Simplex TrueAlert ES Installation Instructions Manual

Page 1
R
NFPA 72 requires that the entire lens be not less than 80 in. and not greater than 96 in. above the finished floor.
Cover.
S/V Appliance.
Building wire.
4 in. x 4 in. electrical box (2-1/8 in. deep).
Backplate.
Screws
-Use 8-32 screws for a 4 in. x 4 in. electrical box.
-Use 6-32 screws for a single or a double gang electrical box.
NFPA 72 requires that the entire lens be not less than 80 in. and not greater than 96 in. above the finished floor.
Cover.
SO Appliance.
Backplate.
4 in. x 4 in. electrical box (2-1/8 in. deep).
Building wire.
Screws
-Use 8-32 screws for a 4 in. x 4 in. electrical box.
-Use 6-32 screws for a single or a double gang electrical box.
Document: Installation instructions Product: TrueAlert ES Addressable
UL listed TrueAlert ES indoor product identification reference:
WM Speaker Indoor Notification Appliances
Type
Wall Mount
Speaker/
Visible
(S/V)
Wall Mount
Speaker Only
(SO)
Cover
colors
-Red
-White
-Red
-White
Components:
49SV-APPLW 49HFV-APPLW 49SV-APPLW-BA 49HFV-APPLW-BA
Components:
49SO-APPLW 49HF-APPLW 49SO-APPLW-BA 49HF-APPLW-BA
Models Operation
Covers:
49SVC-WRFEU 49SVC-WRFIRE 49SVC-WRS 49SVC-WWALT 49SVC-WWBA 49SVC-WWS
49SVC--WWFIRE
Covers:
49SOC-WRFEU 49SOC-WRBF 49SOC-WRBC 49SOC-WRBA 49SOC-WWS 49SOC-WWFIRE
49SOC-WRBLANK 49SOC-WRFIRE
49SVC-WRBF 49SVC-WRBC 49SVC-WRBA 49SVC-WRALT 49SVC-WWBC 49SVC-WWBF
49SVC-WWFEU
49SOC-WRS 49SOC-WWBA 49SOC-WWBC 49SOC-WWBF 49SOC-WWFEU
49SOC-WWBLANK 49SOC-WWALT 49SOC-WRALT
Backplates:
49MP-SVWR 49MP-SVWW
Backplates:
49MP-SOWR 49MP-SOWW
These appliances provide a visible (VO) or audible/visible (A/V) warning of an alarm condition when activated from the control panel of a compatible UL/ULC Listed, Simplex Fire Alarm System. Consult Simplex Fire Alarm panel documentation for compatibility information. The speakers can be turned ON/OFF individually under compatible panel control.
Note: For information about TrueAlert ES appliance testing consult TrueAlert ES Addressable Appliances Troubleshooting (579-1049).
Mounting instructions:
Kit contents: Appliance x1. Not included:
Order a Backplate separately for each appliance, with 8-32 1 inch mounting screws x2, and 6-32 1 inch mounting screws x2. Order a cover separately for each appliance. Electrical box: 4 inch square, 2-1/8 inch minimum depth required.
1. Select the mounting location and install the electrical box using screws suitable for the mounting surface.
2. Bring the building wiring through the rectangular opening in the backplate.
3. Connect the building wires to the backplate. See the wiring section on page 2.
4. Secure the backplate to the electrical box using the provided hardware. Install the backplate so that the contacts are above the opening for the wiring.
5. Set the appliance settings. See the settings section on page 3.
6. Attach the cover to the appliance.
7. Attach the assembled appliance to the backplate.
Figure 1. Mounting instructions
IMPORTANT. When the notification appliance emits light or sound, it indicates the possibility of an emergency si tuation that requires the immediate
Fire Alarm and Signaling Code (NFPA 72), ULC Standard CAN/ULC-S524: Installation of Fire Alarm System s, the appropriate model building codes, and
© 2015-2016 Tyco Fire Protection Products. All rights reserved. Specifications and other information shown were current as of publication and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauth orized use is strict ly prohibited.
so on, and specific requirements of the Local Authority Having Jurisdiction (AHJ). These Notificati on Appliances are not intend ed for installation within hazardous locations as defined by the National Electrical Code (NEC) or NFPA.
SAFETY. Always install, maintain, and test Notification Appliances within their specifications. Failure to follow all safety precautions and instructions may result in loss of life and property due to non-functioning Notification Appliances. Some Notification Appliances use high voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance Circuit is disconnected at the control panel before installing, repairing, or internally adjusting any Notifi cation Appliances. Even with electrical power removed, some Notification Appliances, such as visible strobes, store a high voltage charge. The high v oltage can cause injury re su lting in death from electri ca l s hock. DO NOT TOUCH EXPOSED CIRCUITRY.
579-1190
Rev. D
Page 2
579-1190 Installation instructions
!
SO Appliance back side.
Terminal 3: ‘NAC -’
Terminal 4: ‘NAC +’
Terminal 1: ‘Audio +’
Terminal 2: ‘Audio -’
Class A wiring, see notes.
From amplifier
Audio +/-.
From compatible SLC controller, see notes.
12
CKT CKT
S/V
56
Audio -
Audio +
To the next appliance or compatible SLC controller, see notes.
S/V Appliance back side
Terminal 5: ‘NAC -’
Terminal 6: ‘NAC +’
Terminal 1: ‘Audio +’
Terminal 2: ‘Audio -’
Audio Audio
12
CKT CKT
SO
34
12
CKT
CKT
SO
-
+
Audio
-
Audio
-
Audio
+
Audio
+
34
SLC +
SLC +
SLC -SLC -
SLC +
SLC -
SLC ­SLC +
12
CKT CKT
S/V
56
Audio
Audio
12
CKT CKT
SO
34
-
+
Audio
-
Audio
+
SLC +
SLC -
SLC +
SLC -
12
CKT CKT
S/V
56
Audio
Audio
12
CKT CKT
SO
34
-
+
Audio
-
Audio
+
SLC +SLC -
SLC +SLC -
Class B wiring, see notes.
From amplifier
Audio +/-.
From compatible SLC controller, see notes.
(T-tapping example)
Note: NAC and SLC are equivalent terms in this figure.
Audio -
Audio +
SLC ­SLC +
Audio ­Audio +
SLC ­SLC +
Wiring instructions:
WARNING: Make sure that all power is disconnected before starting the installation.
1. At the electrical box, connect the building wiring to the CKT + and CKT - terminals on the backplate.
2. To ensure proper continuity, use a torque wrench to tighten the terminal block screws to 12-15 inch-pounds.
3. Ensure that the correct polarity is maintained for each strobe unit.
4. Signal Line Circuit (SLC) wiring must be twisted pair (TWP). CKT Terminals accept 2 Wires: 12-18 American wire gauge (AWG) TWP.
IMPORTANT:
Do not bring the conduit through the rear of the electrical box. Strip the lead insulation to 7/16 inch maximum.
Wiring notes:
1. Assign a maximum of 127 active appliances to a circuit. Assign a
2. Notification appliances are rated using an individual module label.
3. Maintain the correct polarity on the terminal connections.
4. Terminals 1 through 6 each accommodate two wires, one wire going
Figure 2. Wiring instructions
maximum of 63 active strobe appliances to a powered circuit. The maximum wire resistance between appliances is 26 ohms. Refer to the Field Wiring Diagrams of the driving compatible fire alarm control panel for further instructions.
in and one wire going out to the next appliance.
5. These appliances are rated to the operating voltage limits of 23-30 VDC. The appliance can fail to operate as intended, and can cause permanent damage to this equipment if it operates outside of these limits.
6. Only operate the TrueAlert IDNAC S/V and SO using a compatible power supply and amplifier.
7. T-tapping is not permitted for Class A wiring.
8. TrueAlert SLC wiring connections are supervised and power-limited.
2
Page 3
579-1190 Installation instructions
To access the switches:
Alarm/ Alert
DIP switch 5 through 7
9
White Tinted
S/V Appliance
SO Appliance
0010 1010 0110 1110
64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79
80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95
96 97 98
99 100 101 102 103 104 105 106 107 108 109 110 111
112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127
0000 1000 0100 1100
S/V only
DIP switch shown is
set at address 7.
DIP switch value:
Reserved for future use.
switches.
Candela selection jumper and candela rating
To access the switches:
Make the audio circuit voltage and power tap selection here
C
W3
H
G
B
AD E F
T1
Audio power TAP pins (S/V & SO)
70V 1W
70V W/2
70V W/4
70V 2W 25V W/4
25V W/2
25V 1W
25V 2W
CD5 (FACP) CD4 (15) CD3 (30)
CD6 (135)
CD7 (185)
CD2 (75) CD1 (110)
Setting the address DIP switch
Each addressable TrueAlert IDNAC notification appliance has a unique address that is set using an eight-position DIP switch (ADDR1). Up to 127 unique addresses can be assigned to an SLC, however, the total appliance loading available may be less due to appliance current requirements.
To Set the address:
1. Unclip the appliance from the backplate by inserting a number 2 Phillips screwdriver, or a similar sized object into the opening at the bottom of the cover. See Figure 3.
2. Use a small screwdriver or pen to set the switches.
3. Record the set address.
4. DIP switch position 8 determines whether this appliance is viewed by the system as an 'ALARM' (OFF) or 'ALERT' (ON) type of appliance. Confirm the setting for the appliance at this address with the FACP system configuration documentation.
5. DIP position 9 selects white flash color (standard - OFF), or tinted strobe power level (ON) for use with add-on domes.
Setting the strobe candela setting
1. Jumpers are factory set as F A CP. Leave the appliance at this setting if
2. If manual selection is required, pull up the candela flag and position the
3. The candela ratings vary when colored lenses are used. Consult the
4. When the appliance is mounted, the candela rating is visible through
Note: To avoid a programming mismatch trouble, an authorized service personnel
Audio circuit configuration, S/V and SO
Move the wire harness position to the correct terminal post for audio circuit voltage and power tap selection. See Figure 4 and the speaker table on the next page.
Figure 3. Setting the DIP switch address
the candela setting is to be programmed from a 4100ES FACP. The candela setting is visible through the slot on the side of the appliance.
pins to select the correct candela setting: 15, 30, 75, 110, 135, 185 candela, or FACP.
TrueAlert ES WM S/V Colored Lens
document (579-1192) for the
specific candela ratings.
the slot on the side of the appliance.
must program one of the 6 candela outputs for each appliance. To set the candela through the Programmer, set it to FACP. For additional information refer to the 4100ES Programmer’s Manual (574-849).
3
Figure 4. Setting the strobe and appliance configuration
Page 4
R
Appliance specifications
Environmental specifications:
Rated DC Control/Strobe Voltage Range
Temperature Range Humidity Range
Connections
SPECIAL APPLICATION 23-30 VDC
32 °F to 120° F (0 °C to 49 °C)
10 % to 93 %, non-condensing at 104 °F (40 °C)
Terminal for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm2)
CAUTION:
• The appliances are available in Red and White. Do not paint or otherwise alte r the fac t or y finishes in any way.
Maximum RMS operating current Candela
selection†
15 cd S/V 47 mA 54 mA 30 cd S/V 57 mA 78 mA
75 cd S/V 100 mA 128 mA 110 cd S/V 132 mA 184 mA 135 cd S/V 160 mA 211 mA 185 cd S/V 208 mA -NA-
Speaker Only SO 9 mA -NA­* For connection to IIDNAC SLCs
† The use of optional colored lenses can affect the device’s candela output. To find the candela output for each color consult the T rueAlert ES
WM S/V Colored Lens
Appliance type
document (579-1192).
UL1971/ULCS526 Clear/White
23V* 23V*
UL1638/ULCS526 Colored Lens
Percent of rated light output at any candela setting
(room temperature)
Vertical dispersion Horizontal dispersion
Y-Plane
Angle
0 100 % 194 % 0 100 % 194 %
5 90 % 192 % ±5 90 % 203 % 10 90 % 132 % ±10 90 % 168 % 15 90 % 129 % ±15 90 % 155 % 20 90 % 145 % ±20 90 % 166 % 25 90 % 150 % ±25 90 % 169 % 30 90 % 112 % ±30 75 % 164 % 35 65 % 124 % ±35 75 % 151 % 40 46 % 114 % ±40 75 % 145 % 45 34 % 90 % ±45 75 % 121 % 50 27 % 91 % ±50 55 % 97 % 55 22 % 78 % ±55 45 % 83 % 60 18 % 72 % ±60 40 % 79 % 65 16 % 68 % ±65 35 % 70 % 70 15 % 75 % ±70 35 % 59 % 75 13 % 74 % ±75 30 % 50 % 80 12 % 68 % ±80 30 % 51 % 85 12 % 63 % ±85 25 % 45 % 90 12 % 45 % ±90 25 % 41 %
UL Req
Output
Typical Output
X-Plane
Angle
UL Req
Output
Typical Output
Wall speaker specifications
Input Voltage
25 VRMS or 70.7 VRMS - Speakers are for connection to compatible fire alarm audio circuits.
Power Taps via Jumper J1 1/4 W, 1/2 W, 1 W and 2 W Frequency
Response
Fire Alarm 400 Hz to 4000 Hz [SV/SO]; 200 Hz to 10000 Hz [HFV/HF] General Signaling 125 Hz to 12 kHz
TrueAlert Addressable Wall Mount S/V and SO Units - speaker jumper setting (25 V or 70 V audio)
UL1480 at 10 ft ULC-S541 at 3 m
Voltage
Jumper J1
to Tap
T ap setting
in Watts
HiSPL (SV/SO)
Models
HiFi (HFV/HF)
Models
HiSPL (SV/SO)
Models
HiFi (HFV/HF)
Models
A/E 1/4 79 76 80 76
Speaker
Only
B/F 1/2 83 80 84 79 C/G 1 87 83 88* 82 D/H 2 90 86 91* 85*
A/E 1/4 79 76 81 78
Speaker
Visible
B/F 1/2 83 80 84 81 C/G 1 86 82 88* 84 D/H 2 89 86 90* 87*
NOTES:
• Reverberant
• Anechoic dBA measurements are a minimum ULC rating based on sound pressure level measurements made in ULC’s anechoic test chamber.
• The sound pressure level decreases by 3 dB at an angular displacement of 75° from the line perpendicular to the speaker’s center. The SPL decreases by 6 dB at an angle of 85° from that line.
* Only marked settings may be used for ULC fire alarm applications.
dBA measurements are a minimum UL rating based on sound level measurements made in UL’s reverberant test chamber.
579-1190
Rev. D
Loading...