Simplex TrueAlarm 4008-9102, TrueAlarm 4008- 9121, TrueAlarm 4008-9101, TrueAlarm 4008-9122 User Manual

TrueAlarm Addressable Fire Alarm Control Panels
UL, ULC, CSFM Listed; FM Approved; 4008 Fire Alarm Control Panel for IDNet Addressable MEA (NYC) Acceptance* Devices and TrueAlarm Addressable Smoke Detection
Features
Control panel operator convenience features:
Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel status information
Operation is programmable using a multi-function
RS-232 service port provides upload/download PC
access for panel configuration and event history logs
Software updates are via PC download Convenient library of standard custom label terms Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
WALKTEST silent or audible system test Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Addressable Devices:
Using IDNet communications, up to 200 addressable
TrueAlarm detection points or addressable device points are available (see page 3 for details)
Two Standard Notification Appliance Circuits (NACs):
Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
®
Selectable for Simplex
SmartSync two-wire
horn/strobe control or synchronized strobe control
FIRE
SYSTEM
SYSTEM
ALARM
ALARM
SUPERVISORY
TROUBLE
SILENCEDACPOWER
ALARM
SUPV
TROUBLE
ALARM
ACK
SYSTEM
ACK
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND A. C. POWER
SERVICING
BEFORE
4008-9102 (Beige) Standard Control Panel
Fire Alarm Annunciator
FIRE
SYSTEM
SYSTEM
ALARM
ALARM
SUPERVISORY
TROUBLE
SILENCEDACPOWER
ALARM
SUPV
TROUBLE
ALARM
ACK
SYSTEM
ACK
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND A. C. POWER
SERVICING
BEFORE
Standard Power Supply:
Provides 3 A maximum @ nominal 24 DC Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
Programmable Active Status Reminder Two auxiliary relays NACs, Relay outputs, and communications circuits
are power limited (AC input, battery circuits, and City Circuit Module outputs are non-power limited)
Available with beige or red cabinet UL listed to Standard 864
Available option modules:
Door mounted 24 LED annunciator (standard on ULC
models)
3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
City Interface Module and Auxiliary Relay Module Remote LCD and LED/Switch Annunciators
S4008-0001-8 8/2012
4008-9122 (Beige) Control Panel with 24 LED Annunciator
(required for ULC applications)
Description
For areas requiring up to 200 addressable input devices and up to 4 NACs, the Simplex 4008 Series fire alarm control panels provide flexible initiating circuit monitoring, extensive programmable control capability, and LCD annunciated circuit-specific 20 character custom labels.
* See page 2 for additional ULC and MEA information. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Standard Feature Details
Addressable operation is provided by an IDNet
signaling line circuit (SLC) capable of communicating to up to 200 addressable devices (points). Addressable devices include: TrueAlarm smoke detecti on, heat detection, and duct detection; supervised addressable modules for single and multiple contact monitoring, manual stations, isolation modules, and a remote signal module (see list on page 4.) (Please note that this panel provides a limited TrueAlarm operation feature set. For larger applications that require the full comp lement of TrueAlar m features, contact your local Simplex product supplier.)
Two, 2 A On-Board NACs provide conventional reverse
polarity operation, selectable as Class A or Class B, with electronic control and overcurrent protection. Operation is selectable for synchronized strobe or SmartSync horn/strobe two wire operation. Horn cont rol can be selected at the panel for: Temporal pattern coding, Steady On, Slow March Time of 20 beats per minute (BPM), or Fast March Time of 120 BPM. Note: When selected for SmartSync horn/strobe control, March Time produces 60 BPM.
The 24 VDC Auxiliary output provides up to 500 mA
for system use. (Auxiliary output current is counted for total power supply capacity.)
Standard Auxiliary Relay Outputs. Two relay outputs
are available, selectable as normally open or normally closed, rated 2 A @ 30 VDC per below:
Aux Relay 1 is normally assigned to General Alarm operation but is programmable (see page 7)
Aux Relay 2 (Trouble) is energized when Normal and is de-energized with a Trouble condition.
Product Selection
Standard Feature Details (Continued)
On-Board Dual Line DACT. Operation can be selected
for Contact ID, SIA, 3/1, 4/2, and BFSK formats. Reporting includes Alarm, Supervisory, Trouble, and AC Failure. Operation includes automatic 24 hour test and programmable power fail report delay.
Power Supply and Battery Charger. DC power output
is 3 A @ 24 VDC for panel use. The temperature compensated battery charger (sealed lead-acid batteries only) is rated for up to 25 Ah batteries per UL 864 and up to 12.7 Ah per ULC-S527. (Up to 12.7 Ah batteries fit in the cabinet, larger batteries require an external cabinet.) Panel electronics can measure and display voltage and current for the power supply, batteries and the battery charger (standard and expansion power supply). Depleted battery trouble is monitored and annunciated and depleted battery cutout can be selected. Active battery status monitor supervises charger operation.
Optional Feature Details
Expansion Power Supply. Provides 3 A total @
24 VDC, two additional 2 A NACs, and an additional auxiliary power output of 500 mA. Output operation is the same as on the standard power supply.
Expansion Relay Module. Provides three relays, one
each for Alarm, Supervisory, and Trouble conditions. Each is jumper selectable as N.O. or N.C. Contacts are rated 2 A @ 30 VDC. Location is the same as for the City Circuit Modules.
City Circuit Modules. These modules are available with
or without on-board disconnect switches, depending on local requirements (either type can be disconnected through the front panel under password control). Connections are for Remote Station (reverse polarity) or Municipal Master (local energy). Reporting includes Alarm, Supervisory, and Trouble.
Control Panel
Model Color Description Listings Standard Feature Summary
4008-9102 Beige 4008-9101 Red
4008-9122 Beige 4008-9121 Red
Standard fire alarm control panel MEA Fire alarm control panel with 24 LED
Annunciator on front door
ULC
UL, FM, &
CSFM
SLC with 200 addressable points, 2 Class B/Class A NACs, 3 A power supply with battery charger; on-board DACT; for input voltage of 120/240 VAC, 50/60 Hz (autoselect)
Option Modules
Model Description
4008-9801 Expansion Power Supply; 3 A, with 2 NACs, 120/240 VAC, 50/60 Hz Select one if required
4008-9802 Expansion Relay Module; 3 relays selectable as either N.O. or N. C. 4006-9805* City Circuit Modules with disconnect switch 4006-9806* City Circuit Modules without disconnect switch
* These City Circuit modules are also used on the 4006 Series control panels.
Select one if required
Accessories
Model Description
2975-9811 Beige semi-flush trim kit; 1 7⁄16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides
2975-9812 Red semi-flush trim kit; 1 7⁄16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides
4009-9801
Batteries, 12 Volt (select one battery model per system standby requirements; order quantity of two)
Model Size Model Size Location Model Size Location
2081-9272 6.2 Ah 2081-9288 12.7 Ah
2081-9274 10 Ah 2081-9827 25 Ah
Beige External Battery Cabinet for up to 25 Ah batteries; mounts close-nippled to control panel cabinet; dimensions = 16 ¼” W x 13 ½” H x 5 ¾” D (413 mm x 343 mm x 146 mm)
For cabinet mount
2081-9275 18 Ah
Requires 4009-9801 External Battery Cabinet (UL listed only)
2 S4008-0001-8 8/2012
TrueAlarm Smoke Detection
TrueAlarm Addressable Detection. IDNet addressable
device compatibility includes Simplex TrueAlarm photoelectric smoke and temperature sensors. The 4008 fire alarm control panel provides a subset of the complete analog TrueAlarm features. TrueAlarm sensors appear to the panel essentially as addressable detectors and that term is used for 4008 documentation.
Approximately every four seconds the addressable smoke detectors transmit an output value based on their smoke chamber condition. The panel CPU internally maintains a current value, peak value, and an average value for each detector’s output. Status is determined by comparing the current value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.
Alarm Determination. Photoelectric detection sensitivity is 2.5%/ft obscuration. All detectors can be selected for a reduced sensitivity detection mode that satisfies the city of Boston requirements. Addressable heat detectors provide a fixed temperature alarm at 135° F (57° C) and may be individually selected to also provide rate-of-rise alarm of 15° F (8.3° C) per minute where applicable.
Keyboard Reference
Diagnostics and Default Device Type
Status Monitoring. 4008 TrueAlarm operation provides
the ability to automatically indicate when an addressable detector is dirty or excessively dirty. The NFPA 72 (National Fire Alarm and Signaling Code ) r e quirement for a test of the sensitivity range of the detectors is fulfilled by the TrueAlarm ability to maintain the sensitivity level of each addressable detector.
Modular Addressable Detector/Base Combination. Modular TrueAlarm addressable detectors use the same base which allows different detector head types (photoel ect ri c smoke, or heat) to be easily interchanged to meet specific application requirements. This feature also allows intentional detector (sensor head) substitution during building construction. When conditions are temporarily dusty, instead of covering the smoke detectors (causing them to be disabled), heat detector heads may be installed without reprogramming the control panel. Although the control panel will indicate an incorrect detector type, the heat detector will operate at a default setting to provide heat detection for building protection at that location.
FIVE STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash t o in dic a te the condition and then when acknowledged, remain on until reset
2 X 20 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 20 characters for custom label information
FIRST ALARM DISPLAY: Operation can be selected for maintained display of first alarm until acknowledged
FIRE
CONTROL
ALARM
PANEL VIEW
with door closed
ALARM
ACK
ALARM ACK acknowledges a Fire
Alarm condition, logs the acknowledge, silences the op erator panel and all annunciator tone-alerts, and steps through the active Alarm list
SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, silences the op erator panel and all annunciator tone-alerts, and steps through the active Supervisory list
FIVE NAVIGATION KEYS: MENU selects the on-screen programming menu; left and right arrows moves the position on the screen, and PREVIOUS and NEXT navigate screen select ion s
SYSTEM
SUPERVISORY
SUPV
ACK
PREVIOUS
MENU
NEXT
SYSTEM
TROUBLE
TROUBLE
ACK
SILENCEDACPOWER
TROUBLE ACK acknowledges system troubles, logs the acknowledge, silences the operator panel and all annunciator tone-alerts, and steps through the active Trouble list
THREE PROGRAMMABLE LEDs
provide custom labeling (lab els ins e rt into a pocket), the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow
ALARM
ALARM
SILENCE
DISABLE ENABLE
FUNCTION
CLEAR
ENTER
EXIT
SYSTEM
RESET
PQRS7TUV8WXYZ
1ABC2DEF
3
GHI4JKL5MNO
6
9
0
ALARM SILENCE causes audible notification appliances to be silenced, used after evac ua tion is complete and while alarm source is being investigated
FOUR EXTENDED FUNCTION KEYS: ENTER confirms selections, EXIT/CLEAR backs out of th e p r e s en t scre en menu and clears information that has n ot be en entered, FUNCTION enables the active function menu, DISABLE/ENABLE to gg les the function or circuit status as appropriate per the selected screen
SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal
ALPHANUMERIC KEYPAD provides
programming entry of numbers and letters
3 S4008-0001-8 8/2012