Simpson Electric Amik 100 Technical Specifications

Amik 100
Reference conditions for Accuracy
Reference temperature Input waveform Sinusoidal (distortion factor 0.005)
Input frequency Auxiliary supply voltage
23°C +/- 2°C
50 or 60 Hz ±2% Rated Value ±1%
Rated Value ±1%
Accuracy
Voltage
Current
Frequency
±1% of range (20... 100% of Nominal value)
±1% of range (10... 100% of Nominal value)
0.5% of mid frequency
Input Voltage
Nominal input voltage (AC RMS)
Max continuous input voltage
Nominal input voltage burden
System PT secondary values
System PT primary values
Phase –Neutral 290V L-N , Line-Line 500V L-L
120% of rated value < 0.3 VA approx. per phase
(For external auxiliary meter) 100VLL to 500VLL programmable
on site. 100VLL to 692kVLL programmable
on site.
Overload Withstand
Voltage
Current
2 x rated value for 1 second, repeated 10 times at 10 second intervals
20x rated value for 1 second, repeated 5 times at 5 min intervals
Operating Measuring Ranges
Voltage Range With External Aux
Voltage Range With Self Power
Current Range Frequency
10… 120% of rated value
80… 120% of rated value 10 … 120% of rated value
45…65 Hz
0.025%/°C for Voltage
0.05%/°C for Current
Limit Switch (Relay)
Switching Voltage & Current for Relay
Enclosure
Front Front with seal (Option) Back
IP 50 IP 65 **
IP 20
Input Current
Nominal input current System CT secondary values
System CT primary values Max continuous input
current Nominal input current
burden
Auxiliary Supply
External Aux Self powered **
Frequency range VA burden
5A AC RMS 1A & 5A programmable on site From 1A up to 9999A
(for 1 or 5 Amp ) 120% of rated value
< 0.2 VA approx. per phase
40 V – 300V AC-DC (± 5 % ) Input voltage range from 80% to
100% of Rated value. (Self powered meter is available only in 3Phase 4 Wire and Single Phase network.) Auxiliary input is derived from Phase 1 (R phase)
45 to 65 Hz 3 VA Approx.
Environmental
Operating temperature Storage temperature
Relative humidity Warm up time
Shock Vibration
Safety
Pollution degree Installation category High Voltage Test
Applicable Standards
EMC Safety
IP for water & dust
-20° to +70°C
-30°C to +80°C 0 to 95% non condensing
Minimum 3 minute 15g in 3 planes
10... 55 Hz, 0.15mm amplitude
2 III
3.3 kV AC, 50Hz for 1 minute between Aux. and measuring inputs
IEC 61326-1: 2005 IEC 61010-1-2001 , Permanently connected use
IEC60529