Simplex Saturn 3000 DV Technical Manual

Final Acceptance
of Instruction Manual
Customer: Austin Generator Service
W.O. #: 63798-07-43/2
Load Bank Types: Saturn 3000 DV
1 Manual Shipped for the Load Bank described above.
2550KW/3000KW, 480/600V, 60KW Res,
LCL PLC, INT/EXT CP, Powered Louvers
This instruction manual has been reviewed and is approved
by me as being fully accurate and representative of the
equipment being supplied thereunder and it (the manual)
meets the customer’s specification/order requirements for
manuals.
Approved by: Date:
1 Manual Received by: Date:
LOAD BANK
TECHNICAL MANUAL
(LBD Series)
Customer: Austin Generator Service
Work Order: 63798-07-43/2
Model: Saturn 3000 DV
June 2007
The information herein is the property of Simplex, Inc. and/or its subsidiaries.
Without written permission, any copying, transmitting to others, and other use
except that for which it is loaned, is prohibited.
(File: 63798-2.p65; Disk: SDCX155)
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 1 of 20
Contents
DESCRIPTION .............................................................................. 2
Control System ...................................................................... 4
Cooling System ..................................................................... 4
Load System .......................................................................... 4
PRIMARY INSPECTION ............................................................... 4
INSTALLATION ............................................................................. 5
Location .................................................................................. 5
Procedure ............................................................................... 6
OPERATION ................................................................................. 6
Local ....................................................................................... 6
Remote ................................................................................... 7
Load Dump ............................................................................. 8
®
FAILURE DETECTION ................................................................. 8
Thermocouple Temperature Switch ..................................... 8
MAINTENANCE ............................................................................ 9
Each Operation ...................................................................... 9
Every 50 Hours or 6 Months ............................................... 10
Motor Lubrication ................................................................ 10
TROUBLESHOOTING ................................................................ 11
Cooling Fan Motor Will Not Operate .................................. 11
Some Load Steps Cannot Be Energized ........................... 11
Cooling Failure Indicated.................................................... 12
DRAWINGS AND PARTS LIST .................................................. 12
APPENDIX A - ABBREVIATIONS USED IN THIS MANUAL ..... 13
APPENDIX B - CALCULATIONS & FORMULAS ...................... 14
APPENDIX C - TORQUE VALUES ............................................. 17
APPENDIX D - PILLOW BLOCK BEARINGS
LUBE INTERVAL ................................................................. 19
APPENDIX E - DRAWINGS........................................................ 20
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
DESCRIPTION
Simplex Load Banks are precision test instruments specifically de­signed to apply discrete, selectable electrical load to a power source while measuring the response of the generator to the applied load. They also provide a means for rou­tine maintenance exercise to as­sure long term reliability and readi­ness of the standby generator. Ex­ercise Load Banks eliminate the detrimental effects of unloaded op­eration of diesel engine generators.
The cabinet on this Load Bank is rated NEMA Type 3R outdoor weatherproof.
Power source testing is accom­plished by applying resistive load steps at unity (1.0) power factor.
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 2 of 20
Load application is by magnetic contactor. All load branch circuits are protected by 200,000AIC class­T fuses.
Operating controls are located on a Local Control Panel and a Remote Con­trol Panel. The Control System is com­prised of 120V and 24VDC discrete components. Common serviceable components include Control Fuses (CF1–CF4) and Load Application Fuses (F1–F189). Lamps on the Local Control Panel indicate the Load Bank operating status. Control priority is determined by the “Mode Selector” switch.
Always remove all power from the load bus and all fan/control power before servicing the Load Bank. Never operate or service a Load Bank that is not properly connected to an earthground.
Part of Pictorial Drawing 47BD164460C
SPECIFICATIONS
Capacity: 2560KW/3000KW @ 1.0 PF
Voltage: 480/600VAC
Connection: 3-Phase, 3-Wire
Frequency: 60Hz
Fan Power: Int./Ext. 480/600V, 3ø, 60Hz
Control Power: Int./Ext. 480/600V, 3ø, 60Hz
120V Transformer
Cooling: Forced Air
Airflow: 60,000 CFM
Max. Air Intake Temp.: 120°F
Nominal Air Temp. Rise: 125°F–500°F Max.
Temperature Rise: °F =
Duty Cycle: Continuous
Serial Number: 63798-07-43/2
KW x 3000
CFM
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
The Local Control Panel contains the following components:
1. Louvers Open, Cooling Failure, Over Temperature, Fan Failure, Access Door Ajar, Louvers Closed, Remote Control Active, Control Power On, Normal Operation, and Load Dump Bypassed indicator lamps
2. Fan/Control Power switch
3. Load Bank Mode switch
4. Auto Load Dump switch
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 3 of 20
ALARM
HORN
SILENCE
LOUVERS
OPEN
COOLING FAILURE
OVER
TEMPERATURE
FAN
FAILURE
LOAD DUMP
BYPASSED
®
5. Load Voltage Selector switch
6. Master Load and load step switches
7. Fan/Control Power Voltage Selec­tor switch
The Remote Control Touch Panel is housed in a suitcase.
This Load Bank is protected against cooling failures (loss of cooling air flow, high intake or exhaust air temperature which could damage the Load Bank or present a safety hazard to the opera­tor). When a cooling failure occurs the automatic safety features in the Control System immediately remove the load from the load source. The malfunction must be corrected and the system must be reset by turning the Load Bank “Off” then “On” before the load can be re­applied.
The Load Bank consists of three princi­pal systems:
LOUVERS
CLOSED
FAN/
CONTROL
POWER
OFF ON REMOTE LOCAL ENABLED BYPASS
RESISTIVE
MASTER
LOAD
OFF ON
42KW
480V
50KW
600V
OFF ON
425KW
480V
500KW
600V
OFF ON
REMOTE
CONTROL
ACTIVE
MODE
SELECT
RESISTIVE LOAD STEP CONTROLS
4.1KW 5KW
OFF ON
85KW
100KW
OFF ON
850KW
1000KW
OFF ON
CONTROL
POWER ON
LOAD DUMP
BYPASS
OFF ON
85KW
100KW
OFF ON
8.5KW 10KW
OFF ON
OFF ON
LOW VOLTAGE
480VAC,3Ø,60HZ
FAN/CONTROL POWER
VOLTAGE SELECTOR
NORMAL
OPERATION
8.5KW 10KW
170KW 200KW
HIGH VOLTAGE
600VAC,3Ø,60HZ
OVER
VOLTAGE
LOAD
VOLTAGE
SELECTOR
480V 600V
21KW 25KW
OFF ON
425KW 500KW
OFF ON
480V 600V
480V 600V
1. Control System
2. Cooling System
3. Load System
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 4 of 20
®
CONTROL SYSTEM
The Control System allows the operator to apply a desired load to the test source and measure the response of the test source to the load. This system also contains the circuitry utilized to discon­nect the load from the test source in the event of cooling failures and/or improp­erly positioned operating controls.
Fan power is applied to the Fan Motor (MOT) through the Fan Circuit Breaker (FCB 1A or FCB 1B), the Disconnect Switch (DSW), the Fan/Control Voltage Selector swtich (S1), the Auto Trans­former, and the Fan Motor Contactor (FMC) contacts. An Overload Relay (OVR) is used to protect the motor.
COOLING SYSTEM
Resistive Load Elements are cooled by a forced air system consisting of a 60" fan blade belt driven by a 30HP, TEFC motor, creating a 50,000 CFM. The fan motor is energized by a 60A, 600V, 3 pole contactor (FMC) and protected by a 100A frame, 60A trip, 3 pole, 600V circuit breaker (FCB).
LOAD SYSTEM
The Load System consists of indepen­dently controlled resistive and/or reac­tive load elements specifically designed for Load Bank systems. They are pro­tected by 200,000AIC, 600VAC fuses.
Simplex Resistive Load Elements con­servatively operate at approximately half the maximum temperature rating of the alloy (1080°F vs. 1920°F). For example:
Alloy: FeCrAl
See Parts Legend Drawing for specific elements used.
These elements are rigidly supported by high-temperature, ceramic-clad, stainless-steel supports. Element-to­element short circuits are virtually elimi­nated. The elements are assembled in discrete trays which are assembled in a vertical “stack”. Each tray is independ­ently serviceable without disturbing ad­jacent trays.
PRIMARY INSPECTION
Preventative visual inspections of the shipping crate and Load Bank is ad­vised. Physical or electrical problems due to handling and vibration may oc­cur. Never apply power to a Load Bank before performing this procedure. The following Nine Point/30 Minute Inspec­tion is recommended before installa­tion, as part of the 50 hour / 6 month maintenance schedule and whenever the Load Bank is relocated:
1. If crate shows any signs of damage examine the Load Bank in the corre­sponding areas for signs of initial problems.
2. Check the entire outside of the cabi­net for any visual damage which could cause internal electrical or mechani­cal problems due to reduced clear­ance.
3. Inspect all hinged panels and doors for smooth and safe operation, try all latches and knobs.
4. Rotate and push all switches through all positions to ensure smooth opera­tion.
5. Check cooling system by inspecting fan motor and blade. Slowly rotate blade by hand and note clearance of blade tip through its rotation near the housing. Observe free rotation of mo­tor shaft.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 5 of 20
®
If any problems are observed during Primary Inspection call the Simplex Service Manager at 217-483-1600 (24hrs.)
6. Inspect all relays, timers, and control modules by opening all accessible panels. Make sure all components are secure in their bases and safety bails are in place. Spot check electri­cal connections for tightness. If any loose connections are found inspect and tighten all remaining connec­tions.
7. Examine all accessible internal elec­trical components such as fuses, contactors and transformers. Check lugged wires at these components.
8. Inspect bottom of crate/enclosure for any components that may have jarred loose during shipment such as indi­cator light lenses, switch knobs, etc.
9. Visually inspect element chamber for foreign objects, broken ceramic in­sulators, mechanical damage.
INSTALLATION
LOCATION
Nema-3R Load Banks are intended for outdoor installation. The load elements in this Load Bank are cooled by a forced air system which discharges through the top of the cabinet. This Load Bank will produce a large quantity of exhaust air. Location of the Load Bank is of prime importance and should be done by trained personnel. It is one of the most critical factors involved in safe operation. The Load Bank must be po­sitioned and installed according to large airflow requirements.
• There must be a minimum clearance of 6 feet on all sides of the Load Bank.
• Load Banks installed indoors must be equipped with an exhaust air duct of minimum back pressure (supplied by others) which routes all Load Bank hot exhaust air outdoors.
• Never install any structure or object at any height above the Load Bank.
• Always locate the Load Bank in a secure area accessible by trained personal
only.
• Use the eyehooks and forklift chan­nels provided to position the Load Bank.
• Never move the Load Bank with the exhaust hood attached.
• Never point the exhaust at a nearby surface or object which may be ad­versely affected by high tempera­ture.
• Never operate the Load Bank in a confined space without regard for adequate intake of air and provision for exit of high temperature exhaust.
• Consider that the Load Bank and a nearby generator set may have to compete for cooling air.
• Never bounce hot exhaust air off nearby objects and allow it to recircu­late through the cooling system.
• Never operate the Load Bank in prox­imity to a sprinkler system.
Failure to properly install this Load Bank may result in substantial damage to or the destruction of the Load Bank, adja­cent equipment and the building in which the Load Bank is installed.
Never operate or service a Load Bank that is not properly con­nected to an earthground.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 6 of 20
®
PROCEDURE
1. Confirm the test source is properly grounded and ground the Load Bank in compliance with NEC.
2. If Remote Control is desired, using CAT 5 Patch Cable, connect the laptop computer to Receptacle 3 on the Load Bank.
3. Confirm all load command switches are in the “Off” position.
4. Confirm the Disconnect Switch (DSW) is in the “Off” position.
See Fan/Control Power Drawing
5.
47B164462B.
480/600V, 3ø, 60Hz, 60A source to FCB 1A as shown.
Consult NEC for proper wire size.
6.
See Control Drawing 47B164461C.
Using #14 AWG copper wire or greater with a torque of 35 in. lbs., connect customer supplied Load Dump contacts to TB‘LD’ 1–2 or place the “Load Dump Mode” switch in the “Bypass” position.
Load is disengaged when the con­tact is open.
Load is engaged when the contact is closed.
7.
See Resistive Load Section 1 Draw­ing 47B164469.
source to the Load Bank as shown.
Consult NEC for proper wire size.
8. Place the Disconnect Switch (DSW) in the “On” position.
9. Place the Fan Circuit Breakers (FCB 1A or FCB 1B) in the “On” position.
Connect and external
Cable the load
OPERATION
LOCAL
1. Place the “Load Voltage Selector” and “Fan/Control Power Voltage Se­lector” switches in the appropriate positions.
2. Place the “Load Bank Mode” switch in the “Local Manual” or “Remote” position.
3. Start-up generator or bring other test source on line.
If External Fan/Control Power is be­ing used, “Fan/Control Power” switch in the “On” position to energize the cooling fan before starting the gen­erator to assure proper fan opera­tion.
4. Adjust power source voltage and fre­quency.
5. Place the “Fan/Control Power” switch in the “On” position to energize the cooling fan.
A false “Cooling Failure” lamp indica­tion may be present until the cooling fan creates sufficient airflow to close the Fan Pressure Switch (PS). The “Normal Operation” lamp illuminates and control voltage is supplied to the “Master Load” switch. With voltage supplied to the “Master Load” switch, the operator is now ready to apply load steps.
6. Verify the illumination of the “Normal Operation” lamp before proceeding.
7. Visually observe correct fan opera­tion and investigate any unusual fan related noises.
8. Check air intake for obstructions and confirm positive air flow.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
9. Select the desired load steps by placing them in the “On” position.
10. Place the “Master Load” switch in the “On” position.
This simultaneously applies all of the load steps which are in the “On” position.
Trim is achieved by flipping the load steps “On” and “Off” while the “Mas­ter Load” is in the “On” position.
11. Adjust source voltage and load. Monitor as needed.
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 7 of 20
Shutdown
1 De-energize the load.
2. Run the cooling fan for 5 minutes to
assure a thorough cool down of all load elements (optional).
3. Place the “Fan/Control Power” switch
in the “Off” position.
REMOTE
There are three screens on the remote touch panel. They are: Control/Status Screen, Load Screen, and Metering Screen.
1. Press the “Activate Remote” button.
2. Press the “Energize Control Power”
to energize the cooling fan.
A false “Cooling Failure” may be indi­cated until the cooling fan creates sufficient airflow to close the Fan Pressure Switch (PS).
3. Verify “Normal Operation” via the
status window before proceeding.
4. Visually observe correct fan opera-
tion and investigate any unusual fan related noises.
Control/Status Screen
Load Screen
6. Select the desired load steps by pressing the desired buttons.
7. Press the “Master Load” button.
This simultaneously applies all of the load steps which are in the “On” position.
Trim is achieved by pressing the load steps “On” and “Off” while the “Master Load” is in the “On” posi­tion.
5. Check air intake for obstructions and confirm positive air flow.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
8. Adjust source voltage and load. Monitor as needed.
SHUTDOWN
1 De-energize the load.
2. Run the cooling fan for 5 minutes to assure a thorough cool down of all load elements (optional).
3. Press the “De-energize Control Power” button.
4. Press the “Release Remote” button.
LOAD DUMP
This Load Bank contains a Load Dump feature which de-energizes all applied load when customer supplied contacts open. Normally closed to run, they are rated at 2A @ 24VDC and should be wired to TB‘LD’ 1–2. When these con­tacts open all applied load will be de­energized and the load section will be disabled. If desired, the customer may install automatic transfer switch con­tacts, a manual pushbutton or circuit breaker for this use.
The operator also has the option of bypassing these contacts and enabling the load section by flipping the “Auto Load Dump” switch to the “Bypass” position. This disables the load dump feature and illuminates the “Load Dump Bypass” lamp.
Do Not allow the Load Bank to operate unattended for extended periods.
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 8 of 20
Metering Screen
FAILURE DETECTION
If a “Failure” occurs the corresponding lamp will illuminate and the load will be de-energized. Before reapplying a load, the failure must be corrected and the system must be reset by turning the Load Bank “Off” then “On”.
This is a permissive/energize-to-run cir­cuit in which all safety sensors must energize their control relays on normal operation before load can be applied. This system includes the following com­ponents:
1. Exhaust Temperature Switches (EXTS1–EXTS4)
2. Pressure Switch (PS)
3. Intake Temperature Switch (INTS)
Thermocouple Temperature Switch
The exhaust temperature network con­sists of a type J thermocouple (TC) and a solid state thermocouple sensor (EXTS). The temperature switch has been factory adjusted for precise Load Bank over temperature protection un­der normal operating conditions. Un­usual operating conditions may require
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 9 of 20
®
For continued safety and for maximum equipment protec­tion, always replace fuses with one of equal rating only.
field adjustment. The setpoint of the Exhaust Temperature Switch (EXTS) may be changed by rotating the adjust­ment knob.
Consult the Simplex Ser­vice Department (217-483-1600 24hrs) before changing the temperature switch setpoint.
MAINTENANCE
The Load Bank has been designed to require minimum maintenance. All com­ponents have been chosen for a long, reliable life. Two basic intervals of main­tenance are required: each operation and every 50 hours or 6 months (which­ever comes first).
EACH OPERATION
Overgreasing is a major cause of bearing and/or motor failure. The amount of grease added should be carefully controlled. Also make sure dirt and con­taminants are not introduced when adding grease.
If lubrication instructions are shown on the motor nameplate, they will supersede this gen­eral instruction.
If motor is nameplated for haz­ardous locations, do not run motor without all of the grease or drain plugs installed.
The air intake screens and louvers, fan and cooling chamber, and exhaust open­ings must be checked for any obstruc­tions or foreign objects. Due to the high volume of air circulated, paper and other items can be drawn into the air intakes. During Load Bank operation insure that air is exiting from the top exhaust vent.
The Pillow Block Bearings (PN
22691040), which are used on Saturn Load Banks, are pre-lu­bricated at the time of manufac­ture. These bearings are lubri­cated with Mobil Mobilith AW2
The load branches should be checked for blown fuses or opened load resis­tors. To check the fuses or load resis­tors, operate the Load Bank from a balanced 3-phase source and check the three line currents. The three cur-
grease (a Lithium based grease). Lubrication using an­other grease may cause bear­ing failure.
See Appendix D ­Pillow Block Bearings Lube In­terval for additional information.
rent readings should be essentially the same. If a sizeable difference is noted one or more load fuses or load resistors may have malfunctioned.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 10 of 20
®
EVERY 50 HOURS OR 6 MONTHS
Check the tightness of the electrical connec­tions. The expansion and contraction caused by Load Bank operation may result in loose con­nections. The vibrations caused by the cooling
Standard 3 yrs. 8 mo. 2 yrs. 8 mo. 1 yr. 3 mo.
Severe 1 yr. 3 mo. 1 yr. 3 mo. 6 mo. 1 mo.
Seasonal See Note 2.
fan may also loosen electrical connections. If the Load Bank is trans­ported “over the road”, the electrical connec­tions should be checked for tightness at a shorter­than-normal time inter­val. See “Primary In­spection”.
Standard: Up to 16 hours of operation per day, indoors, 100°F maximum ambient.
Severe: Greater than 16 hours of operation per day. Continuous operation under high
ambient temperatures (100° to 150°F) and/or any of the following: dirty, moist locations, high vibration (above NEMA standards), heavy shock loading, or where shaft extension end is hot.
Seasonal: The motor remains idle for a period of 6 months or more.
Note:
1. For motors nameplated as “belted duty only” divide the above intervals by 3.
2. Lubricate at the beginning of the season. Then follow service schedule above.
MOTOR LUBRICATION
Motors are properly lubricated at the time of manufacture. It is not necessary to lubricate at the time of installation unless the motor has been in storage for a period of 12 months or longer (refer to lubrication procedure that follows).
Inspect the fan motor supplied with your Load Bank for grease fittings. If the motor contains grease fittings you must lubricate the motor. If lubrication in­structions are shown on the motor name­plate, they will supersede this general instruction. Belt driven cooling fans have bearings which should be lubricated. Bearings should be lubricated every 50 hours of operation or 6 months which­ever comes first.
RELUBRICATION TIME INTERVAL
for motors with regreasing provisions.
NEMA Frame Size
140 – 180 210 – 360 400 – 510
1800 RPM Over 1800 1800 RPM Over 1800 1800 RPM Over 1800
and less RPM and less RPM and less RPM
Lubrication Procedure
1. Stop motor. Disconnect and lock out of service.
2. Remove contaminants from grease inlet area.
3. Remove filler and drain plugs.
4. Check filler and drain holes for block­age and clean as necessary.
5. Add proper type and amount of grease. See the Relubrication Time Intervals table for service schedule and Relubrication Amounts table (see next page) for volume of grease required.
6. Wipe off excess grease and replace filler and drain plugs.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 11 of 20
®
7. Motor is ready for operation.
Warning: If motor is nameplated for hazardous locations, do not run mo­tor without all of the grease or drain plugs installed.
Grease Type
Unless stated otherwise on the motor nameplate, the motors on this Load Bank are pregreased with a polyurea mineral oil NGLI grade 2 type grease. Some compatible brands of polyurea mineral base type grease are:
• Chevron SRI #2
• Rykon Premium #2
• Exxon Polyrex EM
• Texaco Polystar RB
TROUBLESHOOTING
This section is designed to aid the elec­trical technician in basic Load Bank system troubleshooting. All of the prob­lems listed can be verified with a basic test meter and/or continuity tester. For safety reasons, when troubleshooting Load Bank systems always remove all test source power, fan/control power, anti-condensation heater power, etc.
RELUBRICATION AMOUNTS
for motors with regreasing provisions.
NEMA Volume
Frame Size cu. in. (fluid oz.)
140 .25 (.14)
180 .50 (.28)
210 .75 (.42)
250 1.00 (.55)
280 1.25 (.69)
320 1.50 (.83)
360 1.75 (.97)
400 2.25 (1.2)
440 2.75 (1.5)
500 3.00 (1.7)
When troubleshooting Load Bank systems always remove all test source power, fan/control power, anti-condensation heater power, etc.
SOME LOAD STEPS CANNOT BE ENERGIZED
COOLING FAN MOTOR WILL NOT OPERATE
1. Inoperative Fan Circuit Breaker (CB)
2. Fan/Control Power not available/ incorrect
3. Inoperative Fan Motor (MOT)
4. Fan Motor Contactor (FMC) de­energized
5. Restriction of air (intake or ex­haust)
6. Fan pressure switch inoperative
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
1. Inoperative load step switches
2. Open load step resistor(s)
3. Inoperative load step relays
4. Inoperative load step contactors
5. Open load step fuses
COOLING FAILURE INDICATED
Exhaust temp above EXTS setpoint:
1. Over temperature sensor failure
2. Fan failure
3. Air restriction (intake or exhaust)
4. Overvoltage condition present
Exhaust temp below EXTS setpoint:
1. Restriction of air (intake or exhaust)
2. Fan pressure switch inoperative
3. Overtemperature sensor failure
DRAWINGS AND PARTS LIST
The drawings included in this manual are the most accurate source of part numbers for your Load Bank. When ordering replacement parts for Simplex Load Banks, always consult the Parts Drawing. When contacting the Simplex Service Department always have your work order and drawing number ready for reference. The Work Order Number and the Drawing Numbers are also lo­cated on each drawing legend.
drawing legend and parts list is illus­trated at right.
A typical
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 12 of 20
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 13 of 20
APPENDIX A - ABBREVIATIONS USED IN THIS MANUAL
Listed below are abbreviations of terms found on Simplex Load Bank Systems. When following a load bank drawing utilize this guide to define abbreviated system and component names. As this is a master list, drawings and text pertaining to your equipment may not contain all these terms.
®
AC-Alternating current
AIC-Ampere interrupting cur-
rent-maximum short circuit fault current a component can safely interrupt
AM-Ammeter
AMSW- Ammeter selector
switch-selects any phase for current reading
CF-Control fuse
CFM-Cubic feet per minute-
used to rate fan air flow capacity and load bank cooling require­ment
CFR-Cooling failure relay­normally energized relay in cooling failure subsystem
CPC-Control power contactor
CPF-Control power fuse
CT-Current transformer- used in
metering circuits
DC-Direct current
EXTS-Exhaust air temperature
switch
FCB-Fan circuit breaker-circuit breaker in series with fan control power
FCVR-Fan control voltage relay­normally energized relay on relay sub-panel
FM-Frequency meter-monitors frequency of test source
FMC-Fan motor contactor­controls power to fan motor
FMSW-Frequency meter switch
FPS-Fan power switch-used to
energize cooling system
GFB-Ground fault breaker
GBTR-Ground breaker tripped
relay
HVR-High voltage relay
Hz-Hertz-cycles per second,
measurement of frequency
IFCV-Incorrect fan/control voltage
INTS-Intake air temperature switch
K-Relay coil/contact designation
KVA-Kilovolt amperes
KVAR-Kilovolt amperes-reactive
KW-Kilowatts
KWM-Kilowatt meter
KWT-Kilowatt meter transducer
LM-Louver motor
LMC-Louver motor contactor
LR-Load resistive element
LX-Load reactive element
L1-Line 1
L2-Line 2
L3-Line 3
MCB-Main circuit breaker
MDS-Main Disconnect Switch
MF-Meter fuse
MLB-Main Load Bus
MOT-Motor
NEMA-National electrical
manufacturer’s association
ODP-Open, drip-proof-refers to motor enclosure
OVR-Overvoltage relay-relay used in overvoltage failure system, located on relay sub­panel
OLR-Overload relay-used for motor protection
OTR-Overtemperature relay­used in failure system
PF-Power factor-in resistive only loads expressed as unity (1.0), in inductive loads expressed as lagging, in capacitive loads expressed as leading
PAR-Control power available relay-relay energized when control power is available
PFM-Power factor meter
PS-Pressure switch-switch used
to detect fan failure
RR-Reset relay
RTM-Running time meter-keeps
time log of equipment use.
TB-Terminal block
TDR-Time delay relay-relay
which times out before contacts change state
TEFC-Totally enclosed, fan cooled-refers to motor enclosure
TEAO-Totally enclosed, air­over-refers to motor enclosure
UPS-Uninterruptable power source
V-Voltage
VSR-Voltage sensing relay
XCB-Reactive load controlling
circuit breaker
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
APPENDIX B ­CALCULATIONS & FORMULAS
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 14 of 20
EXAMPLES
Using line voltages and currents:
The following calculations are used to determine the actual kilowatt load being applied by the Load Bank, when line voltages and currents are known (at 1.0 power factor).
3 Phase
1. Read all three line currents and find the average reading.
2. Read all three line-to-line voltages and find the average reading.
3. Multiply the average current times the average voltage.
4. Multiply the answer of step #3 times the square root of 3 (1.732).
5. Divide the answer of step #4 by 1000. The answer is the actual kilowatts of load being applied by the Load Bank.
Single Phase
1. Determine the line current.
2. Determine the line-to-line voltage.
3. Multiply the line current times the line-to-line voltage.
4. Divide the answer of step #3 by 1000.
3 Phase
Current Readings Voltage Readings
A1 = 249A V A2 = 250A V A
= 254A V
3
A1 + A2 + A
Average Current =
3
= 481V
1-2
= 479V
2-3
= 483V
3-1
3
249+250+254
=
3
= 251A
V
+ V
Average Voltage =
1-2
+ V
2-3
3-1
3
481 + 479 + 483
=
3
= 481V
Volts x Amps x 1.732
Kilowatts =
1000
481 x 251 x 1.732
=
1000
5. The answer of step #4 is the actual kilowatts being applied by the load
= 209.1KW
bank.
Single Phase
Current Reading: 150A Voltage Reading: 240V
Volts x Amps
Kilowatts =
1000
150 x 240
=
1000
= 36.1KW
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
The following calculations are used to determine the amount of current when the desired amount of kilowatts is ap­plied at 1.0 power factor.
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 15 of 20
EXAMPLES
When desired amount of kilowatts is applied at 1.0 PF:
3 Phase
3 Phase
1. Multiply the desired amount of kilo­watts to be applied by 1000.
2. Multiply the operating voltage times the square root of 3 (1.732)
3. Divide the answer of step #1 by the answer of step #2.
4. The answer of step #3 is the average line current with the desired kilowatts applied at 1.0 power factor.
Single phase
1. Multiply the desired amount of kilo­watts to be applied by 1000.
2. Divide the answer of step #1 by the operating voltage.
3. The answer of step #2 is the average line current with the desired amount of kilowatts applied at 1.0 power fac­tor.
The following calculations are used to determine a step kilowatt rating at other than a rated voltage. This is accom­plished by referencing the load step to a KW value at a known voltage.
Applied: 50KW Operating Voltage: 480V
KW x 1000
Amperage =
Volts x 1.732
50 x 1000
=
480 x 1.732
50,000
=
831.36
= 60.1
Single Phase
Applied: 25KW Operating Voltage: 240V
KW x 1000
Amperage =
Volts
25 x 1000
=
240
25,000
=
240
= 104.2
1. Determine the new unrated operat­ing voltage.
2. Divide the new operating voltage by
Determining step KW at other than rated voltage:
Applied: 80KW Operating Voltage: 450V
Rated Voltage: 480V
the reference voltage.
3. Square the answer of step #2.
4. Multiply the answer of step #3 times the reference kilowatt value of the load step which the new kilowatt rat­ing is desired.
Step KW = (Oper. Volt. ÷ Rated Volt.)2 x Applied KW
= (450
÷ 480)
2
x 80
= .93752 x 80
= 70.3
5. The answer of step #4 is the kilowatt rating of the load step at the new voltage.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 16 of 20
FORMULAS
Alternating Current Direct Current
Kilowatts 1 phase Volts x Amps x PF* Volts x Amps
1000 1000
3 phase 1.732 x Volts x Amps x PF*
1000
*Power Factor, expressed as decimal.
(Resistive Load Bank PF is 1.0)
Amperes 1 phase KW x 1000 KW x 1000
®
(KW known)
Volts x PF Volts
3 phase KW x 1000
1.732 x Volts x PF
KVA 1 phase Volts x Amps
1000
3 phase 1.732 x Volts x Amps
1000
Amperes 1 phase KVA x 1000
(KVA known)
Volts
3 phase KVA x 1000
1.732 x Volts
KVAR 1 phase Volts x Amps x 1-PF
2
1000
3 phase 1.732 x Volts x Amps x 1-PF
2
1000
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
APPENDIX C - TORQUE VALUES
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 17 of 20
FAN BLADES
FAN TORQUE
PART NO. BOLT SIZE FT LBS // IN LBS
13820000 SET SCREW 11.7 // 140
13820500 SET SCREW 11.7 // 140
13821000 SET SCREW 8.3 // 100
13822000 1/4 — 20 7.5 // 90
13823000 1/4 — 20 7.5 // 90
13824000 1/4 — 20 7.5 // 90
13825100 1/4 — 20 7.5 // 90
13826000 1/4 — 20 7.5 // 90
13827500 5/16” 13 // 156
13827600 5/16” 13 // 156
13828000 3/8” 24 // 288
MOTORS, BRACKETS, BUS BAR CONNECTIONS
BOLT/NUT TORQUE
SIZE GRADE FT LBS // IN LBS
CONTACTORS
See torque values on the front of the contactor.
ELEMENTS/TRAYS
TERM/NUT TORQUE
SIZE INCH LBS
#6 Rod ends 4
#10 Element Conn. 20
1/4-20” High Voltage Contact Simplex
MAIN LOAD BLOCKS- ALL SIZES
WIRE TORQUE
CONNECTION SIZE FT LBS // IN LBS
LOAD SIDE 4-14AWG 2.9 // 35
LINE SIDE 500MCM-4/0 31 // 375
3/0-4/0 20 // 240
2/0-6AWG 10 // 120
8AWG 3.3 // 40
.250 (1/4-20) Grade 5, dry 8 // 96
.250 (1/4-20) Grade 2, dry 5.5 // 66
.312 (5/16) Grade 5, dry 17 // 204
.312 (5/16) Grade 2, dry 11 // 132
.375 (3/8) Grade 5, dry 30 // 360
.375 (3/8) Grade 2, dry 19 // 228
.437 (7/16) Grade 5, dry 50 // 600
.437 (7/16) Grade 2, dry 30 // 360
.500 (1/2) Grade 5, dry 75 // 900
STYLE SIZE INCH LBS
Cutler-Hammer 14-10 AWG 20
1-Phase
Merlin Gerin 14-1/0 50
3-Phase
CIRCUIT BREAKERS
WIRE TORQUE
8 AWG 25
6-4 AWG 27
3-1/0 AWG 45
.500 (1/2) Grade 2, dry 40 // 480
.562 (9/16) & up Grade 5, dry 110 // 1320
.562 (9/16) & up Grade 2, dry 55 // 660
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 18 of 20
APPENDIX C - TORQUE VALUES CONT’D
®
FUSEBLOCKS
MANUF. WIRE TORQUE
PART NO. SIZE INCH LBS
BM6031SQ, 10-18 AWG 20 BM6032SQ, BM6033SQ;
600V, 30A
T60060-2SR 10-18 AWG 20
600V, 60A
T60030-3CR, 10-14 AWG 35
600V, 30A
T60060-3CR,
600V, 60A
60100-3CR,
600V, 100A
8 AWG 40
4-6 AWG 45
2-3 AWG 50
MISCELLANEOUS-TERMINALS, METERS, SWITCHES, COILS, RELAYS, XFORMERS
CONNECTION TORQUE
SIZE INCH LBS
45
610
819
TAPER-LOCK BUSHINGS
BUSHING NUMBER TORQUE
1008, 1108 55 IN LBS
1210, 1215, 1310, 1610, 1615 15 FT LBS
2012 23 FT LBS
2517, 2525 36 FT LBS
3020, 3030 67 FT LBS
3535 83 FT LBS
4040 142 FT LBS
4545 204 FT LBS
5050 258 FT LBS
6050, 7060, 8065 652 FT LBS
10085, 12010 1142 FT LBS
CAM-LOK STUDS
THREADED MAXIMUM
STUD TORQUE
5/16” – 18 15 FT LBS
1/2” – 13 40 FT LBS
10 31
1/4-20” 66
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 19 of 20
APPENDIX D - PILLOW BLOCK BEARINGS LUBE INTERVAL
The Pillow Block Bearings (PN 22691040), which are used on Saturn Load Banks, are pre-lubricated at the time of manufacture. These bearings are lubricated with Mobil Mobilith AW2 grease (a Lithium based grease).
Lubrication using another grease may cause bearing failure.
®
If the lube interval is
less than a month use the Weekly Relube Quantity at each relube cycle.
If the lube interval is greater than a month and less than a year use the Monthly Relube Quantity.
If the lube interval is greater than a year use the Yearly Relube Quantity.
8 hrs./day 16 hrs./day 24 hrs./day
Minimum Lube Interval 6500 hrs. 116 wks. 58 wks. 38 wks.
Maximum Lube Interval 9100 hrs. 162 wks. 81 wks. 54 wks.
Weekly Relube Quantity 0.14 ozs.
Monthly Relube Quantity 0.21 ozs.
Yearly Relube Quatity 0.28 ozs.
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 20 of 20
APPENDIX E - DRAWINGS
Title Drawing
Pictorial ............................................ 47BD164460C
Control Section................................. 47B164461C
Fan/Control ...................................... 47B164462B
Local Manual Control ....................... 47B164463B
PLC Control...................................... 47B164464C
PLC Communications Control .......... 47B164465A
PLC Control Wiring .......................... 47B164466B
®
Metering ........................................... 47B164467A
Resistive Contactors Coil ................. 47B164468
Load Section 1 of 3 .......................... 47B164469
Load Section 2 of 3 .......................... 47B164470
Load Section 3 of 3 .......................... 47B164471
Load Strapping 1 of 4 ....................... 47B164472
Load Strapping 2 of 4 ....................... 47B164473
Load Strapping 3 of 4 ....................... 47B164474
Load Strapping 4 of 4 ....................... 47B164475
Load Tray Layout ............................. 47BD164476A
Non-Standard Elements ................... 47B164477A
Local Control Panel .......................... 47BD164478B
Remote Control Panel ...................... 47BD164479
Parts Legend 1 of 2 .......................... 47B164480A
Parts Legend 2 of 2 .......................... 47B164481B
Subpanel Layout 1 of 2 .................... 47BD164482C
Subpanel Layout 2 of 2 .................... 47BD164483B
Nameplates ...................................... 47BD164484B
Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
Loading...