Application
Amik 200 /201
Amik 200/ 201
panel meters. It measures electrical parameters like AC Voltage, AC Current, Frequency, Active, Reactive, Apparent Power, Import
Export Energy & many more.
Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog
Product Features
On site
programmable
PT / CT ratios
User selectable
CT Secondary
5A /1A
User selectable
PT Secondary
Low back depth
Four function
keys
Demand
Measurement
3 line 4 digits
LED display
RPM
Measurement
Energy Count
Storage
User selectable
3 phase 3 Wire
or 4Wire or
Single phase
Network
Onsite selection
of Auto scroll /
Fixed Screen
It is possible to program primary of external
potential Transformer (PT), primary of
external Current Transformer (CT) on site via
front panel keys by entering into
Programming mode.
The secondary of external Current
Transformer (CT) can be programmed on
site to either 5A or 1A using front panel keys.
The instrument has very low back depth
(behind the panel) of less than 55 mm
(Without output option).
Using the four function key, it is possible to
go desired parameter screen instantly..
Measures & Displays Current Demand,
kVA Demand, kW Import Demand,
kW Export Demand. Any of the parameters
can be assigned to optional Limit switch.
Simultaneous display of 3 Parameters.
The instrument display Rotation per minutes
for generator applications. Number of poles
can be set on site depending upon
application requirement.
In case of power failure, the instrument
memorizes the last energy count. Every
1 min, the instrument updates the energy
counter in the non-volatile memory.
User can program on site the network
connection as either
3 Phase 3 Wire or 4 Wire or single phase
network using front panel keys.
,QFDVHRIVHOISRZHUHGFRQÀJXUDWLRQHLWKHU
3 Phase 4 wire or single phase network is
available.
Optional Pulse
Output /
Limit switch
(Relay output)
Pulse Output
Limit Switch
Optional
MODBUS
(RS485) Output
Storage of
parameters
possible
Enclosure
Protection for
(for back)
dust and water
IEC60529.
EMC
Compatibility
Interference
Emission
Interference
Immunity
Electrostatic
discharge contact
/air. (ESD)
EM Field
Not Available
Not Available
Not Available
The optional Modbus output enables the
instrument to transmit all the measured
parameters over standard MODBUS (RS-485).
RS-485
The MODBUS com
The instrument stores minimum and
maximum values for System Voltage, System
Current, Run Hour, ON Hour & number of
Interrupts. Every 60 sec stored values are
updated.
Conforms to IP 50 (for front face) & IP 20
Compliance to International standard
IEC 61326.
IEC 61326-1 : 2005, Class A
IEC 61326-1 : 2005
IEC 61000-4-2 -- 4kV/8kV
IEC 61000-4-3 -- 10 V/m
(80 MHz to 1 GHz)
– 3 V/m (1.4 Ghz to 2 GHz)
-- 1 V/m (2 GHz to 2.7 GHz)
![](/html/9f/9f01/9f0148974f7797bf532576d0792d49b041291d0855823f1873f917cc4f3ab67d/bg2.png)
Product Features
Amik 200 /201
True RMS
measurement
Energy
Measurement
(Import & Export)
Programmable
Energy format &
Energy rollover
count
The instrument measures distorted wave
form up to 15th Harmonic.
Active Energy (kWh), Reactive Energy
(kVArh), Apparent Energy (kVAh).
Any of the parameters can be assigned to
optional Pulse output.
Customer can assign the format for energy
display on MODBUS (RS-485) in terms of
W, kW or MW. Additional to this, customer
can also set a rollover count from 7 to 14 digits
depending on the energy format, after which
the energy will roll back to zero.
Burst
Surge
Conducted RF
Rated Power
Frequency
magnetic Field
Voltage dip
-- 70% during 25/30 cycles.
Short
interruptions
cycles.
IEC 61000-4-4 -- 2 kV (5/50 ns, 5 kHz)
IEC 61000-4-5 -- 1 kVLL / 2 kVLN.
IEC 61000-4-5 -- 3 V (150 kHz to 80 MHz)
IEC 61000-4-8 -- 30 A/m
IEC 61000-4-11 -- 0% during 1 cycle.
-- 40% during 10/12 cycles.
IEC 61000-4-11 -- 0% during 25/30 cycles.
25 cycles for 50 Hz test.
30 cycles for 60 Hz test.