Simplex TrueAlert 4906-9208, TrueAlert 4906-9211, TrueAlert 4905-9837, TrueAlert 4905-9847, TrueAlert 4905-9840 Instructions Manual

UL, ULC, CSFM Listed* Dual Emergency Communication
Appliances, Clear/Amber Strobes
Features
Individually addressed and separately controlled multi-candela V/O (visible only) notification appliance with one amber ALERT strobe and one clear lens FIRE strobe provides:
Combination unit allows mounting two visible
notification appliances at the same installation site
flash rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, or 110 cd
Advanced addressable notification controlled by IDNAC
SLCs from Simplex
with EPS/EPS+ power supplies (and 4009 IDNAC Repeaters) providing regulated 29 VRMS allowing strobes to operate with lower current even under battery backup
Amber lens with “ALERT” lettering produces a signal
unique from clear lens fire alarm evacuation strobes for use with Emergency Communications Systems
Clear lens with “FIRE” lettering provides visible
notification for fire alarm conditions
Both strobes connect on same SLC, are separately
addressed, and provide independent operation; (Operation is clear/Fire OR amber/Alert, not both)
Wiring supervision to each strobe allowing
“T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)
TrueAlert Device Reports at the control panel
detailing appliance point ID, custom label, type, and candela setting (see sample on page 2)
Magnet test diagnostics to assist checkout and testing
of appliances and wiring
Compatibility with ADA requirements; (refer to
important installation information on page 3)
Compatibility with legacy TrueAlert addressable
systems for upgrade and replacement (see page 4)
Clear lens strobe is UL listed to Standard 1971, ULC
listed to Standard S526
Amber lens strobe is UL listed to Standard 1638 (due to
non-white lens); and provides light dispersion patterns of UL Standard 1971; ULC listing is to Standard S526
LED indicator and magnet test feature:
Each appliance LED can be selected to display each
polling cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address AND pulses to indicate the intensity selection; a brief output of the strobe is also selectable to confirm operation
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:235 for allowable values and/or conditions concerning material presented in this document. FM approval and MEA (NYC) acceptance is not applicable. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
S4906-0009-3 3/2014
®
4100ES fire alarm control panels
TrueAlert Addressable Notification Appliances
Combination Clear/Amber Strobe Assembly (front and
side view shown, available with red or white housing)
Mechanical design features:
Rugged, high impact, flame retardant thermoplastic
housing for flush or surface wall mount; available with red or white housing
Individual strobe housings mount onto a common
bracket that does not extend into box and easily mounts to standard electrical boxes
Wall mount wiring terminal access is from front of
housing to assist installation, inspection, and testing
Mounting options include adapter skirts for surface
mounting and box adapter plates
Description
Multi-Candela TrueAlert addressable combination strobes are individually addressed and individually
controlled with power, supervision, and control supplied from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 4.) A single assembly provides an amber lens strobe for non-fire alarm, alert notification for use with Emergency Communications Systems, and a clear lens strobe for fire alarm notification.
Strobe Application Reference
Amber strobes used as part of an Emergency Communications system are located to provide the same area coverage as required of clear lens fire alarm strobes. Specific Emergency Communications requirements are discussed in detail in document UFC 4-021-01 (USA Department of Defense, United Facilities Criteria) and in NFPA 72, Chapter 24 (2010 and 2013 editions).
Proper strobe coverage criteria is further described in the National Fire Alarm Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).
P
1
-
Mar-1
4
T
V
A
A
A
IDNAC SLC Operation Advantage
TrueAlert V/O Appliances with Addressable Strobes on IDNAC SLCs provide visible notification
using a single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit
supervision integrity by providing supervision that extends beyond the appliance wiring connections.
Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VRMS
source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power an d seco ndary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.
Reducing Installation and Testing Time. With separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of the magnet test feature improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.
By providing an amber lens strobe with a clear lens strobe, the combination strobe assembly allows a single electrical installation to provide both types of visible notification.
TrueAlert Addressable Diagnostics
Test Features. Controllers can be selected to pulse each
appliance’s LED when it receives a supervision poll. When the controller is selected for diagnostic mode, the appliance magnet test feature provides a response at the individual appliance being tested.
Silent Appliance Magnet Test. In this test mode, in response to the magnet test, the appliance LED pulses sequentially to conveniently indicate the appliance’s address.
Operational Appliance Testing. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert (and TrueAlert ES) appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.
TrueAlert Addressable Wiring Isolator
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate short circuited wiring from functionin g wi ri n g. (R efer t o dat a sheet S4905-0001 for additional information.)
TrueAlert Device Reports detail type, candela rating,
and location per appliance (see sample below, amber lens type is AMB).
Product Selection
Model
4906-9208 Red
4906-9211 White
4905-9837 Red
4905-9847 White
4905-9840 Red
Housing
Color
Description Dimensions
Multi-Candela Addressable Combination Strobe assembly with amber lens, ALERT strobe on top and clear lens, FIRE strobe on bottom; intensity selectable as: 15, 30, 75, or 110 candela
Surface Mount Adapter Skirt, use to cover surface mounted electrical boxes
Adapter Plate for mounting to installed Simplex Model
2975-9145 box; for flush mounted boxes only
TrueAlert Device Reports Reference
Service Port REPORT 5 : TrueAlert Device Report
POINT ID CUSTOM LABEL T14-1-1 Location Label . . . up to 40 characters T14-1-2 Break Room 5 T14-1-3 Boiler Room Fire T14-1-4 Boiler Room Alert
10 ¾” H x 5 ” W x 3 (273 mm x 130 mm x 100 mm)
10 ½” H x 5 ¼” W x 1 ¾” D (267 mm x 133 mm x 44 mm)
Total depth with strobe assembly = 5 ” (143 mm)
5
12
16
(313 mm x 146 mm x 1.5 mm)
2:34:56am MON 17
DEVICE
YPE
/O 15 /V 110 /V 75 MB 75
15
⁄16” D
” H x 5 ¾” W x 0.06 thick
CANDELA
age 1
2 S4906-0009-3 3/2014
Strobe Details and Mounting Height Reference
Strobe Details
Hole for bracket
Transparent
housing and lens
assembly (clear
4
for FIRE, amber
for ALERT)
Wiring
access hole
Wiring
terminals
LED indicator
Address setting
DIP switch
Hole for bracket mounting
Intensity selection plug, accessible
only from rear of housing; factory
setting is FACP, controlled by panel
Strobe intensity viewing slot
mounting
3
2
1
110 75 30 15
FACP
WALL MOUNT INSTALLATION
Adapter skirt (shown
for reference)
Clear/Amber
Strobe assembly
5" (127 mm)
Bottom of FIRE lens is either
even with, or slightly above
bottom of 4" square boxes and
3-gang surface mount box
NFPA 72 requires that the
entire FIRE lens be not less
than 80" and not greater
than 96" above the finished
floor
IMPORTANT!
HEIGHT REFERENCE
3-gang box outline, surface mount
4-gang box outline, flush mount
4" square box outline, flush mount or surface mount
81" (2.06 m) minimum for
80" (2.03 m)
4-gang flush
minimum for
4" square box
and 3-gang surface
mount box
mount box
Installation Reference
Screw (1) to attach
cover, and screws
(4) to attach strobes
to bracket (supplied)
Housing cover
(supplied)
Optional Adapter Skirt for
Amber lens
strobe (supplied)
Magnetic test locations
Alternate surface mount electrical boxes, 3-gang mounted
vertically; Steel City 3G-1/2 (or 3/4), or Raco 952; 8-5/8" x 4-1/
2" x 1-5/8" deep (219 mm x 114 mm x 41 mm), by others
surface mounted boxes
(ordered separately)
4" (102 mm) square box for flush 1-1/2" (38 mm) deep, by others
Mounting bracket (supplied)
Clear lens strobe (supplied)
mounted vertically; Steel City 4G4D 1/2; 7-5/8" x 4"
x 2-1/8" D; (194 mm x 102 mm x 54 mm), by others
mount or surface mount,
Alternate flush mount electrical box, 4-gang
3 S4906-0009-3 3/2014
TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference
Compatible Controller
4100ES with EPS+ or EPS Power Supply S4100-0100
4009 IDNAC Repeater S4009-0004
Data Sheet
Reference
Controller
Output
IDNAC SLC
IDNAC SLC
Output Voltage
29 VRMS
(regulated)
Appliance Voltage
Design Reference
23 VRMS
(with 6 VRMS drop)
Specifications
Common Specifications (see page 2 for appliance dimensions)
Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C) Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per terminal for in/out wiring
Clear/Amber Strobes 579-847
Installation Instruction Reference
Strobe Specifications
Typical Operating Voltage Range
Supervisory Requirements 1 unit load each, 2 unit loads total per 4906-9208
Flash Rate and Synchronized SLC Loading Candela Setting 15 cd 30 cd 75 cd 110 cd
23 VRMS Current Ratings, for connection to IDNAC Addressable SLCs
Note: Amber strobes and clear strobes provide notification for two different functions and are not activated at the same time.
Adapter Skirts 574-790
Adapter Plate 574-791
23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating)
1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30 resistance between appliances
50 mA 75 mA 137 mA 190 mA
TrueAlert Strobe LEGACY Compatibility Reference
Compatible Controller
4100ES or 4100U with TrueAlert Power Supply S4100-0031
TrueAlert Addressable Controller (4009T) S4009-0003
Electrical Ratings Difference for Retrofit Applications
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting 15 cd 30 cd 75 cd 110 cd
17 VRMS Current Ratings, use when connected
to TrueAlert Addressable SLCs per above
Data Sheet
Reference
64 mA 98 mA 187 mA 253 mA
Controller Output
TrueAlert
Addressable SLC
Available Strobe
Intensity
15, 30, 75, and
110 cd
Appliance Voltage
Minimum
VRMS 4009 TPS, Remote TrueAlert Power Supply S4100-0037
17
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4906-0009-3 3/2014
www.simplexgrinnell.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Loading...