Simplicity 514067-UAD-A-0509 User Manual

APPLICATION GUIDE
24 — must be grounded close to the Simplicity LINC
®
The shield must be connected to ground at each device.
R C
24V power is polarity sensitive, incorrect wiring could result in board damage.
Simplicity
®
LINC GATEWAY

OVERVIEW

The Simplicity®LINC Gateway operates as a Modbus® Client providing an interface between a BACnet® MS/TP control system and devices that communicate using the Modbus RTU protocol. The Simplicity BACnet Building Automation System (BAS).
The Simplicity products equipped with Simplicity 4/2/2008 as well as prior Simplicity®Elite™ and Simplicity® with Intelli-Comfort™ controllers.
®
LINC allows monitoring and control by a thi rd-party
®
LINC is preconfigured to provide an interface to UP
®
controllers manufactured after
®
The Simplicity unit and utilizes 24 VAC power from the unit’s control transformer. One port is connected to the UP controller. The other port must be connected to the BACnet MS/TP network.
The Simplicity®LINC Gateway is preconfigured to obtain operational data points from the controller and expose them on a BACnet MS/TP network.
NOTE: Not all Simplicity
LINC mounts inside the control panel of the UP
®
operating parameters are controlled/
monitored by the Simplicity
®
LINC.
FIGURE 1: WIRE CONNECTIONS
514067-UAD-A-0509
514067-UAD-A-0509
MAC Address of 21
1
0
4
0
16
0
0
0
21
1
2
0
0
0
32
64
0
99
MAC Address of 99
A0
A1
A2
A3
A4
A5
A6
A7
A0
A1
A2
A3
A4
A5
A6
A7

CONNECTION

The Simplicity®LINC has 2 ports, one for connection to the BAS network (BACnet) and one to the Simplicity® board (Modbus).
BACNET NETWORK
The only connection required in the field is to the BACnet (BAS) network.
NOTE: Proper termination and grounding of the shields must
be observed.
DIP switches A0-A7 on the Simplicity selection of the MAC Address. The MAC Address identifies the
Simplicity
99. The default DIP switch setting is 1. A Device Instance (DE) Modifier is used by the Simplicity
and defaulted to 230. The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001. The default Unit Name is YORK_RTU.
FIGURE 2: MAC ADDRESS EXAMPLES
®
LINC to other devices and must be between 1 and
1 2 3 4 5 6 7 8
1
2
4
8
16
32
64
128
1 2 3 4 5 6 7 8
1
2
4
8
16
32
64
128
®
LINC board allow
ON
ON
®
LINC
TABLE 1: BAUD RATE SELECTION SETTINGS
DIP Setting Baud Rate
1 110 2 300 3 600 41200 52400 64800 79600 8 19200
9 20833 10 28800 11 38400 12 57600 13 76800 14 115200

MODBUS CONNECTION

The UP device communicates with the Simplicity the Modbus RTU protocol on an RS485 connection. Connection and addressing of the UP product is completed at the factory. No further adjustment should be done.
The default Simplicity® board address is 1. Do not engage the Address button on the Simplicity® board. This changes the address and causes a Modbus communication failure.
®
If a problem arises with the Simplicity exposed by the Simplicity®LINC requires modification, the U P controller software can be manipulated using a Microsoft© Windows-based PC with the Simplicity (downloadable from the UP website). To connect the PC to the UP controller, a FREEnet USB adaptor (Part No. S103101967000), which is an RS232 to RS485 adapter, and FREEnet adapter cable (S102538682000) are required and available through SOURCE1 (Toll-free at 1-800-536-6112).
LINC or a parameter not
®
PC software
®
LINC using
SOFTWARE SETUP
The control sequence is managed by the Simplicity® controller. The data points on these systems are mapped to standard AV and BV BACnet Objects. As a preconfigured application, no configuration is necessary in the Simplicity
®
LINC Gateway.
DIP switches B0-B3 on the Simplicity®LINC board allow for selection of the BACnet transfer speed.The default speed is set at 38.4k baud. Other speeds can be chosen as shown in Table
1.
2 Johnson Controls Unitary Products
514067-UAD-A-0509

FLASH MEMORY MANAGEMENT

®
The Flash Memory chip used in the Simplicity
controllers has
a 1,000,000 write cycle rating. To prevent premature failure of the flash memory, it should not
be written to more often than once every 10 minutes, on average.
Under unusual circumstances it could take up to two minutes for newly updated data to be seen.
ADDITIONAL CAPABILITY

MODBUS COMMUNICATION ALARM

One digital point is available to indicate communication problems between the Simplicity BI 84 (MODBUS_ALARM) is used to indicate Modbus communication problems between the Simplicity Gateway and the UP controller. When "on" this point indicates loss of Modbus communication. The last data received from the UP controller remains in the Simplicity function as if communications were normal.
NOTE: The MODBUS ALARM (BI84) is the only method to
verify communication between the Simplicity UP controller.
®
LINC and the UP controller.
®
LINC
®
LINC and it continues to
®
LINC and
Johnson Controls Unitary Products 3
514067-UAD-A-0509
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (2) AV 14 ACC_OVER_TME Accumulated Unoccupied Override Time
(in hours)
R (2) AV 15 ACTIVE_ALARM Active Alarm
R (5) BV 16 AIR_PROOF_SW Air Proving Switch Status (1=closed,
0=open/no air flow)
R/W (2) AV 79 OAQ_STPT 1000 0 5000 Air Quality Setpoint Outside
R (5) BV 85 ALARM_1_ON Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 86 ALARM_2_ON Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 87 ALARM_3_ON Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 88 ALARM_4_ON Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 89 ALARM_5_ON Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R (2) AV 33 BLDG_STATIC Building Static Pressure
R (5) BV 29 BP_SENS_INST Building Static Pressure Sensor Installed
R/W (2) AV 57 BLDG_SP_STPT 0.1 -0.25 0.25 Building Static Pressure Setpoint
R/W (2) AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint
(degrees F)
R (5) BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling
Enabled
R (5) BV 35 CVM_HEATING Comfort Ventilation Mode for Heating
Enabled
R (5) BV 33 COM_VENT_STA Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
R/W (2) AV 24 COM_V_HI_SP 80 60 85 Comfort Ventilation Upper Setpoint
(degrees F)
R (5) BV 23 COOLING_ENA Cooling Mode Enabled
R (5) BV 21 FAN_ON_W_SEN CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
R (2) AV 56 CV_VAV_SELEC CV/VAV Selected (0= Valid CV, 1=Valid
VAV, 2= Invalid Value)
R (2) AV 8 IAQ_VALUE Demand Ventilation (IAQ) Value (PPM)
R (5) BV 39 DEMAND_VENT Demand Ventilation (using Inside Sensor)
Enabled
R/W (2) AV 18 DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint
R (2) AV 67 REVISION xx Device Revision
R (5) BV 90 DF_SW_INST Dirty Filter Switch Installed
R (5) BV 15 DIRT_FILT_SW Dirty Filter Switch Status (0=open,1=closed/
fault)
R (2) AV 35 DUCT_STATIC Duct Static Pressure
R/W (2) AV 58 DUCT_SP_STPT 1.5 0 5 Duct Static Pressure Setpoint
R/W (2) AV 59 DUCT_SD_STPT 4.5 0 5 Duct Static Pressure Shutdown Setpoint
R (2) AV 31 ECO_DAMP_OUT Economizer Damper Output Status
(0-100%)
TABLE 2: POINTS LIST IN DESCRIPTION ORDER
4 Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint
R (5) BV 7 ECONO_INST Economizer Installed
R (5) BV 36 ECO_L_TO_SAT Economizer Loading to Control Supply Air
Temperature Enabled
R/W (2) AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position
R (5) BV 31 ECONO_STATUS Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
R/W (2) AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint
R/W (2) AV 23 ECON_OAT_ENA 55 40 80 Economizer Outside Air Temperature
Enable Setpoint
R/W (2) AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy Setpoint
R/W (2) AV 21 ECO_2ND_STPT 50 40 65 Economizer Second Stage Setpoint
R (2) AV 41 E_C1_ACM_HRS Elite Compressor #1 Accumulated Run
Time (in hours)
R (5) BV 42 E_COMP1_STAT Elite Compressor #1 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 45 E_C1_OVRLOAD Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 42 E_C2_ACM_HRS Elite Compressor #2 Accumulated Run
Time (in hours)
R (5) BV 46 E_COMP2_STAT Elite Compressor #2 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 49 E_C2_OVRLOAD Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 43 E_C3_ACM_HRS Elite Compressor #3 Accumulated Run
Time (in hours)
R (5) BV 51 E_COMP3_STAT Elite Compressor #3 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 54 E_C3_OVRLOAD Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 44 E_C4_ACM_HRS Elite Compressor #4 Accumulated Run
Time (in hours)
R (5) BV 55 E_COMP4_STAT Elite Compressor #4 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 58 E_C4_OVRLOAD Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 50 E_CFAN1_STAT Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 59 E_CFAN2_STAT Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 41 E_FAN_ OVER Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
R (5) BV 60 E_GAS_VLVE1 Elite Gas Valve #1 Input Status (1=ener-
gized, 0=not energized)
R (5) BV 62 E_GAS_VLVE2 Elite Gas Valve #2 Input Status (1=ener-
gized, 0=not energized)
R (5) BV 64 E_GAS_VLVE3 Elite Gas Valve #3 Input Status (1=ener-
gized, 0=not energized)
514067-UAD-A-0509
Johnson Controls Unitary Products 5
514067-UAD-A-0509
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 44 E_HPS1 Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 48 E_HPS2 Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 53 E_HPS3 Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 57 E_HPS4 Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (5) BV 40 E_IFAN_STAT Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 61 E_LIMIT_ 1 Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
R (5) BV 63 E_LIMIT_ 2 Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
R (5) BV 65 E_LIMIT_ 3 Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
R (5) BV 43 E_LPS1 Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 47 E_LPS2 Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 52 E_LPS3 Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 56 E_LPS4 Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (2) AV 32 EXH_DAMP_OUT Exhaust Damper Output Status (0-100%)
R (5) BV 30 EX_FAN_STAT Exhaust Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 10 EX_VFD_INST Exhaust VFD Installed
R (5) BV 32 FRECOOL_STAT Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
R (5) BV 68 HEAT_1_STAT H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
R (5) BV 69 HEAT_2_STAT H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
R (5) BV 70 HEAT_3_STAT H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)
R (2) AV 76 H1_ACCUM_HRS Heating #1 Accumulated Run Time
(in hours)
R (2) AV 77 H2_ACCUM_HRS Heating #2 Accumulated Run Time
(in hours)
R (2) AV 78 H3_ACCUM_HRS Heating #3 Accumulated Run Time
(in hours)
R (5) BV 25 HEATING_ENA Heating Mode Enabled
R/W (2) AV 27 HGR_HUM_STPT 50 0 100 Hot Gas Reheat Humidity Setpoint (percent
Humidity)
R (5) BV 18 HGR_STAT Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
R (2) AV 47 HGR_VLV_OUT Hot Gas Reheat Valve Output Status
(0-100%)
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
6 Johnson Controls Unitary Products