UL, ULC, CSFM Listed; FM Approved; 4008 Fire Alarm Control Panel for IDNet Addressable
MEA (NYC) Acceptance* Devices and TrueAlarm Addressable Smoke Detection
Features
Control panel operator convenience features:
Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel
status information
Operation is programmable using a multi-function
keypad and the panel LCD or via service computer (PC)
RS-232 service port provides upload/download PC
access for panel configuration and event history logs
Software updates are via PC download
Convenient library of standard custom label terms
Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
WALKTEST silent or audible system test
Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Addressable Devices:
Using IDNet communications, up to 200 addressable
TrueAlarm detection points or addressable device points
are available (see page 3 for details)
Two Standard Notification Appliance Circuits (NACs):
Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
®
Selectable for Simplex
SmartSync two-wire
horn/strobe control or synchronized strobe control
FIRE
SYSTEM
SYSTEM
ALARM
ALARM
SUPERVISORY
TROUBLE
SILENCEDACPOWER
ALARM
SUPV
TROUBLE
ALARM
ACK
SYSTEM
ACK
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
SERVICING
BEFORE
4008-9102 (Beige) Standard Control Panel
Fire Alarm Annunciator
FIRE
SYSTEM
SYSTEM
ALARM
ALARM
SUPERVISORY
TROUBLE
SILENCEDACPOWER
ALARM
SUPV
TROUBLE
ALARM
ACK
SYSTEM
ACK
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
SERVICING
BEFORE
Standard Power Supply:
Provides 3 A maximum @ nominal 24 DC
Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up
to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
Programmable Active Status Reminder
Two auxiliary relays
NACs, Relay outputs, and communications circuits
are power limited (AC input, battery circuits, and City
Circuit Module outputs are non-power limited)
Available with beige or red cabinet
UL listed to Standard 864
Available option modules:
Door mounted 24 LED annunciator (standard on ULC
models)
3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
City Interface Module and Auxiliary Relay Module
Remote LCD and LED/Switch Annunciators
S4008-0001-8 8/2012
4008-9122 (Beige) Control Panel with 24 LED Annunciator
(required for ULC applications)
Description
For areas requiring up to 200 addressable input devices and
up to 4 NACs, the Simplex 4008 Series fire alarm control
panels provide flexible initiating circuit monitoring,
extensive programmable control capability, and LCD
annunciated circuit-specific 20 character custom labels.
* See page 2 for additional ULC and MEA information. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California
Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or
conditions concerning material presented in this document. It is subject to re-examination,
revision, and possible cancellation. Additional listings may be applicable, contact your local
Simplex product supplier for the latest status. Listings and approvals under Simplex Time
Recorder Co. are the property of Tyco Fire Protection Products.
Standard Feature Details
Addressable operationis provided by an IDNet
signaling line circuit (SLC) capable of communicating to up
to 200 addressable devices (points). Addressable devices
include: TrueAlarm smoke detecti on, heat detection, and
duct detection; supervised addressable modules for single
and multiple contact monitoring, manual stations, isolation
modules, and a remote signal module (see list on page 4.)
(Please note that this panel provides a limited TrueAlarm
operation feature set. For larger applications that require the
full comp lement of TrueAlar m features, contact your local
Simplex product supplier.)
Two, 2 A On-Board NACs provide conventional reverse
polarity operation, selectable as Class A or Class B, with
electronic control and overcurrent protection. Operation is
selectable for synchronized strobe or SmartSync
horn/strobe two wire operation. Horn cont rol can be
selected at the panel for: Temporal pattern coding, Steady
On, Slow March Time of 20 beats per minute (BPM), or
Fast March Time of 120 BPM. Note: When selected for
SmartSync horn/strobe control, March Time produces
60 BPM.
The 24 VDC Auxiliary output provides up to 500 mA
for system use. (Auxiliary output current is counted for
total power supply capacity.)
Standard Auxiliary Relay Outputs. Two relay outputs
are available, selectable as normally open or normally
closed, rated 2 A @ 30 VDC per below:
Aux Relay 1 is normally assigned to General Alarm
operation but is programmable (see page 7)
Aux Relay 2 (Trouble) is energized when Normal and is
de-energized with a Trouble condition.
Product Selection
Standard Feature Details (Continued)
On-Board Dual Line DACT.Operation can be selected
for Contact ID, SIA, 3/1, 4/2, and BFSK formats.
Reporting includes Alarm, Supervisory, Trouble, and AC
Failure. Operation includes automatic 24 hour test and
programmable power fail report delay.
Power Supply and Battery Charger. DC power output
is 3 A @ 24 VDC for panel use. The temperature
compensated battery charger (sealed lead-acid batteries
only) is rated for up to 25 Ah batteries per UL 864 and up
to 12.7 Ah per ULC-S527. (Up to 12.7 Ah batteries fit in
the cabinet, larger batteries require an external cabinet.)
Panel electronics can measure and display voltage and
current for the power supply, batteries and the battery
charger (standard and expansion power supply). Depleted
battery trouble is monitored and annunciated and depleted
battery cutout can be selected. Active battery status
monitor supervises charger operation.
Optional Feature Details
Expansion Power Supply. Provides 3 A total @
24 VDC, two additional 2 A NACs, and an additional
auxiliary power output of 500 mA. Output operation is the
same as on the standard power supply.
Expansion Relay Module. Provides three relays, one
each for Alarm, Supervisory, and Trouble conditions.
Each is jumper selectable as N.O. or N.C. Contacts are
rated 2 A @ 30 VDC. Location is the same as for the City
Circuit Modules.
City Circuit Modules. These modules are available with
or without on-board disconnect switches, depending on
local requirements (either type can be disconnected
through the front panel under password control).
Connections are for Remote Station (reverse polarity) or
Municipal Master (local energy). Reporting includes
Alarm, Supervisory, and Trouble.
Control Panel
Model Color Description Listings Standard Feature Summary
4008-9102 Beige
4008-9101 Red
4008-9122 Beige
4008-9121 Red
Standard fire alarm control panel MEA
Fire alarm control panel with 24 LED
Annunciator on front door
ULC
UL, FM, &
CSFM
SLC with 200 addressable points,
2 Class B/Class A NACs, 3 A power
supply with battery charger; on-board
DACT; for input voltage of
120/240 VAC, 50/60 Hz (autoselect)
Option Modules
Model Description
4008-9801 Expansion Power Supply; 3 A, with 2 NACs, 120/240 VAC, 50/60 Hz Select one if required
4008-9802 Expansion Relay Module; 3 relays selectable as either N.O. or N. C.
4006-9805* City Circuit Modules with disconnect switch
4006-9806* City Circuit Modules without disconnect switch
* These City Circuit modules are also used on the 4006 Series control panels.
Select one if required
Accessories
Model Description
2975-9811 Beige semi-flush trim kit; 1 7⁄16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides
2975-9812 Red semi-flush trim kit; 1 7⁄16” (37 mm) wide; includes four corners and trim pieces for top, bottom, and sides
4009-9801
Batteries, 12 Volt (select one battery model per system standby requirements; order quantity of two)
Model Size Model Size Location Model Size Location
2081-9272 6.2 Ah 2081-9288 12.7 Ah
2081-9274 10 Ah 2081-9827 25 Ah
Beige External Battery Cabinet for up to 25 Ah batteries; mounts close-nippled to control panel cabinet;
dimensions = 16 ¼” W x 13 ½” H x 5 ¾” D (413 mm x 343 mm x 146 mm)
device compatibility includes Simplex TrueAlarm
photoelectric smoke and temperature sensors. The 4008 fire
alarm control panel provides a subset of the complete
analog TrueAlarm features. TrueAlarm sensors appear to
the panel essentially as addressable detectors and that term
is used for 4008 documentation.
Approximately every four seconds the addressable smoke
detectors transmit an output value based on their smoke
chamber condition. The panel CPU internally maintains a
current value, peak value, and an average value for each
detector’s output. Status is determined by comparing the
current value to its average value. Tracking this average
value as a continuously shifting reference point filters out
environmental factors that cause shifts in sensitivity.
Alarm Determination. Photoelectric detection sensitivity
is 2.5%/ft obscuration. All detectors can be selected for a
reduced sensitivity detection mode that satisfies the city of
Boston requirements. Addressable heat detectors provide a
fixed temperature alarm at 135° F (57° C) and may be
individually selected to also provide rate-of-rise alarm of
15° F (8.3° C) per minute where applicable.
Keyboard Reference
Diagnostics and Default Device Type
Status Monitoring. 4008 TrueAlarm operation provides
the ability to automatically indicate when an addressable
detector is dirty or excessively dirty. The NFPA 72
(National Fire Alarm and Signaling Code ) r e quirement for
a test of the sensitivity range of the detectors is fulfilled by
the TrueAlarm ability to maintain the sensitivity level of
each addressable detector.
Modular Addressable Detector/Base Combination.
Modular TrueAlarm addressable detectors use the same base
which allows different detector head types (photoel ect ri c
smoke, or heat) to be easily interchanged to meet specific
application requirements. This feature also allows
intentional detector (sensor head) substitution during
building construction. When conditions are temporarily
dusty, instead of covering the smoke detectors (causing
them to be disabled), heat detector heads may be installed
without reprogramming the control panel. Although the
control panel will indicate an incorrect detector type, the
heat detector will operate at a default setting to provide heat
detection for building protection at that location.
FIVE STATUS INDICATOR LEDs provide system status indications in
addition to LCD information, LEDs flash t o in dic a te the condition and
then when acknowledged, remain on until reset
2 X 20 LCD READOUT, LED backlighted during normal conditions and abnormal
operating conditions, provides up to 20 characters for custom label information
FIRST ALARM DISPLAY: Operation can be selected for maintained display of first
alarm until acknowledged
FIRE
CONTROL
ALARM
PANEL VIEW
with door closed
ALARM
ACK
ALARM ACK acknowledges a Fire
Alarm condition, logs the
acknowledge, silences the op erator
panel and all annunciator tone-alerts,
and steps through the active Alarm list
SUPV ACK acknowledges system
supervisory conditions, logs the
acknowledge, silences the op erator
panel and all annunciator tone-alerts,
and steps through the active
Supervisory list
FIVE NAVIGATION KEYS: MENU selects
the on-screen programming menu; left and
right arrows moves the position on the
screen, and PREVIOUS and NEXT
navigate screen select ion s
SYSTEM
SUPERVISORY
SUPV
ACK
PREVIOUS
MENU
NEXT
SYSTEM
TROUBLE
TROUBLE
ACK
SILENCEDACPOWER
TROUBLE ACK acknowledges
system troubles, logs the
acknowledge, silences the
operator panel and all annunciator
tone-alerts, and steps through the
active Trouble list
THREE PROGRAMMABLE LEDs
provide custom labeling (lab els ins e rt into
a pocket), the top two LEDs are
selectable as red or yellow, the bottom
LED is selectable as green or yellow
ALARM
ALARM
SILENCE
DISABLE
ENABLE
FUNCTION
CLEAR
ENTER
EXIT
SYSTEM
RESET
PQRS7TUV8WXYZ
1ABC2DEF
3
GHI4JKL5MNO
6
9
0
ALARM SILENCE causes audible notification appliances
to be silenced, used after evac ua tion is complete and
while alarm source is being investigated
FOUR EXTENDED FUNCTION KEYS: ENTER confirms
selections, EXIT/CLEAR backs out of th e p r e s en t scre en menu
and clears information that has n ot be en entered, FUNCTION
enables the active function menu, DISABLE/ENABLE to gg les
the function or circuit status as appropriate per the selected
screen
SYSTEM RESET restores
control panel to normal when
all alarmed inputs are
returned to normal
ALPHANUMERIC
KEYPAD provides
programming entry of
numbers and letters
3 S4008-0001-8 8/2012
Compatible Simplex Peripherals (see specifications on page 5 for notification appliances)
Detector Heads and Addressable Bases (refer to page 3 for 4008 detector/sensor terminology)
Model Detector Head Type Compatible Addressable Base Data Sheet
4098-9792, Standard detector base
4098-9714
4098-9733
Photoelectric
Heat, 135° F (57° C)
4098-9789, Base for remote LED or relay
4098-9791, Features of 4098-9789 and remote supervised relay
4098-9794, Sounder base S4098-0028
S4098-0019
4098-9793, IDNet Isolator base S4098-0025
4098-9754 Photo and Heat
4098-9795, Dual address sounder base
4098-9796, Dual address standard base
NOTE: These bases require
two addresses
S4098-0033
Duct Detection
Model Description Data Sheet
4098-9755 Addressable Duct Detector Housing with 4098-9714 detector, no relay control
4098-9756 Addressable Duct Detector Housing with 4098-9714 detector, with remote relay control
S4098-0030
Addressable Devices
Model and Description Data Sheet Model and Description Data Sheet Model and Description Data Sheet
4090-9001 Supervised IAM
4090-9051 Supervised IAM 4090-9106 CL A ZAM 4099-9001, 4099-9002,
S4090-0001
4090-9002 Relay IAM S4090-0002 4090-9116 IDNet Isolator S4090-0005
4090-9101 CL B ZAM
S4090-0003
4090-9007 Signal IAM S4090-0010
& 4099-9003 Manual
S4099-0001
Stations
Compatible System Expansion Panels
Model Type Description Data Sheet
4003 Series Voice Control Panel
4009 Series Remote NAC Extender
Provides a remote voice control panel with on-board NACs, internal
microphone, and remote microphone input
Provides remote NACs; includes power supply and battery charger;
4 extenders max/NAC; 4008 uses NAC output to provide control
S4003-0002
S4009-0002
Note: Contact your local Simplex Product Supplier for additional compatible peripherals.
Remote Annunciator Options
The 4008 supports up to four annunciator options
including:
Door Mounted 24 LED Annunciator
4610-9111 Remote LED/Switch Annunciators
4606-9101 Remote LCD Annunciators
Annunciators communicate at a rate of 9600 baud with
power supplied by separate wiring.
4610-9111 LED Annunciator Features:
16 LEDs with programmable functions and dedicated
LEDs for Alarm Silenced, Lost Communications,
Trouble, and Power-on
Keyswitch access controlled switches for
Acknowledge, Alarm Silence, Reset, and Lamp Test
Local tone-alert
4606-9101 LCD Annunciator Features:
LCD readout with two lines of 40 characters each and
Power Supply Output 3 A maximum @ 24 VDC in alarm
Battery Charger
Input Current, Standard 2 A maximum @ 120 VAC input; 1.5 A maximum @ 240 VAC input
Input Current with
Expansion Power Supply
4 A maximum @ 120 VAC input; 3 A maximum @ 240 VAC input
Temperature compensated charger is rated for up to 25 Ah per UL 864; up to
12.7 Ah per ULC-S527
Notification Appliance Circuits (NACs) (NOTE: Total DC current = 3 A maximum per power supply)
General Rating
Special Application Rating =2 A per NAC
Strobe synchronization is UL listed across all
four system NACs for these 4906 Series
appliances
Regulated 24 VDC Rating = 1.5 A per NAC
NOTE: Maximum strobe
supply or expansion power supply is 1.35
per power supply (2.7 A total); remainder of
power supply rating is available for other
loading
load on main power
2 A maximum @ 24 VDC, per NAC; available as Class A or Class B;
Class B end-of-line resistor = 10 k, ½ W; Model 4081-9008 (P/N 733-894)
Simplex 4901 Series (horns) and 4906 Series Multi-Candela non-addressable
strobes, horn/strobes, and speaker/strobes (contact your Simplex product
representative for compatible appliances)
Power for other UL listed appliances; use associated external synchronization
A
modules where required
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum per power supply)
Auxiliary Power Output 500 mA maximum @ 24 VDC
Standard Auxiliary Relay Outputs
Wiring Connections Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
Contacts rated 2 A @ 30 VDC, 0.35 power factor;
jumper selectable as N.O. or N.C.
IDNet Communications
Quantity Up to 200 addressable devices (see list on page 4)
Suppression
Wire Size 18 AWG (0.82 mm2)
Unshielded twisted pair (UTP)
Wire Types
Shielded twisted pair (STP)
Distance from Control Panel to Farthest
Device
Total Wire Length Allowed With “T” Taps for
Class B Wiring
Total Capacitance Allowed 0.6 µF (600 nF)
For wiring external to building, use Overvoltage Protector 2081-9044 at each end
of the connection; refer to data sheet S2081-0016 for details
Acceptable for most applications; not for use with wiring in conduit with either NAC
or AC power wiring (or similar)
Shielded wire may provide protection from unexpected sources of interference and
may be required for some applications; review system with your local Simplex
product supplier
Up to 4000 feet (1219 m) with 125 devices; 32
Up to 2500 feet (762 m) with 200 devices; 51
Up to 10,000 ft (3 km)
Annunciator Communications
Quantity Supported Up to four annunciator modules per panel (see page 4 for details)
Wiring Size and Type See descriptio n for IDNet wiring above
Wiring Distances
Line Matching Resistor
Suppression
Bus-Style Wiring Up to 4000 ft (1219 m); 0.58 µF (580 nF) maximum capacitance; 35 max.
“T-Tap” Wiring Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device
Bus-Style Wiring Connect one at panel and one at end of line
“T-Tap” Wiring Connect one at panel and one at farthest device
Use 2081-9044 Overvoltage Protectors where wiring leaves and enters a building
(refer to data sheet S2081-0016)
100 , ½ W; 4081-9011;
(part number 733-974)
Option Module Ratings
Expansion Relay
Module 4008-9802
Contact Ratings 2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C.
Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2)
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range Up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
5 S4008-0001-8 8/2012
Supervisory and Alarm Currents
Model Module Supervisory Alarm
4008-9101
4008-9102
4008-9121
4008-9122
4008-9801 Expansion Power Supply 50 mA 60 mA
4008-9802 Expansion Relay Module 10 mA per energized relay 10 mA per energized relay
4006-9805
4006-9806
4606-9101
4610-9111
** Current Calculation Information:
1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads and all auxiliary loads.
Standard fire alarm control panel 135 mA + 0.8 mA per IDNet device 190 mA + 1 mA per IDNet device
Control panel with 24 LED Annunciator 153 mA + 0.8 mA per IDNet device 240 mA + 1 mA per IDNet device
City Circuit Module with disconnect
switch
City Circuit Module without disconnect
switch
Remote LCD Annunciator (see data
sheet S4606-0001)
Remote LED/Switch Annunciator (see
data sheet S4610-0001)
30 mA 60 mA
30 mA 60 mA
65 mA 140 mA
40 mA
(all LEDs and tone-alert on)
70 mA
Addressable Device Information
The following addressable device types and hardware point types are provided. A combination of autoprogram, and either
front panel or PC programming allows the operation to be selected per application.
Available Fire Detection Device Types
Device Description Options
Photoelectric
Addressable
Detector
Heat Detector
Photoelectric
Detector with
Heat Detector
Sounder base (selectable
TrueAlarm operation with
sensitivity = 2.5%/ft
Fixed temperature thermal
detection at 135° F (57.2° C)
Combination detector, dual address base with options available per above
for single station operation)
With relay output
Sounder base (selectable
for single station operation)
With relay output
With communications isolator
Selectable for all detectors to be at city of
Boston sensitivity of 3.7%/ft
With communications isolator
Individually selectable to add rate-of-rise heat
detection of 15° F/minute (8.3° C/minute)
Addressable Hardware Point Types
Function Type Description Function Type Description
FIRE Fire monitor device WSO Combination waterflow and water supervisory device
WATER Waterflow monitor device SUPV Supervisory monitor
SMOKE Smoke detector device STYLEC Style C fire monitor
SO Sprinkler Supervisory LATSUPV
IAM
SIGNAL Signal IAM MAZAM Class A addressable IDC monitor module
RIAM Addressable Relay ADRPUL Addressable manual station
Individual Addressable
Module
ISOL Addressable Isolator
MBZAM Class B addressable IDC monitor module
Verified fire alarm; an alarm level causes the alarm
verification cycle to start
Latching supervisory monitor (supervisory latches
until system is reset)
6 S4008-0001-8 8/2012
NAC Operation Modes
Function Type Description
SSIG Alarm signal, on until silenced
RSIG Alarm signal, on until reset
TROUBLE Trouble signal
SUPV Supervisory signal
QALERT SmartSync 2-wire horn/strobe control; horn on until silenced, strobe on until reset
Provides Wheelock strobe synch protocol when using only Wheelock strobes on panel, not to be mixed with
Simplex strobes
Relay Operation Modes
The following relay operations are selectable from either the front panel or the PC programmer.
Common Fire Alarm Operations
Function Type Relay Ac tivate s Up o n Relay Deactivates Upon
SRELAY General Alarm Silence
RRELAY General Alarm Reset
SUPV Supervisory condition Clear
TRBL Trouble condition Clear
Special Functions
Function Type Description
UTILITY Utility input in the same alarm group activates
PRIMARY General alarm; relay is tied to Primary Elevator Recall contacts
ALTERN General alarm; relay is tied to Alternate Elevator Recall contacts
DRESET Relay provides 24 VDC power to 4-wire addressable detectors; relay turns off for 5 seconds on System Reset
DHOLDER
Relay provides 24 VDC to larger door holder relay with separate power source; relay activates on general
alarm to remove power to door holder relay and close doors
Additional Programming Feature Details
Function Details
Custom labels
Message Library
History logs
Autoprogram
Alarm Groups
WALKTEST
Manual Control Allows selection of individual relays or NACs for system testing
Passcode
Protection
(4-digit number)
Up to 20 characters per point; a built-in message library provides for commonly used words for easy front
panel programming
For front panel label creation convenience, the following words can be selected as part of a custom label
( _designates a built-in space; typing the first letter of a word/number will select the closest word in
alphabetical/numerical sequence)
North
South
East
West
Front
Three separate logs: Alarm (100 entries), Supervisory (100 entries), and Trouble (300 entries); logs can be
queried separately, or as a combined log; logs can be downloaded for printing or archiving using the RS-232
service port
Automatically scans system for installed option modules and configures panel programming accordingly;
modes are available to detect new modules only, recreate default programming and then add all modules
found; Scans of addressable loop adds addressable devices, displays total added; checks for duplicate
addresses and identifies errors
Up to 99 alarm groups are available, any point may be in up to 3 alarm groups; this allows NAC and relay
operation to be associated with inputs according to local response requirements
Allows one person to perform system testing; alarm or trouble tests are followed by automatic reset; the alarm
zone is sounded out by associated audible notification or the response is silently logged into the Alarm log
Level 1 = Acknowledge, Silence, System Reset, View logs, View point information, and Lamp Test
Level 2 = All Level 1 + Set Time/Date, Point Control, Enable/Disable points
Level 3 = All Level 2 + Clear logs, Clear verification tallies, Custom label editing, and WALKTEST
Level 4 = All Level 3 + Programming, Upload/Download; this is the Service access level
Center
rear
5th
Flr_1
Flr_2
Flr_3
Flr_4
Flr_5
RM_
Basement
Floor
Garage
Hallway
HVAC_Room
Kitchen
Lobby
Office
Patient
upper
lower
main
first
2nd
3rd
4th
Boiler_RM
Classroom
Closet_
Corridor
Elect_RM
Elevator
Entrance
Restroom
Room
Stairway
Storeroom
Wing
Zone
7 S4008-0001-8 8/2012
Installation and Module Placement Reference
Box width 15-5/8" (397 mm)
Knockouts are
located on top
and sides
(Top and side views are
shown with door installed)
Box depth = 4-3/4" (121 mm)
Main board
FIRE
ALARM
ALARM
ACK
13-1/2"
(343 mm)
Display
Assembly
Main board
AC Input Terminals
No conduit or wiring in this area
13-1/4" (337 mm)
* Indicates optional modules
Door LED Annunciator Details
11-1/4" (286 mm)
SYSTEM
SYSTEM
SUPERVISORY
TROUBLE
SUPV
TROUBLE
ACK
ACK
PREVIOUS
MENU
NEXT
Battery Area
ALARM
SILENCEDACPOWER
ALARM
SILENCE
DISABLE
ENABLE
FUNCTION
EXIT
CLEAR
ENTER
SYSTEM
RESET
ABC2DEF
1
GHI4JKL5MNO
PQRS7TUV8WXYZ
0
Door thickness
5/8" (16 mm)
3
6
9
Expansion
Power Supply*
City Module*
or Expansion
Relay Module*
16"
(406 mm)
NOTE: For semi-flush mounting, cabinet
must extend 1-1/2" (38 mm)
minimum from wall surface
RED LEDYELLOW LED
14 CUSTOM LABEL AREAS are
available, typically for location
identification and NAC
annunciation (shown labeled for
reference, blank labels are
provided); dual LED locations have
a Red LED (top) and a Yellow LED
(bottom); labels insert into pockets
behind the overlay; LED operation
is programma ble to track other
monitored status conditions
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USAS4008-0001-8 8/2012