Secos is a highly innovative control system for surface temperature control where both volume flow and temperature are constantly
measured and optimally controlled. This ensures permanent hydraulic balancing at all times.
1
Secos system manifolds
• Supply and return manifolds made of stainless steel 1" female
thread.
• One filling / emptying / flushing / venting device per manifold.
• Pre-assembled snap-on board to accommodate the Secos
actuator.
• Secos multi-sensors mounted and wired at the factory.
• Delivered ready for installation on manifold bracket with sound
insulation.
• Outlets in ¾" Eurocone.
• Including Simplex filling and drainage plugs.
1 Product description
2
1
4
6
3
7
5
2
Secos energy saving controller
• Central core of the Secos Energy Control System.
• Evaluation of the system data and automatic control according
torequirements.
• To control the flow rate as well as the heat output in each circuit.
• Suitable for heating and cooling.
• Bus communication between energy-saving controller and
actuators.
• For up to 8 seperate room thermostats
• Assignment of the room thermostats to Secos actuators possible.
• With building management system connection (Modbus).
• Wireless connection via app Flamconnect.
• External condensation monitor can be connected.
• Valve and pump protection function.
• For all other features see "Functions & Features":
3
Secos actuator for ceramic valves
• Low power consumption - consumption only during movement.
• Continuous adjustment with precise position control.
• Prewired plug connection.
• Only 1 plug for all Secos actuators.
• Snap-on: Snap-on technology for mechanical and electrical
connection with just one click for error-free and time-saving
installation.
4
Secos mounting bracket
• Manifold bracket including sound insulation.
• Mounting in distribution cabinet or wall mounting.
• Sturdy version made of galvanized steel.
5
Secos multisensor
• For recording the volume flow and return temperature in each
heating circuit.
• No moving elements.
• Minimal pressure loss.
• Zero-flow detection.
• Prewired at the factory.
6
Secos supply line temperature sensor
• Recording of the supply line temperature in the system.
• Additional safety device for monitoring the maximum permissible
supply line temperature.
7
Secos disc valves
Unlike conventional standard systems with li valves, Secos works
with ceramic disc valves which are actuated by a rotary movement.
The specially designed ceramic discs allow linear valve opening,
which ensures a uniform valve characteristic curve. In conjunction
with the Secos actuators and the infinitely variable valve positions,
this enables very precise control of the volume flows in all heating
circuits.
Disc valve with trend-setting ceramic technology.
•
• For heating / cooling applications.
• Wear-resistant.
• Long service life.
• Stepless and precise supply line control in combination
withSecos actuators.
The illustrations are symbolic and may deviate from the respective product.
These instructions describe the installation, operation and maintenance of the Secos control system for surface temperature control.
Please read these instructions carefully before starting the installation work.
In the event of non-observance, all guarantee and warranty claims are void.
The instructions are intended for trained specialist tradesmen who have the appropriate knowledge in handling heating systems,
waterpipe installations and electrical installations.
Installation and commissioning may only be carried out by trained specialist personnel.
The illustrations are symbolic and may deviate from the actual product.
Subject to technical modifications and errors.
2.1. Intended purpose and proper use
The Secos Energy Control System is used to distribute heating water in water heating and cooling systems. The system simultaneously
records and controls the volume flows and temperatures of individual circuits.
The Secos Energy Control System is ideal for both new buildings and refurbishments.
The control system may only be operated with the media, operating and ambient conditions specified in the technical data.
The Secos Energy Control System may only be installed and operated in frost-protected, dry rooms.
The Secos Energy Control System should be protected against solar radiation, heat radiation and vibration.
Operation outside the permissible operating and ambient conditions can cause damage to the system.
Usage contrary to the regulations and changes in assembly, construction or components can endanger the safe operation of the system
and lead to the exclusion of all warranty and guarantee claims.
2.2. Flamconnect app for operation
Commissioning the energy control system.
XThe Flamconnect app must be installed on a terminal device (Android or IOS) before commissioning and operation.
Work on the heating system must be performed by qualified specialist personnel in compliance with the respective applicable regulations,
guidelines and technical rules.
In addition to country-specific guidelines and local regulations, the following technical rules must be observed:
• DIN EN 12828 Heating systems in buildings
• DIN 18 380 Central heating systems and hot water supply systems
• DIN EN 60335 Electrical apparatus for household and similar uses
• DIN EN 60730 Automatic electrical control equipment
• DIN EN 1264 Underfloor heating - systems and components
• VDI 2035 Scale formation in drinking water heating systems and water heating systems
Avoidance of damage to water heating appliances.
• VDE 0100 Series of standards for the installation of electrical equipment
• BGV Regulations of the employers' liability insurance association (accident prevention
Warning symbolWarning wordMeaning
HAZARDHazards to persons.
Non-observance will result in death or serious injury.
WARNINGHazards to persons.
Non-observance may result in death or serious injury.
CAUTIONHazards to persons.
Non-observance can lead to minor injuries.
CAUTIONInformation to prevent damage to property, to understand or to optimise work processes.
regulations)
The illustrations are symbolic and may deviate from the respective product.
Secos - Simplex Energy Control SystemSecos system manifolds Secos energy saving controllerSecos actuators
2
123
1
Art. no. 1 + 2 +
F18804Secos System, 4 circuits1 x F188201 x F18840 4 x F18841
F18805Secos System, 5 circuits1 x F188211 x F18840 5 x F18841
F18806Secos System, 6 circuits1 x F188221 x F18840 6 x F18841
F18807Secos System, 7 circuits1 x F188231 x F18840 7 x F18841
F18808Secos System, 8 circuits1 x F188241 x F18840 8 x F18841
F18809Secos System, 9 circuits1 x F188251 x F18840 9 x F18841
F18810Secos System, 10 circuits1 x F188261 x F1884010 x F18841
F18811Secos System, 11 circuits1 x F188271 x F1884011 x F18841
F18812Secos System, 12 circuits1 x F188281 x F1884012 x F18841
F18813Secos System, 13 circuits1 x F188291 x F1884013 x F18841
F18814Secos system, 14 circuits1 x F188301 x F1884014 x F18841
3
3
Art. no.Art. no.Art. no.
Completeness of the delivery
Please check the goods are intact and complete immediately aer receipt of the delivery.
Any damage or complaints must be reported immediately.
4.2. Flamconnect app for operation of the Secos energy-saving controller
The Secos energy-saving controller is operated using an app via a tablet or smartphone. You can use either iOS or Android devices.
You can download the required app from the respective stores.
As soon as the Flamconnect app is installed on your device, you can connect to the Secos Energy Saving Control System via the QR code
onthe housing and operate your Secos Energy Control System with ease.
For further information see the chapter on Operation and handling.
Number of connectable room thermostatsUp to 8
Number of operable heating circuits per control zone1 - 14 heating circuits
Dimensions H x W x D328 x 97 x 61 mm
Protection codeIP 20
Permissible ambient conditions-10 - 60 °C, max. relative humidity 80 %, air pressure 750 - 1050 hPa
Supply voltage230V AC / 50-60 Hz
Power consumptionmax. 500 W
Output voltage for circulating pump230V AC / 50-60 Hz
Interface for building management systemModbus RTU
Frequency range for wireless connection2402 - 2484 MHz
Maximum transmitting power5 dBm
Secos system manifolds
Number of heating circuits4 - 14 heating circuits
Dimensions(See Dimensions table)
Max. operating temperature:75 °C
Max. operating pressure:10 bar
Volume flow per heating circuit0 - 8 l/min
Operating medium:Heating water according to VDI 2035
Pressure loss system manifold completekvs 1.19 m³/h
Primary connectionsG1" F
Secondary connectionsG3/4" M Eurocone
Material of manifold barStainless steel
Material of valvesceramic disc valves
Secos supply line temperature sensorØ 6 x 50 mm
Closing stroke ceramic valve90°
Secos actuator
Dimensions H x W x D47 x 77 x 57 mm
Operating temperature-10 to 60 °C
Protection codeIP 20
Secos multisensor
Measuring range for flow rate0 - 8 l/min
Measuring range for temperature+10 to +75 °C
Sensor characteristics
Temperature10 °C15 °C20 °C25 °C30 °C35 °C40 °C45 °C50 °C55 °C60 °C65 °C70 °C75 °C
Multisensor [Ω]52.052.953.954.955.856.857.858.759.760.761.662.663.564.5
Temperature sensor
6. Installation of Secos system manifold and Secos energy saving controller unit
The hydraulics must be checked for leak-tightness before installation of the electronics. It must be ensured that no moisture can enter
theelectronics.
6.1. Installation of system manifold
The primary connections on the unit as
delivered are located on the le-hand
side.
1
Return line
2
Supply line
3
Temperature sensor supply line le
Conversion from le to right
For this purpose on the upper manifold
(return line)
Observe space requirements for accessories energy saving controller
incl. mounting location, connection set and pipe mounting.
See table for dimensions of fixing points (F, G).
See table for minimum clearance (L).
The Secos system manifold can be operated
in various installation positions.
However, if the system manifold is to
be operated outside the recommended
installation position, the energy saving
controller unit must not be placed in areas
where water ingress is a risk.
The hydraulics must be checked for
leak-tightness before installation of the
electronics.
It must be ensured that no moisture can
enter the electronics.
1
The Secos system manifold can be
mounted horizontally rotated from 0° to 360°.
11 Recommended mounting position
12 Other possible mounting positions
Do not install the Secos energy-saving
controller below water-bearing connections!
1
0 - 360°
13 Installation options for energy saving controller
The illustrations are symbolic and may deviate from the respective product.
The valves can be operated using the handle
caps or with an Allen key. In the return
manifolds, the valves may only be operated
manually with the drive units disassembled.
1
To open: turn anticlockwise by 90°
2
To close: turn clockwise by 90°
6.4.4. Leak-tightness test
Check all components of the system
including all prefabricated elements for
leaks and rework accordingly in the event
of leakage. Adjust the test pressure and test
duration to the respective piping system
andthe respective operating pressure.
Fill the heating system only with filtered
(if possible), treated water according to
VDI2035 and completely vent the system.
16 Manual operation of the valves
17 Leak-tightness test
1
90°
4 mm
2
6.4.5. Protection for snap-on boards
Attach the protective card
immediately aer leak test
1. Remove from the insert
2. Fold at the intended fold line.
3. Completely cover the actuator plinth
with sensor cable and Bus cable
4. Fix the protectic cover
18 Packaging serves as protection during the construction phase
2
1
4
The illustrations are symbolic and may deviate from the respective product.
There are various ways of installing the Secos energy saving controller.
Installation site
If the Secos system manifold is installed in the recommended position, the ideal installation location for the Secos energy saving controller
is within reach of the preconfigured connection cables.
If required, the Bus cable can be extended with optional accessories. The cable of the Secos supply line temperature sensor can also be
extended by the customer. For further information see the Electrical connection chapter.
A - Mounting on top hat rail
Mount the controller on the top-hat rail
located in the cabinet.
1
Mount below
2
Pull upwards
3
Press to the rear and snap in
at the top
To disassemble, press the controller
upwards and pull it forward at the top.
Then unscrew below.
B - Wall mounting
1. Hold the energy-saving controller unit
against the wall and mark fixing points
on the wall.
2. Fasten with appropriate fasteners
(dowels, screws provided by customer).
Work on the electrical system and the opening of electrical housings may only be carried out when the system is de-energised and only by
authorised specialist personnel. Ensure correct terminal assignment and polarity. Protect the electrical components against overvoltage.
Improper electrical connection may result in danger to life through electric shock.
XElectrical connection should only be carried out by an electrician approved by the local power supply company
and in accordance with the locally applicable regulations.
XDisconnect the supply voltage before working.XDo not open the housing parts!
8.2. Connection terminals in the energy saving controller
To install, simply push the cable in as far as it will go. To disassemble, press the button and pull out the cable.
Spring terminal
Screw terminal
Multiple assignment is possible
21 Spring terminal
22 Screw terminal
7 mm
9 mm
2
7 mm
2
0.14 - 1.5 mm
9 mm
0.5 - 1.5 mm
7 mm
2
0.14 - 1.5 mm
2
0.5 - 1.0 mm
2
0.25 - 0.5 mm
7 mm
The illustrations are symbolic and may deviate from the respective product.
ShieldScreen interfaceInterface to building management systems
GND BUSGround interface
AChannel A for data communication interface
BChannel B for data communication interface
+24V BUSPower supply interface
System busReverse-polarity-protected plug to the system manifold
GNDGround analogue output switching valve 0 - 10 V
AOSignal analogue output switching valve 0 - 10 V
GNDGround external condensation monitor
0..20 mA-
0..10VInput signal external condensation monitor
+24V 40mAPower supply of external condensation monitor
pt-Temperature sensor for supply line, polarity freely selectable
pt+Temperature sensor for supply line, polarity freely selectable
C/O GNDGround changeover (potential-free)
C/O INInput signal changeover (potential-free)
L1 – L8Power supply of the room thermostats
N1 – N8Neutral conductor of the room thermostats
out 1 - 7
in
C/O outChangeover signal for display on room thermostat 8 (Master)
L outPhase pump for 230 V output
N outNeutral conductor for 230 V output
Description
(BMS) and other systems. Table with data
points available in a separate document
"Connectivity Guide". The document can be
downloaded from the following address: www.
simplex-armaturen.de/manuals/secos.
Switching signal of the respective room thermostats
Output lowering signal for room thermostat 1 - 7 (slave)
Input lowering signal from room thermostat 8 (master)
Protective conductor for 230 V output
Protective conductor for power supply system
LPhase energy supply system
NNeutral conductor for power supply system
X Ensure correct polarityX If intended or prescribed for pumps, connect the protective earth conductor to the protective earth connection terminals of the
controller. Observe the following points: Ensure that the protective earth conductor is also connected to the controller on the power
supply side.
X Strain relief using flexible cables required: the enclosed cable ties must be used and tightened so that the cable cannot come loose.
8.5. Connect Secos temperature sensor for supply line
a. When connecting to the controller, it is not necessary to pay attention to polarity.
A cable with 2 x 0.5 mm² can be used to extend the sensor up to 2 m.
Sensor is already mounted in immersion sleeve.
8.6. Connect Secos system bus
a. Insert plug, if necessary use extension (optional accessory)
b. 1x Bus cable ready to plug in, twist-proof.
The illustrations are symbolic and may deviate from the respective product.
Improper electrical connection may result in danger to life through electric shock.
XElectrical connection should only be carried out by an electrician approved by the local power supply company
and in accordance with the locally applicable regulations.
XDisconnect the supply voltage before working.XDo not open the housing parts!
Up to 8 room thermostats can be connected to the energy saving
controller. If a room thermostat is used as master, it must be connected to terminal location 8.
The remaining terminal locations 1 - 7 can be used as required. All
heating circuits are assigned to the room thermostats in the app.
Both 2-point room thermostats and room thermostats with
PWMcharacteristic can be connected and utilised.
Only 230V room thermostats may be connected.
24 Connection of Master / Slave room thermostats
L1-7 N1-7
23 Connecting room thermostats
Slave
L
NL
in-timer
T
Set-back operation for room thermostats
Thermostat with set-back output is connected to terminal block 8. Thermostats with set-back input use this signal via the respective
connection, terminal blocks 1 to 7.
25 Connection of room thermostats with cooling operation
Secos
24 V230 V
L1-7 N1-7
Slave
N
The energy-saving controller registers the cooling mode via the C/O IN input and can control the individual thermal circuits accordingly.
Auto-inverting
In the app you can set whether the room thermostat signal should be inverted. With "Auto-inverting", the room thermostat automatically
detects whether the system is in cooling mode and automatically carries out signal processing (prerequisite: c/o out of the energy-saving
controller is connected to the master room thermostat).
Non-inverting
With "Non-inverting" there is no connection between the c/o out and the room thermostat, or the room thermostat does not have a
corresponding remote station. In this case, the controller inverts the room thermostat signals when switching to cooling mode (signal from
cold source at c/o in).
in-timer
T
Nout-
LL
T
timer
Master
in-C/O
The illustrations are symbolic and may deviate from the respective product.
Supply line temperature, bus cable for activators, if necessary c/o,
ifnecessary ext. Condensation monitor, if necessary MODBUS,
ifnecessary c/o valve 0-10V).
If other condensation monitors are used, it must be ensured that the
voltage supply of the condensation monitor is taken from the energy
saving controller and that a potential-free changeover contact is
then fed back to a 0..10V interface.
If the external condensation monitor is triggered, all valves are
closed and the pump interface is deactivated. As soon as the
condensation monitor reports no further condensation, the system
returns to regular operation.
XThe high-quality electronics of the actuator must be installed with appropriate care!XPins could be bent. This can result in the sensor or the complete drive no longer making contact.
A - Installing the actuator
Snap-on: Plug-in technology for mechanical
and electrical connection with just one click
for error-free and time-saving installation
1
Set up carefully
2
Feel the spindle and align the housing
flush with the snap-on board by
turning it slightly.
3
Press the actuator downwards until
itperceptibly locks into place.
B - Dismantling the actuator
1
To unlock the actuator, press at the
marked point
2
and li out at the same time
28 Installing the actuator
1
2
29 Removing the actuator
3
2
Note:
When reassembling, the actuators must be
placed back on their respective snap-on
boards.
Otherwise the actuators will have to be
reassigned to function as expected.
Aer reinstallation, the energy saving controller must be restarted.
1
The illustrations are symbolic and may deviate from the respective product.
The following requirements must be met for successful commissioning:
X All components of the system are installed and assembled.X The entire system is leak-tight.X All necessary electrical connections have been made.X A terminal device (tablet / smartphone) is available with the Flamconnect app installed.
9.1. Flamconnect app
X The Secos energy-saving controller can only be set and operated via a smart device with the Flamconnect app installed.X One smart device can be connected to one controller at a time.
X The app is the tool for the expert for commissioning, logging, monitoring and diagnosis.
Download app:
For system requirements, see description in the respective App Store
a. Play-Store - Android version
b. iOS App Store - Apple version
In the Flamconnect app, you will be guided step-by-step through
the commissioning process.
The settings can be changed later at any time via the app.
1 Supply controller with power
2 Open the Flamconnect app
3 Scan QR code of controller
1
Label with QR Code
4 Enter connection code
2
Passkey: Input required to pair the smart device with
thecontroller.
5 Configuration
Follow the further steps in the app:
• Go through the checklist to ensure the conditions for operation
have been met.
• Identify actuators starting from the le
• Parameterisation of the system (operating mode heating/
cooling/ both, output per room or flow rate per heating circuit)
• General settings and system balancing function
• Assignment of circuits and thermostats with input of heating
load/volume flows, cooling function, radiator thermostats.
• It is also possible to operate heating circuits without the
assignment of a room thermostat. However, this requires manual
entry of the desired power level [1 - 100 %].
31 QR code
32 QR code & passkey
Device name: 03000001
Passkey: 123456
33 Actuator
1
1
2
1
LED: Display of the operating statuses
2
Key to identify the actuators
Aer successful identification, the actuators may no longer be
exchanged with each other. If an exchange is necessary, the energy
saving controller must be restarted and the activators must be
identified and re-assigned.
6 Set / activate functions
Automatic flushing function: (see chapter on Operation)
Connect the flushing pump in the direction of flow. Flushing of the
individual circuits now takes place automatically, in series, until this
has been successfully carried out and confirmed by the operator.
(Connection to the smart device is not necessary during the whole
process)
Screed protocol function: (see chapter on Operation)
Aer commissioning, the screed protocol function can be activated
via the Flamconnect app.
1
2
The illustrations are symbolic and may deviate from the respective product.
To set or activate the functions, the energy saving controller must be connected to a tablet or smartphone via the Flamconnect app.
10.3.1. Flushing function
The flushing function is usually required by the installer when the heating system is commissioned. During flushing, the air from the heating
circuits is flushed and separated. The heating water is pumped through the heating circuits in series at maximum speed to flush air bubbles
out of the pipes. The automatic flushing process must be started in the app and will then run automatically and independently of the app.
At the end of the flushing process, the flushing function must be terminated in the app again. Only then does the energy-saving controller
go into normal operation mode.
Flushing process
1
Return line
2
Supply line
Signalling on the energy saving controller
Status LED: During the flushing function, the LED on the energy saving controller flashes green
Aer successful completion of the function, the LED lights up green
37 Flushing
1
2
.
slowly about 1x per second.
Aer completion and in the event of an error, the red
Signalling on the actuator
Status LED: LED on the valve of the heating circuit that is being flushed flashes green
Flushing process OK = LED green
Flushing process not OK = LED red
30Secos - Simplex Energy Control System
.
. In this case, please repeat the procedure or flush manually.
LED lights up. In this case, please repeat the procedure or flush manually.
Aer commissioning, the "Screed protocol"
function can be activated.
The supply line temperature is recorded at
regular intervals. The data can then be used
to create the screed heating log.
This function can be activated even if no
actuators have yet been installed. However,
it must be ensured that all valves including
all supply line and return valves are open.
If the actuators are already installed, they
must be removed and the valve opened
manually. The sequence of the actuators
must not be confused ifcommissioning has
already been carriedout.
Otherwise, the actuators will have to be
reassigned.
38 Screed log
1
2
10.3.3. Valve and pump protection function
To ensure operational safety, the valves and the pump of the fixed-value control set are moved automatically during longer periods of
inactivity. Aer a power failure, an automatic reference run is performed. We therefore recommend keeping the unit permanently under
power.
10.3.4. Function of switching valve
This function enables individual control of a switching valve via the 0-10 V output. The configuration takes place in the app under
"Advanced Function".
10.3.5. Function of radiators
If radiators are connected to the heating circuits, they can be parameterised with dierent properties:
a. Radiators without thermostatic valve: These are controlled similarly to surface heating circuits via the respective room thermostat.
b. Radiators with thermostatic valve / thermostatic head on the radiator: In this case, no room thermostat is assigned to the circuit.
Thevalve of the corresponding heating circuit is permanently opened and hydraulically balanced. The control is based on the design
value [W]. The heating circuit is opened by means of the thermostatic valve / thermostatic head.
The illustrations are symbolic and may deviate from the respective product.
If the maximum permissible supply line temperature (factory setting 55 °C) is exceeded in heating mode, all valves are closed.
In cooling mode, all valves are closed if the minimum permissible supply line temperature of 15 °C is not reached.
10.4.2. Comparison of supply line / return line temperature
During heating operation, the spread between supply and return line temperature is constantly monitored. If the temperature in the return
line rises above the supply line temperature, the corresponding valve is closed.
10.5. Data export
The values set or recorded in the energy saving controller can be conveniently exported via the Flamconnect app and then used for further
logging purposes such as the commissioning log or the screed heating log.
For this purpose the exported file can be imported into the respective template.
The templates can be found at: https://simplex-armaturen.de/manuals/secos
For maintenance and in case of service, a connection via the app is necessary to view the current status, the error history and to check and
correct the causes. A general visual inspection of the entire system, in particular for leaks, must also be carried out.
11.1. Maintenance interval:
Irrespective of desiredl intervals, it is recommended that the system be checked at least once a year by a specialist. Maintenance costs are
usually amortized, meaning that unnecessary repair costs are oen avoided,m by this preventative maintenance, and therefore ongoing
costs are reduced.
11.2. Drainage, venting and shut-off possibilities
Flushing process
1
Shutting off
2
Flushing / venting
3
Flushing / draining
If flushing is required, this can be done
conveniently using the automatic flush
function.
39 Shutting o, flushing, venting
11.3. Replacing multisensors
1
Depressurise the system
2
Remove actuator
(see chapter on Installing the Secos actuator)
3
Carefully loosen the plug by opening out the catches and
pressing the plug from above. The Bus cable must not be
damaged. If necessary, press the Bus cable slightly to the
side with a plastic object to release the sensor cable.
2
1
1
3
40 Replacing multisensors
1
2
3
3
0
0 bar
4
Remove cap
5
Replace sensor
Fix the sensor cable so that the sensor cable does not
twist while the sensor cap is being tightened
5
3
The illustrations are symbolic and may deviate from the respective product.
Secos means Simplex Energy Control System and is a highly
innovative control system for surface temperature control.
2. How does Secos work?
Due to a constant volume flow and temperature measurement
in each heating circuit the hydraulic balancing values are
optimally and immediately adjusted.
3. How does the commissioning take place?
When the Secos energy-saving controller is connected for the
first time with the "Flamconnect" app, you will be prompted
toperform the commissioning.
You will be guided step by step through the required process.
4. Do you need to set more?
The hydraulic adjustment starts to work at the point of input
ofthe above-mentioned values. However, all settings can be
modified and additional functions specified later.
5. Can conventional room thermostats be used?
Secos is very flexible and can be used with all 230V room
thermostats which generate an analogue signal such as
a two-point or PWM signal.
6. Do the valves stick?
No, the ceramic disc valves are designed, and the material
selected, to ensure that the valves remain free, durable and
reliable. Additionally, any longer downtimes of individual
valves will be detected and the valves moved at periodic
intervals, to maintain freedom.
7. How sensitive are the Secos multisensors?
The Secos multisensors do not contain any moving parts.
Theyare therefore wear-free and function even with dirty water.
8. What happens in the event of a defect or fault?
In such an event, the Secos Energy Saving Controller will
register a warning signal. Then, the smartphone or tablet which
is connected via the Flamconnect app to the Secos energy
saving controller can be used to carry out a detailed analysis.
9. How does flushing take place?
There is an automatic flushing program, which can
conveniently be started after connection (e.g. using flushing
equipment) via the "Flamconnect" app. The automatic
flushing program flushes the heating circuits separately
and automatically until a reliable and constant volume flow
isdetected by the Secos multisensors.
10. Can I also shut off heating circuits without a Secos actuator?
Yes, the Secos disc valves can be manually opened and closed
in the supply and return lines.
11. Is Secos compatible with other laying systems?
Secos is compatible with all commercially available underfloor
heating laying systems such as staple, nub plate, hook and
loop, drywall, support matting and renovation systems
12. Can all underfloor heating pipes be used?
All commercially available underfloor heating pipes can be
used. These are connected with the Secos system manifold
using Eurocone compression fittings.
F18840 Secos energy saving controllerEnergy saving controller for up to 8 room thermostats, up to 14 circuits
1
F18841Secos actuatorfor adjusting the ceramic disc valves
2
F18850Secos multisensor Multi-sensor with cable, plug and screw-on cap
3
F18852Secos supply line temperature sensorSupply line sensor without immersion sleeve
4
2
42 Total spare parts
1
4
2
3
14.2. Accessories
Note: not included in the scope of delivery!
Article no.ArticleInformation
F18854Secos BUS extension for connection cableExtension cable with plug for BUS connection (2m)
F18855Secos external condensation monitorExternal condensation monitor for decentralised application
The illustrations are symbolic and may deviate from the respective product.
Separate products and packaging into their respective material groups (e.g. paper, metals, plastics or non-ferrous metals) and dispose of
them in accordance with the applicable national legislation.
Electronic components, batteries and accumulators may not be disposed of in household waste, but must be disposed of properly in
accordance with the applicable guidelines.
Scope of application/note: WEEE registration for the Waste Electrical Equipment Register: DE30940639
CE conformitySimplex Armaturen & Systeme GmbH hereby declares that the
product Simplex SECOS ESC is in conformity with the essential requirements and the other relevant provisions of Directives 2011/65/
EU, 2014/30/EU and 2014/35/EU.
The complete conformity assessment can be downloaded from
the following address: www.simplex-armaturen.de/de/docfinder/
conformity/
The illustrations are symbolic and may deviate from the respective product.
Product range39
Page 40
Our general terms and conditions of business and our guarantee conditions apply.
In perfect harmony with
Flowing Compositions
www.flowing-compositions.com
www.simplex-armaturen.de
Simplex Armaturen & Systeme GmbH
Isnyer Straße 28
D-88260 Argenbühl - Eisenharz
T +49 (0) 7566 9408-0
F +49 (0) 7566 9408-75
E secos@simplex-armaturen.de
Art.No. K80402220 Version 10/2020
40Secos - Simplex Energy Control System