Simplex TrueAlert 49HF-APPLW User guide

TrueAlert Addressable Notification Appliances
UL, ULC Listed* Wall and Ceiling Mount Addressable Speaker
and Speaker Visible Notification Appliances
Features
Individually addressed and controlled Speaker (S/O) and Speaker Visible (S/V) notification appliances
Advanced addressable notification controlled by IDNAC
SLCs provides regulated 29 VDC for low current operation even under battery backup.
allows audio wiring to be T-tapped for class B wiring, reducing wiring costs and wiring distances.
Speaker selectivity is controlled by the panel. Only those
speakers that are needed are connected to the audio NAC.
Separate appliance and cover selection greatly simplifies
the ordering and installation process.
Strobe intensity can be programmed from the control
panel or the device for S/V models.
Self-Test Mode allows on-board sensors to detect the
strobe and speaker output and then report their status to the control panel.
Wiring terminals separate from the Audio terminals. TrueAlert Device Reports at the control panel detailing
appliance point ID, custom label, type, and candela setting.
Magnet test diagnostics to assist checkout and testing of
appliances and wiring.
Compatibility with ADA requirements.
LED indicator and magnet test feature
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address and pulses to indicate the intensity selection; a brief output of the strobe is also selectable to confirm operation
Mechanical design features
Rugged, high impact, flame retardant thermoplastic
housings are available for wall or ceiling mount models
Covers are available in red or white with various
lettering options
Covers can be easily removed without disturbing the
connected housing and avoiding trouble conditions
In/out wiring terminals for 18 AWG to 12 AWG Mounts to 4” square 2 ” gang US electrical boxes
* Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
S49SWC-0001-1 11/2015
Ceiling and Wall Mount Addressable Speaker Only and
Speaker Visible Strobes
Features (Continued)
Speaker design features
High quality voice and tone reproduction with taps for
¼, ½, 1, or 2 W, at 25 or 70.7 VRMS
Speakers have capacitor input for connection to DC
supervised NACs and are wired separately from strobes
Listed to UL 1480 and ULC S541* Compliant with NFPA 72, 520 Hz Low Frequency
Signal Requirements for Sleeping Areas
High and low frequency response models available,
200-10000 Hz and 400-4000 Hz respectively.
Description
Wall and ceiling mount addressable speaker and speaker visible appliances provide convenient
installation to standard electrical boxes. The speaker is individually addressed and individually controlled with power, supervision, and control supplied from a Simplex fire alarm control panel IDNAC Signaling Line Circuit (SLC). Audio is provided by a panel that supports audio output or from a separate audio source. Appliances use a multi-tapped speaker for audio/tone notification.
Strobe Application Reference
Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications of: the National Fire Alarm and Signaling Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).
IDNAC SLC Operation Advantage
TrueAlert Addressable speaker and speaker visible appliances on IDNAC SLCs provide visible
and audio notification using two separate two-wire circuits that also confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit supervision integrity by providing supervision that extends beyond the appliance wiring connections. Reduced current usage on IDNAC SLCs A constant 29 VDC source voltage is maintained, even during battery standby. This allows appliances to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, use of smaller gauge wiring, or combinations of these benefits.
Reducing Installation and Testing Time
With separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of the magnet test feature improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.
TrueAlert Addressable Wiring Isolator
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. Refer to data sheet S4905-0001 for additional information.
TrueAlert ES Diagnostics
Test Features
Controllers can be selected to pulse each appliance’s LED when it receives a supervision poll. When the controller is selected for diagnostic mode, the appliance magnet test feature provides a response at the individual appliance being tested.
Silent Appliance Magnet Test
The appliance LED pulses sequentially to conveniently indicate the appliance’s address when a magnet is applied.
Operational Appliance Testing In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to indicate proper operation.
TrueStart Instrument Two (TSIT)
The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert (and TrueAlert ES) appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.
Wall Mount Appliance Product Selection
Wall Mount S/O Appliances* (Refer to data sheet S49SOW-0001 for full product selection including covers and mounting plates)
Model Dimensions Description Data Sheet Reference
49SO-APPLW(-BA) 49HF-APPLW(-BA) High fidelity S/O appliance only
Wall Mount S/V Appliances* (Refer to data sheet S49SVW-0001 for full product selection including covers, mounting plates, and
multi-color strobe lens)
Model Series Dimensions Description Data Sheet Reference
49SV-APPLW(-BA) 49HFV-APPLW(-BA) High fidelity S/V appliance only *Note: Wall mount models require separately ordered back plate. See related datasheet for details.
5 ½” H x 5” W x 1 ½” D (139 mm x 128 mm x 38 mm)
7 ” H x 5” W x 1 ¾” D (187 mm x 128 mm x 43 mm)
S/O appliance only
S/V appliance only
S49SOW-0001
S49SVW-0001
Ceiling Mount Appliance Product Selection
Ceiling Mount S/O Appliances (Refer to data sheet S49SOC-0001 for full product selection and installation requirements)
Model Dimensions Description Data Sheet Reference
49SO-APPLC(-BA) 49HF-APPLC(-BA) High fidelity S/O appliance only
Ceiling Mount S/V Appliances (Refer to data sheet S49SVC-0001 for full product selection and installation requirements)
Model Series Dimensions Description Data Sheet Reference
49SV-APPLC(-BA) 49HFV-APPLC(-BA) High fidelity S/V appliance only 49SVH-APPLC(-BA) High candela S/V appliance only
49HFVH-APPLC(-BA)
49HFVH-APLCA-BA
49HFVH-APLCB-BA Note: Select appliance, cover and mounting back plate (where required) separately. (-BA) indicates model is available either with or
without the -BA suffix. Model numbers ending in -BA are assembled in the USA
7 ” H x 7 ” W x 1 ¼” D ( 180 mm x 180 mm x 32 mm)
8 ” H x 7 ” W x 3” D (206 mm x 180 mm x 76 mm)
S/O appliance only
S/V appliance only
Clear lens high fidelity high candela S/V appliance only Amber lens high fidelity high candela S/V appliance only Blue lens high fidelity high candela S/V appliance only
S49SOC-0001
S49SVC-0001
2 S49SWC-0001-1 11/2015
IDNAC SLC Controller Compatibility Reference
Compatible Controllers
4100ES with EPS+ or EPS Power Supply S4100-0100 4009 IDNAC Repeater S4009-0004
4100ES Flex 50 Amplifiers 4100ES Constant Supervision and Signal Cards
Data Sheet
Reference
S4100-0034
Controller Output
IDNAC SLC
IDNAC SLC Output
Voltage
29 VDC
(regulated)
Appliance Voltage
Design Reference
23 VDC
(with 6 VDC drop)
Specifications
General Specifications (refer to individual model data sheets for further specifications, install and operation details)
Typical Operating Voltage Range Environmental 32° to 120° F (0° to 49° C); 10% to 93%, non-condensing at 104° F (40° C)
Connections
IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads. See device and compatible fire panel
23 - 30 VDC, Special Application
Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per terminal for in/out wiring. Use Unshielded Twisted Pair (UTP) for IDNAC and audio wiring.
installation instructions for circuit current load limits.
Speaker Specifications
Input Voltage 25 or 70.7 Vrms Power Taps ¼, ½, 1, and 2 W
Frequency Response
400 to 4000 Hz and 200 to 10000 Hz, respectively.
General Signaling = 125 to 12 kHz
Strobe Specifications
Typical Operating Voltage Range 23 - 30 VDC, Special Application Supervisory Requirements 1 unit load (= 0.8 mA control panel current) Flash Rate 1 Hz
UTP, unshielded twisted pair recommended
IDNAC SLC Wiring Specifications (refer to control panel installation instructions for more information)
Note: Speakers are for connection to compatible fire alarm audio circuits only.
Maximum wire length allowed with “T-Taps” for Class B wiring per SLC = 10,000 ft
(3048 m)
Maximum wire length to any appliance = 4000 ft (1219 m). This can be doubled to 8000ft (2438m) by using a 4009 IDNAC Repeater.
S49 Series Speaker Datasheet Reference
Model Data Sheet Reference
Wall Mount Speaker Only Appliance S49SOW-0001 Wall Mount Speaker Visible Appliance S49SVW-0001 Ceiling Mount Speaker Only Appliance S49SOC-0001 Ceiling Mount Speaker Visible Appliance S49SVC-0001
3 S49SWC-0001-1 11/2015
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S49SWC-0001-1 11/2015
www.simplex-fire.com
© 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Loading...