Simplex TrueAlert 4906-9202, TrueAlert 4906-9204, TrueAlert 4905-9910, TrueAlert 4905-9926 Instructions Manual

TrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved; Multi-Candela Visible Only (V/O) MEA (NYC) Acceptance* Appliances (Strobes), Ceiling Mount
Features
Individually addressed and controlled multi-candela V/O (visible only) notification appliances provide:
Multi-candela xenon strobe with synchronized 1 Hz
flash rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, or 110 cd
Advanced addressable notification controlled by IDNAC
SLCs from Simplex
®
4100ES fire alarm control panels
with EPS/EPS+ power supplies (and 4009 IDNAC Repeaters) providing regulated 29 VRMS allowing strobes to operate with lower current even under battery backup
Wiring supervision to each strobe allowing
“T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)
TrueAlert Device Reports at the control panel
detailing appliance point ID, custom label, type, and candela setting (see sample on page 2)
Magnet test diagnostics to assist checkout and testing
of appliances and wiring
Compatibility with ADA requirements Compatibility with legacy TrueAlert addressable
systems for upgrade and replacement (see page 3)
UL listed to Standard 1971 and ULC-S526*
LED indicator and magnet test feature:
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address AND pulses to indicate the intensity selection; a brief output of the strobe is also selectable to confirm operation
Mechanical design features:
Rugged, high impact, flame retardant ceiling mount
thermoplastic housings are available in red or white
Rear of housing does not extend into box and easily
mounts to standard electrical boxes
Mounting options include red wire guards and
adapters for surface mounted electrical boxes
See page 2 for wire guard listings. This product has been approved by the California State
*
Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:235 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
Ceiling Mount Addressable V/Os
Description
Multi-Candela TrueAlert addressable strobes
provide convenient installation to standard electrical boxes. The strobe is individually addressed and individually controlled with power, supervision, and control supplied from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 3.)
Strobe Application Reference
Proper selection of visible notification is de p endent on occupancy, location, local codes, and proper applications of: the National Fire Alarm and Signaling Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).
IDNAC SLC Operation Advantage
TrueAlert addressable appliances on IDNAC SLCs
provide separate visible (and audible) notification using a single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit supervision integrity by providing supervision that extends beyond the appliance wiring connections.
Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VRMS
source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power an d seco ndary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.
S4906-0004-3 5/2013
P
1
-
May-13
T
V
A
A
A
IDNAC SLC Operation Advantage (Cont’d)
Reducing Installation and Testing Time. With
separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of the magnet test feature improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.
TrueAlert Addressable Wiring Isolator
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. (Refer to data sheet S4905-0001 for additional information.)
TrueAlert Addressable Diagnostics
Test Features. Controllers can be selected to pulse each
appliance’s LED when it receives a supervision poll. When the controller is selected for diagnostic mode, the appliance magnet test feature provides a response at the individual appliance being tested.
Silent Appliance Magnet Test. In this test mode, in response to the magnet test, the appliance LED pulses sequentially to conveniently indicate the appliance’s address.
Operational Appliance Testing. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert (and TrueAlert ES) appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.
Product Selection
Multi-Candela Ceiling Mount Addressable Strobe
Model
4906-9202 Red White
4906-9204 White Red
Housing
Color
“FIRE” Lettering Dimensions Description
4 ¾” x 2
(121 mm x 75 mm x 67 mm)
5
⁄16” x 2 ” D
Multi-Candela Addressable Strobe; intensity selectable as: 15, 30, 75, or 110 candela
V/O Adapters (see diagram on page 3)
Model Description Dimensions
4905-9910
Ceiling Mount, Surface Mount Adapter Plate, zinc plated; required for ceiling surface mount
4 ” x 3 ” (124 mm x 79 mm)
Wire Guards (see diagram on page 3)
Model Description Dimensions
4905-9926*
* UL listed by Space Age Electronics Inc.
Ceiling Mount Red wire guard with mounting plate, compatible with semi-flush or surface mounted boxes
6 ” x 4 ” x 2
(156 mm x 111 mm x 73 mm)
TrueAlert Device Reports Reference
Service Port REPORT 5 : TrueAlert Device Report
POINT ID CUSTOM LABEL T14-1-1 Location Label . . . up to 40 characters T14-1-2 Break Room 5 T14-1-3 Boiler Room T14-1-4 Elec. Room 7
DEVICE
YPE
/O 15 /V 110 /V 75 /V 30
2:34:56am MON 20
CANDELA
age 1
2 S4906-0004-3 5/2013