For combined radiator-surface heatings the RTL-TH
DIGITAL Regulation Box is used for the room tempe-
rature-dependent regulation of the surface heating
while limiting the return flow temperature.
3. Technical Description
The regulation box consists of a wall insulation
box with a pre-mounted valve module, an electrothermal actuator, a protective cap, an air vent plug,
a flowmeter for measuring and regulating the volume flow and a wall cover.
The valve module is provided with a 3/4“ male
thread (Euro taper) for a connection via Simplex
compression adapter on the pipe side.
The valve is comfortable activated with the room temperature controller RTL-TH DIGITAL.
This programmable temperature controller allows
programming switching events (up to 9 per day) and
temperatures according to personal needs. Aer
installation the device automatically shows the time
of day and the room temperature.
In AUTO mode, the heater will be automatically activated according to programmed time and temperature. Program 1 is the default pre-set program (see 8.
room temperature controller).
Room temperature will be regulated based on the
Work on heating systems must only be done by qualified
professional personnel and in accordance with the
respective applicable regulations, guidelines and rules of
engineering.
Refer in particular to:
DIN EN 1264: Surface integrated heating and cooling
systems
DIN EN 12828: Heating systems in buildings
DIN 18 380: Heating systems and central hot water
heating systems
VDE 0100: Creating low voltage systems
VDI 2035: Scale formation in domestic water heating
systems and water heating systems
BGV: German Professional Association Regulations
(accident prevention regulations)
DIN = The German Institute for Standardisation
EN = European Standards
VDE = German Association for Electrical, Electronic &
Information Technologies
VDI = Association of German Engineers
Installation and Operating Instructions
RTL-TH DIGITAL
Regulation Box
EN
1. Features
room temperature. The return flow temperature
of the surface heating (measured by the remote
sensor) will be limited. The heater will be switched
on when the room temperature drops below the
current set-point.
In case of function „Min Return Temp“ (H3) it will be
heated if the return temperature drops below the set
min-value. This is even when the room temperature
is too high (permanent floor temperature).
In case of function „Max Return Temp“ (H3) heating
will be stopped if the return temperature exceeds
the set max-value. This is even when the room
temperature is too low.
Adjusting the maximum return temperature „Max Return Temp“ (H3) is absolutely necessary for reliable and troublefree operation because otherwise
there might be damage to the floor structure!
Caution:
The maximum permissible supply flow temperature of the surface heating must be respected.
4. Installation
1
zone 1zone 0
zone 2
RTL-TH DIGITAL Regulation Box
2
Note for arranging the regulating box in rooms
with showers or bathtubs:
The regulation box has to be arranged outside of
the zones 0, 1 and 2 in conformity with DIN VDE
0100-701 to prevent contact with splashing water.
Prepare the insulation box for the mounting by
inserting the fixing clips from the backside into
the drill holes at the corner points of the box and
securing them with the supplied screws so that
they cannot fall out.
The fixing clips are arranged crossed-over. The
clips can also be exchanged in any way depending
upon the construction site situation. The clips can
be moved horizontally in order to create a depth
compensation as long as the screws have not been
finally fixed.
The box is positioned to fixing clips on the rough
wall in a suiciently large wall recess (approx. 180 x
230 mm). Please pay attention to the mark of the
protective cap to the surface of the finished wall
in order to adjust the box optimally in the depth.
Aerwards fix the box with the adjusting screws.
2
1
3
Before the connection of the pipings, the notches
on the box are to be formed by breaking out the
walls at the corresponding positions.
2 of 12
Please pay attention to a tension-free installation
and the correct flow direction (supply flow le
- see arrow mark!) when connecting the piping
system. Reversely mounted connections cause
valve noises and a bad control behaviour.
Tension-free compression connection must also
be guaranteed when the system is in operation,
i.e. expansion loops or appropriate securing of
the pipeline must be provided.
Before starting the plaster and wall covering
works, the box is to be covered with a protective
cap. The remaining space between the box and
the wall notch can be filled with PU foam.
3
Aer finishing the wall covering works, the final
mounting is done by removing the protective cap
and putting on the wall cover.
4 Functional diagram
Radiator
Regulation
Box
Installation Room Temperature Controller
Caution: The room temperature controller must
only be opened and installed by a qualified electrician, according to the wiring diagram on the device
and in this installation instructions and in compliance with all applicable safety regulations.
To maintain compliance with Protection Class II,
user access to the rear of the device must be prevented.
This electronic device is an “independently mounted regulation”. It is used to control the temperature
only in dry and cloesed rooms, under normal environmental conditions. It conforms to EN 60730 and
works according to operating principle 1C.
The controller should be mounted at a location in
the room which:
■ can be easily accessed
■ is free of curtains, cabinets, shelves, etc.
■ allows free air circulation
■ is not exposed to direct sunlight
■ is not draughty (when doors or windows are
opened)
■ is not directly influenced by the source of heat
■ is not located on an outer wall
■ is approx. 1.5 m above the floor
5 Installation diagram
Room temperature controller
Mansonry
Wall insulation box
Wall cover
Plaster
Screed
Insulation
Base floor
6a
6b
Fitting in a conduit box Ø 60 mm
6a
Remove the display unit
Remove the frame
Mount it following the reverse procedure
Caution: Mounting in plastic wall boxes only.
To insert or remove a flexible wire press pin.
6b
3 of 12
The plastic tab must be in place to provide insulation between the terminals/wires and the mounting
screw.
6c
Eletcric Connection
Remove the splash guard for connecting terminal in
the box.
7a
Caution: Disconnect electric circuit from supply.
Connecting according to wiring diagram.
For solid and flexible wires 1 - 2.5 mm2.
The return temperature sensor (plug 3 and 4 on the
regulation box) can be connected by using a 2-lead
cable suitable for 230 V up to 50 m. Avoid laying
sensor cable alongside power cables, for example
inside a conduit.
The protective earth is pre-wired on the housing and
can be connected to the terminal box using the
prepared 2-pin terminal connector.
Caution: The sensor is at mains voltage.
6c
7a
Wiring Diagram
Caution:
Maximum length of removed
cable insulation 8 mm.
Plug 1+2:
Room temperature controller connection
Terminal block
Actuator
230 V ~ 50 Hz
PE
N
L
Plug 3+4:
Return temperature
sensor connection
2-pin connector for
connecting protective earth
4 of 12
Earthing connection
housing
Flowmeter
Return temperature sensor
5. Technical Data
Room Temperature Controller
TypeRTL-TH DIGITAL (type 527 8134)
Supply voltage230 V AC 50 HZ (195…253 V)
Room temperature setting range5 °C ... 30 °C; in 0.5 °C steps
Return temperature setting range10 °C ... 50 °C; in 0.5 °C steps
Temperature resolution0.1 °C steps
Output RelayNO contact
Switching current10 mA ... 10(4) A, 230 V~
Output signalPulse width modulation (PWM)
Minimum programmable time10 min.
Power consumption ~ 1.2 W
Accuracy of clock < 4 min. / year
Power reserve ~ 10 years
Ambient temperatureoperating 0 °C up to 40 °C (without condensation)
Storage -20 °C up to 70 °C (without condensation)
Voltage and current for the purposes of
interference measurements
230 V, 0.1 A
Degree of protectionIP 30
Protection class of housingII (see installation room temperature controller)
Cable length return temperature sensor4 - 50 m
Connection threadM 30 x 1.5
Rated voltage230 V ~
Maximum switch-on0.5 A
Continuous output2.5 - 3 W
Designnormally closed
Degree of protection /
IP42 / II
Protection class
Overtension protection /
present
Position indication
6. Ventilation
The system can be ventilated as necessary using the
ventilation valve installed.
7. Flowmeter
Flowmeter regulating valve for the regulating the volume flow. The upper part of the valve consists of a
valve cone with a rising spindle and a handwheel for
adjustment. The sight glass is installed in the hand
wheel where the flow can be read directly in L/min
on the printed scale depending upon the position of
indicator unit. The adjustment on the flowmeter can
be blocked by the delivered stop cap and sealed if
desired.
Volume Flow Regulation
Remove the lock cap. The control is performed by
turning the black handwheel whereby the valve
cone will be turned down when turning to the right.
The volume flow will decrease until reaching the
complete blocking. The opening of the valve is performed by turning it in the opposite direction.
Cleaning Flowmeter
The sight glass and measuring spring can be removed for maintenance and cleaned, even at full
system pressure. In order to do so, hold the black
5 of 12
hand wheel firmly and turn to the le to remove the
sight glass.
Do not use any tools when removing the sight
glass! Risk of breakage!
Unscrew the sight glass quickly and removed, together with the spring located inside. The flowmeter
locks automatically once the sight glass and spring
have been removed. In this condition, there may
be some slight water loss from the valve. Clean the
sight glass quickly and screw together again in the
opposite order.
8
Indicator unit
Sight glass with
scale
Spindle
8. Room Temperature Controller
8.1 Features
■ One line text display for simplified operation
■ Back light
■ Real time clock (setting of year, month, day, time)
■ Automatic Summer- Winter time change over
■ Max 9 events per day (each day independently)
■ Pre-set and adjustable programs
■ Optimum-Start
■
Arm chair programming (with display unit removed)
■ OFF-Function, key to be pressed for 10 sec.
■ Holiday-Mode (date from - until can be set)
■ Timer (Party) specific temperature for configurable
duration
■ Energy consumption display (heating on time *
cost) for last 2 days, -week, -month, -year
■ Energy cost per hour configurable
■ Frost protection
■ Range limits for adjusting max and min temp.
■ Access protection
■ Operating language can be selected
■ Valve protection
■ Adaptation to valves normally open or normally
closed
8.2 Operation Instructions
The most important functions at a glace
Pre-set programs
There are 3 pre-set time/temperature programs in
the controller. Pre-set program 1 is the default (see
next page). Therefore, if pre-set program 1 is the
best program to suit the application, there will be no
need to change the time/temperature settings on
the device.
9
Keys1234
–+OK
Valve body
Valve cone
Impact pane
Valve bottom part
Actual day
Actual room
temperature
Calling for heat
(blinks if
detached from
power module
or there is no
mains power)
Helping text
Mode = AUTO
Time = 14:31
6 of 12
Setting a
constant room
temperature
without the timer
programming -
function
“manual“
Press key 1 to access the menu. Press key 3 (+) twice until the menu option MAN appears.
Select this mode by pressing key 4 (OK). Selecting this option will automatically take you from
the menu and return you to the normal display mode. MAN will be displayed at bottom le of
the display.
The desired room temperature can be set using keys 2 (-) and 3 (+).
This will apply until altered; timer programs are deactivated.
Activating timer
programming -
function
“automatic“
Changing the
currently
selected room
temperature
Selecting pre-set
setting times
(programs)
Programming
your own setting
times
Press key 1 to return to the menu. Press key 3 (+) once until the menu option AUTO appears.
Select thus mode by pressing key 4 (OK).
Selecting this option will automatically take you
from the menu and return you to the normal display mode. AUTO will be displayed at bottom
le of the display.
If no other selection has been made, pre-set timer program 1 will be active.
Set the desired room temperature from the normal display by pressing keys 2 (-) or 3 (+) and
confirm with key 4 (OK).
During the change the desired temperature will flash, then the display will change back to the
standard setting (either desired or current temperature, as required – see Complete Instructions
G10).
If the MAN function is active, the change will be permanently set as the new desired
temperature. If the AUTO feature is active, the change will be valid until the next programmed
timer switch time. When this time is reached, the programmed temperature will be set
as the new desired temperature. The program will then continue to run as normal.
Press key 1 to return to the menu. Press key 3 (+) six times until the menu option USER
SETTINGS appears.
Press key 4 (OK) to select this sub-menu. This will bring up menu option 6.1 SELECT PROGRAM.
Press key 4 to select the menu. Select the desired program (1 to 3) with keys 2 (-) or 3 (+) and
confirm with key 4 (OK).
Leave the menu by pressing key 1 () twice.
See room thermostat complete Instructions 8.4
8.3 Short Instructions Installer Settings
Setting the
return temperature in the floor
circuit
Press key 1 to access the menu. Press key 3 (+) seven times until the menu option
INSTALLER SETTINGS appears.
Press key 4 (OK) to select this sub-menu.
The menu option H1 APPLICATION will appear. Press key 3 two more times to reach
menu option H3 RETURN TEMP LIMITS MIN/MAX. Press key 4 (OK) to select this menu.
You will first see the lower temperature limit flashing. The standard setting here is OFF. If
desired, you can press keys 2 (-) and 3 (+) to set the lower temperature limit, i.e. the lowest
return water temperature, within the range 10°C to 35°C. The recommended setting is
OFF.
Confirm the value displayed by pressing key 4 (OK). You will automatically go back to the
display used for setting the upper return temperature limit. This can be altered within the
range 10 °C to 50 °C.
Note: due to the latency of the valve actuator, a higher water temperature may briefly be
achieved! To avoid unnecessary temperature spikes in the floor temperature, select the
minimum temperature for optimal living comfort. The standard setting is 35 °C.
Confirm again using key 4 (OK) and leave the menu by pressing key 1 () twice.
7 of 12
8.4 Detailed Instructions
Pre-set Programs
There are 3 pre-set time/temperature programs in
the controller. Pre-set program 1 (as shown below)
is the default. Therefore, if pre-set program 1 is the
Program 1
Monday to Friday
Events 1 2 3 4 5 6
Time 06:00 08:30 12:00 14:00 17:00 22:00
Temperature °C 21.0 18.0 21.0 18.0 21.0 15.0
Saturday and Sunday
Events 1 2 3 4 5 6
Time 07:00 10:00 12:00 14:00 17:00
Temperature °C 21.0 18.0 21.0 21.0 21.0 15.0
23:00/22:00*
Program 2
Monday to Friday
Events 1 2 3 4 5 6
Time 06:00 08:30 12:00 14:00 17:00 22:00
Temperature °C 21.0 18.0 21.0 18.0 21.0 15.0
Saturday and Sunday
Events 1 2
Time 07:00 23:00/22:00*
Temperature °C 21.0 15.0
best program to suit the application, there will be
no need to change the time/temperature settings
on the device. To select another program see G1
(Program select).
Mo – Fr
Sa – So
6:00 h8:00 h10:00 h 12:00 h 14:00 h16:00 h18:00 h20:00 h22:00 h
*23:00/22:00 = 23:00 for Saturday
Mo – Fr
Sa – So
6:00 h8:00 h10:00 h 12:00 h 14:00 h16:00 h18:00 h20:00 h22:00 h
*23:00/22:00 = 23:00 for Saturday
Program 3
Monday to Friday
Events 1 2 3 4
Time 06:00 08:30 17:00 22:00
Temperature °C 21.0 18.0 21.0 15.0
Saturday and Sunday
Events 1 2 3 4
Time 07:00 10:00 12:00 23:00/22:00*
Temperature °C 21.0 18.0 21.0 15.0
6:00 h8:00 h10:00 h 12:00 h 14:00 h16:00 h18:00 h20:00 h22:00 h
Mo – Fr
Sa – So
*23:00/22:00 = 23:00 for Saturday
Notes for Programming
■ Entering a code: change value with + – key then
press OK
■ Activated settings terminate automatically 3 min.
aer the last key press, without saving. They return
to the mode which was active before entering the
settings, e.g. AUTO, MAN, HOLIDAY, TIMER, AT HOME
■ When going through user or installer settings the
item number used in the manual will be display ed, e.g. G1 „Program select“
■ There may be gaps in the sequence of menu
numbers.
Troubleshooting
1. It is getting warm too late: a. Are clock and program events set correctly?
b. Is the „Optimum Start“ feature switched on? (see H7)
Did the controller had enough time (serveral days) to
adapt to the room’s characteristics?
c. Is an automatic change between Summer and Winter time
activated? (see G5)
2. The controller does not accept any changes:Is access protection switched on? (see G6)
3. The range of temperature setting is limited:Are temperature limits set (see G7)
4. Temperature display doesn‘t change:Is display of set-temperature activated ? (see G10)
5. The room heats up too slow:The return temperature may be limited from the controller‘s
max-limiter (see H3).
6. The room becomes too warm:The return temperature may be limited from the controller‘s
Min-limiter. (see H3)
8 of 12
Description of Functions and Operation
How the room temperatur controller can be used.
Change temperature until next switching event> see keys + – in AUTO
Controlling the temperature according to pre-set profiles> see main menu, AUTO
Set a constant temperature (manual operation)
Set temperature for a number of hours > see main menu, TIMER
Set temperature for a specific date > see main menu, HOLIDAY
Use a separate program for special days > see main menu, AT HOME
Adjust the controller to personal needs> see main menu, USER SETTINGS
Adjust the controller to application needs > see main menu, INSTALLER SETTINGS
Keys
+ – in AUTO (-)Set temperature temporarily until next switching event. Indicated by „-“
behind AUTO-. First key-press shows set value, following ones change it.
+ – in menuScroll through the menu
OKAccepts modification / selection
InfoShow related details in AUTO, MAN, TIMER, HOLIDAY, AT-HOME.
To cancel press key again.
MenuEnter menus. + – key to move
for 10 sec.
Go one step back
Switch o connected load. Display shows OFF. Details see G4
> see main menu, MAN
to confirm / activate
OK
Main Menu
A MENUUse + – keys in order to navigate through the menu
B AUTOThe temperature will be controlled automatically according to the time
and temperature of the selected program, see G1. Use + – keys to
change temperature until next switching event.
C MANThe temperature will be controlled continuously according to the tem-
perature set in this menu. Use + – key to change temperature.
D TIMERThe temperature will be controlled temporarily according to the hours
and temperature set in this menu. On terminating TIMER mode, the previously active mode will be re-activated. HOLIDAY terminates TIMER.
E HOLIDAYThe temperature will be controlled between the dates and the tempe-
rature set in this menu. HOLIDAY starts at 0 h of the first day, it ends at
24 h of the last day. In the period of time before HOLIDAY starts, AUTO
will be active. While waiting for holiday start date, other mode can be
selected (AUTO, MAN, TIMER, HOME). INFO provides details of the
pending holiday. In this situation holiday period will start automatically
when the DATE FROM occurs. When holiday ends it returns to the mode
which was in place before activating HOLIDAY.
F AT HOMEThe temperature will be controlled automatically according to the time
and temperature of the program configured here (independent from
AUTO). The program is the same for all days. Monday‘s program is used
as the pre-set. It needs to be terminated by user, e.g, by selecting AUTO.
Usage: for holiday at home, illness etc.
G USER SETTINGSCustomise the controller according to personal requirementsOK
H INSTALLATER
SETTINGS
Customise the controller according to application requirements
(from installer only)
to confirm / activate
OK
OK
OK
OK
OK
OK
9 of 12
Customise the Controller according to Personal Requirements
G
USER SETTINGSCustomise the controller according to personal requirementsdefault settings
( ) = value range
1
Program selectSelect one of the pre-defined programs, see 8.4
(If another program is chosen, settings will not be saved)
2
Event Setting
3
Clock SettingsSet Date and Time
4
O Heating
Permanent
5
Summer/Winter
time change over
6
Key LockProtect controller against unauthorised use. Re-activate via code = 93NO
7
Room
temperature
limits
min/max
8
Cost/Hr for
Energy
9
Energy
consumption
to date
10
Set temperature
to read
11
Adjust
Temperature
13
BacklightContinuously OFF or temporarily illuminates aer key pressSHORT
14
LanguageSelect preferred operating language
15
InfoDisplays controller-type and -version.
16
Reset user
settings only
Modify Time and Temperature of active program, see 8.4.
Each event can be reduced to the previous one or to 00:00 h.
Each event can be extended up to 23:50 h, then ->>> is indicating that
the event is in the next day. By pressing + or – key at ->>> a time can
be adjusted. Max 9 events are possible.
The first digit indicates the actual event e.g. 3. 12:00-14:00 shows event 3.
Events can be set for day-blocks as well, when selecting days (Mon...Fri,
Sat/Sun, Mon...Sun).
In order to finish programming, press repeatedly.
Switch o the heater, the controller remains on power. Display reading
OFF. Frost protection may happen if selected, see H6.
Switching ON again by activating e.g. AUTO or by pressing key for 10
sec. When re-activating via key or this menu, AUTO will be activated.
Select if automatic Summer/Winter-Time changeoverYES
Limits the temperature which can be set by the user. If both values are
the same, no adjustment is possible. This aects AUTO, MAN, HOL, TIMER, AT-HOME, EVENT SETTING (G2). The active program / mode
will not be aected automatically.
The assumed energy cost per hour (in cent/h) can be set. To use this
mode as hour meter set costs/h at 100.
Shows the approximate energy cost of the controlled area. For the last:
2 days, week (7 days), month (30 days), year (365 days). On the actual
day, calculation is up to current time. In case of overflow 9999 will be
displayed. This feature mainly can be used for electric heating.
Calculation: On-Time of heater x cost per hour see above. Reset see H9
Show set temperature instead of room temperatureNO
Adjust temperature to personal needs0.0
Only USER SETTINGS will be set to factory settings. The energy
counter will not be re-set; to do this see H9.
(P1 ... P3)
as selected
(-5.0 ... +5.0)
(SHORT, OFF)
P1
at G1
NO
5; 30 °C
100
(1 ... 999)
NO
10 of 12
Change Installer Settings
Caution! These settings should only be set-up by a qualified person. They can influence safety and the
proper functioning of the system.
H
INSTALLATER
SETTINGS
0
CodeEnter Code (= 7) in order to access the menus. It is valid for 1 hour.
1
ApplicationRoom temperature controller with limiting the return temperature for
3
Return temp
limits min/max
5
Valve protectionThe output will be activated for the specified time each day at 10:00 h
6
Frost protectionSet frost protection temperature. Only if controller is switched OFF,
7
Optimum startThe set temperature will be reached at the time specified in the pro-
8
Valves NOIf valves normally open have to be usedNO
9
Energy counter
reset
10
Display of return
temperature
11
Reset allAll INSTALLER and USER SETTINGS will be set to its Factory settingNO
Customise the controller according application needs
(by installer only)
Simplex Regulation Boxes
Limits the return temperature. Selectable is:
Minimum return temperature (lower limit):
The valve is opened when the selected water temperature falls
below and closes automatically when it reaches the programmed
temperature limit (constant floor tempering). OFF = no limit
Maximum return temperature (upper limit):
The valve is closed when the selected return temperature is reached and opens automatically when it falls below the programmed temperature limit.
e.g. Min. temp. = 21 °C, the heating water does not sink below 21 °C
even if the room is too warm.
Max. temp. = 35 °C, the heating water does not rise above 35 °C,
even if the room is too cold.
If the lower limit is not needed it should be set to OFF.
in the morning
the temperature will be controlled to that value, see G4
gram. During pre-heating time, AUTO_ will be displayed.
The energy counter will be set to 0NO
The temperature measured from remote sensor will be displayed (for
service purpose)
default settings
( ) = value range
regulation box
surface heating
refer to 1
OFF
(OFF, 10...Tmax)
35 °C
(Tmin...50)
3 min
(OFF, 1 ... 10)
5 °C
(OFF, 5 ... 30)
YES
Temperature
Error Indication
In case of errors, «Err» is blinking. The following errors can be displayed:
CONFIGURATION Display- and powermodule do not fit
use only suitable parts
switch o and on power supply
COMMUNIKATIONCommunication between display- and power unit fails
unplug and re-plug display unit
switch o and on power supply
EXT SENSOR 1. Error of remote sensor
Let a professional electrician check the wiring (terminal block of regulation box).
replace sensor
2. Over- or under run of valid display range
On all these errors, heating will be activated with 30 % of time.
11 of 12
Dimensional Drawing
wall box
wall box
ABCDEFGHIK
G 3/4 a502111972715613864210270
Pressure Loss Diagram
completely open; kvs value [m
3
/h]: 1.48
Table of Resistance for Remote Temperature
Sensor
Temperature Resistance Temperature Resistance
10 °C66.8 kΩ30 °C 26.3 kΩ
pressure loss ∆p [kPa]
pressure loss ∆p [mbar]
20 °C 41.3 kΩ 40 °C 17.0 kΩ
25 °C 33 kΩ 50 °C 11.3 kΩ
Batteries
the product life, by professional personnel only.
(Data in mm)
In compliance with the EU Directive
2006/66/EC, the button cell battery
located on the printed circuit board inside
this product, can be removed at the end of
flow rate [l/h]
02/2019
The illustrations are symbolic and may dier from the respective product. Errors and technical changes reserved.