READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents
of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS – PART 15. This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with
NFPA72® after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100 % tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10 % of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
Introduction
This publication describes the installation procedure for 4100-5101 (120 VAC), 4100-5102 (220 VAC/230 VAC/240 VAC), 4100-5103 (120 VAC with
battery disconnect) Expansion Power Supplies (XPSs), and the 4100-5115 Expansion NAC Module (XNAC). This product is compatible with 4100U and
4100ES fire alarm controls units (FACUs).
Important: Verify FACU system programmer, executive, and slave software compatibility when installing, or replacing system components. Refer to
the Technical Support Information and Downloads website for compatibility information.
Expansion Power Supply Modules
This publication describes the installation procedure for the following:
• 4100-5101 Expansion Power Supply (XPS), 120 VAC, 60 Hz
The XPS distributes added card power and signal power via the PDI. Signal power is available only in the bay in which the XPS is located. The source of
card power is selected by jumpers P4 & P5 on the PDI.
The XPS includes three NACs, and may be expanded to 6 NACs with the 4100-5115. NACs are wired as Class B or Class A. All circuits are power limited
in accordance with UL 864. The NACs support non-addressable TrueAlert and conventional reverse-polarity operation.
The notification appliance circuits on these modules can be used as regulated 24 VDC circuits, or special application circuits. When used as generic 24
VDC regulated circuits, only 4 Amps of current is available across the three circuits, and any 24 VDC appliance may be attached. When used as special
applications NACs, the full 9 Amps of current is available at the three circuits and only the compatible appliances listed in Table 5 may be connect to
these circuits. The SPS/RPS can synchronize compatible appliances across all three circuits when those circuits are used as special applications NACs.
The XPS has a 9 A capacity. Each NAC is rated at 3 A. A NAC can also be configured as an auxiliary power point, in which case it is rated at 2 A. The
total load at 24 VDC must be no more than 9 A. The total load includes NACs (on the XPS or the XNAC Module), auxiliary power, card power, and signal
power used by modules plugged into the same bay.
Note: If NACs are to be used as auxiliary outputs, they must be configured as such in the Panel Programmer. Programming may also be required for
dedicated auxiliary outputs; refer to the ES Panel Programmer's Manual (574-849).
NACs are monitored for short and open circuits. If a short circuit occurs, the affected NAC will not be energized.
A NAC mis-wiring test, which checks for NACs that are shorted together, can be initiated on command from the operator interface.
AC power and battery backup are provided to the XPS through a connection to the PDM.
Detection of an earth fault on XPS wiring is performed by the SPS, RPS or XBC. Detection is 10k ohm minimum.
The 4100-5103 model is required in jurisdictions, such as Canada, where depleted battery conditions are required by local code to result in power-
down of the unit until AC power is restored. The system must also be programmed for depleted battery cutout for each power supply.
574-772 Rev. Q
XPS and XNAC Installation Instructions
The Expansion Power Supply (XPS)
XPS features
Figure 1 is an illustration of the XPS.
Figure 1: The Expansion Power Supply
LEDs
The XPS has the following LEDs:
• LED1 (yellow)*. Illuminates when NAC 1 is active or in a trouble state; otherwise, it is off.
• LED2 (yellow)*. Illuminates when NAC 2 is active or in a trouble state; otherwise, it is off.
• LED3 (yellow)*. Illuminates when NAC 3 is active or in a trouble state; otherwise, it is off.
• LED4 (green). Illuminates when the XPS is running off of AC power; otherwise, it is off.
• LED5 (yellow). General status LED.
- On steady: overcurrent tripped.
- Single repeating flash: battery not connected.
• LED6 (yellow). Illuminates when communication loss with the CPU occurs. Normally off.
*During initialization of the XPS, LEDs 1, 2, and 3 illuminate because the NACs are held in the isolate stage and create an open circuit trouble.
Input and output specifications
Table 1 summarizes the input and output specifications for the XPS.
Table 1: Input and output specifications
AC input specifications
4100-5102220 VAC/230 VAC/240 VAC @ 50 Hz or 60 Hz 2 A Max
4100-5103120 VAC @ 60 Hz, nominal, 4 A Max
DC output specifications
All XPSsMinimum: 19.5 VDC Maximum: 32 VDC Ripple: 2 VDC p-p @ full load (9 A)
Environmental operating range
The 4100U/4100ES modules are rated to operate at ambient temperatures from 32°F - 120°F (0°C-49°C).
The 4100U/4100ES modules are rated for operation at 90°F (32°C), 93% RH (non-condensing).
page 2574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 1. Mounting the XPS
Guideline
The XPS is normally mounted on the rightmost top and bottom positions of the PDI in a 4100 expansion cabinet. Before mounting the XPS, follow
these guidelines:
• Disconnect power to the system or remove power at the breaker before mounting or installing any modules.
Mounting
Use Figure 2, and the following instructions to mount the XPS.
1.Insert the two tabs on the bottom of the XPS into the rightmost two slots in the cabinet.
2.Push the XPS assembly against the back of the expansion bay.
a.Connect to the PDI as shown in Figure 2.
b.Correctly align the screw hole at the top of the XPS assembly with the hole in the bay chassis.
c.Use one #6 torx screw to secure the assembly to the expansion box.
Note: When installing into the 4100-2301 expansion bay, the front door should be removed to avoid damage to the XPS.
Figure 2: XPS mounting
page 3574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 2. XPS configuration
XPS configuration consists of setting the address switch as described in this section.
Setting the address
The XPS device address is set using DIP switch SW1, which is a bank of eight switches. From left to right, see Figure 3, these switches are designated as
SW1-1 through SW1-8. The function of these switches is as follows:
• SW1-1. This switch sets the baud rate for the internal 4100 communications line running between the card and the 4100 CPU. Set this switch
to ON to communicate.
• SW1-2 through SW1-8. These switches set the card's address within the 4100 FACU. See Figure 4 for a complete list of the switch settings for
all of the possible card addresses.
Note: You must set these switches to the value assigned to the card by the Panel Programmer.
Figure 3: DIP switch SW1
page 4574-772 Rev. Q
XPS and XNAC Installation Instructions
Figure 4: XPS card addresses
page 5574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 3. Internal wiring
The XPS gets its power from the power distribution module or PDM (4100U and 4100ES only) or the power distribution terminal block (4100-2301
expansion bay only). The PDM or terminal block takes power directly from the AC mains and the two backup batteries, and distributes power to each
bay in the cabinet.
Figure 5 shows the PDM in the 4100U/4100ES connecting to a host FACU with two XPSs.
Figure 5: System Power
The instructions in this section describe how to connect the XPS to AC mains and batteries in both regular 4100U/4100ES back boxes and the
4100-2301 expansion bay (for for non-4100U/4100ES back boxes).
page 6574-772 Rev. Q
XPS and XNAC Installation Instructions
Power distribution module connections
The power distribution module (PDM) connects to the SPS, RPS, or XPS in each bay. One PDM is used for each back box. Use the following
instructions to properly connect the PDM to each bay.
1.Route the black and white AC power wires to the supplied ferrite bead. Loop the wires twice through the bead as shown in Figure 6.
Figure 6: Loop wires through bead as shown
2.Wire 120 VAC/220 VAC/230 VAC/240 VAC to the PDM, keeping AC wires at least 1 in. away from all other wires. AC power must stay in the right side
of the cabinet, in the non-power-limited area.
3.Connect batteries to P5 on the PDM using harness 734-015.
4.Connect the 734-012 harness (734-013 for 220 V/230 V/240 V versions) from the next connector on the PDM to the first XPS.
a.Connect the separate red and black wires (with yellow female terminations) to plugs P4 (black) and P5 (red) on the XPS.
b.Connect the white and black wires, which terminate together in a white snap-on connector, to the connector at the bottom of the XPS
assembly, as shown in Figure 7. The black wire must be closer to the wall at the XPS connection point.
5.Repeat step 4 for the second XPS, if applicable.
1.
Figure 7: XPS/PDM connection
page 7574-772 Rev. Q
XPS and XNAC Installation Instructions
4100-2301 expansion bay wiring
If the XPS is being installed in a 4100-2301 expansion bay (for non-4100U/4100ES 2975-91xx Back Boxes):
1.For DC wiring, connect the battery block (635-852) to the XPS using harness 734-050. Feed red and black wires through the side rail to the front
of the XPS to prevent wire damage when the front panel is lowered. Connect the separate red and black wires (with yellow female terminations) to
plugs P4 (black) and P5 (red) on the XPS.
2.For AC wiring, connect the white and black wires (harness 734-049) from the 120 V and NEUT terminal blocks to the connector at the bottom of
the XPS assembly, keeping AC wires at least 1 in. away from all other wires. AC power must be kept to the right side of the cabinet, in the nonpower-limited area. The black wire must be closer to the wall at the XPS connection point.
Figure 8: XPS connection when mounted in a 4100 style box
page 8574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 4. XPS field wiring
The XPS provides three outputs for reverse-polarity notification appliance circuits. This section describes basic NAC wiring from the XPS to 4100compatible appliances.
NAC wiring styles
The XPS supports both Class A and Class B NAC wiring.
Class A wiring provides a circuit path XPS in the event of a single open circuit somewhere in the loop. Class A wiring requires that two wires are routed
from the XPS to each appliance, and then back again to the XPS.
Class A NAC wiring table
Table 2 lists the maximum distances from the XPS to the last appliance in a Class A configuration, depending on wire gauge and current. Use Table 2 to
calculate wire distances for your application if you are using Class A wiring.
Table 2: Class A wiring distances
Alarm current @ 24 V
0.25 A420 ft (128 m)667 ft (203 m)1,063 ft (324 m)1,691 ft (515 m)6 ohm
0.50 A210 ft (64 m)334 ft (102 m)532 ft (162 m)845 ft (258 m)3 ohm
0.75 A140 ft (43 m)222 ft (68 m)354 ft (108 m)564 ft (172 m)2 ohm
1 A105 ft (32 m)167 ft (51 m)266 ft (81 m)423 ft (129 m)1.5 ohm
1.25 A84 ft (26 m)133 ft (41 m)213 ft (65 m)338 ft (103 m)1.2 ohm
1.50 A70 ft (21 m)111 ft (34 m)177 ft (54 m)282 ft (86 m)1 ohm
1.75 A60 ft (18 m)95 ft (29 m)152 ft (46 m)242 ft (74 m)0.86 ohm
2 A53 ft (16 m)83 ft (25 m)133 ft (41 m)211 ft (64 m)0.75 ohm
2.25 A47 ft (14 m)74 ft (23 m)118 ft (36 m)188 ft (57 m)0.67 ohm
2.50 A42 ft (13 m)67 ft (20 m)106 ft (32 m)169 ft (51 m)0.60 ohm
2.75 A38 ft (12 m)61 ft (19 m)97 ft (30 m)154 ft (47 m)0.55 ohm
3 A35 ft (11 m)56 ft (17 m)89 ft (27 m)141 ft (43 m)0.50 ohm
Note:
• Max. distance = distance from XPS to last appliance.
• This table is calculated at 50°C (120°F). If you are installing in locations that could be exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output voltage.
• If CI wire is used instead of housing cable in a fire rated enclosure, reduce wiring distances by 38 ft (12 m) for every 10 ft (3 m) of potential
exposure.
• If Wheelock appliances employing EZ Mount SNAP bases are used, reduce the wiring distance and wiring resistance by:
- 12 gauge wire: 3.5 ft for each appliance, 0.0125 ohm for each appliance
- 14 gauge wire: 2.2 ft for each appliance, 0.0125 ohm for each appliance
- 16 gauge wire: 1.4 ft for each appliance, 0.0125 ohm for each appliance
- 18 gauge wire: 0.9 ft for each appliance, 0.0125 ohm for each appliance
Max. distance w/ 18
AWG (0.8231 mm²)
Max. distance w/ 16
AWG (1.309 mm²)
Max. distance w/ 14
AWG (2.081 mm²)
Max. distance w/ 12
AWG (3.309 mm²)
DC resistance
page 9574-772 Rev. Q
XPS and XNAC Installation Instructions
Class B NAC wiring table
Table 3 lists the maximum distances from the XPS to the last appliance in a Class B configuration, depending on wire gauge and current. Use Table 3 to
calculate wire distances for your application if you are using Class B wiring.
Table 3: Class B wiring distances
Alarm current @ 24 V
0.25 A840 ft (256 m)1,335 ft (407 m)2,126 ft (648 m)3,382 ft (1,031 m)12 ohm
0.50 A420 ft (128 m)667 ft (203 m)1,063 ft (324 m)1,691 ft (515 m)6 ohm
0.75 A280 ft (85 m)445 ft (136 m)709 ft (216 m)1,127 ft (344 m)4 ohm
1 A210 ft (64 m)334 ft (102 m)532 ft (162 m)845 ft (258 m)3 ohm
1.25 A168 ft (51 m)267 ft (81 m)425 ft (130 m)676 ft (206 m)2.4 ohm
1.50 A140 ft (43 m)222 ft (68 m)354 ft (108 m)564 ft (172 m)2 ohm
1.75 A120 ft (37 m)191 ft (58 m)304 ft (93 m)483 ft (147 m)1.71 ohm
2 A105 ft (32 m)167 ft (51 m)266 ft (81 m)423 ft (129 m)1.5 ohm
2.25 A93 ft (28 m)148 ft (45 m)236 ft (72 m)376 ft (115 m)1.33 ohm
2.50 A84 ft (26 m)133 ft (41 m)213 ft (65 m)338 ft (103 m)1.2 ohm
2.75 A76 ft (23 m)121 ft (37 m)193 ft (59 m)307 ft (94 m)1.09 ohm
3 A70 ft (21 m)111 ft (34 m)177 ft (54 m)282 ft (86 m)1 ohm
Note:
• Max. distance = distance from XPS to last appliance.
• This table is calculated at 50°C (120°F). If you are installing in locations that could be exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output voltage.
• If CI wire is used instead of housing cable in a fire rated enclosure, reduce wiring distances by 38 ft (12 m) for every 10 ft (3 m) of potential
exposure.
Max. distance w/ 18
AWG (0.8231 mm²)
Max. distance w/ 16
AWG (1.309 mm²)
Max. distance w/ 14
AWG (2.081 mm²)
Max. distance w/ 12 AWG
(3.309 mm²)
DC resistance
Guidelines
• All wiring is 18 AWG (0.8231 mm²) (minimum) to 12 AWG (3.309 mm²) (maximum).
• All wiring is supervised and power-limited.
• The maximum alarm current is 3 A for each circuit. The supervisory current is 2.03 mA at 24 VDC.
• The nominal voltage rating is 24 VDC, 2 V p-p ripple (maximum).
• The total available current from the XPS is 9 A, unless it is used for REGULATED 24 VDC notification appliances, where the XPS is rated for 4
Amps notification current, and 1 Amp for other uses. Total available auxiliary power current is 5 A (1 Amp for REG 24), and rated at 2 A for each
circuit. Current used for card power by modules plugged into the PDI, as well as any auxiliary 24 VDC current, must be deducted from the total
9 A available current.
• All wiring that leaves the building requires over-voltage protection. Install module 2081-9044 (3 A) or 2081-9028 (1/4 A) inside a UL-Listed
electrical box wherever wire enters or exits the building. When using the 2081-9044, the maximum alarm current is reduced to 1/4 A for that
part of the circuit downstream of the module.
• Terminal designations + and - are for the alarm state.
• Compatible appliances for NACs are listed in Table 4.
• A maximum of 70 appliances can be supported for each circuit. If you are using 49CMT or 49CMTV series appliances, note that each of these
appliances counts as five units, therefore no more than 13 49CMT or 49CMTV series appliances may be placed on one circuit.
• For CE compliant systems, use the ferrite beads as shown in each figure. Loop wires once through the ferrite beads as shown in Figure 9.
4100-5129 includes three ferrite beads, order as needed.
Figure 9: Loop wires as shown.
• Auxiliary power only: In order to connect a circuit using power-limited wiring, the devices being powered must all be addressable, or a ULListed EOL relay must be used to supervise the circuit. See Figure 10 for wiring directions for the EOL relay.
Note: The 2098-9739 Relay is used as an example. Other UL-Listed EOL relays can be used, depending on the application.
page 10574-772 Rev. Q
XPS and XNAC Installation Instructions
Figure 10: The EOL relay
Figure reference: *2098-9739
• The notification appliance circuits on the XPS are rated for special application and for regulated 24 VDC operation in accordance with UL864,
9th Edition.
• When used with the notification appliances listed in Table 4 or Table 5, each NAC is rated for 3 A, and total XPS capacity is rated at 9 A. This
rating is the UL864 special application rating. Appliances listed in Table 4 and Table 5 are synchronized in accordance with UL864, between
all NACs on the XPS, and any NACs on an SPS, RPS or XPS within the same 4100U/4100ES system, but not if appliances are mixed from both
tables. Appliances from Table 4 will be 1/2 second out of audible sync with appliances from Table 4 in the same system. All appliances any
given SPS, RPS or XPS must be from either Table 4 or Table 5, mixing of appliances from both tables is not possible within a power supply.
• For use with notification appliances not listed in Table 4 or Table 5, each circuit is rated for 2 A maximum, with a total notification appliance
load of 4A for each XPS. This rating is the UL 864 regulated 24 VDC rating. Synchronization of strobes and other appliances requires use of the
associated, listed, compatible synchronization module. Consult supplier of notification appliances for synchronization limits and details.
• Non-pulsing, linear-type notification appliances, such as horns or bells may be used up to the full rating (3 A/NAC, 9 A total for the XPS).
• If Wheelock appliances employing EZ Mount SNAP bases are used, reduce the wiring distance and wiring resistance by:
12 gauge wire: 7.0 ft for each appliance, 0.025 ohm for each appliance
14 gauge wire: 4.4 ft for each appliance, 0.025 ohm for each appliance
16 gauge wire: 2.8 ft for each appliance, 0.025 ohm for each appliance
18 gauge wire: 1.8 ft for each appliance, 0.025 ohm for each appliance
page 11574-772 Rev. Q
XPS and XNAC Installation Instructions
Class A NAC wiring
To connect the XPS to appliances using Class A wiring, read the following instructions and refer to Figure 11.
1.Route wire (between 12 [3.309 mm²] and 18 AWG [0.8231 mm²]) from the B+ and B- outputs on TB1 of the XPS to the appropriate inputs on a
peripheral notification appliance. Use NAC1, NAC2, or NAC3.
2.Route wire from the first appliance to the next one. Repeat for each appliance.
3.Route wire from the last appliance to the A+ and A- inputs on the same NAC circuit of TB1 of the XPS.
4.Repeat steps 1 through 3 for each NAC output you want to use.
5.Leave the 10k, factory-installed, 1/2 W, brown/black/orange resistor (378-030) on each unused circuit. The circuit must connect B+ to B- terminals.
No external end-of-line resistor is needed for circuits in use.
Figure 11: Class A wiring
Note: * Ferrite beads required for CE compliance. Use kit 4100-5129.
page 12574-772 Rev. Q
XPS and XNAC Installation Instructions
Class B NAC wiring
To connect the XPS to appliances using Class B wiring, read the following instructions and refer to Figure 12.
1.Use NAC1, NAC2, or NAC3 to route wire (between 12 [3.309 mm²] and 18 AWG [0.8231 mm²]) from B+ and B- on the XPS to the first appliance.
2.Route wire to the next appliance as shown in the figure. Repeat for each appliance.
3.Route wire from the last appliance to the EOLR harness (10k ohm, 1/2 W: P/N 733-894, PID# 4081-9008).
4.Repeat steps 1 through 3 for each NAC output you want to use.
5.Leave the 10k, 1/2 W, brown/black/orange resistor (378-030) on each unused circuit. The circuit must connect B+ to B- terminals.
Figure 12: Class B wiring
Note: * Ferrite beads required for CE compliance. Use kit 4100-5129.
page 13574-772 Rev. Q
XPS and XNAC Installation Instructions
Auxiliary power wiring
The XPS can receive auxiliary power appliances via the dedicated auxiliary power tap (TB2). If additional power is needed, any of the three NAC outputs
can be used as auxiliary power inputs.
Figure 13, shows how the XPS should be wired for auxiliary power at any given terminal.
• All wiring is 18 AWG (0.8231 mm²) (minimum) to 12 AWG (3.309
mm²) (maximum).
• All wiring is power-limited.
• Auxiliary power may be taken from the dedicated auxiliary power
tap or from an unused NAC.
• If auxiliary power is taken from NAC terminals, the NAC must
be configured as an auxiliary power point type in the panel
programmer.
• Programming may be required for dedicated auxiliary outputs.
• Remove end-of-line resistors from circuits used for auxiliary power.
• External wiring is not supervised unless an end-of-line relay is
wired coil to auxiliary power, and normally open contacts are
monitored by a system power point. Relay current must be
considered as part of the load.
• All wiring that leaves the building requires over-voltage protection.
Install module 2081-9044 (3 A) or 2081-9028 (1/4 A) inside a UL
Listed electrical box wherever wire enters or exits the building. A
maximum of four 2081-9044 modules may be connected to one
channel. When using the 2081-9044, the maximum alarm current
is reduced to 1/4 A for that part of the circuit downstream of the
module.
• CE compliant systems require ferrite beads. Use kit 4100-5129.
• All auxiliary power taps are rated at 2 A. The total auxiliary power
current available is 5 A. The overall total current available is 9 A,
including NAC, auxiliary, and card power. Current used for card
power by modules plugged into the PDI, and an current from aux.
24 V, must be deducted from the 9 A available current.
• Voltage rating: 24 VDC (nominal), 2 V P-P ripple (maximum). The
following devices connect to 2 A aux power:
- 2088-series relays and door holders
- 2098-series four-wire smoke detectors
- 2190-series monitor and signal ZAMs
- 4090-series IDNet ZAMs
- 4098-series four-wire smoke detectors and duct detectors
- Printer
- 4190-9050
- 4190-9051 4-20 mA ZAMs
- LCD Annunciator
• Resettable 24 V is obtained from any aux power point by
programming the point as type resettable 24 V. Refer to the
programming manual for details.
Figure 13: Auxiliary power wiring
** 4090-9117 IDNet Power Isolator
page 14574-772 Rev. Q
* See Figure 14
XPS and XNAC Installation Instructions
Step 5. Installing the XNAC
The 4100-5115 Expansion NAC Module (XNAC) is an option board that provides three NACs in addition to the three NACs already on the XPS. The
XNAC plugs onto the XPS.
If you are not installing an XNAC, skip this section and continue on to
The XNAC
The XNAC has three NACs, each rated at 3 A. As on the XPS, there is one status LED for each NAC.
Mounting the XNAC
The XNAC mounts to the top of the XPS as shown in the instructions and Figure 14.
Note: The XNAC cannot be installed on an XPS that is mounted to a 4100-2301 expansion bay that is used in a non-4100U/4100ES back box (a back
box with PID series 2975-91xx).
Step 6. Troubleshooting.
Figure 14: Mounting the XNAC
1. Insert plastic standoffs (202-078) and a metal standoff (202-077) to the XPS as shown in Figure 14.
2. Plug J1 on the XNAC into P3 on the XPS using a header (166-549). The holes on the edges of the XNAC should be aligned with the tops of the
standoffs.
3. Secure the XNAC to the standoffs using four screws.
4. Connect the XNAC's signal power harness to P1 on the XPS.
Wiring the XNAC
The XNAC uses the same wiring rules as TB1 on the XPS. Refer to
XNAC cannot be used for auxiliary power.
Step 4. XPS field wiring to wire the XNAC to notification appliances. Note that the
page 15574-772 Rev. Q
XPS and XNAC Installation Instructions
Step 6. Troubleshooting
This section describes the messages that may appear on the 4100 display when using the XPS. Trouble messages appear on the left as titles, and
possible causes are listed to the right in the text.
No Communications with Master
For communications to work, the XPS requires a 0 V connection to the PDM. Be sure to attach a fast-on connector to the PC board and also ensure
that the fuse in the black battery lead is intact.
AC Power Loss
Voltage has fallen below an acceptable level. A problem may exist in the wiring, in the power distribution module, or into dedicated AC power.
Battery Not Connected/ Battery Depleted
The battery is not connected or is depleted. The precise status of the battery is given by the SPS. These modules report Low Battery. This trouble is
merely to indicate a wiring problem to the XPS (blown fuse, not connected, etc.).
Expansion NAC Card Configuration Mismatch
Either the XNAC card is missing even though the XPS was configured to have one, or there is an un-configured XNAC card physically installed.
NAC Miswired Trouble
This trouble is active when a NAC-to-NAC short is detected. The NACs that are shorted are also indicated. Any combination of NACs 1 through 6 can be
mis-wired together. The panel displays up to 4 mis-wiring faults.
Connecting additional power to motherboards
The XPS can be used to supply motherboards with an additional 24 V. Use Figure 15 to connect 24 V from the XPS to motherboards in the system.
Figure 15: Additional 24 V power wiring
page 16574-772 Rev. Q
XPS and XNAC Installation Instructions
NAC-compatible notification appliances and accessories
Table 4: Special application NAC-compatible notification appliancess & accessories
P/NDescription
4904-9168V/O 15CD RED FREE-RUN TNA
4904-9171V/O 15CD WHITE FREE-RUN TNA
4904-9176V/O 24VDC 15CD RED VER F/S
4904-9177V/O 24VDC 15CD WHT VER F/S
4904-9178V/O 24VDC 15CD RED HORIZ F/S
4904-9183V/O 24VDC 15CD RED CEIL F/S
4904-9331V/O 15CD RED SYNC TNA
4904-9342V/O 15CD WHITE SYNC TNA
4904-9345V/O 24VDC 15CD WHT PLAIN F/S
4904-9174V/O 24VDC 30CD RED VER F/S
4904-9180V/O 24VDC 30CD RED HORIZ F/S
4904-9184V/O 24VDC 30CD RED CEIL F/S
4904-9346V/O 24VDC 30CD WHT PLAIN F/S
4904-9169V/O 75CD RED FREE-RUN TNA
4904-9172V/O 75CD WHITE FREE-RUN TNA
4904-9332V/O 75CD RED SYNC TNA
4904-9343V/O 75CD WHITE SYNC TNA
4904-9170V/O 110CD RED FREE-RUN TNA
4904-9173V/O 110CD WHITE FREE-RUN TNA
4904-9175V/O 24VDC 110CD RED VER F/S
4904-9181V/O 24VDC 110CD WHT VER F/S
4904-9182V/O 24VDC 110CD RED HOR F/S
4904-9185V/O 24VDC 110CD RED CEIL F/S
4904-9333V/O 110CD RED SYNC TNA
4904-9344V/O 110CD WHITE SYNC TNA
4906-9101V/O 15/30/75/110cd W/M RED TNA
4906-9103V/O 15/30/75/110cd W/M WHT TNA
4906-9102V/O 15/30/75/110cd C/M RED TNA
4906-9104V/O 15/30/75/110cd C/M WHT TNA
4906-9105V/O WEATHERPROOF W/M RED
4906-9106V/O WEATHERPROOF W/M WHT
4906-9109HiCandela W/M V/O, RED
4906-9110HiCandela C/M V/O, WHITE
4906-9111HiCandela W/M V/O, WHITE
4906-9112HiCandela C/M V/O, RED
4906-9113V/O WEATHERPROOF W/M (CAN) RED
4903-9356S/V 15CD RED 25/70V TNA
4903-9359S/V 15CD WHITE 25/70V TNA
4903-9150S/V 24VDC 15CD RED HORIZ F/S
4903-9153S/V 24VDC 15CD RED VER F/S
4903-9193S/V 24VDC 15CD WHT HORIZ F/S
4903-9196S/V15CD RND
4903-9148S/V 24VDC 30CD RED HORIZ F/S
4903-9194S/V 24VDC 30CD WHT HORIZ F/S
4903-9197S/V, 30CD, RND TNA
4903-9357S/V 75CD RED 25/70V TNA
4903-9360S/V 75CD WHITE 25/70V TNA
4903-9358S/V 110CD RED 25/70V TNA
4903-9361S/V 110CD WHITE 25/70V TNA
4903-9198S/V 110CD, RND TNA
4906-9151S/V 15/30/75/110cd W/M RED TNA
4906-9153S/V 15/30/75/110cd W/M WHT TNA
4906-9154S/V 15/30/75/110cd C/M WHT TNA
4901-9820HORN 24VDC RED TNA
4901-9822HORN 24VDC RED
4009-9201NAC EXTENDER 120VAC, IDNET
4009-9301NAC EXTENDER, 240VAC, IDNET
4009-94014009 T/A ADDR CONTROLLER
page 17574-772 Rev. Q
Table 4: Special application NAC-compatible notification appliancess & accessories
P/NDescription
4903-9252A/V 24VDC 15CD RED HOR F/S
4903-9253A/V 24VDC 30CD RED HOR F/S
4903-9254A/V 24V 110CD RED HOR F/S
4903-9255A/V 24VDC 15CD RED VER F/S
4903-9256A/V 24V 110CD RED VER F/S
4903-9257A/V 24VDC 15CD WHT HOR F/S
4903-9258A/V 24VDC 30CD WHT HOR F/S
4903-9417A/V 15CD RED SYNC TNA
4903-9418A/V 75CD RED SYNC TNA
4903-9419A/V 110CD RED SYNC TNA
4903-9425A/V 15CD RED STD TNA
4903-9426A/V 75CD RED STD TNA
4903-9427A/V 110CD RED STD TNA
4903-9428A/V 15CD WHITE SYNC TNA
4903-9429A/V 75CD WHITE SYNC TNA
4903-9430A/V 110CD WHITE SYNC TNA
4903-9431A/V 15CD WHITE STD TNA
4903-9432A/V 75CD WHITE STD TNA
4903-9433A/V 110CD WHITE STD TNA
4906-9127A/V 15/30/75/110cd W/M RED
4906-9129A/V 15/30/75/110cd W/M WHT
4906-9128A/V 15/30/75/110cd C/M RED
4906-9130A/V 15/30/75/110cd C/M WHT
4906-9131A/V WEATHERPROOF W/M RED
4906-9132A/V WEATHERPROOF W/M WHT
4906-9139HiCandela W/M A/V, RED
4906-9140HiCandela C/M A/V, RED
4906-9141HiCandela W/M A/V, WHITE
4906-9142HiCandela C/M A/V, WHITE
4906-9143A/V WEATHERPROOF W/M (CAN) RED
4905-9815SMARTSYNC ADAPTER, TNA
4905-9938SMARTSYNC CTL MODULE
4090-9005SRP
4090-9006SRP w/ENCLOSURE
49CMT-APPLWMT HORN
49CMT-WRFMT HORN
49CMT-WRF-BAMT HORN
49CMT-WWFMT HORN
49CMT-WWF-BAMT HORN
49CMTV-APPLWMT HORN/STROBE
49CMTV-WRFMT HORN/STROBE
49CMTV-WRF-BAMT HORN/STROBE
49CMTV-WWFMT HORN/STROBE
49CMTV-WWF-BA
4098-9772
4098-9773
MT HORN/STROBE
SENSOR BASE WITH 520 Hz SOUNDER
CO SENSOR BASE WITH 520 Hz SOUNDER
XPS and XNAC Installation Instructions
page 18574-772 Rev. Q
XPS and XNAC Installation Instructions
Cooper Wheelock appliances
Table 5: Cooper Wheelock appliances
Compatible with 4100U/4100ES XPS Wheelock protocol for special applications
Synchronizing horn strobes
AS-241575WAS Series Horn Strobe. 24V, 15/75Cd, Wall Mount
AS-24MCWAS Series Horn Strobe. 24V, Multi-Cd, Wall Mount
AS-24MCCAS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount
AS-24MCWHAS Series Horn Strobe. 24V, Multi-High-Cd, Wall Mount
AS-24MCCHAS Series Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount
ASWP-2475W, ASWP-2475CAS Series WP Horn Strobe. 24V, 30Cd, Wall or Ceiling Mount
ASWP-24MCWHAS Series WP Horn Strobe. 24V, Multi-High-Cd, Wall Mount
ASWP-24MCCHAS Series WP Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount
ASA-24MCW, ASB-24MCWAS Series Horn Strobe. 24V, Multi-Cd, Wall Mount. Amber/Blue
ASA-24MCC, ASB-24MCCAS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount. Amber/Blue
HS4-241575WHS4 Series Horn Strobe. 24V, 15/75Cd, Wall Mount
HS4-24MCWHS4 Series Horn Strobe. 24V, Multi-Cd, Wall Mount
HS4-24MCWHHS4 Series Horn Strobe. 24V, Multi-High-Cd, Wall Mount
HS4-24MCCHS4 Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount
HSRHN STR, Red, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount
HSWHN STR, White, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount
HSRSHN STR, Silver Red, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount
HSWSHN STR, Silver White, 2-Wire, Wall, 12/24V, 3dB, 8Cd, 5Mount
HSRCHN STR, Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount
HSWCHN STR, White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount
HSRCSHN STR, Silver Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount
HSWCSHN STR, Silver White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 8Cd, 5Mount
NS-241575WNS Series Horn Strobe. 24V, 15/75Cd, Wall Mount
NS-24MCWNS Series Horn Strobe. 24V, Multi-Cd, Wall Mount
NS-24MCCNS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount
NS-24MCCHNS Series Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount
ZNS-MCWZNS Series Horn Strobe. 24V, Multi-Cd, Wall Mount
ZNS-MCWHZNS Series Horn Strobe. 24V, Multi-High-Cd, Wall Mount
ZNS-24MCCZNS Series Horn Strobe. 24V, Multi-Cd, Ceiling Mount
ZNS-24MCCHZNS Series Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount
Synchronizing strobes
RSS-241575WRSS Series Strobe. 24V, 15/75Cd, Wall Mount
RSSP-241575WRSSP Series Strobe. 12V or 24V, 15/75Cd, Wall Mount
RSS-24MCW, RSSP-24MCWRSS/RSSP Series Strobe. 24V, Multi-Cd, Wall Mount
RSS-24MCWH, RSSP-24MCWHRSS/RSSP Series Strobe. 24V, Multi-High-Cd, Wall Mount
RSS-24MCC, RSS-24MCCRRSS Series Strobe. 24V, Multi-Cd, Ceiling Mount (R=Round)
RSS-24MCCH, RSS-24MCCHRRSS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount (R=Round)
RSSR-2415W, RSSR-2415CRSS Series Strobe. 24V, 15Cd, Red, Wall or Ceiling Mount
RSSR-2475W, RSSR-2475CRSS Series Strobe. 24V, 75Cd, Red, Wall or Ceiling Mount
RSSR-24110CRSS Series Strobe. 24V, 110Cd, Red, Ceiling Mount
RSSA-24110W, RSSB-24110W,—
RSSG-24110W, RSSR-24110WRSS Series Strobe. 24V, 110Cd, Wall Mount. Amber/Blue/Green/Red.
RSSA-24MCC, RSSB-24MCC,—
RSSG-24MCC, RSSR-24MCCRSS Series Strobe. 24V, Multi-Cd, Ceiling Mount. Amber/Blue/Green/Red.
RSSA-24MCCH, RSSB-24MCCH,—
RSSG-24MCCH, RSSR-24MCCHRSS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount. Amber/Blue/Green/Red.
RSSPA-24MCCRSSP Series Strobe. 24V, Multi-Cd, Ceiling Mount. Amber
RSSWPA-2475WRSS Series WP Strobe. 24V, Wall Mount. Amber
RSSWPA-24MCCH,—
RSSWPB-24MCCH,—
RSSWPG-24MCCH,—
RSSWPR-24MCCHRSS Series WP Strobe. 24V, Multi-High-Cd, Ceiling Mount. Amber/Blue/Green/Red.
RSSWP-2475W, RSSWP-2475CRSS Series WP Strobe. 24V, 30Cd, Wall or Ceiling Mount
RSSWP-24MCWHRSS Series WP Strobe. 24V, Multi-High-Cd, Wall Mount
RSSWP-24MCCHRSS Series WP Strobe. 24V, Multi-High-Cd, Ceiling Mount
STRSTR, Red, 2-Wire, Wall 12/24V, 8Cd, 5 Mount
STWSTR, White, 2-Wire, Wall 12/24V, 8Cd, 5 Mount
page 19574-772 Rev. Q
XPS and XNAC Installation Instructions
Table 5: Cooper Wheelock appliances
Compatible with 4100U/4100ES XPS Wheelock protocol for special applications
STRSSTR, Silver Red, 2-Wire, Wall 12/24V, 8Cd, 5 Mount
STWSSTR, Silver White, 2-Wire, Wall 12/24V, 8Cd, 5 Mount
STRCSTR, Red, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount
STWCSTR, White, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount
STRCSSTR, Silver Red, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount
STWCSSTR, Silver White, 2-Wire, Ceiling Mount, 12/24V, 8Cd, 5 Mount
ZRS-MCWZRS Series Strobe. 24V, Multi-Cd, Wall Mount
ZRS-MCWHZRS Series Strobe. 24V, Multi-High-Cd, Wall Mount
ZRS-24MCCZRS Series Strobe. 24V, Multi-Cd, Ceiling Mount
ZRS-24MCCHZRS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount
Appliances with synchronizing strobes
(Only strobe portion compatible with 4008 Wheelock protocol for special applications)
AMT-241575W,—
AMT-241575W-NYCAMT Series Multi-Tone Horn Strobe. 24V, 15/75Cd, Wall Mount
AMT-24MCWAMT Series Multi-Tone Horn Strobe. 24V, Multi-Cd, Wall Mount
MT-241575WMT Series MT Horn Strobe. 24V, 15/75Cd, Wall Mount.
MT-24MCWMT Series Multi-Tone Horn Strobe. 24V, Multi-Cd, Wall Mount
MTWP-2475W, MTWP-2475CMTWP Series MT Horn Strobe. 24V, 30Cd, Wall or Ceiling Mount
MTWP-24MCWHMTWP Series MT Horn Strobe. 24V, Multi-High-Cd, Wall Mount
MTWP-24MCCHMTWP Series MT Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount
MTWPA-2475W, MTWPB-2475W—
MTG-24MCCH, MTR-24MCCH
MTWPA-24MCCH,—
MTWPB-24MCCH,—
MTWPG-24MCCH,—
MTWPR-24MCCHMTWP Series Multi-Tone Horn Strobe. 24V, Multi-High-Cd, Wall Mount. Amber/Blue/Green/Red
ET70WP-2475W, ET70WP-2475CET70WP Series Speaker Strobe. 24V, 30Cd, Wall or Ceiling Mount
ET70WP-24185WET70WP Series Speaker Strobe. 24V, 185Cd, Wall Mount
ET70WP-24177CET70WP Series Speaker Strobe. 24V, 177Cd, Ceiling Mount
ET70WPA-2475ET70WP Series Speaker Strobe. 24V, Wall or Ceiling Mt. Amber
CH70-241575WCH70 Series Chime Strobe. 24V, 15/75Cd, Wall Mount
CH70-24MCWCH70 Series Chime Strobe. 24V, Multi-Cd, Wall Mount
CH90-24MCCCH90 Series Chime Strobe. 24V, Multi-Cd, Ceiling Mount
CH70-24MCWHCH70 Series Chime Strobe. 24V, Multi-High-Cd, Wall Mount
CH90-24MCCHCH90 Series Chime Strobe. 24V, Multi-High-Cd, Ceiling Mount
E50-241575WE50 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount
E50-24MCWE50 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
E50-24MCWHE50 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
E50A-24MCC, E50B-24MCCE50 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mt. Amber/Blue
E60-24MCWE60 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
E60-24MCWHE60 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
E60-24MCCE60 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
E60-24MCCHE60 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
E70-241575WE70 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount
E70-24MCWE70 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
E70-24MCWHE70 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
E70-24MCC, E90-24MCCE70/E90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
E90-24MCCHE90 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
E60A-24MCC, E70A-24MCC,—
E70B-24MCC, E90A-24MCC,—
E90B-24MCCE60/E70/E90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount. Amber/Blue
ET70-241575W, ET90-241575WET70/ET90 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount
ET70-24MCWET70 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
ET70-24MCWHET70 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
ET70-24MCC, ET90-24MCCET70/ET90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
Amber/Blue/Green/Red
MT Series Multi-Tone Horn Strobe. 24V, Multi-High-Cd, Wall Mount.
Amber/Blue/Green/Red
page 20574-772 Rev. Q
XPS and XNAC Installation Instructions
Table 5: Cooper Wheelock appliances
Compatible with 4100U/4100ES XPS Wheelock protocol for special applications
ET70WPG-2475, ET70WPG-2475—
ET70WPG-2475 , ET70WPB-247—
ET70WPG-2475W, ET70WPR-247ET70WP Series Speaker Strobe. 24V, Wall or Ceiling Mt. Green, Blue, Red
(Only strobe portion compatible with 4008
Wheelock protocol for special applications)
ET90-24MCCHET90 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
ET80-241575WET80 Series Speaker Strobe. 24V, 15/75Cd, Wall Mount
ET80-24MCWET80 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
ET80-24MCWHET80 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
S8-24MCCS8 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
S8-24MCCHS8 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
SA-S70-24MCWSA-S70 Series Amp-Speaker Strobe. 24V, Multi-Cd, Wall Mount
SA-S90-24MCCSA-S90 Series Amp-Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
Synchronizing horns
AH-24AH Series Horn. 24V
AH-24WPAH Series Weatherproof Horn. 12V or 24V
HNRHorn, Red, 2-Wire, Wall, 12/24V, 3dB, 5 Mount
HNWHorn, White, 2-Wire, Wall, 12/24V, 3dB, 5 Mount
HNRSHorn, Silver Red, 2-Wire, Wall, 12/24V, 3dB, 5 Mount
HNWSHorn, Silver White, 2-Wire, Wall, 12/24V, 3dB, 5 Mount
HNRCHorn, Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount
HNWCHorn, White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount
HNRCSHorn, Silver Red, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount
HNWCSHorn, Silver White, 2-Wire, Ceiling Mount, 12/24V, 3dB, 5 Mount
HS-24HS Series Horn. 24V
MIZ-24SMIZ Series Horn. 24V
NH-12/24, NH-12/24RNH Series Horn. 12/24V (R=Round)
ZNHZNH Series Horn. 12/24V
Coded audible appliances
AMT-12/24, AMT-12/24-NYCAMT Series Multi-Tone Horn. 12/24V, Wall or Ceiling Mount
CH70, CH90CH70/CH90 Series Chime. 24V, Wall or Ceiling Mount
CSX10-24-DC, CSXG10-24-DCCSX Series Bell. 24V, Wall Mount
MT-12/24, MT4-12/24MT Series Multi-Tone Horn. 12/24V, Wall or Ceiling Mount
Non-synchronizing appliances
MB-G6-24, MB-G10-24MB Series Bell. 24V, Wall Mount