Non-Addressable Peripherals
UL, ULC, CSFM Listed; 4905-9835 Temporal Code 4
FM Approved* Module for CO Gas Alarm Notification
Features
Provides Temporal Code 4 (TC4) NAC (Notification
Appliance Circuit) control for Carbon Monoxide
(CO) gas warning:
The TC4 CO gas warning is a repeated sequence of four
1 2
ON
cycles of 100 msec on with 100 msec off, followed by
5 seconds off per NFPA 720, Standard for the
Installation of Carbon Monoxide (CO) Warning
Equipment in Dwelling Units
Compatible appliances includes: CO Sounder Base
4098-9798, 4901-9820 Horn (set for free-run), and 4903
Series 4-wire A/V appliances horn input (not compatible
with SmartSync horn control appliances)
Compatible Simplex
4100ES, 4100U, or 4010ES NAC outputs
4009 IDNet NAC Extender NAC outputs
®
equipment NAC sources:
4905-9835 Temporal Code 4 Module
(shown approximately 1/2 size)
Each module requires an input NAC that powers the 3A
rated output NAC for control of compatible audible
notification appliances only (not for strobes)
Three selectable operation modes:
Synchronized operation allows a separate and
dedicated control NAC to both activate and synchronize
the Temporal Code 4 output timing of up to 20,
4905-9835 modules
Unsynchronized operation also allows the separate and
dedicated control NAC to activate the Temporal Code 4
Description (Continued)
CO gas alarm, or fire alarm. Use of the 4905-9835
Temporal Code 4 Module allows the NFPA 720 Temporal
Code 4 signal to be generated using a standard Steady On
audible appliance NAC input. Under the fire alarm panel’s
control, the audible notification signal can be selected for a
conventional fire pulse pattern for a fire alarm condition, or
the Temporal Code 4 pattern can be activated for a CO gas
alarm condition.
output timing of up to 20, 4905-9835 modules, but
without synchronization between the modules
Stand-Alone operation allows the input NAC in alarm
to activate Temporal Code 4 timing for NACs dedicated
for CO gas alarm; no fire alarm signals are available, no
control NAC is used
For both Synchronized and Unsynchronized modes,
when the control NAC is off, the module output NACs
will follow the fire alarm signals of the input NAC
NOTE: For TC4 output, both the input NACs and the
control NACs requires a Steady On signal
Compact, sealed construction:
Mounts in standard 4” square electrical box
Screw terminals for wiring connections
Listed to UL Standard 864 and ULC Standard S527
Description
CO gas alarm warnings are required to be different from
fire alarm warnings. In the event of a CO gas alarm, the
presence of a Temporal Code 4 audible signal pattern
identifies the type of condition to the responders to assist in
determining the proper actions to be taken.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:328
for allowable values and/or conditions concerning material presented in this document. This
product was not accepted by MEA (NYC) as of document revision date. Additional listings
may be applicable; contact your local Simplex product supplier for the latest status. Listings
and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection
Products.
S4905-0006-5 4/2013
Specifications
For 24 VDC NACs, up to 3 A
NAC Control
Input NAC Current
Requirements
Control NAC Current
Requirements
Mounting Distance
to input NAC Source
Wire Connections
Dimensions
Mounting Plate
Material
Temperature Range
Humidity Range Up to 93% RH at 100° F (38° C)
maximum, limited by input NAC
rating; for control of audible
notification appliances compatible
with TC4 code pulse duty cycle
Supervisory current = 0.18 mA
Alarm current = 15 mA
Supervisory current = 0 mA
Alarm current = 3 mA
Mount close-nippled, 20 ft (6 m)
maximum distance
Screw terminals for in/out wiring,
18 to 12 AWG wire
(0.82 to 3.31 mm
4” x 4 ⅛” x 1 ⅜” D
(102 mm x 105 mm x 35 mm)
Sheet metal, galvanized
32° to 120° F (0° to 49° C),
intended for indoor operation
2
)

System Connection Reference
Dedicated control NAC
NAC input to TC4
Module, 3 A maximum
4905-9835 Temporal Code 4 (TC4) Module
4098-9798 CO
Sensor Sounder
1 2
ON
Base*
4901-9820 Horn, 4903 Series 4-wire A/V horn,
or other compatible (not SmartSync control)
24 VDC audible notification appliances
TC4 NAC output, 3 A maximum
Fire Alarm Control Panel
(4100ES shown for reference)
IDNet or RUI Communications
per system requirements
4009 IDNet NAC Extender (shown, uses IDNet
communications) or Remote 4100ES MINIPLEX
transponder with NACs (uses RUI communications)
Mounting Reference
Mounting Box (supplied separately), 4" square
(102 mm), minimum depth = 2-1/8" (54 mm),
RACO 232 or equal
TM
4009 IDNet NAC EXTENDER
Dedicated control NAC to the next Temporal
Code 4 Module, up to 20 total maximum; requires
1 2
ON
end-of-line resistor per source NAC requirements
Appliance NACs require
CAUTION
DISCONNECT
POWER
BEFORE
SERVICING
end-of-line resistor per
source NAC requirements
* Note: IDNet communications wiring
(not shown) is required to connect
to each 4098-9798 CO Sensor
Sounder Base
4" square cover plate, RACO 752
or equal (supplied separately)
Additional Reference
Document Description Document Description
579-840 Installation Instructions S4010-0004 4010ES Control Panel
S4098-0041 CO Sensor Base data sheet S4901-0010 4901-9820 Horns
S4100-0031 4100ES Basic Reference S4903-0011 4903 Series 4-wire A/Vs
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA is a trademark of the National Fire
Protection Association.
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4905-0006-5 4/2013
www.simplexgrinnell.com
© 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.