Simplicity 514067-UAD-A-0509 User Manual

APPLICATION GUIDE
24 — must be grounded close to the Simplicity LINC
®
The shield must be connected to ground at each device.
R C
24V power is polarity sensitive, incorrect wiring could result in board damage.
Simplicity
®
LINC GATEWAY

OVERVIEW

The Simplicity®LINC Gateway operates as a Modbus® Client providing an interface between a BACnet® MS/TP control system and devices that communicate using the Modbus RTU protocol. The Simplicity BACnet Building Automation System (BAS).
The Simplicity products equipped with Simplicity 4/2/2008 as well as prior Simplicity®Elite™ and Simplicity® with Intelli-Comfort™ controllers.
®
LINC allows monitoring and control by a thi rd-party
®
LINC is preconfigured to provide an interface to UP
®
controllers manufactured after
®
The Simplicity unit and utilizes 24 VAC power from the unit’s control transformer. One port is connected to the UP controller. The other port must be connected to the BACnet MS/TP network.
The Simplicity®LINC Gateway is preconfigured to obtain operational data points from the controller and expose them on a BACnet MS/TP network.
NOTE: Not all Simplicity
LINC mounts inside the control panel of the UP
®
operating parameters are controlled/
monitored by the Simplicity
®
LINC.
FIGURE 1: WIRE CONNECTIONS
514067-UAD-A-0509
514067-UAD-A-0509
MAC Address of 21
1
0
4
0
16
0
0
0
21
1
2
0
0
0
32
64
0
99
MAC Address of 99
A0
A1
A2
A3
A4
A5
A6
A7
A0
A1
A2
A3
A4
A5
A6
A7

CONNECTION

The Simplicity®LINC has 2 ports, one for connection to the BAS network (BACnet) and one to the Simplicity® board (Modbus).
BACNET NETWORK
The only connection required in the field is to the BACnet (BAS) network.
NOTE: Proper termination and grounding of the shields must
be observed.
DIP switches A0-A7 on the Simplicity selection of the MAC Address. The MAC Address identifies the
Simplicity
99. The default DIP switch setting is 1. A Device Instance (DE) Modifier is used by the Simplicity
and defaulted to 230. The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001. The default Unit Name is YORK_RTU.
FIGURE 2: MAC ADDRESS EXAMPLES
®
LINC to other devices and must be between 1 and
1 2 3 4 5 6 7 8
1
2
4
8
16
32
64
128
1 2 3 4 5 6 7 8
1
2
4
8
16
32
64
128
®
LINC board allow
ON
ON
®
LINC
TABLE 1: BAUD RATE SELECTION SETTINGS
DIP Setting Baud Rate
1 110 2 300 3 600 41200 52400 64800 79600 8 19200
9 20833 10 28800 11 38400 12 57600 13 76800 14 115200

MODBUS CONNECTION

The UP device communicates with the Simplicity the Modbus RTU protocol on an RS485 connection. Connection and addressing of the UP product is completed at the factory. No further adjustment should be done.
The default Simplicity® board address is 1. Do not engage the Address button on the Simplicity® board. This changes the address and causes a Modbus communication failure.
®
If a problem arises with the Simplicity exposed by the Simplicity®LINC requires modification, the U P controller software can be manipulated using a Microsoft© Windows-based PC with the Simplicity (downloadable from the UP website). To connect the PC to the UP controller, a FREEnet USB adaptor (Part No. S103101967000), which is an RS232 to RS485 adapter, and FREEnet adapter cable (S102538682000) are required and available through SOURCE1 (Toll-free at 1-800-536-6112).
LINC or a parameter not
®
PC software
®
LINC using
SOFTWARE SETUP
The control sequence is managed by the Simplicity® controller. The data points on these systems are mapped to standard AV and BV BACnet Objects. As a preconfigured application, no configuration is necessary in the Simplicity
®
LINC Gateway.
DIP switches B0-B3 on the Simplicity®LINC board allow for selection of the BACnet transfer speed.The default speed is set at 38.4k baud. Other speeds can be chosen as shown in Table
1.
2 Johnson Controls Unitary Products
514067-UAD-A-0509

FLASH MEMORY MANAGEMENT

®
The Flash Memory chip used in the Simplicity
controllers has
a 1,000,000 write cycle rating. To prevent premature failure of the flash memory, it should not
be written to more often than once every 10 minutes, on average.
Under unusual circumstances it could take up to two minutes for newly updated data to be seen.
ADDITIONAL CAPABILITY

MODBUS COMMUNICATION ALARM

One digital point is available to indicate communication problems between the Simplicity BI 84 (MODBUS_ALARM) is used to indicate Modbus communication problems between the Simplicity Gateway and the UP controller. When "on" this point indicates loss of Modbus communication. The last data received from the UP controller remains in the Simplicity function as if communications were normal.
NOTE: The MODBUS ALARM (BI84) is the only method to
verify communication between the Simplicity UP controller.
®
LINC and the UP controller.
®
LINC
®
LINC and it continues to
®
LINC and
Johnson Controls Unitary Products 3
514067-UAD-A-0509
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (2) AV 14 ACC_OVER_TME Accumulated Unoccupied Override Time
(in hours)
R (2) AV 15 ACTIVE_ALARM Active Alarm
R (5) BV 16 AIR_PROOF_SW Air Proving Switch Status (1=closed,
0=open/no air flow)
R/W (2) AV 79 OAQ_STPT 1000 0 5000 Air Quality Setpoint Outside
R (5) BV 85 ALARM_1_ON Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 86 ALARM_2_ON Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 87 ALARM_3_ON Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 88 ALARM_4_ON Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 89 ALARM_5_ON Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R (2) AV 33 BLDG_STATIC Building Static Pressure
R (5) BV 29 BP_SENS_INST Building Static Pressure Sensor Installed
R/W (2) AV 57 BLDG_SP_STPT 0.1 -0.25 0.25 Building Static Pressure Setpoint
R/W (2) AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint
(degrees F)
R (5) BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling
Enabled
R (5) BV 35 CVM_HEATING Comfort Ventilation Mode for Heating
Enabled
R (5) BV 33 COM_VENT_STA Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
R/W (2) AV 24 COM_V_HI_SP 80 60 85 Comfort Ventilation Upper Setpoint
(degrees F)
R (5) BV 23 COOLING_ENA Cooling Mode Enabled
R (5) BV 21 FAN_ON_W_SEN CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
R (2) AV 56 CV_VAV_SELEC CV/VAV Selected (0= Valid CV, 1=Valid
VAV, 2= Invalid Value)
R (2) AV 8 IAQ_VALUE Demand Ventilation (IAQ) Value (PPM)
R (5) BV 39 DEMAND_VENT Demand Ventilation (using Inside Sensor)
Enabled
R/W (2) AV 18 DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint
R (2) AV 67 REVISION xx Device Revision
R (5) BV 90 DF_SW_INST Dirty Filter Switch Installed
R (5) BV 15 DIRT_FILT_SW Dirty Filter Switch Status (0=open,1=closed/
fault)
R (2) AV 35 DUCT_STATIC Duct Static Pressure
R/W (2) AV 58 DUCT_SP_STPT 1.5 0 5 Duct Static Pressure Setpoint
R/W (2) AV 59 DUCT_SD_STPT 4.5 0 5 Duct Static Pressure Shutdown Setpoint
R (2) AV 31 ECO_DAMP_OUT Economizer Damper Output Status
(0-100%)
TABLE 2: POINTS LIST IN DESCRIPTION ORDER
4 Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint
R (5) BV 7 ECONO_INST Economizer Installed
R (5) BV 36 ECO_L_TO_SAT Economizer Loading to Control Supply Air
Temperature Enabled
R/W (2) AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position
R (5) BV 31 ECONO_STATUS Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
R/W (2) AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint
R/W (2) AV 23 ECON_OAT_ENA 55 40 80 Economizer Outside Air Temperature
Enable Setpoint
R/W (2) AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy Setpoint
R/W (2) AV 21 ECO_2ND_STPT 50 40 65 Economizer Second Stage Setpoint
R (2) AV 41 E_C1_ACM_HRS Elite Compressor #1 Accumulated Run
Time (in hours)
R (5) BV 42 E_COMP1_STAT Elite Compressor #1 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 45 E_C1_OVRLOAD Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 42 E_C2_ACM_HRS Elite Compressor #2 Accumulated Run
Time (in hours)
R (5) BV 46 E_COMP2_STAT Elite Compressor #2 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 49 E_C2_OVRLOAD Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 43 E_C3_ACM_HRS Elite Compressor #3 Accumulated Run
Time (in hours)
R (5) BV 51 E_COMP3_STAT Elite Compressor #3 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 54 E_C3_OVRLOAD Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 44 E_C4_ACM_HRS Elite Compressor #4 Accumulated Run
Time (in hours)
R (5) BV 55 E_COMP4_STAT Elite Compressor #4 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 58 E_C4_OVRLOAD Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 50 E_CFAN1_STAT Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 59 E_CFAN2_STAT Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 41 E_FAN_ OVER Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
R (5) BV 60 E_GAS_VLVE1 Elite Gas Valve #1 Input Status (1=ener-
gized, 0=not energized)
R (5) BV 62 E_GAS_VLVE2 Elite Gas Valve #2 Input Status (1=ener-
gized, 0=not energized)
R (5) BV 64 E_GAS_VLVE3 Elite Gas Valve #3 Input Status (1=ener-
gized, 0=not energized)
514067-UAD-A-0509
Johnson Controls Unitary Products 5
514067-UAD-A-0509
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 44 E_HPS1 Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 48 E_HPS2 Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 53 E_HPS3 Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 57 E_HPS4 Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (5) BV 40 E_IFAN_STAT Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 61 E_LIMIT_ 1 Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
R (5) BV 63 E_LIMIT_ 2 Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
R (5) BV 65 E_LIMIT_ 3 Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
R (5) BV 43 E_LPS1 Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 47 E_LPS2 Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 52 E_LPS3 Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 56 E_LPS4 Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (2) AV 32 EXH_DAMP_OUT Exhaust Damper Output Status (0-100%)
R (5) BV 30 EX_FAN_STAT Exhaust Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 10 EX_VFD_INST Exhaust VFD Installed
R (5) BV 32 FRECOOL_STAT Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
R (5) BV 68 HEAT_1_STAT H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
R (5) BV 69 HEAT_2_STAT H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
R (5) BV 70 HEAT_3_STAT H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)
R (2) AV 76 H1_ACCUM_HRS Heating #1 Accumulated Run Time
(in hours)
R (2) AV 77 H2_ACCUM_HRS Heating #2 Accumulated Run Time
(in hours)
R (2) AV 78 H3_ACCUM_HRS Heating #3 Accumulated Run Time
(in hours)
R (5) BV 25 HEATING_ENA Heating Mode Enabled
R/W (2) AV 27 HGR_HUM_STPT 50 0 100 Hot Gas Reheat Humidity Setpoint (percent
Humidity)
R (5) BV 18 HGR_STAT Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
R (2) AV 47 HGR_VLV_OUT Hot Gas Reheat Valve Output Status
(0-100%)
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
6 Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 66 E_FREEZE_ST Hot H2O Freeze Thermostat Switch #1
Input Status (1=closed, 0=open/fault)
R (2) AV 55 HW_VLV_OUT Hot Water Valve Output Status (0-100%)
R (5) BV 2 HYDRONC_HEAT Hydronic Heat Enabled
R (5) BV 3 HH_REVER_VLV Hydronic Heat Reverse Actuated Valve
Installed
R/W (2) AV 62 HYD_S1_SA_SP 120 80 180 Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)
R/W (2) AV 63 HYD_S2_SA_SP 150 80 180 Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)
R/W (2) AV 80 IO_DVNT_STPT 700 0 2000 Indoor/Outdoor Demand Ventilation
Setpoint
R (2) AV 45 I_C1_ACM_HRS Intelli-Comfort Compressor #1 Accumulated
Run Time (in hours)
R (5) BV 73 I_COMP1_STAT Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)
R (2) AV 46 I_C2_ACM_HRS Intelli-Comfort Compressor #2 Accumulated
Run Time (in hours)
R (5) BV 76 I_COMP2_STAT Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)
R (5) BV 79 I_CFAN_STAT Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 72 I_FAN_OVER Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)
R (5) BV 82 I_FREEZE_1 Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)
R (5) BV 83 I_FREEZE_2 Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)
R (5) BV 80 I_GAS_VLVE1 Intelli-Comfort Gas Valve #1 Input Status
R (5) BV 75 I_HPS1 Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed, 0=open/fault)
R (5) BV 78 I_HPS2 Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed, 0=open/fault)
R (5) BV 71 I_IFAN_STAT Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 81 I_LIMIT_1 Intelli-Comfort Limit Switch #1 Input Status
R (5) BV 74 I_LPS1 Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed, 0=open/fault)
R (5) BV 77 I_LPS2 Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed, 0=open/fault)
R (5) BV 28 INTELLI-STRT Intelli-Start Enabled
R/W (5) BV 13 LOADSHED Loadshed (0=clear loadshed, 1=set load-
shed operation)
R (5) BV 19 LOW_AMB_OVRD Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)
514067-UAD-A-0509
Johnson Controls Unitary Products 7
514067-UAD-A-0509
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 14 LOW_SUP_VOLT Low Supply Voltage (0=comps not overrid-
den by LSV, 1=comps overridden)
R/W (5) BV 96 MANUAL_WRITE Manual Write Command to ModlINC
R/W (2) AV 28 MAX_TH_OFSET 3 0 5 Max Temperature/Humidity Setpoint Offset
R/W (2) AV 30 MAX_DMV_ECON 50 0 100 Maximum Demand Ventillation Economizer
Position
R (5) BV 11 MODBUS_ALARM Modbus Communication Alarm
R (5) BV 9 MOD_EX_INST Modulating Exhaust Installed
R/W (2) AV 61 MWU_RAT_STPT 70 50 85 Morning Warm-Up and VAV Heating: Return
Air Temperature Setpoint (degrees F)
R (5) BV 6 MORN_WARM-UP Morning Warm-Up Enabled
R (2) AV 16 NUMBER_COMPS Number of Compressors Available
R (2) AV 48 NUMBER_HEAT Number of Heat Stages Available
R/W (2) AV 1 OCC_COOL_SP 72 45 99 Occupied Cooling Setpoint
R/W (5) BV 1 OCCUPIED_ENA Occupied Enabled
R/W (2) AV 50 OCC_HEAT_SP 68 45 99 Occupied Heating Setpoint
R (5) BV 93 OCC_COMS_ENA Occupied Thermostat or Communication
Input Enabled
R (2) AV 17 OP_COOL_STPT Operating Cooling Setpoint
R (2) AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint
R/W (2) AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differential
R/W (2) AV 74 OAT_COOL_L_O 45 0 100 Outdoor Air Temperature Cooling Lockout
Temperature
R/W (2) AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperature HeatingLockout
Temperature
R (2) AV 11 AMB_AIR_ENTH Outside Air Enthalpy
R (2) AV 10 AMB_AIR_HUM Outside Air Humidity
R (5) BV 37 OAH_SENSOR Outside Air Humidity Sensor Enabled
R (2) AV 7 AMB_TEMP Outside Air Temperature
R (2) AV 9 OAQ_VALUE 1000 0 5000 Outside Demand Ventilation (OAQ) Value
(PPM)
R (5) BV 8 PWR_EX_INST Power Exhaust Installed
R (5) BV 20 POP_ENABLED Pre-Occupancy Purge Enabled
R/W (2) AV 81 POP_HOURS 4 0 23 Pre-Occupancy Purge Time (hours)
R/W (2) AV 82 POP_MINUTES 0 0 59 Pre-Occupancy Purge Time (minutes)
R (5) BV 17 PURGE_SWITCH Purge Switch Status (0=open,1=closed)
R/W (5) BV 12 REDLINE Redline (0=clear redline, 1=set redline
operation)
R (5) BV 4 REM_CONT_ENA Remote Control Enabled
R (2) AV 13 RET_AIR_ENTH Return Air Enthalpy
R (2) AV 12 RET_AIR_HUM Return Air Humidity
R (2) AV 5 RET_AIR_TEMP Return Air Temperature
R (5) BV 38 RAH_SENSOR Return/Inside Air Humidity Sensor Enabled
R (2) AV 6 SPACE_TEMP Space (Indoor) Air Temperature
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
8 Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 71 SPCE_ALM_TMP 0 0 25 Space Sensor Alarm Temperature (degrees
F, 0 = disabled)
R/W (2) AV 72 SPCE_ALM_TIM 0 0 120 Space Sensor Alarm Time (minutes F, 0 =
disabled)
R (5) BV 26 SEN_FAULT_EN Space Sensor Fault Override (Construction
Mode) Enabled
R/W (2) AV 73 SP_OFF_RANGE 3 0 5 Space Temprature Sensor Offset Range
(0-5 degrees)
R (2) AV 4 SUP_AIR_TEMP Supply Air Temperature
R/W (2) AV 70 SAT_ALM_COOL 0 0 80 Supply Air Temperature Alarm Setpoint for
Cooling
R/W (2) AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for
Heating
R (5) BV 22 SAT_COOLING Supply Air Temperature Limit for Cooling
Enabled
R/W (2) AV 3 SAT_COOL_SP 50 40 65 Supply Air Temperature Limit for Cooling
Setpoint (degrees F)
R (5) BV 24 SAT_HEATING Supply Air Temperature Limit for Heating
Enabled
R/W (2) AV 52 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating
Setpoint (degrees F)
R (2) AV 34 SFAN_VFD_OUT Supply Fan VFD Output Status (0-100%)
R (2) AV 36 ALARM_1 System Alarm #1
R (2) AV 37 ALARM_2 System Alarm #2
R (2) AV 38 ALARM_3 System Alarm #3
R (2) AV 39 ALARM_4 System Alarm #4
R (2) AV 40 ALARM_5 System Alarm #5
R/W (2) AV 29 TH_OFFSET 5 1 10 Temperature/Humidity % Humidity that =
1°F of Offset
R/W (2) AV 26 TEM_HUM_STPT 50 20 80 Temperature/Humidity Setpoint (percent
Humidity)
R (5) BV 67 FAN_HEAT Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
R/W (2) AV 2 UNOC_COOL_SP 85 45 99 Un-Occupied Cooling Setpoint
R/W (2) AV 51 UNOC_HEAT_SP 60 45 99 Un-Occupied Heating Setpoint
R/W (2) AV 75 UNOC_OVR_TP 60 0 240 Unoccupied Override Time Period
R/W (2) AV 65 VAV_CL_LO_SP 55 40 70 VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)
R/W (2) AV 66 VAV_SAT_RSET 72 40 85 VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature)(degrees F)
R/W (2) AV 64 VAV_CL_HI_SP 60 40 70 VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)
R (5) BV 5 VAV_OCC_HEAT VAV Occupied Heating Enabled
R/W (2) AV 60 VAV_OHEAT_SP 68 40 85 VAV Occupied Heating Setpoint (degrees F)
514067-UAD-A-0509
Johnson Controls Unitary Products 9
514067-UAD-A-0509
Read/ Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 1 OCC_COOL_SP 72 45 99 Occupied Cooling Setpoint
R/W (2) AV 2 UNOC_COOL_SP 85 45 99 Un-Occupied Cooling Setpoint
R/W (2) AV 3 SAT_COOL_SP 50 40 65 Supply Air Temperature Limit for Cooling
Setpoint (degrees F)
R (2) AV 4 SUP_AIR_TEMP Supply Air Temperature
R (2) AV 5 RET_AIR_TEMP Return Air Temperature
R (2) AV 6 SPACE_TEMP Space (Indoor) Air Temperature
R (2) AV 7 AMB_TEMP Outside Air Temperature
R (2) AV 8 IAQ_VALUE Demand Ventilation (IAQ) Value (PPM)
R (2) AV 9 OAQ_VALUE 1000 0 5000 Outside Demand Ventilation (OAQ) Value
(PPM)
R (2) AV 10 AMB_AIR_HUM Outside Air Humidity
R (2) AV 11 AMB_AIR_ENTH Outside Air Enthalpy
R (2) AV 12 RET_AIR_HUM Return Air Humidity
R (2) AV 13 RET_AIR_ENTH Return Air Enthalpy
R (2) AV 14 ACC_OVER_TME Accumulated Unoccupied Override Time (in
hours)
R (2) AV 15 ACTIVE_ALARM Active Alarm
R (2) AV 16 NUMBER_COMPS Number of Compressors Available
R (2) AV 17 OP_COOL_STPT Operating Cooling Setpoint
R/W (2) AV 18 DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint
R/W (2) AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position
R/W (2) AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint
R/W (2) AV 21 ECO_2ND_STPT 50 40 65 Economizer Second Stage Setpoint
R/W (2) AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint
R/W (2) AV 23 ECON_OAT_ENA 55 40 80 Economizer Outside Air Temperature Enable
Setpoint
R/W (2) AV 24 COM_V_HI_SP 80 60 85
Comfort Ventilation Upper Setpoint (degrees F)
R/W (2) AV 25 COM_V_LOW_SP 70 60 85
Comfort Ventilation LowerSetpoint (degrees F)
R/W (2) AV 26 TEM_HUM_STPT 50 20 80 Temperature/Humidity Setpoint (percent
Humidity)
R/W (2) AV 27 HGR_HUM_STPT 50 0 100 Hot Gas Reheat Humidity Setpoint (percent
Humidity)
R/W (2) AV 28 MAX_TH_OFSET 3 0 5 Max Temperature/Humidity Setpoint Offset
R/W (2) AV 29 TH_OFFSET 5 1 10 Temperature/Humidity % Humidity that = 1°F
of Offset
R/W (2) AV 30 MAX_DMV_ECON 50 0 100 Maximum Demand Ventillation Economizer
Position
R (2) AV 31 ECO_DAMP_OUT Economizer Damper Output Status (0-100%)
R (2) AV 32 EXH_DAMP_OUT Exhaust Damper Output Status (0-100%)
R (2) AV 33 BLDG_STATIC Building Static Pressure
R (2) AV 34 SFAN_VFD_OUT Supply Fan VFD Output Status (0-100%)
R (2) AV 35 DUCT_STATIC Duct Static Pressure
R (2) AV 36 ALARM_1 System Alarm #1
R (2) AV 37 ALARM_2 System Alarm #2
TABLE 3: POINTS LIST IN OBJECT ORDER
10 Johnson Controls Unitary Products
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (2) AV 38 ALARM_3 System Alarm #3
R (2) AV 39 ALARM_4 System Alarm #4
R (2) AV 40 ALARM_5 System Alarm #5
R (2) AV 41 E_C1_ACM_HRS Elite Compressor #1 Accumulated Run Time
(in hours)
R (2) AV 42 E_C2_ACM_HRS Elite Compressor #2 Accumulated Run Time
(in hours)
R (2) AV 43 E_C3_ACM_HRS Elite Compressor #3 Accumulated Run Time
(in hours)
R (2) AV 44 E_C4_ACM_HRS Elite Compressor #4 Accumulated Run Time
(in hours)
R (2) AV 45 I_C1_ACM_HRS Intelli-Comfort Compressor #1 Accumulated
Run Time (in hours)
R (2) AV 46 I_C2_ACM_HRS Intelli-Comfort Compressor #2 Accumulated
Run Time (in hours)
R (2) AV 47 HGR_VLV_OUT Hot Gas Reheat Valve Output Status
(0-100%)
R (2) AV 48 NUMBER_HEAT Number of Heat Stages Available
R (2) AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint
R/W (2) AV 50 OCC_HEAT_SP 68 45 99 Occupied Heating Setpoint
R/W (2) AV 51 UNOC_HEAT_SP 60 45 99 Un-Occupied Heating Setpoint
R/W (2) AV 52 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating
Setpoint (degrees F)
R/W (2) AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for
Heating
R/W (2) AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperature HeatingLockout
Temperature
R (2) AV 55 HW_VLV_OUT Hot Water Valve Output Status (0-100%)
R (2) AV 56 CV_VAV_SELEC CV/VAV Selected (0= Valid CV, 1=Valid VAV,
2= Invalid Value)
R/W (2) AV 57 BLDG_SP_STPT 0.1 -0.25 0.25 Building Static Pressure Setpoint
R/W (2) AV 58 DUCT_SP_STPT 1.5 0 5 Duct Static Pressure Setpoint
R/W (2) AV 59 DUCT_SD_STPT 4.5 0 5 Duct Static Pressure Shutdown Setpoint
R/W (2) AV 60 VAV_OHEAT_SP 68 40 85 VAV Occupied Heating Setpoint (degrees F)
R/W (2) AV 61 MWU_RAT_STPT 70 50 85 Morning Warm-Up and VAV Heating: Return
Air Temperature Setpoint (degrees F)
R/W (2) AV 62 HYD_S1_SA_SP 120 80 180 Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)
R/W (2) AV 63 HYD_S2_SA_SP 150 80 180 Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)
R/W (2) AV 64 VAV_CL_HI_SP 60 40 70 VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)
R/W (2) AV 65 VAV_CL_LO_SP 55 40 70 VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)
R/W (2) AV 66 VAV_SAT_RSET 72 40 85 VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature) (degrees F)
R (2) AV 67 REVISION 0 0 xx Device Revision
514067-UAD-A-0509
Johnson Controls Unitary Products 11
514067-UAD-A-0509
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differential
R/W (2) AV 70 SAT_ALM_COOL 0 0 80 Supply Air Temperature Alarm Setpoint for
Cooling
R/W (2) AV 71 SPCE_ALM_TMP 0 0 25 Space Sensor Alarm Temperature
(degrees F, 0 = disabled)
R/W (2) AV 72 SPCE_ALM_TIM 0 0 120 Space Sensor Alarm Time (minutes F,
0 = disabled)
R/W (2) AV 73 SP_OFF_RANGE 3 0 5 Space Temprature Sensor Offset Range
(0-5 degrees)
R/W (2) AV 74 OAT_COOL_L_O 45 0 100 Outdoor Air Temperature Cooling Lockout
Temperature
R/W (2) AV 75 UNOC_OVR_TP 60 0 240 Unoccupied Override Time Period
R (2) AV 76 H1_ACCUM_HRS Heating #1 Accumulated Run Time (in hours)
R (2) AV 77 H2_ACCUM_HRS Heating #2 Accumulated Run Time (in hours)
R (2) AV 78 H3_ACCUM_HRS Heating #3 Accumulated Run Time (in hours)
R/W (2) AV 79 OAQ_STPT 1000 0 5000 Air Quality Setpoint Outside
R/W (2) AV 80 IO_DVNT_STPT 700 0 2000 Indoor/Outdoor Demand Ventilation Setpoint
R/W (2) AV 81 POP_HOURS 4 0 23 Pre-Occupancy Purge Time (hours)
R/W (2) AV 82 POP_MINUTES 0 0 59 Pre-Occupancy Purge Time (minutes)
R/W (2) AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy Setpoint
R/W (5) BV 1 OCCUPIED_ENA Occupied Enabled
R (5) BV 2 HYDRONC_HEAT Hydronic Heat Enabled
R (5) BV 3 HH_REVER_VLV Hydronic Heat Reverse Actuated Valve
Installed
R (5) BV 4 REM_CONT_ENA Remote Control Enabled
R (5) BV 5 VAV_OCC_HEAT VAV Occupied Heating Enabled
R (5) BV 6 MORN_WARM-UP Morning Warm-Up Enabled
R (5) BV 7 ECONO_INST Economizer Installed
R (5) BV 8 PWR_EX_INST Power Exhaust Installed
R (5) BV 9 MOD_EX_INST Modulating Exhaust Installed
R (5) BV 10 EX_VFD_INST Exhaust VFD Installed
R (5) BV 11 MODBUS_ALARM Modbus Communication Alarm
R/W (5) BV 12 REDLINE Redline (0=clear redline, 1=set redline
operation)
R/W (5) BV 13 LOADSHED Loadshed (0=clear loadshed, 1=set loadshed
operation)
R (5) BV 14 LOW_SUP_VOLT Low Supply Voltage (0=comps not
overridden by LSV, 1=comps overridden)
R (5) BV 15 DIRT_FILT_SW Dirty Filter Switch Status (0=open,1=closed/
fault)
R (5) BV 16 AIR_PROOF_SW Air Proving Switch Status (1=closed,
0=open/no air flow)
R (5) BV 17 PURGE_SWITCH Purge Switch Status (0=open,1=closed)
R (5) BV 18 HGR_STAT Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
12 Johnson Controls Unitary Products
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 19 LOW_AMB_OVRD Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)
R (5) BV 20 POP_ENABLED Pre-Occupancy Purge Enabled
R (5) BV 21 FAN_ON_W_SEN CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
R (5) BV 22 SAT_COOLING Supply Air Temperature Limit for Cooling
Enabled
R (5) BV 23 COOLING_ENA Cooling Mode Enabled
R (5) BV 24 SAT_HEATING Supply Air Temperature Limit for Heating
Enabled
R (5) BV 25 HEATING_ENA Heating Mode Enabled
R (5) BV 26 SEN_FAULT_EN Space Sensor Fault Override (Construction
Mode) Enabled
R (5) BV 28 INTELLI-STRT Intelli-Start Enabled
R (5) BV 29 BP_SENS_INST Building Static Pressure Sensor Installed
R (5) BV 30 EX_FAN_STAT Exhaust Fan Output Status (0=output is OFF,
1=output is ON)
R (5) BV 31 ECONO_STATUS Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
R (5) BV 32 FRECOOL_STAT Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
R (5) BV 33 COM_VENT_STA Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
R (5) BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling
Enabled
R (5) BV 35 CVM_HEATING Comfort Ventilation Mode for Heating
Enabled
R (5) BV 36 ECO_L_TO_SAT Economizer Loading to Control Supply Air
Temperature Enabled
R (5) BV 37 OAH_SENSOR Outside Air Humidity Sensor Enabled
R (5) BV 38 RAH_SENSOR Return/Inside Air Humidity Sensor Enabled
R (5) BV 39 DEMAND_VENT Demand Ventilation (using Inside Sensor)
Enabled
R (5) BV 40 E_IFAN_STAT Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 41 E_FAN_ OVER Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
R (5) BV 42 E_COMP1_STAT Elite Compressor #1 Output Status (0=output
is OFF, 1=output is ON)
R (5) BV 43 E_LPS1 Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 44 E_HPS1 Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 45 E_C1_OVRLOAD Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 46 E_COMP2_STAT Elite Compressor #2 Output Status (0=output
is OFF, 1=output is ON)
514067-UAD-A-0509
Johnson Controls Unitary Products 13
514067-UAD-A-0509
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 47 E_LPS2 Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 48 E_HPS2 Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 49 E_C2_OVRLOAD Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 50 E_CFAN1_STAT Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 51 E_COMP3_STAT Elite Compressor #3 Output Status (0=output
is OFF, 1=output is ON)
R (5) BV 52 E_LPS3 Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 53 E_HPS3 Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 54 E_C3_OVRLOAD Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 55 E_COMP4_STAT Elite Compressor #4 Output Status (0=output
is OFF, 1=output is ON)
R (5) BV 56 E_LPS4 Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (5) BV 57 E_HPS4 Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (5) BV 58 E_C4_OVRLOAD Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 59 E_CFAN2_STAT Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 60 E_GAS_VLVE1 Elite Gas Valve #1 Input Status
(1=energized, 0=not energized)
R (5) BV 61 E_LIMIT_ 1 Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
R (5) BV 62 E_GAS_VLVE2 Elite Gas Valve #2 Input Status
(1=energized, 0=not energized)
R (5) BV 63 E_LIMIT_ 2 Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
R (5) BV 64 E_GAS_VLVE3 Elite Gas Valve #3 Input Status
(1=energized, 0=not energized)
R (5) BV 65 E_LIMIT_ 3 Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
R (5) BV 66 E_FREEZE_ST Hot H2O Freeze Thermostat Switch #1 Input
Status (1=closed, 0=open/fault)
R (5) BV 67 FAN_HEAT Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
R (5) BV 68 HEAT_1_STAT H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
R (5) BV 69 HEAT_2_STAT H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
R (5) BV 70 HEAT_3_STAT H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
14 Johnson Controls Unitary Products
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 71 I_IFAN_STAT Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 72 I_FAN_OVER Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)
R (5) BV 73 I_COMP1_STAT Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)
R (5) BV 74 I_LPS1 Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed, 0=open/fault)
R (5) BV 75 I_HPS1 Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed, 0=open/fault)
R (5) BV 76 I_COMP2_STAT Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)
R (5) BV 77 I_LPS2 Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed, 0=open/fault)
R (5) BV 78 I_HPS2 Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed, 0=open/fault)
R (5) BV 79 I_CFAN_STAT Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 80 I_GAS_VLVE1 Intelli-Comfort Gas Valve #1 Input Status
R (5) BV 81 I_LIMIT_1 Intelli-Comfort Limit Switch #1 Input Status
R (5) BV 82 I_FREEZE_1 Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)
R (5) BV 83 I_FREEZE_2 Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)
R (5) BV 85 ALARM_1_ON Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 86 ALARM_2_ON Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 87 ALARM_3_ON Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 88 ALARM_4_ON Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 89 ALARM_5_ON Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 90 DF_SW_INST Dirty Filter Switch Installed
R (5) BV 93 OCC_COMS_ENA Occupied Thermostat or Communication
Input Enabled
R/W (5) BV 96 MANUAL_WRITE Manual Write Command to ModlINC
514067-UAD-A-0509
Johnson Controls Unitary Products 15
514067-UAD-A-0509

TROUBLESHOOTING

The Simplicity®LINC Gateway consists of two printed circuit boards.
TABLE 4: SIMPLICITY
The PWR LED should be on during operation. The RX and TX LEDs should flash when a signal is either received or sent.
If the PWR LED does not come on but the RX and TX flash, then the PWR LED is broken.
®
LINC GATEWAY
RS485 BOARD (Bottom) BacNET Board (Top)
Normal Board Operation Normal Board Operation
Faulty Board Operation Faulty Board Operation
LEDs LA and LB flash about once per second. LED GP105 will remain on within 45-60 seconds after power up, signifying normal operation. The PWR LED should be on during operation. The RX and TX LEDs should flash when a signal is either received or sent.
If the PWR LED does not come on but the RX and TX flash, then the PWR LED is broken.
If the TX and / or RX LEDs do not flash, it may represent a problem with the field wiring or configuration problems in the field side of the BacNET board. It may also indicate incorrect polling parameters such as baud rate or parity.
Power Source 24 ± 15% VAC (Obtained from the Roof Top Unit) Frequency 45 to 65 HZ Power Consumption Nominal >2 VA Operating Environment -40 to 160° F (-40 to 70° C) 10 to 95% non-condensing Size (H x W x D) 5.0 x 2.4 x 1.8 in. (128 x 61 x 45.75 cm) Weight 0.2 lb. (0.09 kg)
Type Microchip SDRAM Memory 2048 bytes FLASH Memory 1024 bytes w/1,000,000 write cycle capability
If the TX and / or RX LEDs do not flash, it may represent a problem with the field wiring or confguration problems in the field side of the BacNet board. It may also indicate incorrect polling parameters such as baud rate or parity.
If the PWR LED does not come on and LA and LB do not flash, call UP Tech Services at 1-877-874-7378.
If GP105 never comes on, call UP Tech Services at 1-877-874-7378.
General
Processor
Interface
Port 1 Type BACnet MS/TP Port 1 Speeds 9.6, 19.2, 38.4, 76.8 kbaud Port 1 Connector 3-pin screw terminals Port 2 Type Modbus RTU (RS485) Port 2 Speeds 9.6, 19,2 kbaud Port 2 Connector 6-pin screw terminals LAN Cable Screened Twisted-Pair (Belden 9272 or 89272) LEDs Controller Status; BACnet; Modbus Switch Selections MAC Address (1-99), Baud Rate
16 Johnson Controls Unitary Products
514067-UAD-A-0509
PWR
(RS485)
PWR
(BACnet)
GP105
(BACnet)
LB
(BACnet)
RX
(RS485)
TX
(RS485)
LA
(BACnet)
TX
(BACnet)
RX
(BACnet)
FIGURE 3: SIMPLICITY
®
LINC GATEWAY LED LOCATION
Johnson Controls Unitary Products 17
Subject to change without notice. Printed in U.S.A. 514067-UAD-A-0509 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing