UL, ULC, CSFM Listed; FM Approved; 4008 Fire Alarm Control Panel for IDNet Addressable
MEA (NYC) Acceptance* Devices and TrueAlarm Addressable Smoke Detection
Features
Control panel operator convenience features:
Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel
status information
Operation is programmable using a multi-function
keypad and the panel LCD or via service computer (PC)
RS-232 service port provides upload/download PC
access for panel configuration and event history logs
Software updates are via PC download
Convenient library of standard custom label terms
Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
WALKTEST silent or audible system test
Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Addressable Devices:
Using IDNet communications, up to 200 addressable
TrueAlarm detection points or addressable device points
are available (see page 3 for details)
Two Standard Notification Appliance Circuits (NACs):
Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
®
Selectable for Simplex
SmartSync two-wire
horn/strobe control or synchronized strobe control
FIRE
SYSTEM
SYSTEM
ALARM
ALARM
SUPERVISORY
TROUBLE
SILENCEDACPOWER
ALARM
SUPV
TROUBLE
ALARM
ACK
SYSTEM
ACK
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
SERVICING
BEFORE
4008-9102 (Beige) Standard Control Panel
Fire Alarm Annunciator
FIRE
SYSTEM
SYSTEM
ALARM
ALARM
SUPERVISORY
TROUBLE
SILENCEDACPOWER
ALARM
SUPV
TROUBLE
ALARM
ACK
SYSTEM
ACK
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
SERVICING
BEFORE
Standard Power Supply:
Provides 3 A maximum @ nominal 24 DC
Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up
to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
Programmable Active Status Reminder
Two auxiliary relays
NACs, Relay outputs, and communications circuits
are power limited (AC input, battery circuits, and City
Circuit Module outputs are non-power limited)
Available with beige or red cabinet
UL listed to Standard 864
Available option modules:
Door mounted 24 LED annunciator (standard on ULC
models)
3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
City Interface Module and Auxiliary Relay Module
Remote LCD and LED/Switch Annunciators
S4008-0001-8 8/2012
4008-9122 (Beige) Control Panel with 24 LED Annunciator
(required for ULC applications)
Description
For areas requiring up to 200 addressable input devices and
up to 4 NACs, the Simplex 4008 Series fire alarm control
panels provide flexible initiating circuit monitoring,
extensive programmable control capability, and LCD
annunciated circuit-specific 20 character custom labels.
* See page 2 for additional ULC and MEA information. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California
Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or
conditions concerning material presented in this document. It is subject to re-examination,
revision, and possible cancellation. Additional listings may be applicable, contact your local
Simplex product supplier for the latest status. Listings and approvals under Simplex Time
Recorder Co. are the property of Tyco Fire Protection Products.
Standard Feature Details
Addressable operationis provided by an IDNet
signaling line circuit (SLC) capable of communicating to up
to 200 addressable devices (points). Addressable devices
include: TrueAlarm smoke detecti on, heat detection, and
duct detection; supervised addressable modules for single
and multiple contact monitoring, manual stations, isolation
modules, and a remote signal module (see list on page 4.)
(Please note that this panel provides a limited TrueAlarm
operation feature set. For larger applications that require the
full comp lement of TrueAlar m features, contact your local
Simplex product supplier.)
Two, 2 A On-Board NACs provide conventional reverse
polarity operation, selectable as Class A or Class B, with
electronic control and overcurrent protection. Operation is
selectable for synchronized strobe or SmartSync
horn/strobe two wire operation. Horn cont rol can be
selected at the panel for: Temporal pattern coding, Steady
On, Slow March Time of 20 beats per minute (BPM), or
Fast March Time of 120 BPM. Note: When selected for
SmartSync horn/strobe control, March Time produces
60 BPM.
The 24 VDC Auxiliary output provides up to 500 mA
for system use. (Auxiliary output current is counted for
total power supply capacity.)
Standard Auxiliary Relay Outputs. Two relay outputs
are available, selectable as normally open or normally
closed, rated 2 A @ 30 VDC per below:
Aux Relay 1 is normally assigned to General Alarm
operation but is programmable (see page 7)
Aux Relay 2 (Trouble) is energized when Normal and is
de-energized with a Trouble condition.
Product Selection
Standard Feature Details (Continued)
On-Board Dual Line DACT.Operation can be selected
for Contact ID, SIA, 3/1, 4/2, and BFSK formats.
Reporting includes Alarm, Supervisory, Trouble, and AC
Failure. Operation includes automatic 24 hour test and
programmable power fail report delay.
Power Supply and Battery Charger. DC power output
is 3 A @ 24 VDC for panel use. The temperature
compensated battery charger (sealed lead-acid batteries
only) is rated for up to 25 Ah batteries per UL 864 and up
to 12.7 Ah per ULC-S527. (Up to 12.7 Ah batteries fit in
the cabinet, larger batteries require an external cabinet.)
Panel electronics can measure and display voltage and
current for the power supply, batteries and the battery
charger (standard and expansion power supply). Depleted
battery trouble is monitored and annunciated and depleted
battery cutout can be selected. Active battery status
monitor supervises charger operation.
Optional Feature Details
Expansion Power Supply. Provides 3 A total @
24 VDC, two additional 2 A NACs, and an additional
auxiliary power output of 500 mA. Output operation is the
same as on the standard power supply.
Expansion Relay Module. Provides three relays, one
each for Alarm, Supervisory, and Trouble conditions.
Each is jumper selectable as N.O. or N.C. Contacts are
rated 2 A @ 30 VDC. Location is the same as for the City
Circuit Modules.
City Circuit Modules. These modules are available with
or without on-board disconnect switches, depending on
local requirements (either type can be disconnected
through the front panel under password control).
Connections are for Remote Station (reverse polarity) or
Municipal Master (local energy). Reporting includes
Alarm, Supervisory, and Trouble.
Control Panel
Model Color Description Listings Standard Feature Summary
4008-9102 Beige
4008-9101 Red
4008-9122 Beige
4008-9121 Red
Standard fire alarm control panel MEA
Fire alarm control panel with 24 LED
Annunciator on front door
ULC
UL, FM, &
CSFM
SLC with 200 addressable points,
2 Class B/Class A NACs, 3 A power
supply with battery charger; on-board
DACT; for input voltage of
120/240 VAC, 50/60 Hz (autoselect)
Option Modules
Model Description
4008-9801 Expansion Power Supply; 3 A, with 2 NACs, 120/240 VAC, 50/60 Hz Select one if required
4008-9802 Expansion Relay Module; 3 relays selectable as either N.O. or N. C.
4006-9805* City Circuit Modules with disconnect switch
4006-9806* City Circuit Modules without disconnect switch
* These City Circuit modules are also used on the 4006 Series control panels.
Select one if required
Accessories
Model Description
2975-9811 Beige semi-flush trim kit; 1 7⁄16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides
2975-9812 Red semi-flush trim kit; 1 7⁄16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides
4009-9801
Batteries, 12 Volt (select one battery model per system standby requirements; order quantity of two)
Model Size Model Size Location Model Size Location
2081-9272 6.2 Ah 2081-9288 12.7 Ah
2081-9274 10 Ah 2081-9827 25 Ah
Beige External Battery Cabinet for up to 25 Ah batteries; mounts close-nippled to control panel cabinet;
dimensions = 16 ¼” W x 13 ½” H x 5 ¾” D (413 mm x 343 mm x 146 mm)
device compatibility includes Simplex TrueAlarm
photoelectric smoke and temperature sensors. The 4008 fire
alarm control panel provides a subset of the complete
analog TrueAlarm features. TrueAlarm sensors appear to
the panel essentially as addressable detectors and that term
is used for 4008 documentation.
Approximately every four seconds the addressable smoke
detectors transmit an output value based on their smoke
chamber condition. The panel CPU internally maintains a
current value, peak value, and an average value for each
detector’s output. Status is determined by comparing the
current value to its average value. Tracking this average
value as a continuously shifting reference point filters out
environmental factors that cause shifts in sensitivity.
Alarm Determination. Photoelectric detection sensitivity
is 2.5%/ft obscuration. All detectors can be selected for a
reduced sensitivity detection mode that satisfies the city of
Boston requirements. Addressable heat detectors provide a
fixed temperature alarm at 135° F (57° C) and may be
individually selected to also provide rate-of-rise alarm of
15° F (8.3° C) per minute where applicable.
Keyboard Reference
Diagnostics and Default Device Type
Status Monitoring. 4008 TrueAlarm operation provides
the ability to automatically indicate when an addressable
detector is dirty or excessively dirty. The NFPA 72
(National Fire Alarm and Signaling Code ) r e quirement for
a test of the sensitivity range of the detectors is fulfilled by
the TrueAlarm ability to maintain the sensitivity level of
each addressable detector.
Modular Addressable Detector/Base Combination.
Modular TrueAlarm addressable detectors use the same base
which allows different detector head types (photoel ect ri c
smoke, or heat) to be easily interchanged to meet specific
application requirements. This feature also allows
intentional detector (sensor head) substitution during
building construction. When conditions are temporarily
dusty, instead of covering the smoke detectors (causing
them to be disabled), heat detector heads may be installed
without reprogramming the control panel. Although the
control panel will indicate an incorrect detector type, the
heat detector will operate at a default setting to provide heat
detection for building protection at that location.
FIVE STATUS INDICATOR LEDs provide system status indications in
addition to LCD information, LEDs flash t o in dic a te the condition and
then when acknowledged, remain on until reset
2 X 20 LCD READOUT, LED backlighted during normal conditions and abnormal
operating conditions, provides up to 20 characters for custom label information
FIRST ALARM DISPLAY: Operation can be selected for maintained display of first
alarm until acknowledged
FIRE
CONTROL
ALARM
PANEL VIEW
with door closed
ALARM
ACK
ALARM ACK acknowledges a Fire
Alarm condition, logs the
acknowledge, silences the op erator
panel and all annunciator tone-alerts,
and steps through the active Alarm list
SUPV ACK acknowledges system
supervisory conditions, logs the
acknowledge, silences the op erator
panel and all annunciator tone-alerts,
and steps through the active
Supervisory list
FIVE NAVIGATION KEYS: MENU selects
the on-screen programming menu; left and
right arrows moves the position on the
screen, and PREVIOUS and NEXT
navigate screen select ion s
SYSTEM
SUPERVISORY
SUPV
ACK
PREVIOUS
MENU
NEXT
SYSTEM
TROUBLE
TROUBLE
ACK
SILENCEDACPOWER
TROUBLE ACK acknowledges
system troubles, logs the
acknowledge, silences the
operator panel and all annunciator
tone-alerts, and steps through the
active Trouble list
THREE PROGRAMMABLE LEDs
provide custom labeling (lab els ins e rt into
a pocket), the top two LEDs are
selectable as red or yellow, the bottom
LED is selectable as green or yellow
ALARM
ALARM
SILENCE
DISABLE
ENABLE
FUNCTION
CLEAR
ENTER
EXIT
SYSTEM
RESET
PQRS7TUV8WXYZ
1ABC2DEF
3
GHI4JKL5MNO
6
9
0
ALARM SILENCE causes audible notification appliances
to be silenced, used after evac ua tion is complete and
while alarm source is being investigated
FOUR EXTENDED FUNCTION KEYS: ENTER confirms
selections, EXIT/CLEAR backs out of th e p r e s en t scre en menu
and clears information that has n ot be en entered, FUNCTION
enables the active function menu, DISABLE/ENABLE to gg les
the function or circuit status as appropriate per the selected
screen
SYSTEM RESET restores
control panel to normal when
all alarmed inputs are
returned to normal
ALPHANUMERIC
KEYPAD provides
programming entry of
numbers and letters