Simplex TYCO VLC-600 Quick Start Manual

TrueAlarm Analog Sensing
UL, ULC, CSFM Listed* VLC-600 TrueAlarm LaserCOMPACT Smoke Sensor with
4100ES/4010ES/4100U IDNet and MAPNET II Communications
Features
Model VLC-600 addressable, analog output air aspiration smoke sensor provides:
VESDA
with the established TrueAlarm analog sensing process for area coverage up to 8000 ft
Compact 8 ” (225 mm) square size Dual stage dust filter that is used on larger systems Obscuration measurements communicated to the fire
alarm control panel for status determination
LaserCOMPACT operation communicating
2
Clean room cable tray
Remote LED indicator
Panel selected sensitivity from 0.016%/ft to 4.08%/ftLocal computer port access for the VESDA Vconfig
Pro software program as used on larger systems
Single LED that indicates local status information Capability of driving a remote LED (ordered
separately)
Addressable manual stations,
TrueAlert sensors and other devices
PULL DOWN
Trouble conditions are also communicated:
Mechanical problems are received as sensor troubles Electrical problems are received as “no answer” troubles Additional details are indicated by the sensor LED and
by accessing sensor diagnostics
Compatible with Simplex
®
4100ES, 4010ES, 4100U, or legacy 4100/4120 fire alarm control panels:
Communications via 4100ES/4010ES/4100U IDNet
or 4100ES/4100U MAPNET II addressable formats
Connection is to the same SLC (signaling line circuit)
with other devices such as addressable manual stations, TrueAlarm area smoke sensors, addressable control modules, etc.
Communications are as a single device and connection is
direct to the SLC without requiring a dedicated interface
4100/4120 requires revision 8.01 or higher software
Three threshold levels are programmable from the fire alarm control panel with typical selections as:
Stage 1 – Alert at 0.016 to 0.6218% obscuration/ft Stage 2 – Pre-Alarm at 0.03 to 0.6234% obscuration/ft Stage 3 – Alarm at 0.05 to 4.08% obscuration/ft NOTE: UL listed evacuation alarm sensitivity is not
to be less sensitive than 0.625%/ft
Sampling pipe network:
Uses standard Vision Systems pipe and inlet in
accordance with Vision Systems Aspire design tool
UL listed to Standard 268 (URXG)
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7259-1728:0109 for allowable values and/or conditions concerning material presented in this document. This product was not approved by FM as of document revision date. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
S4098-0036-7 7/2013
TrueAlarm LaserCOMPACT System Connections
Description
Air aspiration technology smoke detection operates
by actively drawing in air for sampling in a high intensity, stable detection chamber. The Model VLC-600 TrueAlarm LaserCOMPACT smoke detector uses the latest in VESDA sampling technology including a highly efficient laser light source and a dual stage dust filter.
TrueAlarm analog sensing occurs when the
TrueAlarm LaserCOMPACT sensor communicates smoke chamber information to the connected fire alarm control panel. The panel evaluates the smoke sensor information against three programmed thresholds and declares an alarm or pre-alarm condition depending on smoke chamber activity.
Status communications. In addition to smoke
chamber information, the TrueAlarm LaserCOMPACT also advises the fire alarm control panel of local trouble conditions. Troubles may include dirty filter, airflow restriction or failure, etc. Specific details are stored in memory at the sensor location.
Typical air inlet
TrueAlarm
Laser
COMPACT
ALARM
ALARMFIRE
CLEAN ROOM SMOKE DETECTOR ALARM
Fire Alarm Control Panel requires 4100ES/4010ES/4100U
IDNet or 4100ES/4100U MAPNET II communications
(4100ES shown for reference)
VLC-600 TrueAlarm LaserCOMPACT Air Aspiration Smoke Sensor
4100ES/4010ES/4100U IDNet or 4100ES/4100U MAPNET II addressable communications
24 VDC power
Operation
Filtered air flow. A high efficiency aspirator
continually draws air through a simple pipe network to a central detector. Air entering the sensor housing passes a flow sensor before the sample is passed through a dual-stage dust filter. The majority of air is exhausted from the detector and where required, back vented to the protected area. The first stage of the air filter removes dust and dirt from the air sample before it enters the smoke detection chamber. A second, ultra-fine filter stage provides a clean air supply to be used inside the detection chamber to form clean air barriers which protect the optical surfaces from contamination.
Laser detection chamber. The detection chamber uses
a stable, highly efficient laser light source and unique sensor configuration to achieve optimum response to a wide range of smoke types. When smoke passes through the detection chamber, it creates light scattering which is detected by very sensitive sensor circuitry. The analog level of the sensor is then communicated to the fire alarm control panel for comparison to pre-selected alarm thresholds.
Operation (Continued)
Status logging. The sensor status history for all alarms,
service, and fault events, is monitored and logged with time and date stamps within the electronics of the sensor, accessible via the local computer port. General trouble status indications are communicated to the panel as either sensor troubles or “no answer” troubles.
Additional Information
Refer to Installation Instructions 19772 shipped with the VLC-600 for additional information.
Product Selection
Model Description
VLC-600 TrueAlarm LaserCOMPACT Smoke Sensor (sampling pipe is ordered separately)
2098-9808
Remote Red LED Status Indicator on single gang stainless steel plate; mounting requires a single ga ng box, 1 ½” minimum depth; connections are color coded wire leads
Specifications
Sensor Voltage 18 to 30 VDC, supplied from fire alarm control panel Sensor Current 205 mA @ 24 VDC; supervisory and alarm
Communications
Electrical Terminations Terminal blocks for 18 to 12 AWG
Operating Conditions
Sampling Network
UL Listed Velocity Range 0 to 4000 ft/min (0 to 1200 m/min)
Alarm Sensitivity Range
Recognized Sensitivity Levels
Sensor Service Access Enclosure Rating NEMA 1 (IP 30)
Weight 4.2 lbs (1.9 kg)
Compatibility
Loading One address, one unit load per sensor
Sensor Ambient 14° F to 103° F (-10° C to 39° C)
Sampled Air -4° F to 140° F (-20° C to 60° C)
Sensor Humidity 10-95% RH, non-condensing
4100ES/4010ES/4100U IDNet or MAPNET II addressable communications, automatically selected
2
Maximum area of coverage = 8000 ft accordance with Vision Systems computer design tool (ASPIRE) and NFPA standards
0.016% to 4.08%/ft obscuration, selected at the fire alarm control panel; NOTE: UL listed evacuation alarm sensitivity is not to be less sensitive than 0.625%/ft
Three levels, selectable and designated as required at the fire alarm control panel
Internal DB-9, RS-232 connection for a service computer using VESDA Vconfig Pro software program (authorized service access only)
, maximum pipe length in
2 S4098-0036-7 7/2013