Simplex XPS Installation Instructions Manual

XPS and XNAC Installation Instructions
Cautions, Warnings, and Regulatory Information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or an authorized agent of your local Simplex product supplier.
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times. FCC RULES AND REGULATIONS – PART 15. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with NFPA72® after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100 % tested. In addition, to ensure that other operations are not inadvertently affected, at least 10 % of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
Introduction
This publication describes the installation procedure for 4100-5101 (120 VAC), 4100-5102 (220 VAC/230 VAC/240 VAC), 4100-5103 (120 VAC with battery disconnect) Expansion Power Supplies (XPSs), and the 4100-5115 Expansion NAC Module (XNAC). This product is compatible with 4100U and 4100ES fire alarm controls units (FACUs).
Important: Verify FACU system programmer, executive, and slave software compatibility when installing, or replacing system components. Refer to the Technical Support Information and Downloads website for compatibility information.
Expansion Power Supply Modules
This publication describes the installation procedure for the following:
• 4100-5101 Expansion Power Supply (XPS), 120 VAC, 60 Hz
• 4100-5102 XPS, 220 VAC/230 VAC/240 VAC 50 Hz/60 Hz
• 4100-5103 XPS, 120 VAC, 60 Hz, with battery disconnect (Canada)
• 4100-5115 Expansion NAC Module (XNAC)
The XPS distributes added card power and signal power via the PDI. Signal power is available only in the bay in which the XPS is located. The source of card power is selected by jumpers P4 & P5 on the PDI.
The XPS includes three NACs, and may be expanded to 6 NACs with the 4100-5115. NACs are wired as Class B or Class A. All circuits are power limited in accordance with UL 864. The NACs support non-addressable TrueAlert and conventional reverse-polarity operation.
The notification appliance circuits on these modules can be used as regulated 24 VDC circuits, or special application circuits. When used as generic 24 VDC regulated circuits, only 4 Amps of current is available across the three circuits, and any 24 VDC appliance may be attached. When used as special applications NACs, the full 9 Amps of current is available at the three circuits and only the compatible appliances listed in Table 5 may be connect to these circuits. The SPS/RPS can synchronize compatible appliances across all three circuits when those circuits are used as special applications NACs.
The XPS has a 9 A capacity. Each NAC is rated at 3 A. A NAC can also be configured as an auxiliary power point, in which case it is rated at 2 A. The total load at 24 VDC must be no more than 9 A. The total load includes NACs (on the XPS or the XNAC Module), auxiliary power, card power, and signal power used by modules plugged into the same bay.
Note: If NACs are to be used as auxiliary outputs, they must be configured as such in the Panel Programmer. Programming may also be required for dedicated auxiliary outputs; refer to the ES Panel Programmer's Manual (574-849).
NACs are monitored for short and open circuits. If a short circuit occurs, the affected NAC will not be energized. A NAC mis-wiring test, which checks for NACs that are shorted together, can be initiated on command from the operator interface. AC power and battery backup are provided to the XPS through a connection to the PDM. Detection of an earth fault on XPS wiring is performed by the SPS, RPS or XBC. Detection is 10k ohm minimum. The 4100-5103 model is required in jurisdictions, such as Canada, where depleted battery conditions are required by local code to result in power-
down of the unit until AC power is restored. The system must also be programmed for depleted battery cutout for each power supply.
574-772 Rev. Q
XPS and XNAC Installation Instructions
The Expansion Power Supply (XPS)
XPS features
Figure 1 is an illustration of the XPS.
Figure 1: The Expansion Power Supply
LEDs
The XPS has the following LEDs:
LED1 (yellow)*. Illuminates when NAC 1 is active or in a trouble state; otherwise, it is off.
LED2 (yellow)*. Illuminates when NAC 2 is active or in a trouble state; otherwise, it is off.
LED3 (yellow)*. Illuminates when NAC 3 is active or in a trouble state; otherwise, it is off.
LED4 (green). Illuminates when the XPS is running off of AC power; otherwise, it is off.
LED5 (yellow). General status LED.
- On steady: overcurrent tripped.
- Single repeating flash: battery not connected.
LED6 (yellow). Illuminates when communication loss with the CPU occurs. Normally off.
*During initialization of the XPS, LEDs 1, 2, and 3 illuminate because the NACs are held in the isolate stage and create an open circuit trouble.
Input and output specifications
Table 1 summarizes the input and output specifications for the XPS.
Table 1: Input and output specifications
AC input specifications
4100-5102 220 VAC/230 VAC/240 VAC @ 50 Hz or 60 Hz 2 A Max 4100-5103 120 VAC @ 60 Hz, nominal, 4 A Max
DC output specifications
All XPSs Minimum: 19.5 VDC Maximum: 32 VDC Ripple: 2 VDC p-p @ full load (9 A)
Environmental operating range
The 4100U/4100ES modules are rated to operate at ambient temperatures from 32°F - 120°F (0°C-49°C). The 4100U/4100ES modules are rated for operation at 90°F (32°C), 93% RH (non-condensing).
page 2 574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 1. Mounting the XPS
Guideline
The XPS is normally mounted on the rightmost top and bottom positions of the PDI in a 4100 expansion cabinet. Before mounting the XPS, follow these guidelines:
• Disconnect power to the system or remove power at the breaker before mounting or installing any modules.
Mounting
Use Figure 2, and the following instructions to mount the XPS.
1. Insert the two tabs on the bottom of the XPS into the rightmost two slots in the cabinet.
2. Push the XPS assembly against the back of the expansion bay.
a. Connect to the PDI as shown in Figure 2. b. Correctly align the screw hole at the top of the XPS assembly with the hole in the bay chassis. c. Use one #6 torx screw to secure the assembly to the expansion box.
Note: When installing into the 4100-2301 expansion bay, the front door should be removed to avoid damage to the XPS.
Figure 2: XPS mounting
page 3 574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 2. XPS configuration
XPS configuration consists of setting the address switch as described in this section.
Setting the address
The XPS device address is set using DIP switch SW1, which is a bank of eight switches. From left to right, see Figure 3, these switches are designated as SW1-1 through SW1-8. The function of these switches is as follows:
SW1-1. This switch sets the baud rate for the internal 4100 communications line running between the card and the 4100 CPU. Set this switch to ON to communicate.
SW1-2 through SW1-8. These switches set the card's address within the 4100 FACU. See Figure 4 for a complete list of the switch settings for all of the possible card addresses.
Note: You must set these switches to the value assigned to the card by the Panel Programmer.
Figure 3: DIP switch SW1
page 4 574-772 Rev. Q
XPS and XNAC Installation Instructions
Figure 4: XPS card addresses
page 5 574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 3. Internal wiring
The XPS gets its power from the power distribution module or PDM (4100U and 4100ES only) or the power distribution terminal block (4100-2301 expansion bay only). The PDM or terminal block takes power directly from the AC mains and the two backup batteries, and distributes power to each bay in the cabinet.
Figure 5 shows the PDM in the 4100U/4100ES connecting to a host FACU with two XPSs.
Figure 5: System Power
The instructions in this section describe how to connect the XPS to AC mains and batteries in both regular 4100U/4100ES back boxes and the 4100-2301 expansion bay (for for non-4100U/4100ES back boxes).
page 6 574-772 Rev. Q
XPS and XNAC Installation Instructions
Power distribution module connections
The power distribution module (PDM) connects to the SPS, RPS, or XPS in each bay. One PDM is used for each back box. Use the following instructions to properly connect the PDM to each bay.
1. Route the black and white AC power wires to the supplied ferrite bead. Loop the wires twice through the bead as shown in Figure 6.
Figure 6: Loop wires through bead as shown
2. Wire 120 VAC/220 VAC/230 VAC/240 VAC to the PDM, keeping AC wires at least 1 in. away from all other wires. AC power must stay in the right side of the cabinet, in the non-power-limited area.
3. Connect batteries to P5 on the PDM using harness 734-015.
4. Connect the 734-012 harness (734-013 for 220 V/230 V/240 V versions) from the next connector on the PDM to the first XPS.
a. Connect the separate red and black wires (with yellow female terminations) to plugs P4 (black) and P5 (red) on the XPS. b. Connect the white and black wires, which terminate together in a white snap-on connector, to the connector at the bottom of the XPS
assembly, as shown in Figure 7. The black wire must be closer to the wall at the XPS connection point.
5. Repeat step 4 for the second XPS, if applicable.
1.
Figure 7: XPS/PDM connection
page 7 574-772 Rev. Q
XPS and XNAC Installation Instructions
4100-2301 expansion bay wiring
If the XPS is being installed in a 4100-2301 expansion bay (for non-4100U/4100ES 2975-91xx Back Boxes):
1. For DC wiring, connect the battery block (635-852) to the XPS using harness 734-050. Feed red and black wires through the side rail to the front of the XPS to prevent wire damage when the front panel is lowered. Connect the separate red and black wires (with yellow female terminations) to plugs P4 (black) and P5 (red) on the XPS.
2. For AC wiring, connect the white and black wires (harness 734-049) from the 120 V and NEUT terminal blocks to the connector at the bottom of the XPS assembly, keeping AC wires at least 1 in. away from all other wires. AC power must be kept to the right side of the cabinet, in the non­power-limited area. The black wire must be closer to the wall at the XPS connection point.
Figure 8: XPS connection when mounted in a 4100 style box
page 8 574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 4. XPS field wiring
The XPS provides three outputs for reverse-polarity notification appliance circuits. This section describes basic NAC wiring from the XPS to 4100­compatible appliances.
NAC wiring styles
The XPS supports both Class A and Class B NAC wiring. Class A wiring provides a circuit path XPS in the event of a single open circuit somewhere in the loop. Class A wiring requires that two wires are routed
from the XPS to each appliance, and then back again to the XPS.
Class A NAC wiring table
Table 2 lists the maximum distances from the XPS to the last appliance in a Class A configuration, depending on wire gauge and current. Use Table 2 to calculate wire distances for your application if you are using Class A wiring.
Table 2: Class A wiring distances
Alarm current @ 24 V
0.25 A 420 ft (128 m) 667 ft (203 m) 1,063 ft (324 m) 1,691 ft (515 m) 6 ohm
0.50 A 210 ft (64 m) 334 ft (102 m) 532 ft (162 m) 845 ft (258 m) 3 ohm
0.75 A 140 ft (43 m) 222 ft (68 m) 354 ft (108 m) 564 ft (172 m) 2 ohm
1 A 105 ft (32 m) 167 ft (51 m) 266 ft (81 m) 423 ft (129 m) 1.5 ohm
1.25 A 84 ft (26 m) 133 ft (41 m) 213 ft (65 m) 338 ft (103 m) 1.2 ohm
1.50 A 70 ft (21 m) 111 ft (34 m) 177 ft (54 m) 282 ft (86 m) 1 ohm
1.75 A 60 ft (18 m) 95 ft (29 m) 152 ft (46 m) 242 ft (74 m) 0.86 ohm
2 A 53 ft (16 m) 83 ft (25 m) 133 ft (41 m) 211 ft (64 m) 0.75 ohm
2.25 A 47 ft (14 m) 74 ft (23 m) 118 ft (36 m) 188 ft (57 m) 0.67 ohm
2.50 A 42 ft (13 m) 67 ft (20 m) 106 ft (32 m) 169 ft (51 m) 0.60 ohm
2.75 A 38 ft (12 m) 61 ft (19 m) 97 ft (30 m) 154 ft (47 m) 0.55 ohm
3 A 35 ft (11 m) 56 ft (17 m) 89 ft (27 m) 141 ft (43 m) 0.50 ohm
Note:
• Max. distance = distance from XPS to last appliance.
• This table is calculated at 50°C (120°F). If you are installing in locations that could be exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output voltage.
• If CI wire is used instead of housing cable in a fire rated enclosure, reduce wiring distances by 38 ft (12 m) for every 10 ft (3 m) of potential exposure.
• If Wheelock appliances employing EZ Mount SNAP bases are used, reduce the wiring distance and wiring resistance by:
- 12 gauge wire: 3.5 ft for each appliance, 0.0125 ohm for each appliance
- 14 gauge wire: 2.2 ft for each appliance, 0.0125 ohm for each appliance
- 16 gauge wire: 1.4 ft for each appliance, 0.0125 ohm for each appliance
- 18 gauge wire: 0.9 ft for each appliance, 0.0125 ohm for each appliance
Max. distance w/ 18 AWG (0.8231 mm²)
Max. distance w/ 16 AWG (1.309 mm²)
Max. distance w/ 14 AWG (2.081 mm²)
Max. distance w/ 12 AWG (3.309 mm²)
DC resistance
page 9 574-772 Rev. Q
XPS and XNAC Installation Instructions
Class B NAC wiring table
Table 3 lists the maximum distances from the XPS to the last appliance in a Class B configuration, depending on wire gauge and current. Use Table 3 to calculate wire distances for your application if you are using Class B wiring.
Table 3: Class B wiring distances
Alarm current @ 24 V
0.25 A 840 ft (256 m) 1,335 ft (407 m) 2,126 ft (648 m) 3,382 ft (1,031 m) 12 ohm
0.50 A 420 ft (128 m) 667 ft (203 m) 1,063 ft (324 m) 1,691 ft (515 m) 6 ohm
0.75 A 280 ft (85 m) 445 ft (136 m) 709 ft (216 m) 1,127 ft (344 m) 4 ohm 1 A 210 ft (64 m) 334 ft (102 m) 532 ft (162 m) 845 ft (258 m) 3 ohm
1.25 A 168 ft (51 m) 267 ft (81 m) 425 ft (130 m) 676 ft (206 m) 2.4 ohm
1.50 A 140 ft (43 m) 222 ft (68 m) 354 ft (108 m) 564 ft (172 m) 2 ohm
1.75 A 120 ft (37 m) 191 ft (58 m) 304 ft (93 m) 483 ft (147 m) 1.71 ohm 2 A 105 ft (32 m) 167 ft (51 m) 266 ft (81 m) 423 ft (129 m) 1.5 ohm
2.25 A 93 ft (28 m) 148 ft (45 m) 236 ft (72 m) 376 ft (115 m) 1.33 ohm
2.50 A 84 ft (26 m) 133 ft (41 m) 213 ft (65 m) 338 ft (103 m) 1.2 ohm
2.75 A 76 ft (23 m) 121 ft (37 m) 193 ft (59 m) 307 ft (94 m) 1.09 ohm 3 A 70 ft (21 m) 111 ft (34 m) 177 ft (54 m) 282 ft (86 m) 1 ohm
Note:
• Max. distance = distance from XPS to last appliance.
• This table is calculated at 50°C (120°F). If you are installing in locations that could be exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output voltage.
• If CI wire is used instead of housing cable in a fire rated enclosure, reduce wiring distances by 38 ft (12 m) for every 10 ft (3 m) of potential exposure.
Max. distance w/ 18 AWG (0.8231 mm²)
Max. distance w/ 16 AWG (1.309 mm²)
Max. distance w/ 14 AWG (2.081 mm²)
Max. distance w/ 12 AWG (3.309 mm²)
DC resistance
Guidelines
• All wiring is 18 AWG (0.8231 mm²) (minimum) to 12 AWG (3.309 mm²) (maximum).
• All wiring is supervised and power-limited.
• The maximum alarm current is 3 A for each circuit. The supervisory current is 2.03 mA at 24 VDC.
• The nominal voltage rating is 24 VDC, 2 V p-p ripple (maximum).
• The total available current from the XPS is 9 A, unless it is used for REGULATED 24 VDC notification appliances, where the XPS is rated for 4 Amps notification current, and 1 Amp for other uses. Total available auxiliary power current is 5 A (1 Amp for REG 24), and rated at 2 A for each circuit. Current used for card power by modules plugged into the PDI, as well as any auxiliary 24 VDC current, must be deducted from the total 9 A available current.
• All wiring that leaves the building requires over-voltage protection. Install module 2081-9044 (3 A) or 2081-9028 (1/4 A) inside a UL-Listed electrical box wherever wire enters or exits the building. When using the 2081-9044, the maximum alarm current is reduced to 1/4 A for that part of the circuit downstream of the module.
• Terminal designations + and - are for the alarm state.
• Compatible appliances for NACs are listed in Table 4.
• A maximum of 70 appliances can be supported for each circuit. If you are using 49CMT or 49CMTV series appliances, note that each of these appliances counts as five units, therefore no more than 13 49CMT or 49CMTV series appliances may be placed on one circuit.
• For CE compliant systems, use the ferrite beads as shown in each figure. Loop wires once through the ferrite beads as shown in Figure 9. 4100-5129 includes three ferrite beads, order as needed.
Figure 9: Loop wires as shown.
Auxiliary power only: In order to connect a circuit using power-limited wiring, the devices being powered must all be addressable, or a UL­Listed EOL relay must be used to supervise the circuit. See Figure 10 for wiring directions for the EOL relay.
Note: The 2098-9739 Relay is used as an example. Other UL-Listed EOL relays can be used, depending on the application.
page 10 574-772 Rev. Q
XPS and XNAC Installation Instructions
Figure 10: The EOL relay
Figure reference: *2098-9739
• The notification appliance circuits on the XPS are rated for special application and for regulated 24 VDC operation in accordance with UL864, 9th Edition.
• When used with the notification appliances listed in Table 4 or Table 5, each NAC is rated for 3 A, and total XPS capacity is rated at 9 A. This rating is the UL864 special application rating. Appliances listed in Table 4 and Table 5 are synchronized in accordance with UL864, between all NACs on the XPS, and any NACs on an SPS, RPS or XPS within the same 4100U/4100ES system, but not if appliances are mixed from both tables. Appliances from Table 4 will be 1/2 second out of audible sync with appliances from Table 4 in the same system. All appliances any given SPS, RPS or XPS must be from either Table 4 or Table 5, mixing of appliances from both tables is not possible within a power supply.
• For use with notification appliances not listed in Table 4 or Table 5, each circuit is rated for 2 A maximum, with a total notification appliance load of 4A for each XPS. This rating is the UL 864 regulated 24 VDC rating. Synchronization of strobes and other appliances requires use of the associated, listed, compatible synchronization module. Consult supplier of notification appliances for synchronization limits and details.
• Non-pulsing, linear-type notification appliances, such as horns or bells may be used up to the full rating (3 A/NAC, 9 A total for the XPS).
• If Wheelock appliances employing EZ Mount SNAP bases are used, reduce the wiring distance and wiring resistance by: 12 gauge wire: 7.0 ft for each appliance, 0.025 ohm for each appliance 14 gauge wire: 4.4 ft for each appliance, 0.025 ohm for each appliance 16 gauge wire: 2.8 ft for each appliance, 0.025 ohm for each appliance 18 gauge wire: 1.8 ft for each appliance, 0.025 ohm for each appliance
page 11 574-772 Rev. Q
XPS and XNAC Installation Instructions
Class A NAC wiring
To connect the XPS to appliances using Class A wiring, read the following instructions and refer to Figure 11.
1. Route wire (between 12 [3.309 mm²] and 18 AWG [0.8231 mm²]) from the B+ and B- outputs on TB1 of the XPS to the appropriate inputs on a peripheral notification appliance. Use NAC1, NAC2, or NAC3.
2. Route wire from the first appliance to the next one. Repeat for each appliance.
3. Route wire from the last appliance to the A+ and A- inputs on the same NAC circuit of TB1 of the XPS.
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the 10k, factory-installed, 1/2 W, brown/black/orange resistor (378-030) on each unused circuit. The circuit must connect B+ to B- terminals. No external end-of-line resistor is needed for circuits in use.
Figure 11: Class A wiring
Note: * Ferrite beads required for CE compliance. Use kit 4100-5129.
page 12 574-772 Rev. Q
XPS and XNAC Installation Instructions
Class B NAC wiring
To connect the XPS to appliances using Class B wiring, read the following instructions and refer to Figure 12.
1. Use NAC1, NAC2, or NAC3 to route wire (between 12 [3.309 mm²] and 18 AWG [0.8231 mm²]) from B+ and B- on the XPS to the first appliance.
2. Route wire to the next appliance as shown in the figure. Repeat for each appliance.
3. Route wire from the last appliance to the EOLR harness (10k ohm, 1/2 W: P/N 733-894, PID# 4081-9008).
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the 10k, 1/2 W, brown/black/orange resistor (378-030) on each unused circuit. The circuit must connect B+ to B- terminals.
Figure 12: Class B wiring
Note: * Ferrite beads required for CE compliance. Use kit 4100-5129.
page 13 574-772 Rev. Q
XPS and XNAC Installation Instructions
Auxiliary power wiring
The XPS can receive auxiliary power appliances via the dedicated auxiliary power tap (TB2). If additional power is needed, any of the three NAC outputs can be used as auxiliary power inputs.
Figure 13, shows how the XPS should be wired for auxiliary power at any given terminal.
• All wiring is 18 AWG (0.8231 mm²) (minimum) to 12 AWG (3.309 mm²) (maximum).
• All wiring is power-limited.
• Auxiliary power may be taken from the dedicated auxiliary power tap or from an unused NAC.
• If auxiliary power is taken from NAC terminals, the NAC must be configured as an auxiliary power point type in the panel programmer.
• Programming may be required for dedicated auxiliary outputs.
• Remove end-of-line resistors from circuits used for auxiliary power.
• External wiring is not supervised unless an end-of-line relay is wired coil to auxiliary power, and normally open contacts are monitored by a system power point. Relay current must be considered as part of the load.
• All wiring that leaves the building requires over-voltage protection. Install module 2081-9044 (3 A) or 2081-9028 (1/4 A) inside a UL Listed electrical box wherever wire enters or exits the building. A maximum of four 2081-9044 modules may be connected to one channel. When using the 2081-9044, the maximum alarm current is reduced to 1/4 A for that part of the circuit downstream of the module.
• CE compliant systems require ferrite beads. Use kit 4100-5129.
• All auxiliary power taps are rated at 2 A. The total auxiliary power current available is 5 A. The overall total current available is 9 A, including NAC, auxiliary, and card power. Current used for card power by modules plugged into the PDI, and an current from aux. 24 V, must be deducted from the 9 A available current.
• Voltage rating: 24 VDC (nominal), 2 V P-P ripple (maximum). The following devices connect to 2 A aux power:
- 2088-series relays and door holders
- 2098-series four-wire smoke detectors
- 2190-series monitor and signal ZAMs
- 4090-series IDNet ZAMs
- 4098-series four-wire smoke detectors and duct detectors
- Printer
- 4190-9050
- 4190-9051 4-20 mA ZAMs
- LCD Annunciator
• Resettable 24 V is obtained from any aux power point by programming the point as type resettable 24 V. Refer to the programming manual for details.
Figure 13: Auxiliary power wiring
** 4090-9117 IDNet Power Isolator
page 14 574-772 Rev. Q
* See Figure 14
XPS and XNAC Installation Instructions
Step 5. Installing the XNAC
The 4100-5115 Expansion NAC Module (XNAC) is an option board that provides three NACs in addition to the three NACs already on the XPS. The XNAC plugs onto the XPS.
If you are not installing an XNAC, skip this section and continue on to
The XNAC
The XNAC has three NACs, each rated at 3 A. As on the XPS, there is one status LED for each NAC.
Mounting the XNAC
The XNAC mounts to the top of the XPS as shown in the instructions and Figure 14.
Note: The XNAC cannot be installed on an XPS that is mounted to a 4100-2301 expansion bay that is used in a non-4100U/4100ES back box (a back box with PID series 2975-91xx).
Step 6. Troubleshooting.
Figure 14: Mounting the XNAC
1. Insert plastic standoffs (202-078) and a metal standoff (202-077) to the XPS as shown in Figure 14.
2. Plug J1 on the XNAC into P3 on the XPS using a header (166-549). The holes on the edges of the XNAC should be aligned with the tops of the standoffs.
3. Secure the XNAC to the standoffs using four screws.
4. Connect the XNAC's signal power harness to P1 on the XPS.
Wiring the XNAC
The XNAC uses the same wiring rules as TB1 on the XPS. Refer to XNAC cannot be used for auxiliary power.
Step 4. XPS field wiring to wire the XNAC to notification appliances. Note that the
page 15 574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 6. Troubleshooting
This section describes the messages that may appear on the 4100 display when using the XPS. Trouble messages appear on the left as titles, and possible causes are listed to the right in the text.
No Communications with Master
For communications to work, the XPS requires a 0 V connection to the PDM. Be sure to attach a fast-on connector to the PC board and also ensure that the fuse in the black battery lead is intact.
AC Power Loss
Voltage has fallen below an acceptable level. A problem may exist in the wiring, in the power distribution module, or into dedicated AC power.
Battery Not Connected/ Battery Depleted
The battery is not connected or is depleted. The precise status of the battery is given by the SPS. These modules report Low Battery. This trouble is merely to indicate a wiring problem to the XPS (blown fuse, not connected, etc.).
Expansion NAC Card Configuration Mismatch
Either the XNAC card is missing even though the XPS was configured to have one, or there is an un-configured XNAC card physically installed.
NAC Miswired Trouble
This trouble is active when a NAC-to-NAC short is detected. The NACs that are shorted are also indicated. Any combination of NACs 1 through 6 can be mis-wired together. The panel displays up to 4 mis-wiring faults.
Connecting additional power to motherboards
The XPS can be used to supply motherboards with an additional 24 V. Use Figure 15 to connect 24 V from the XPS to motherboards in the system.
Figure 15: Additional 24 V power wiring
page 16 574-772 Rev. Q
XPS and XNAC Installation Instructions
NAC-compatible notification appliances and accessories
Table 4: Special application NAC-compatible notification appliancess & accessories
P/N Description
4904-9168 V/O 15CD RED FREE-RUN TNA 4904-9171 V/O 15CD WHITE FREE-RUN TNA 4904-9176 V/O 24VDC 15CD RED VER F/S 4904-9177 V/O 24VDC 15CD WHT VER F/S 4904-9178 V/O 24VDC 15CD RED HORIZ F/S 4904-9183 V/O 24VDC 15CD RED CEIL F/S 4904-9331 V/O 15CD RED SYNC TNA 4904-9342 V/O 15CD WHITE SYNC TNA 4904-9345 V/O 24VDC 15CD WHT PLAIN F/S 4904-9174 V/O 24VDC 30CD RED VER F/S 4904-9180 V/O 24VDC 30CD RED HORIZ F/S 4904-9184 V/O 24VDC 30CD RED CEIL F/S 4904-9346 V/O 24VDC 30CD WHT PLAIN F/S 4904-9169 V/O 75CD RED FREE-RUN TNA 4904-9172 V/O 75CD WHITE FREE-RUN TNA 4904-9332 V/O 75CD RED SYNC TNA 4904-9343 V/O 75CD WHITE SYNC TNA 4904-9170 V/O 110CD RED FREE-RUN TNA 4904-9173 V/O 110CD WHITE FREE-RUN TNA 4904-9175 V/O 24VDC 110CD RED VER F/S 4904-9181 V/O 24VDC 110CD WHT VER F/S 4904-9182 V/O 24VDC 110CD RED HOR F/S 4904-9185 V/O 24VDC 110CD RED CEIL F/S 4904-9333 V/O 110CD RED SYNC TNA 4904-9344 V/O 110CD WHITE SYNC TNA 4906-9101 V/O 15/30/75/110cd W/M RED TNA 4906-9103 V/O 15/30/75/110cd W/M WHT TNA 4906-9102 V/O 15/30/75/110cd C/M RED TNA 4906-9104 V/O 15/30/75/110cd C/M WHT TNA 4906-9105 V/O WEATHERPROOF W/M RED 4906-9106 V/O WEATHERPROOF W/M WHT 4906-9109 HiCandela W/M V/O, RED 4906-9110 HiCandela C/M V/O, WHITE 4906-9111 HiCandela W/M V/O, WHITE 4906-9112 HiCandela C/M V/O, RED 4906-9113 V/O WEATHERPROOF W/M (CAN) RED 4903-9356 S/V 15CD RED 25/70V TNA 4903-9359 S/V 15CD WHITE 25/70V TNA 4903-9150 S/V 24VDC 15CD RED HORIZ F/S 4903-9153 S/V 24VDC 15CD RED VER F/S 4903-9193 S/V 24VDC 15CD WHT HORIZ F/S 4903-9196 S/V15CD RND 4903-9148 S/V 24VDC 30CD RED HORIZ F/S 4903-9194 S/V 24VDC 30CD WHT HORIZ F/S 4903-9197 S/V, 30CD, RND TNA 4903-9357 S/V 75CD RED 25/70V TNA 4903-9360 S/V 75CD WHITE 25/70V TNA 4903-9358 S/V 110CD RED 25/70V TNA 4903-9361 S/V 110CD WHITE 25/70V TNA 4903-9198 S/V 110CD, RND TNA 4906-9151 S/V 15/30/75/110cd W/M RED TNA 4906-9153 S/V 15/30/75/110cd W/M WHT TNA 4906-9154 S/V 15/30/75/110cd C/M WHT TNA 4901-9820 HORN 24VDC RED TNA 4901-9822 HORN 24VDC RED 4009-9201 NAC EXTENDER 120VAC, IDNET 4009-9301 NAC EXTENDER, 240VAC, IDNET 4009-9401 4009 T/A ADDR CONTROLLER
page 17 574-772 Rev. Q
Table 4: Special application NAC-compatible notification appliancess & accessories
P/N Description
4903-9252 A/V 24VDC 15CD RED HOR F/S 4903-9253 A/V 24VDC 30CD RED HOR F/S 4903-9254 A/V 24V 110CD RED HOR F/S 4903-9255 A/V 24VDC 15CD RED VER F/S 4903-9256 A/V 24V 110CD RED VER F/S 4903-9257 A/V 24VDC 15CD WHT HOR F/S 4903-9258 A/V 24VDC 30CD WHT HOR F/S 4903-9417 A/V 15CD RED SYNC TNA 4903-9418 A/V 75CD RED SYNC TNA 4903-9419 A/V 110CD RED SYNC TNA 4903-9425 A/V 15CD RED STD TNA 4903-9426 A/V 75CD RED STD TNA 4903-9427 A/V 110CD RED STD TNA 4903-9428 A/V 15CD WHITE SYNC TNA 4903-9429 A/V 75CD WHITE SYNC TNA 4903-9430 A/V 110CD WHITE SYNC TNA 4903-9431 A/V 15CD WHITE STD TNA 4903-9432 A/V 75CD WHITE STD TNA 4903-9433 A/V 110CD WHITE STD TNA 4906-9127 A/V 15/30/75/110cd W/M RED 4906-9129 A/V 15/30/75/110cd W/M WHT 4906-9128 A/V 15/30/75/110cd C/M RED 4906-9130 A/V 15/30/75/110cd C/M WHT 4906-9131 A/V WEATHERPROOF W/M RED 4906-9132 A/V WEATHERPROOF W/M WHT 4906-9139 HiCandela W/M A/V, RED 4906-9140 HiCandela C/M A/V, RED 4906-9141 HiCandela W/M A/V, WHITE 4906-9142 HiCandela C/M A/V, WHITE 4906-9143 A/V WEATHERPROOF W/M (CAN) RED 4905-9815 SMARTSYNC ADAPTER, TNA 4905-9938 SMARTSYNC CTL MODULE 4090-9005 SRP 4090-9006 SRP w/ENCLOSURE 49CMT-APPLW MT HORN 49CMT-WRF MT HORN 49CMT-WRF-BA MT HORN 49CMT-WWF MT HORN 49CMT-WWF-BA MT HORN 49CMTV-APPLW MT HORN/STROBE 49CMTV-WRF MT HORN/STROBE 49CMTV-WRF-BA MT HORN/STROBE 49CMTV-WWF MT HORN/STROBE 49CMTV-WWF-BA 4098-9772 4098-9773
MT HORN/STROBE SENSOR BASE WITH 520 Hz SOUNDER CO SENSOR BASE WITH 520 Hz SOUNDER
XPS and XNAC Installation Instructions
page 18 574-772 Rev. Q
XPS and XNAC Installation Instructions
Cooper Wheelock appliances
Table 5: Cooper Wheelock appliances
Compatible with 4100U/4100ES XPS Wheelock protocol for special applications Synchronizing horn strobes
AS-241575W AS Series Horn Strobe. 24V, 15/75Cd, Wall Mount AS-24MCW AS Series Horn Strobe. 24V, Multi-Cd, Wall Mount AS-24MCC AS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount AS-24MCWH AS Series Horn Strobe. 24V, Multi-High-Cd, Wall Mount AS-24MCCH AS Series Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount ASWP-2475W, ASWP-2475C AS Series WP Horn Strobe. 24V, 30Cd, Wall or Ceiling Mount ASWP-24MCWH AS Series WP Horn Strobe. 24V, Multi-High-Cd, Wall Mount ASWP-24MCCH AS Series WP Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount ASA-24MCW, ASB-24MCW AS Series Horn Strobe. 24V, Multi-Cd, Wall Mount. Amber/Blue ASA-24MCC, ASB-24MCC AS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount. Amber/Blue HS4-241575W HS4 Series Horn Strobe. 24V, 15/75Cd, Wall Mount HS4-24MCW HS4 Series Horn Strobe. 24V, Multi-Cd, Wall Mount HS4-24MCWH HS4 Series Horn Strobe. 24V, Multi-High-Cd, Wall Mount HS4-24MCC HS4 Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount HSR HN STR, Red, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount HSW HN STR, White, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount HSRS HN STR, Silver Red, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount HSWS HN STR, Silver White, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount HSRC HN STR, Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount HSWC HN STR, White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount HSRCS HN STR, Silver Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount HSWCS HN STR, Silver White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount NS-241575W NS Series Horn Strobe. 24V, 15/75Cd, Wall Mount NS-24MCW NS Series Horn Strobe. 24V, Multi-Cd, Wall Mount NS-24MCC NS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount NS-24MCCH NS Series Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount ZNS-MCW ZNS Series Horn Strobe. 24V, Multi-Cd, Wall Mount ZNS-MCWH ZNS Series Horn Strobe. 24V, Multi-High-Cd, Wall Mount ZNS-24MCC ZNS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount ZNS-24MCCH ZNS Series Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount
Synchronizing strobes
RSS-241575W RSS Series Strobe. 24V, 15/75Cd, Wall Mount RSSP-241575W RSSP Series Strobe. 12V or 24V, 15/75Cd, Wall Mount RSS-24MCW, RSSP-24MCW RSS/RSSP Series Strobe. 24V, Multi-Cd, Wall Mount RSS-24MCWH, RSSP-24MCWH RSS/RSSP Series Strobe. 24V, Multi-High-Cd, Wall Mount RSS-24MCC, RSS-24MCCR RSS Series Strobe. 24V, Multi-Cd, Ceiling Mount (R=Round) RSS-24MCCH, RSS-24MCCHR RSS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount (R=Round) RSSR-2415W, RSSR-2415C RSS Series Strobe. 24V, 15Cd, Red, Wall or Ceiling Mount RSSR-2475W, RSSR-2475C RSS Series Strobe. 24V, 75Cd, Red, Wall or Ceiling Mount RSSR-24110C RSS Series Strobe. 24V, 110Cd, Red, Ceiling Mount RSSA-24110W, RSSB-24110W, — RSSG-24110W, RSSR-24110W RSS Series Strobe. 24V, 110Cd, Wall Mount. Amber/Blue/Green/Red. RSSA-24MCC, RSSB-24MCC, — RSSG-24MCC, RSSR-24MCC RSS Series Strobe. 24V, Multi-Cd, Ceiling Mount. Amber/Blue/Green/Red. RSSA-24MCCH, RSSB-24MCCH, — RSSG-24MCCH, RSSR-24MCCH RSS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount. Amber/Blue/Green/Red. RSSPA-24MCC RSSP Series Strobe. 24V, Multi-Cd, Ceiling Mount. Amber RSSWPA-2475W RSS Series WP Strobe. 24V, Wall Mount. Amber RSSWPA-24MCCH, — RSSWPB-24MCCH, — RSSWPG-24MCCH, — RSSWPR-24MCCH RSS Series WP Strobe. 24V, Multi-High-Cd, Ceiling Mount. Amber/Blue/Green/Red. RSSWP-2475W, RSSWP-2475C RSS Series WP Strobe. 24V, 30Cd, Wall or Ceiling Mount RSSWP-24MCWH RSS Series WP Strobe. 24V, Multi-High-Cd, Wall Mount RSSWP-24MCCH RSS Series WP Strobe. 24V, Multi-High-Cd, Ceiling Mount STR STR, Red, 2-Wire, Wall 12/24V, 8Cd, 5 Mount STW STR, White, 2-Wire, Wall 12/24V, 8Cd, 5 Mount
page 19 574-772 Rev. Q
XPS and XNAC Installation Instructions
Table 5: Cooper Wheelock appliances
Compatible with 4100U/4100ES XPS Wheelock protocol for special applications
STRS STR, Silver Red, 2-Wire, Wall 12/24V, 8Cd, 5 Mount STWS STR, Silver White, 2-Wire, Wall 12/24V, 8Cd, 5 Mount STRC STR, Red, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount STWC STR, White, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount STRCS STR, Silver Red, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount STWCS STR, Silver White, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount ZRS-MCW ZRS Series Strobe. 24V, Multi-Cd, Wall Mount ZRS-MCWH ZRS Series Strobe. 24V, Multi-High-Cd, Wall Mount ZRS-24MCC ZRS Series Strobe. 24V, Multi-Cd, Ceiling Mount ZRS-24MCCH ZRS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount
Appliances with synchronizing strobes
(Only strobe portion compatible with 4008 Wheelock protocol for special applications) AMT-241575W, — AMT-241575W-NYC AMT Series Multi-Tone Horn Strobe. 24V, 15/75Cd, Wall Mount AMT-24MCW AMT Series Multi-Tone Horn Strobe. 24V, Multi-Cd, Wall Mount MT-241575W MT Series MT Horn Strobe. 24V, 15/75Cd, Wall Mount. MT-24MCW MT Series Multi-Tone Horn Strobe. 24V, Multi-Cd, Wall Mount MTWP-2475W, MTWP-2475C MTWP Series MT Horn Strobe. 24V, 30Cd, Wall or Ceiling Mount MTWP-24MCWH MTWP Series MT Horn Strobe. 24V, Multi-High-Cd, Wall Mount MTWP-24MCCH MTWP Series MT Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount MTWPA-2475W, MTWPB-2475W
MTWP Series Multi-Tone Horn Strobe. 24V, Wall Mount. MTWPG-2475W, MTWPR-2475W MTA-24MCCH, MTB-24MCCH,
MTG-24MCCH, MTR-24MCCH MTWPA-24MCCH, — MTWPB-24MCCH, — MTWPG-24MCCH, — MTWPR-24MCCH MTWP Series Multi-Tone Horn Strobe. 24V, Multi-High-Cd, Wall Mount. Amber/Blue/Green/Red ET70WP-2475W, ET70WP-2475C ET70WP Series Speaker Strobe. 24V, 30Cd, Wall or Ceiling Mount ET70WP-24185W ET70WP Series Speaker Strobe. 24V, 185Cd, Wall Mount ET70WP-24177C ET70WP Series Speaker Strobe. 24V, 177Cd, Ceiling Mount ET70WPA-2475 ET70WP Series Speaker Strobe. 24V, Wall or Ceiling Mt. Amber CH70-241575W CH70 Series Chime Strobe. 24V, 15/75Cd, Wall Mount CH70-24MCW CH70 Series Chime Strobe. 24V, Multi-Cd, Wall Mount CH90-24MCC CH90 Series Chime Strobe. 24V, Multi-Cd, Ceiling Mount CH70-24MCWH CH70 Series Chime Strobe. 24V, Multi-High-Cd, Wall Mount CH90-24MCCH CH90 Series Chime Strobe. 24V, Multi-High-Cd, Ceiling Mount E50-241575W E50 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount E50-24MCW E50 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount E50-24MCWH E50 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount E50A-24MCC, E50B-24MCC E50 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mt. Amber/Blue E60-24MCW E60 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount E60-24MCWH E60 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount E60-24MCC E60 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount E60-24MCCH E60 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount E70-241575W E70 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount E70-24MCW E70 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount E70-24MCWH E70 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount E70-24MCC, E90-24MCC E70/E90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount E90-24MCCH E90 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount E60A-24MCC, E70A-24MCC, — E70B-24MCC, E90A-24MCC, — E90B-24MCC E60/E70/E90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount. Amber/Blue ET70-241575W, ET90-241575W ET70/ET90 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount ET70-24MCW ET70 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount ET70-24MCWH ET70 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount ET70-24MCC, ET90-24MCC ET70/ET90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
Amber/Blue/Green/Red
MT Series Multi-Tone Horn Strobe. 24V, Multi-High-Cd, Wall Mount.
Amber/Blue/Green/Red
page 20 574-772 Rev. Q
XPS and XNAC Installation Instructions
Table 5: Cooper Wheelock appliances
Compatible with 4100U/4100ES XPS Wheelock protocol for special applications
ET70WPG-2475, ET70WPG-2475 — ET70WPG-2475 , ET70WPB-247 — ET70WPG-2475W, ET70WPR-247 ET70WP Series Speaker Strobe. 24V, Wall or Ceiling Mt. Green, Blue, Red (Only strobe portion compatible with 4008 Wheelock protocol for special applications) ET90-24MCCH ET90 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount ET80-241575W ET80 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount ET80-24MCW ET80 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount ET80-24MCWH ET80 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount S8-24MCC S8 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount S8-24MCCH S8 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount SA-S70-24MCW SA-S70 Series Amp-Speaker Strobe. 24V, Multi-Cd, Wall Mount SA-S90-24MCC SA-S90 Series Amp-Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
Synchronizing horns
AH-24 AH Series Horn. 24V AH-24WP AH Series Weatherproof Horn. 12V or 24V HNR Horn, Red, 2-Wire, Wall, 12/24V, 3dB, 5 Mount HNW Horn, White, 2-Wire, Wall, 12/24V, 3dB, 5 Mount HNRS Horn, Silver Red, 2-Wire, Wall, 12/24V, 3dB, 5 Mount HNWS Horn, Silver White, 2-Wire, Wall, 12/24V, 3dB, 5 Mount HNRC Horn, Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount HNWC Horn, White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount HNRCS Horn, Silver Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount HNWCS Horn, Silver White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount HS-24 HS Series Horn. 24V MIZ-24S MIZ Series Horn. 24V NH-12/24, NH-12/24R NH Series Horn. 12/24V (R=Round) ZNH ZNH Series Horn. 12/24V
Coded audible appliances
AMT-12/24, AMT-12/24-NYC AMT Series Multi-Tone Horn. 12/24V, Wall or Ceiling Mount CH70, CH90 CH70/CH90 Series Chime. 24V, Wall or Ceiling Mount CSX10-24-DC, CSXG10-24-DC CSX Series Bell. 24V, Wall Mount MT-12/24, MT4-12/24 MT Series Multi-Tone Horn. 12/24V, Wall or Ceiling Mount
Non-synchronizing appliances
MB-G6-24, MB-G10-24 MB Series Bell. 24V, Wall Mount
page 21 574-772 Rev. Q
© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
574-772 Rev. Q
Loading...