Simplex TrueAlert 4906-9228, TrueAlert 4906-9230, TrueAlert 4905-9927, TrueAlert 4905-9928, TrueAlert 4905-9915 Instructions Manual

...
TrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved; Multi-Candela Audible/Visible MEA (NYC) Acceptance* (A/V) Appliances; Ceiling Mount
Features
Individually addressed and controlled multi-candela A/V (audible/visible) notification appliances provide:
Multi-candela xenon strobe with synchronized 1 Hz
flash rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, or 110 cd
Advanced addressable notification controlled by
IDNAC SLCs from Simplex
®
4100ES fire alarm control
panels with EPS/EPS+ power supplies (and 4009 IDNAC Repeaters) providing regulated 29 VRMS allowing strobes to operate with lower current even under battery backup
Wiring supervision to each strobe allowing “T-tapped”
connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)
TrueAlert Device Reports at the control panel
detailing appliance point ID, custom label, type, and candela setting (see sample on page 2)
Magnet test diagnostics to assist checkout and testing
of appliances and wiring
Compatibility with ADA requirements Compatibility with legacy TrueAlert addressable
systems for upgrade and replacement (see page 4)
Strobe operation listed to UL Standard 1971 and ULC
Standard S526
Horn operation listed to UL Standard 464 and ULC
Standard S525
LED indicator and magnet test feature:
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address AND pulses to indicate the intensity selection; a brief output of the strobe and the horn is also selectable to confirm operation
Mechanical design features:
Rugged, high impact, flame retardant thermoplastic
housings are available in red or white
Rear of housing does not extend into box and easily
mounts to standard electrical boxes
Mounting options include red wire guards and
adapters for surface mount electrical boxes
Audible notification appliance (horn):
Low current electronic horn with harmonically rich
output sound for either coded or steady operation
Horns sound as Temporal or March Time pattern
(60 or 120 BPM), or on continuously, controlled separately from visible appliances on the same two-wire circuit
Output is “high” or “low” (~5 dBA difference);
IDNAC SLC control selects output per device
Ceiling Mount Addressable A/Vs
Description
Multi-Candela TrueAlert addressable A/Vs provide
convenient installation to standard electrical boxes. Operation is individually addressed and individually controlled with power, supervision, and control supplied from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 3.)
Strobe Application Reference
Proper selection of visible notification is de p endent on occupancy, location, local codes, and proper applications of: the National Fire Alarm and Signaling Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).
IDNAC SLC Operation Advantage
TrueAlert A/V Addressable Appliances on IDNAC SLCs provide audible and visible notificat i on usi n g a
single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit.
This operation increases circuit supervision integrity by providing supervision that extends beyond the appliance wiring connections.
See page 2 for wire guard listings. This product has been approved by the California State
*
Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:239 for allowable values and/or conditions concerning material presented in this document. Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
Accepted for use – City of New York Department of
S4906-0005-3 5/2013
P
1
-
May-13
T
V
A
A
A
IDNAC SLC Operation Advantage (Cont’d)
Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VRMS
source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power an d seco ndary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.
Reducing Installation and Testing Time. With separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of the magnet test feature improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.
Product Selection
TrueAlert Addressable Wiring Isolator
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. (Refer to data sheet S4905-0001 for additional information.)
TrueAlert Addressable Diagnostics
Test Features. Controllers can be selected to pulse each
appliance’s LED when it receives a supervision poll. When the controller is selected for diagnostic mode, the appliance magnet test feature provides a response at the individual appliance being tested.
Silent Appliance Magnet Test. In this test mode, in response to the magnet test, the appliance LED pulses sequentially to conveniently indicate the appliance’s address.
Operational Appliance Testing. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash and the horn will briefly sound to indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert (and TrueAlert ES) appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.
Multi-Candela Ceiling Mount Addressable A/Vs
Model
4906-9228 Red White
4906-9230 White Red
Housing
Color
“FIRE”
Lettering
Description Dimensions
Addressable Horn with Multi-Candela Strobe; intensity selectable as: 15, 30, 75, or 110 candela
4 ¾ L” x 6 ” W x 2 ” D
(121 mm x 175 mm x 67 mm)
Wire Guards and Ceiling Mount A/V Adapter
Model Description Dimensions
4905-9927* Red Wire Guard for mounting to flush mounted electrical box
4905-9928* Red Adapter Plate, required for surface mount guard 9” x 7” (229 mm x 178 mm)
4905-9915 White
4905-9916 Red
* UL listed by Space Age Electronics Inc.
Surface Mount Adapter Box Extension, use to cover 1-1/2” deep surface mounted boxes
(121 mm x 175 mm x 38 mm)
8 ½” x 6 ” x 3”
(216 mm x 156 mm x 76 mm)
4 ¾" x 6 " x 1 ½" deep,
TrueAlert Device Reports Reference
Service Port REPORT 5 : TrueAlert Device Report
POINT ID CUSTOM LABEL T14-1-1 Location Label . . . up to 40 characters T14-1-2 Break Room 5 T14-1-3 Boiler Room T14-1-4 Elec. Room 7
DEVICE
YPE
/O 15 /V 110 /V 75 /V 30
2:34:56am MON 20
CANDELA
age 1
2 S4906-0005-3 5/2013
Ceiling Mount A/V and Guard Installation Reference
4" (102 mm) square box, 1-1/2" (38 mm) minimum depth
Ceiling reference, flush mounted box
Optional 4905-9915 (white) or 4905-9916 (red) Adapter, recommended for surface mounted box
Ceiling reference, surface mounted box
Wiring terminals and address setting are located behind the housing
Magnetic test area
Optional 4905-9927
Red Wire Guard
End View
Strobe intensity viewing slot
110753015FACP
Strobe housing straight-on view
Intensity selection plug, accessible only from rear of lens housing; factory setting is FACP, controlled by panel
LED indicator
TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference
Optional 4905-9928 Adapter Plate, required for surface mounted electrical box
Four mounting clamps included, two each side
Compatible Controller
Data Sheet
Reference
4100ES with EPS+ or EPS Power Supply S4100-0100
4009 IDNAC Repeater S4009-0004
Controller
Output
IDNAC SLC
IDNAC SLC
Output Voltage
29 VRMS
(regulated)
Appliance Voltage
Design Reference
23 VRMS
(with 6 VRMS drop)
Specifications
General Specifications (see page 2 for dimensions)
Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections
Terminal blocks for 18 AWG to 12 AWG (0.82 mm terminal for in/out wiring
Reference Installation Instructions 579-808
Electrical Specifications
Typical Operating Voltage Range
Flash Rate and Synchronized SLC Loading
Candela Setting 15 cd 30 cd 75 cd 110 cd Horn Output Selection High Low High Low High Low High Low
23 VRMS Current Ratings, for connection to IDNAC Addressable SLCs, horn steady on
Horn Output Characteristics 2400 to 3700 Hz sweep, modulated at 120 Hz rate
Sound Type (see Note)
Horn Output Ratings
@ 10 ft (3 m)
Reverberant Chamber,
Setting High Low High Low
UL 464 Test
Anechoic Chamber 90 dBA 84 dBA 86 dBA 80 dBA
23 VRMS to 31 VRMS, Special Application (see page 4 for 17 VRMS rating) 1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30
resistance between appliances
75 mA 70 m A 110 mA 105 mA 198 mA 193 mA 250 mA 245 mA
Steady Coded
84.6 dBA 79.1 dBA 80.6 dBA 75.5 dBA
2
to 3.31 mm2); two wires per
Note: Coded horn values are typical of the output measured with a Temporal or March Time pattern and with a sound level meter
reading on a “fast” setting. Under the same test conditions, coded horn output “peak” sound level readings are typically 4 dBA higher.
3 S4906-0005-3 5/2013
TrueAlert Strobe LEGACY Compatibility Reference
Compatible Controller
Data Sheet
Reference
4100ES or 4100U with TrueAlert Power Supply S4100-0031
TrueAlert Addressable Controller (4009T) S4009-0003
Electrical Ratings Difference for Retrofit Applications
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting
15 cd 30 cd 75 cd 110 cd
Horn Output Selection High Low High Low High Low High Low
17 VRMS Current Ratings, use when connected
to TrueAlert Addressable SLCs per above
82 mA 77 mA 135 A 130 mA 249 mA 244 mA 335 mA 330 mA
Controller Output
TrueAlert
Addressable SLC
Available Strobe
Intensity
15, 30, 75, and
110 cd
Appliance Voltage
Minimum
VRMS 4009 TPS, Remote TrueAlert Power Supply S4100-0037
17
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4906-0005-3 5/2013
www.simplexgrinnell.com
© 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.