S45-3600B/W
Cat6/6A UTP 180° Keystone Jack 110 Style, Toolless,
w/6 Color ID, 568B Wiring Label, ANSI/TIA 568.2-D,
ISO/IEC 11801 Class E, Ea, UL
TERMINATION INSTRUCTIONS
TIA / EIA
T568B
White/Orange
Orange
White/Green
Green
Blue
White/Blue
White/Brown
Brown
White/Green
1
Green
2
White/Orange
3
Orange
6
4
5
7
JACK PIN
DESIGNATIONS
8
TIA / EIA
T568A
1
1.6"
Strip off 1.6 inch of cable jacket.
Fold back the drain wire.
2
Insert a cable into the termination cap and
fan out all four twisted pairs.
Following the instruction of the color-coded
wire position printed on the termination cap,
position conductors into the slots and make
sure the conductors are in the proper slot.
Trim the ends of the conductors.
Secure the hinged outlet by using
a crimp tool until it completely
snap to effect the connection.
3
4
5
Cable Tie
Install the termination cap to outlet, which
will also allocate the conductors sitting on
the slots.
Cable Fixture
Fasten a cable tie wrap to secure
drain wire on the cable fixture.