Simpson 501 Specification Sheet

Page 1
•
Five Test Voltages: 50, 100, 250, 500, and 1000 VDC
•
Voltage Measurement to 1000 V AC/DC
•
Test Probe Signal Lamp Illuminates Work Area and Indicates Pass/Fail of Insulation Resistance
•
Battery Powered with Battery Test and Battery Charge Indicator
•
Rugged Tester Design for Industrial Applications with Leatherette Carrying Case
501 Insulation Tester
Ordering Information
ACCESSORIES Catalog No.
501 Insulation Tester, 1000 V 12501
INSULATION RESISTANCE
DIRECT AND ALTERNATING CURRENT
(1) Referring to scale length
REFERENCE CONDITIONS Ambient Temperature: 73⬚F (23⬚C) ⫾ 4⬚F (2⬚C) Relative Humidity: 45 to 55% Measurement Magnitude Frequency: 45-65 Hz (voltage measurements) Line Voltage Waveform: Sine, deviation between effective and rectified value < .5% Battery Voltage: 9V ⫾ .5V Operating Position: Horizontal
ELECTROMAGNETIC COMPATIBILITY EMC Interference Emission:
EN 50081-1: 1992
Interference Immunity:
EN 50082-1: 1992
ELECTRICAL SAFETY Designed to IEC 1010-1 Protection Class: II Test Voltage: 5.55Kv Overvoltage Classification: II Pollution Degree: 2 Protection: Housing IP52
AMBIENT CONDITIONS Operating Temp. Range: 32⬚F (0⬚C) to 104⬚F (40⬚C) Storage Temp. Range: -4⬚F (-20⬚C) to 140⬚F (60⬚C) (without batteries) Relative Humidity: Max. 45-55%, condensation must be avoided MECHANICAL DESIGN Dimensions:
W
6.50” (165mm) x
D
4.33” (110mm) x H 4.92” (125mm)
Weight:3.5 lbs. (1.6kg) (with batteries) POWER SUPPLY
Standard or Storage Battery: 6 ea. 1.5V “D” size batteries Working Range:7V to 10V Battery Service Life: Number of possible measurements with 1 set of “D” size
batteries (with lamp in test prod switched off): at least 3,000 measurements of an insulation resistance of 1M⍀ (Nominal Voltage of1000 V, 5 sec. Measurement duration, switched off for 25 sec. etc.)
Specifications
(1) Switching Accuracy
Measuring Ranges
Measuring
Range Open-Circuit Voltage
Uo
Internal Resist ance R
i
Lamp in Test Prod
1)
Lights for Resistance
0…50K⍀
20K⍀…1M⍀
200K⍀…20M⍀
60V
30K⍀ 10K⍀ 40K⍀
> 100K⍀
0…100K⍀
40K⍀…2M⍀
400K⍀…40M⍀
120V
60K⍀ 20K⍀ 80K⍀
> 200K⍀
0…250K⍀
100K⍀…5M⍀
1M⍀…100M⍀
300V
150K⍀
50K⍀
200K⍀
> 500K⍀
0…500K⍀
200K⍀…10M⍀
2M⍀…200M⍀
600V
300K⍀ 100K⍀ 400K⍀
> 1M⍀
0…1M⍀
400K⍀…20M⍀
4M⍀…400K⍀
1200V
600K⍀ 200K⍀ 800K⍀
> 2M⍀
0…4K⍀ 9V
⫺⫺
Measuring
Range Frequency
Internal
Resistance
Maximam
Overload Intrinsic Error (1)
0 to 1000V
AC/DC
0 or 40 to 200Hz 900K⍀ 1200V AC/DC
Continuous
⫾2.5%
rev_1 11/2/04