Balance Amps
G300 & G400 Only
Balance Amps - Instantaneous sum of the phase current waveforms. This is a measure of the neutral current + earth leakage.
System Average Amps =
(Irms1 + Irms2 + Irms3)/3.
Time-Averaged Amps
G100 through G400
The calculated average of phase amps taken over a user defi nable time period
(10s to 2500s).
T
VI
A rolling time window is used and the display updated every T
/10 with the
VI
average of the most recent period displayed.
Peak Time-Averaged Amps
G100 through G400
The maximum value of Time- Averaged amps. These are stored in non-volatile memory when the meter loses auxiliary power
Press AMP and VOLTS to reset all three peaks to zero.
9
3.3 Voltage Menu
Press the VOLTS key to select from the available Voltage Menu pages.
Phase Volts
All Meter Types
Phase 1 True rms volts
Phase 2 True rms volts.
Phase 3 True rms volts.
This display is updated every second.
Line Volts
All Meter Types
Line 1 Volts (Phases 1-2)
Line 2 Volts (Phases 2-3)
Line 3 Volts (Phases 3-1)
This display is updated every second.
Peak Hold Phase Volts
Meter Type G300 & G400
The maximum value of displayed phase volts. These are stored in non-volatile memory when the meter loses auxiliary power
Press AMP and VOLTS to reset all three maximums to zero.
Time-Averaged Volts
All Meter Types
The calculated average of phase volts taken over a user defi nable time period T
(10s to 2500s).
VI
A rolling time window is used and the display updated every T
/10 with the
VI
average of the most recent period displayed.
10
Peak Time-Averaged Volts
All Meter Types
The maximum value of Time- Averaged volts. These are stored in non-volatile memory when the meter loses auxiliary power
Press AMP and VOLTS to reset all three maximums to zero.
3.4 Power Menu (Meter Types G100-G400)
Press the POWER key to select from the available Power Menu pages.
System Power (kW)
Meter Types G100 through G400
System Real Power (Watts)
Frequency (Measured on V1)
System, PF
A symbol after the PF value indicates a capacitive load.
System Power (kVA)
Meter Type G400 Only
System Apparent Power (VA)
Frequency (Measured on V1)
System, PF
A symbol after the PF value indicates a capacitive load.
System Power (kvar)
Meter Types G300 & G400 Only
System Reactive Power (VAr)
Frequency (Measured on V1)
System, PF
A symbol after the PF and kvar values indicate a capacitive load.
11
Phase Watts
Meter Types G100 through G400
Phase 1 watts
Phase 2 watts.
Phase 3 watts
Phase VA
Meter Type G400 Only
Phase 1 VA
Phase 2 VA.
Phase 3 VA
Phase var
Meter Types G300 & G400 Only
Phase 1 var
Phase 2 var.
Phase 3 var
A symbol after a var value indicates a capacitive load.
A negative sign before a var reading indicates export reactive power.
12
Mean Demand (MD)
Meter Types G300 & G400 Only
The calculated average of the system power values taken over a user defi nable time period T
(1min to 60min).
p
A rolling time window is used and the display updated every T
/30 with the
p
averages of the most recent period displayed.
Peak Hold MD
Meter Types G300 & G400 Only
The maximum value of each power MD value. These are stored in non-volatile memory.
Press AMP and VOLTS to reset all three maximums to zero. See attached link option on page.
Real Energy (Wh)
Meter Types G200 through G400 Only
This register accumulates when kW is positive (import).
This value returns to 0 when the value exceeds 99999999.
This register is stored in non-volatile memory when auxiliary power is not supplied to the meter.
*Press AMP & VOLTS and hold for 5 seconds to reset Kwh to zero if this option is installed.
13
Apparent Energy (VAh)
Meter Type G400 Only
VAh Accumulating register.
This value returns to 0 when the value exceeds 99999999.
This register is stored in non-volatile memory when auxiliary power is not supplied to the meter.
Reactive Energy (varh)
Meter Type G300 & G400 Only
Import varh Accumulating register.
This value returns to 0 when the value exceeds 99999999.
This register is stored in non-volatile memory when auxiliary power is not supplied to the meter.
Reactive Energy Inductive
Meter Types G300 & G400 Only
This register is separate from the main import varh register and accumulates only when the measured load is inductive.
This register resets at 99999999 and is saved in non volatile memory.
Reactive Energy Capacitive
Meter Types G300 & G400 Only
This register is separate from the main import varh register and accumulates only when the load is capacitive.
This register resets at 99999999 and is saved in non volatile memory.
NOTE 1: Meters may be supplied with all Peak Reset keypad functions disabled.
NOTE 2: Meters may be supplied with an Energy Reset Option (ref section 5)
14
GIMA Option Links
1. Option Links
WARNING
Risk of Electric Shock!
Isolate the instrument supply and all inputs before accessing the option links
Four option links may be accessed on the rear of the GIMA display PCB. Meters are normally shipped with all these links fi tted.
*Not customer programmable. Contact Simpson before changing.*
1.1 Option Link Detection
For safe operation the instrument supply and all inputs must be isolated before accessing option links. The link settings are only detected during power-up of the auxiliary supply to the meter
2. Enable Programming Menu (Link1)
If this link is removed the user may not gain access to the programming menu using the front panel keys. For further details of programming the GIMA refer to the meter operating instructions.
3. Disable Reset Energy (LINK2)
If this link if fi tted the Energy Registers may be reset by:
Press P to display any energy register
Press AMP and VOLTS together and hold until energy resister resets to zero (approx 5S).
If this link is removed the Energy Registers may not be reset
NOTE: Once reset to zero the accumulated energy readings may not be recovered.
4. Disable Reset Peaks (LINK3)
If this link is removed the peak hold and peak demand values may be reset by:
Select any display page showing a Peak Hold or Peak Demand value.
Press AMP or VOLTS together and hold until the peak value resets to zero (approx 2S).
If this link is fi tted the peak and peak demand values may not be reset
NOTE: Once reset the zero and peak and peak demand values will be replaced by
values measured in the following second.
5. Pulse Output #2 (LINK4)
If this link is fi tted the second pulse output will be triggered by changes in the import kvarh register.
If this link is omitted the second pulse output will be triggered by changes in the kVah register.
15
3.5 Reset of Energy Registers
Meters may be supplied with an option to reset energy registers to zero using the front keys. If the option is fi tted, press AMP and VOLTS together while displaying any energy register and hold for approximately 3 seconds. All energy registers are simultaneously reset to zero. Once reset the registers may not be recovered.
3.6 Scrolling Menu (Meter Types G100 through G400)
Press the SCROLL key to select the Auto Scrolling Per-Phase Menu.
Per-Phase Display Pages
Meter Types G100 through G400
Three pages show the Amps Volts and Power Factor of phases 1-3 consecutively.
The Phase automatically advances after approximately 5 seconds.
A symbol indicates a capacitive load.
Press the SCROLL key to advance the scrolling pages more quickly.
16
3.7 Meter Type Display Menus
G100 Menus
AMPS VOLTS POWER SCROLL
Phase Amps Phase Volts System Power (kw),Hz,PF Phase 1 PF, V, I
Time Averaged Amps Line Volts Phase Watts Phase 2 PF, V, I
Peak Time Averaged Amps
AMPS VOLTS POWER SCROLL
Phase Amps Phase Volts System Power (kw),Hz,PF Phase 1 PF, V, I
Time Averaged Amps Line Volts Phase Watts Phase 2 PF, V, I
Peak Time Averaged Amps
AMPS VOLTS POWER SCROLL
Phase Amps Phase Volts System Power (kw),Hz,PF Phase 1 PF, V, I
Time Averaged Amps Line Volts System Power
Time Averaged Volts Phase 3 PF, V, I
Peak Time Averaged Volts
G200 Menus
Time Averaged Volts Import Real Energy (Wh) Phase 3 PF, V, I
Peak Time Averaged Volts
G300 Menus
Phase 2 PF, V, I
(kvar),Hz,PF
Peak Time Averaged Amps
Time Averaged Volts Phase Watts Phase 3 PF, V, I
Peak Time Averaged Volts
Phase var
Maximum Demands (MD)
Peak Hold MDs
Import Real Energy (Wh)
Import Reactive Energy (varh)
Reactive Energy Inductive
Reactive Energy Capacitive
17
G400 Menus
AMPS VOLTS POWER SCROLL
Phase Amps Phase Volts System Power (kw),Hz,PF Phase 1 PF, V, I
Peak Hold Phase Amps
System and Balance Amps
Time Averaged Amps Time Averaged Volts Phase Watts
Peak Time Averaged Amps
Line Volts System Power
(kVA),Hz,PF
Peak Hold Phase Volts
Peak Time Averaged Volts
System Power (kvar),Hz,PF
Phase VA
Phase var
Maximum Demands (MD)
Peak Hold MDs
Import Real Energy (Wh)
Apparent Energy (VAh)
Import Reactive Energy (varh)
Reactive Energy Inductive
Reactive Energy Capacitive
Phase 2 PF, V, I
Phase 3 PF, V, I
18
3.8 Display Scaling
Measured values displayed on the LCD are scaled by the user settings of CT and/or PT primaries to provide optimum resolution.
3.8.1 Voltage Scaling
PT Setting Resolution
10V
- 80V
L-L
81V
L-L
801V
L-L
8,001V
>80,000V
L-L
- 800V 0.1 V
– 8,000V
- 80,000V
L-L
L-L
L-L
L-L
0.01 V
1 V
0.01 kV
0.1kV
3.8.2 Current Scaling
CT Setting Resolution
5A - 8A 0.001 A
9A - 80A 0.01 A
81A - 800A 0.1 A
801A – 8,000A 1 A
>8,000A 0.01 kA
3.8.3 Power Scaling (W, VA, var)
PT Setting x CT Setting Phase Parameters System Parameters
100VA - 1,400VA 0.1 W 0.001 kW
1,401VA - 14,000VA 0.001 kW 0.01 kW
14,001VA - 140,000VA 0.01 kW 0.1 kW
140,001VA - 1,400,000VA 0.1 kW 1 kW
1,400,001VA - 14,000,000VA 1 kW 0.01 MW
14,000,001VA - 140,000,000VA 0.01 MW 0.1 MW
140,000,001VA – 1,000,000,000VA 0.1 MW 1 MW
3.8.4 Energy Registers (Wh, VAh, varh)
PT Setting x CT Setting Resolution
100VA - 1,400VA .001 kWh
1,401VA - 14,000VA 0.01 kWh
14,001VA - 140,000VA 0.1 kWh
140,001VA - 1,400,000VA 1 kWh
1,400,001VA - 14,000,000VA 0.01 MWh
14,000,001VA - 140,000,000VA 0.1 MWh
140,000,001VA – 1,000,000,000VA 1 MWh
3.8.5 Miscellaneous
All Settings Resolution
System and Phase PF 0.001
THD 0.1%
Harmonics 0.1%
Frequency 0.1 hz
19
3.9 Isolated Pulse Outputs
GIMA meters which display kWh and/or kvarh incorporate isolated pulse output(s). These outputs provide a simple interface to external systems such as building management centres etc.
Each output takes the form of a normally open, volt free contact pair which provides a low resistance, for 100mS, at the end of a pre-set number of increments of the associated energy register (‘pulse rate’). The pulse rate of each output may be programmed by the user to match the requirements of the external system. For further details on programming the GIMA refer to Section 5.
Figure 2.1 Pulse Output Connection
20
4. Installation
4.1 Panel Mounting
Panels should be of thickness 1mm to 4mm with a square cut-out of 92mm (+0.8 - 0.0). A minimum depth of 72mm should be allowed behind the panel for the meter. Remove the panel mounting clips and insert the meter into the cut-out from the front of the panel. Push the meter home. Ensure the screws in each panel mount clip are fully retracted and insert the clips as shown in the diagram below. Tighten the screws to secure the meter fi rmly in the panel.
DO NOT OVERTIGHTEN.
Figure 4-1 Fitting The Meter in a Panel
21
4.2 CT Connections
The GIMA is designed for use with external current transformers (CTs). Recommended types should conform to Class 1 per IEC 60044-1. The secondary of the CT should be specifi ed to suit the input rating defi ned on the meter label. Cables used for the current circuit should have a maximum conductor size of 4.0mm and should be kept as short as possible to reduce cable losses loading the CT secondary.
CT Inputs to the meter are isolated from each other and all other parts of the circuit. This allows use on a wide variety of systems including those requiring common and/or earthed CT secondaries.
WARNING :
NEVER leave the secondary of a current transformer open circuit while
a primary current fl ows. In this condition dangerous voltages may be
produced at the secondary terminals.
4.3 Voltage Connections
2
Cables used for the voltage measurement circuit should be insulated to a minimum of 600V AC and have a minimum current rating of 250mA. The maximum conductor size is 4.0mm
External protection fuses are recommended for the voltage measurement inputs. These should be rated at 160mA maximum, Type F, and should be able to withstand voltages greater than the maximum input to the meter.
4.4 Auxiliary Mains Supply (L & N)
The GIMA uses an isolated auxiliary mains supply separate from the voltage measurement inputs. This may be connected separately or in parallel with the measurement inputs provided the ratings detailed on the instrument label are not exceeded.
Separate connection of the auxiliary mains is required, for example, when :
x A suitable supply voltage is not available locally.
x Measurement voltages are expected to vary over a wide range
x A backup supply is required to maintain meter display
2
.
The auxiliary mains supply is not internally fused. External fusing is required to protect the meter. External fuses should be rated at 250mA 250V Type T. The meter ratings are detailed on the instrument label.
WARNING :
CHECK the instrument LABELS for correct input ratings. Incorrectly rated
inputs may permanently damage the device.
22
4.5 Connection Schematics
Figure 4-2 3-Phase 3-Wire 2CTs
Figure 4-3 3-Phase 3-Wire 3CTs (See Note 2)
23
Figure 4-4 3-Phase 4-Wire (See Note 2)
Figure 4-5 Single Phase
24
Figure 4-6 3 Phase 3 Wire Using Potential Transformers (2CTs)
Note 1: It is possible to use 3 current transformers in conjunction with potential transformers. Refer to Figure 4-3 for details of CT connection.
Note 2: Some systems require the S2 terminals of each CT to be connected to common point. This common point may be earthed. The GIMA has isolated CT inputs facilitating this type of connection.
25
5. Meter Setup
5.1 Programming Menu
To enter programming mode:
Hold
Press SCROLL button twice to go to the next menu.
4-Digit Security Code
Current Transformer Primary
AMPS and SCROLL together for 5 Seconds.
This page is only shown if a security code greater than 0 is set via serial
communication.
Press S or T to select each digit (least signifi cant fi rst)
Press to move to the next most signifi cant digit.
A correct 4 digit security code is required to access other programming menu pages.
Press S or T to select from the standard list of CT primaries while / is displayed. (List Mode)
Potential Transformer Primary
Press S or T to increase or decrease the value by 10 while F is displayed. (Fine adjust)
Press and S together to toggle between L and F.
Press to accept the set value. CT values range from 5A 25000A
Press S or T to select from the standard list of PT primaries while F is displayed. (List Mode)
Press S or T to increase or decrease the value by 10 while F is displayed. (Fine adjust)
Press and S together to toggle between L and F.
Press to accept the set value. PT values range from 10V to 440kV.
26
Pulse Rate
This sets the amount of energy (kWh) required to trigger each Pulse 1 output.
Pulse 2 is set at the same rate but linked to a different register (eg kvarh).
Press S or T to select the next/ previous Pulse Rate from a standard list.
Press to accept the set value.
Pulse Length
Current/Voltage Time Ave Period
(Note 1)
This sets the contact closure time in seconds for both pulse outputs.
Press S or T to select the next/ previous Pulse Length from a standard list between 0.1 and 20 seconds.
Press to accept the set value. Pulse lengths range from 0.1S to 20.0S.
Note: Ensure pulse length < maximum pulse rate in seconds
This sets the integration period in seconds used for the sliding time window average calculation for current and voltage.
Press S or T to increment or decrement the value.
Press to accept the set value.
The Time Average period may be set in the range 10 – 2500S In steps of 10 Seconds.
27
Power MD Integration Period
(Note 1)
This sets the integration period in minutes used for the sliding time window MD calculation for power.
Press S or T to increment or decrement the value.
Press to accept the set value.
The MD Integration period may be set in the range 1 – 60 minutes in steps of 1 minute.
This sets the instantaneous system kW level above which the Hours Run timer will accumulate.
Below this level Hours Run will remain unchanged.
Press S or T to increment or decrement the value. The speed of change will increase as the button is held.
Press to accept the set value.
Note 1. Some setup screens are only available on meters with corresponding measurement options.
6. Options
6.1 Internal Modbus Communications
The GIMA may be supplied with RS485 Modbus communications. This is available as a factory fi tted internal option.
28
7. Specifi cation
Inputs
System 3-Phase 3 or 4 Wire Unbalanced Load
Voltage Vb. 230 / 400 Volt. 3-Phase 3 or 4 Wire
Current Ib 5 Amp from external current transformers (CTs)
Measurement Range
Voltage
Current
Frequency Range
Fundamental
Harmonics
Input Loading Voltage Current
Overloads Voltage Current
Vb. 63 / 110 Volt optional Vb. 120 / 208 Volt optional
Ib 1 Amp optional Fully Isolated (2.2kV each phase)
20% to 120%
0.5% to 120%
45 to 65Hz Up to 30th harmonic
Less than 0.1 VA per phase Less than 0.1 VA per phase
x2 for 2 seconds maximum (CAT III) x40 for 0.5 seconds maximum
Auxiliary Supply
Standard 230 Volt 50/60Hz ±15%
Overload CAT III
Options 110 Volt 50/60Hz ±15%
Load 3 VA Maximum
Isolation 2.2kV (1 minute)
Display
Display Type Custom, supertwist, LCD with LED backlight
Data Retention 10 years minimum
Stores energy registers, user settings, peaks and Hours Run
Display Format Display Update
Digital (Pulse) Outputs
Function 1 pulse / energy unit (Output #1=N Wh, Output #2=N varh)
Scaling Programmable
2 Rows x 4 Digits, 1 Row x 8 Digits + Legends 1 second
Pulse Period Programmable 100ms minimum. (2ms Rise, 2ms Fall)
Type N/O Volt free contact. Optically isolated BiFET
Contacts 100mA AC/DC max, 100V AC/DC max
Isolation 2.2kV (50V #1 to #2)
29
Accuracy
Phase Current 0.2% Ib (1.0% Rdg. 0.05 Ib d Iph d 1.2 Ib) ±1 digit.
Neutral Current 0.6% Ib (2.0% Rdg. 0.05 Ib d In d 1.2 Ib) ±1 digit.
Phase Voltage 0.2% Vb (1.0% Rdg. 0.2 Vb d Vph d 1.2 Vb) ±1 digit.
Line-Line Voltage 0.3% Vb (1.0% Rdg. 0.2 Vb d VLL d 1.2 Vb) ±1 digit.
Phase Watts 0.4% FS (1.0% Rdg. 0.05FS d P d 1.2FS) ±1 digit.
Phase VA 0.6% FS (1.5% Rdg. 0.05FS d Q d 1.2FS) ±1 digit.
Phase var 0.8% FS (2.0% Rdg. 0.05FS d S d 1.2FS) ±1 digit.
Phase PF ± 0.2 Degrees
System Watts 0.6% FS (1.0% Rdg. 0.05FS d P d 1.2FS) ±1 digit.
System VA 1.0% FS (1.5% Rdg. 0.05FS d Q d 1.2FS) ±1 digit.
System var 1.5% FS (2.0% Rdg. 0.05FS d S d 1.2FS) ±1 digit.
System PF ± 0.2 Degrees
Frequency ±0.05Hz. 45Hz d F d 65Hz
Wh Register Class 1.0 EN 61036, EN 62053-21, BS 8431
VAh Register Class 2.0
varh Registers Class 2.0 IEC 1268, EN 60253-23, BS 8431
% THD Amps ± 0.5% THD 0.05 Ib d Iph d 1.2 Ib
% THD Volts ± 0.5% THD 0.2 Vb d Vph d 1.2 Vb
General
Environment IP54
Mechanical
Timebase Better than 100ppm
Temperature
Operating
Storage
-10 deg C to +65 deg C
-25 deg C to +70 deg C
Humidity <75% non-condensing
Enclosure DIN 96mm x 96mm Mablex ULV94-V-O
Dimensions 96mm x 96mm x 80mm (72mm behind panel)
130mm behind panel with options unit fi tted
Weight Approx. 400g
Terminals Rising Cage. 4.0mm
2
cable max
30
Loading...