Simplex MINIPLEX 4100ES User guide

4100ES Fire Control Panels
UL, ULC, CSFM Listed; Addressable Fire Detection and Control FM Approved * MINIPLEX Transponders
Features
4100ES Series MINIPLEX transponders allow remotely located initiating and notification functions:
Transponder operation is available as standard or with
local mode operation
Communications with the host fire alarm control panel
Initiating functions include:
Addressable device support including TrueAlarm
analog sensor compatibility
Conventional initiating device circuit (IDC) support
Notification functions include:
Addressable strobe and horn notification using
enhanced power delivery IDNAC SLCs
Emergency voice/alarm communications Conventional DC notification appliance circuits (NACs)
Local mode operation provides:
Default local initiating and notification operation in the
event of a communications loss with the host control panel
Enabling of an optional Local Mode Controller with a
local alarm sounder, LED status indicators, and keyswitch enabled control switches
Support for IDNet addressable devices, addressable and
conventional notification appliances, and default output tones from local amplifiers
Optional modules include:
Digital or Analog audio riser modules for connection to
system audio signals
Digital or analog input audio amplifiers with integral
on-board NACs
Power supplies with or without battery chargers City Connect modules and RS-232 ports for printers or
maintenance terminals
Alarm relays, auxiliary relays, additional IDC modules,
and NAC expansion modules
Cabinets are equipped with solid doors (beige or red) and in one, two, or three bay sizes
Listed to:
UL Std. 864, Fire Detection and Control (UOJZ), and
Smoke Control Service (UUKL)
UL Std. 2017, Process Management Equipment (QVAX) UL Std. 1076, Proprietary Alarm Units-Burglar (APOU) UL Std. 1730, Smoke Detector Monitor (UULH) ULC Std. S527-99
* See pages 4 and 5 for product that is listed as UL or ULC. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
MINIPLEX
transponder
IDNet addressable
devices
ALARMFIRE
PULL DOWN
Audio NAC
Emergency Operating Instructions
ALARMS
SYSTEM WARNINGS
Alarm Silenced
Fire AlarmPri ority 2 Ala rm
Supervisory Trouble
Fire Alarm
Priority 2
Supv
Trouble
Alarm
Ack
Ack
Ack
Ack
Silence
Event
More
Time
Info
Previous
Menu
On
Next
Enable
Arm
Off
Lamp
Disable
Auto
Disarm
Test
Alarm or Warning Condition
System indicator flashing. Tone On. Press Alarm Silence.
How to Acknowledge / View Events
Press ACK located under flashing indicator. Repeat operation until all events are acknowledged. Local tone will silence.
Addressable strobes
DISCONNECT A.C. POWER
N
AND
C
BATTERY
O
BEFORE
A
SERVICING
I
U
T
T
U
I
SERVICING
A
BEFORE
O
BATTERY AND
C
A.C. POWER
N
DISCONNECT
Fire Alarm Local Mode Controller
CONTROL ENABLE
A B C
D E F G H I
ZONE1SIG2AUX
3
J K LM N OP Q R
FB4IO5IDNet
6
AC Power
S T U V W X Y Z /
P7A8L
9
'SP' ( ) , 0 :
System
NET ADDR
Reset
DEL
0
Enter C/Exit
How to Silence Building Signals
How to Reset System
Press System Reset. Press Ack to silence tone device.
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
on IDNAC SLC
Alarm
Local Mode
Alarm
Local mode
Control
Silenced
Local Mode Active
Alarm
Reset
Silence
Power On
controller
4100ES Fire Alarm Control Panel
with Voice Control
Typical 4100ES MINIPLEX System One-Line Drawing
Introduction
4100ES MINIPLEX transponders connect to a host
4100ES Fire Alarm Control Panel using Simplex® remote unit interface (RUI) communications. At the transponder, RUI communications are received by the transponder interface module and translated into the same internal communications format that is used in the host control panel.
Remotely located modules. With RUI communications, the transponder can remotely provide the same initiating and notification functions that occur at the host control panel without requiring multiple long distance wiring runs. Connections to the host panel are low current communications and audio wiring with distances up to 2500 ft (762 m).
Additional Reference. Refer to document S4100-0100 and the other documents listed on page 3 for additional information concerning the extensive initiating and notification features of the 4100ES fire alarm control panels.
S4100-0103 5/2013
Module Bay Description
Transponder model 4100-9600 includes a bay
assembly, a power distribution interface module (PDI), a Basic Transponder Interface Module, and an interconnect harness. Communications with the host fire alarm control panel are via a Remote Unit Interface (RUI) connection that allows for up to 2500 ft (762 m) distance. RUI can communicate with up to a total of 31 remote devices and can be either Style 4 or Style 7 communications.
Transponder model 4100-9601 substitutes a Local Mode Transponder Module for the Basic Transponder Module.
Optional Expansion Bays each include a PDI and accept a variety of optional modules (refer to list starting on page 4).
The Battery Compartment (bottom) accepts two batteries, up to 50 Ah, that can be mounted within the cabinet. Battery mounting does not interfere with available module space. A power supply with battery charger is required for each battery set.
Packaging Availability
Modules are power-limited (except as noted, such as
relay modules)
Enclosure are available for one, two, or three bay sizes
or for cabinet rack mounting
Boxes and solid doors are available in beige or red
(ordered separately)
Up to eight close-nippled cabinets can be connected at
one transponder location (close-nippled is mounted within 20 ft (6 m) and with interconnecting wiring enclosed in conduit)
Refer to document S4100-0037 for enclosure details
Local Mode Control Operation
Default Stand-Alone Operation. In the event of a
communications loss with the host fire alarm control panel, model 4100-9601 MINIPLEX Local Mode Transponders provide fire alarm response default operation for its connected devices and appliances per the following.
Input Operation. During local mode operation, TrueAlarm initiating devices connected to the transponder will cause an alarm at their least sensitive alarm threshold.
Local Mode Control Operation (Continued)
Notification Operation. Fire alarm conditions reported
against a fire alarm point type within a transponder in local mode will cause all notification appliance circuits in that transponder to:
Sound a general alarm temporal pattern horn tone Activate visible notification appliance circuits
Local Mode Module Support. Local mode operation provides support for the following 4100ES modules:
Enhanced Power Supplies (EPS+/EPS) including
on-board IDNAC SLCs
IDNet 1+ addressable device circuits, including those
on-board the EPS+, IDNet 1+ expansion modules, and the Quad IDNet Isolator Module
Expansion Power Supplies (XPS) including on-board
NACs and expansion signal modules, operated at a temporal pattern
4100ES amplifiers will provide their on-board horn tones
(500 Hz) at a temporal pattern through their on-board amplifier NACs
Firefighter Telephone control modules in local mode Local Mode Operation Module Exclusion. Modules
not listed above but that are listed as compatible with MINIPLEX transponders per this document, do not interfere with local mode operation but are not supported during local mode operation.
Local Mode Controller
Operation. During local mode operation, an optional
Local Mode Controller will indicate status (see illustration below) and can be enabled using a keyswitch to perform local alarm silence or reset. If alarms occurring during local mode are reset using a Local Mode Controller, upon restoration of communications, those alarms will not be sent to the master controller. If alarms are still present upon restoration of communications, then the alarm condition will be reported and host fire alarm control panel programmed alarm functions will occur. When communications are re-established, the local mode transponder restores automatically.
Mounting. Local Mode Controllers are mounted on three-gang plates, are available in beige or red, and for either flush or semi-flush mounting. (See page 7 for details).
Photoelectric sensors will alarm at 3.7%/ft smoke
obscuration
Ionization sensors will alarm at 1.3%/ft obscuration
Heat sensors will alarm at a fixed temperature of 135° F
(57° C)
TrueAlarm device LEDs will be activated to indicate a
device in alarm
Fire Alarm Local Mode Controller
Local Mode
CONTROL
ENABLE
Control
Alarm
Reset
Silence
See Operating Instruction 579-343
Alarm
Alarm
Silenced
Local Mode Active
Power
On
Local Mode Controller Module
2 S4100-0103 5/2013
Typical Multi-Floor MINIPLEX Audio System
ALARMFIRE
PULL DOWN
Seventh floor
Legend:
Sixth floor
Fifth floor
Fourth floor
Third floor
PULL DOWN
PULL DOWN
PULL DOWN
PULL DOWN
PULL DOWN
ALARMFIRE
DISCONNECT A.C. POWER
N
C
AND BATTERY
O
BEFORE
A
SERVICING
I
U
T
T
U
I
SERVICING
A
BEFORE
O
BATTERY
AND
C
N
A.C. POWER DISCONNECT
MINIPLEX transponder
Addressable strobes on IDNAC SLC
Speaker NAC
ALARMFIRE
TrueAlarm sensors and IDNet/MAPNET II
ALARMFIRE
PULL DOWN
addressable circuits
Audio riser wiring,
ALARMFIRE
twisted pair
RUI communications wiring, twisted, shielded pair
ALARMFIRE
ALARMFIRE
DISCONNECT A.C. POWER
N
C
AND BATTERY
O
BEFORE
A
SERVICING
I
U
T
T
U
I
SERVICING
A
BEFORE
O
BATTERY
AND
C
A.C. POWER
N
DISCONNECT
MINIPLEX transponder
Emergency Operati ng In struct ion s
A B C
D E F G H I
ZONE1SIG2AUX
3
J K LM N O P Q R
FB4IO5IDNet
6
AC Power
ALARMS
SYSTEM WARNINGS
S T U V W X Y Z /
Alarm Silenced
Fire Alarm Pri orit y 2 Alarm
Supervisory Trouble
P7A8L
9
'SP' ( ) , 0 :
Fire Ala rm
Priority 2
Supv
Trouble
Alarm
System
NET ADDR
Ack
Ack
Ack
Ack
Silence
Reset
DEL
0
Enter C/Exit
More
Event
Previous
Info
Time
Menu
On
Next
Enable
Arm
Off
Lamp
Disable
Auto
Disarm
Test
Alarm or Warning Condition
How to Silence Building Signals
System indicator flashing. Tone On. Press Alarm Silence.
How to Reset System
How to Acknowledge / View Events
Press ACK located under flashing indicator.
Press System Reset.
Repeat operation until all events are ac know ledged.
Press Ack to silence tone device.
Local tone will silence.
Second floor
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
4100ES Fire Alarm Control Panel
with Voice Control
First floor
Additional 4100ES Data Sheet Reference
Subject Data Sheet Subject Data Sheet
MINIPLEX Transponders for conventional (non-addressable) notification applications
S4100-0035
Enclosures S4100-0037 Remote Annunciators S4100-0038 LED/Switch Modules S4100-0032 Remote Battery Charger S4081-0002 4100ES Audio/Phone Modules S4100-0034 Addressable Device Compatibility S4090-0011 IDNet+ Module with Quad Isolator S4100-0046
3 S4100-0103 5/2013
Basic Panel Modules and Accessories S4100-0100 Network Display Unit (NDU) S4100-0102
MINIPLEX Transponder Product Selection
Transponder Type
Model Description Supv. Alarm
4100-9600
4100-9601
Basic Transponder, includes bay equipment with power distribution interface, and 4100-0620 Basic Transponder Interface Module mounted in Block A
Local Mode Transponder, includes bay equipment with power distribution interface, and 4100-0625 Local Mode Transponder Interface Module mounted in Block A
in local mode 112 mA 112 mA
87 mA 87 mA
normal 87 mA 87 mA
Local Mode Controller Selection
Model Description Supv. Alarm
4601-9108 Flush mount 4601-9109 Surface mount 4601-9110 Flush mount 4601-9111 Surface mount
Red with white lettering
Beige with black lettering
Local Mode Controller, 3-gang plate mounted; flush mount requires a 1 ½” (38 mm) deep 3-gang box; surface mount controllers include a matching mounting box; see p. 7 for details
normal 12 mA 12 mA
in local mode 20 mA 60 mA
Communication Modules
Model Description Size Supv. Alarm
4100-6031
4100-6032 City Circuit, without disconnect switches N.A. 20 mA 36 mA
4100-6033 Alarm Relay, 3 Form C relays, 2 A @ 32 VDC N.A. 15 mA 37 mA
4100-6038 Dual RS-232 Interface 1 Slot 132 mA 132 mA
4100-6045 Decoder Module 3 Slots 85 mA 163 mA
4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA
4100-9816 Master Clock Interface Module with one standard RS-232 port (see S4100-0033) 1 Slot 132 mA 132 mA
Select one per EPS+ or EPS
City Circuit, with disconnect switches
N.A. 20 mA 36 mA
Enhanced and Expansion Power Supplies and Accessories (see specification details on page 6)
Model Voltage/Listing Description Size Supv. Alarm
UL &
4100-5311 120 VAC
4100-5313 220-240 VAC UL
4100-5325 120 VAC
4100-5327 220-240 VAC UL
Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to two Class A or two Class B SLC outputs; provides short circuit isolation between each Class A
4100-6103
Model Voltage/Listing Description Size Supv. Alarm
4100-5101 120 VAC UL
4100-5103 120 VAC, Canadian ULC
4100-5102 220-240 VAC UL
4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA
4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum 4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet
or B output circuit; connect up to two DCAI modules per IDNAC SLC input up to a maximum of 6 DCAI modules per EPS; each isolated output SLC used requires one IDNAC address; the total current remains controlled by the Class B input source SLC at 3 A maximum
Enhanced Power Supply (EPS+); 9 A Enhanced Power
ULC
Supply/battery charger with 250 point IDNet 1+ interface, 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and auxiliary relay; 120 VAC model has selectable low battery cutout
UL &
Enhanced Power Supply (EPS); 9 A Enhanced Power
ULC
Supply/battery charger with 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and auxiliary relay; 120 VAC model has selectable low battery cutout
Expansion Power Supply (XPS); 9 A output, 3 built-in Class A/B NACs, rated 3 A for Special Application appliances (2 A for Regulated DC); NACs can be selected as auxiliary power outputs, derated to 2 A for continuous duty, total per XPS is 5 A; 4100-5103 has low battery cutout
4 Blocks
Right
Side
4 Blocks
Right
Side
1 Block 6.5 mA 6.5 mA
2 Blocks 50 mA 50 mA
217 mA 480 mA
with 200 IDNet
devices and 20
device LEDs in alarm
125 mA 220 mA
Miscellaneous Options and Accessories
Model Description
4100-1290
4100-0632 Terminal Block Utility Module with 2, 16 position terminal blocks on 4” x 5” single block, for of up to 12 AWG wire (3.31 mm2)
4100-0633 Door Tamper Switch, connects into Transponder Interface Module, one per cabinet assembly if required
4100-0634 120 VAC 4100-0635 220/230/240 VAC
4100-9837 Green LED Power-on Indicator Kit, required for ULC listing of MINIPLEX transponder; mounts on solid door knockout
2081-9031
* Standard power supply NACs can provide synchronized strobe or SmartSync, two-wire operation. Continued on next page
24 Point I/O Module for external connections, select each point as either a switch input (momentary or maintained) or an output (for lamp/LED/relay); requires 1 Slot (refer to data sheet S4100-0032 for additional information)
Power Distribution Module (PDM) select per system voltage; one required per box
Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 , 1 W, encapsulated, two 18 AWG leads (0.82 mm2), 2 ½” L x 1 ” W x 1” H (64 mm x 35 mm x 25 mm)
4 S4100-0103 5/2013
MINIPLEX Transponder Product Selection (Continued)
Audio Riser Modules
Model Description Size Supv. Alarm
4100-0621
4100-0622
Dual Channel Analog Audio Riser Module; accepts one or two separate audio signals from host control panel; mounts in Block B, is controlled by Transponder Interface Module
3-8 Channel Digital Audio Riser Module; similar to analog module, except receives and decodes a digital input signal with up to eight audio channels; with Non-Alarm Audio input
1 Block 0 mA 15 mA
1 Block 70 mA 70 mA
Analog Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible*
Model Description Details
4100-1361 25 VRMS output
4100-1362 70.07 VRMS output NAC rating = 0.5 A
4100-1312 25 VRMS output
4100-1313 70.7 VRMS output NAC rating = 0.707 A
Flex-35, 35 W Amplifier, constant supervision compatible
Flex-50, 50 W Amplifier, constant supervision compatible
Includes three on-board Class B audio NACs; power is supplied from an EPS+, EPS, or XPS
NAC rating = 1.4 A
NAC rating = 2 A
35 W, or 100 speakers
50 W, or 100 speakers
100 W Analog Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage 25 VRMS 70.7 VRMS
4100-1314 4100-1315 120 VAC, 60 Hz UL
4100-1316 4100-1317 120 VAC, 60 Hz ULC
4100-1318 4100-1319 220/230/240 VAC, 50/60 Hz UL
4100-1320
4100-1322
4100-1324
4100-1321
4100-1323
4100-1325
Power Supply Input/Listing Description Details
Includes six, Class B audio NACs; NAC rating = 50 W or 100 speakers maximum; 2 A @ 25 VRMS;
1.4 A @ 70.7 VRMS
Uses the six Class B NACs of primary amplifier
120 VAC, 60 Hz UL
120 VAC, 60 Hz ULC
220/230/240 VAC, 50/60 Hz UL
Primary
100 W
Amplifier
Backup
100 W
Amplifier
ULC models have low battery dropout circuit
Digital Emergency Voice/Alarm Communications Equipment*
Model Description Details
4100-1363 25 VRMS output
4100-1364 70.07 VRMS output NAC rating = 0.5 A
4100-1326 25 VRMS output
4100-1327 70.7 VRMS output NAC rating = 0.707 A
Flex-35, 35 W Amplifier, constant supervision compatible
Flex-50, 50 W Amplifier, constant supervision compatible
Includes three on-board Class B audio NACs; power is supplied from an EPS+, EPS, or XPS
NAC rating = 1.4 A
NAC rating = 2 A
35 W, or 100 speakers
50 W, or 100 speakers
100 W Digital Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage 25 VRMS 70.7 VRMS
4100-1328 4100-1329 120 VAC, 60 Hz UL
4100-1330 4100-1331 120 VAC, 60 Hz ULC
4100-1332 4100-1333 220/230/240 VAC, 50/60 Hz UL
4100-1334 4100-1335 120 VAC, 60 Hz UL
4100-1336 4100-1337 120 VAC, 60 Hz ULC
4100-1338 4100-1339 220/230/240 VAC, 50/60 Hz UL
Power Supply Input/Listing Description Details
Primary
100 W
Amplifier
Backup
100 W
Amplifier
Includes six, Class B audio NACs; NAC rating = 50 W or 100 speakers maximum; 2 A @ 25 VRMS;
1.4 A @ 70.7 VRMS
Uses the six Class B NACs of primary amplifier
ULC models have low battery dropout circuit
Options for use with either Analog or Digital Amplifiers
Model Description Details and Mounting Reference
4100-1245
4100-1246
4100-1248
4100-1249
4100-1259
4100-1260
Flex-35/50 Expansion NAC Module; adds three Class B audio NACs
Flex-35/50 Class A Adapter Module; converts three on-board NACS to Class A operation
100 W Amplifier Expansion NAC Module; NAC ratings = 1.5 A, 50 W, or 100 speakers max.
100 W Class A Adapter Module; NAC ratings = 2 A, 50 W, or 100 speakers max.
25 VRMS Output; NAC rating = 2 A, 50 W, or 100 speakers max.
70.7 VRMS Output; NAC rating = 0.707 A, 50 W, or 100 speakers max.
Constant Supervision Adapter for three NACs; select per amplifier output; not compatible with amplifier NAC expansion modules; deactivated when on batteries
Choose one per
amplifier
Choose one per amplifier
Mounts on Flex-35/50 assembly; NAC ratings = 1.5 A, 35/50 W, or 100 speakers maximum; Supv = 8 mA, Alarm = 60 mA
Mounts on Flex-35/50 assembly; NAC ratings = 2 A, 50 W, or 100 speakers maximum; Supv =10 mA, Alarm = 30 mA
Provides six additional Class B audio NACs, mounts on 100 W amplifier assembly; Supv = 17 mA, Alarm = 60 mA
Converts six on-board NACs to Class A operation, mounts on 100 W amplifier assembly; Supv = 1 mA, Alarm = 60 mA
Supv = 10 mA on batteries; Alarm = 35 mA
Supv = 38 mA on batteries; Alarm = 70 mA
Converts three Class B audio NACS to Class A or Class B Constant Supervision NACs; mounts on Flex-35/50 or 100 W amplifier assembly; use two for the six NACs on 100 W amplifiers
Firefighters Telephone Options*
Model Description Size Supv. In Use
4100-1272
4100-1273 Telephone Class A Adapter Module; mounts on 4100-1272; no additional current required
* Refer to document S4100-0034 for additional audio information. Continued on next page
5 S4100-0103 5/2013
Expansion Telephone Control Module with three Class B telephone NACS; required when telephone circuits are mounted in transponder;
1 Block 80 mA 130 mA
MINIPLEX Transponder Product Selection (Continued)
Audio Expansion Signal Module and Options
Model Description Details and Mounting Reference
Converts one NAC input to three NAC outputs; selects between two inputs; for Flex-35/50 amplifiers only, two input NACs are required; Single Block module mounts in expansion bay; Supv = 20 mA; Alarm = 80 mA
Expands module capacity to six, Class B NACs; Supv = 0.84 mA; Alarm = 60 mA
Converts 3 Class B, NACs to Class A; Supv = 0 mA; Alarm = 30 mA
NAC rating = 1.4 A, 50 W, or 100 speakers max.;
Supv = 38 mA on batteries (constant supervision deactivated); Alarm = 70 mA
These modules mount on the 4100-5116; select one max. per 4100-5116 as required
4100-5116
4100-1266
4100-1267
4100-1268
Expansion Signal Module; three, 1.5 A Class B NACs for Audio applications; up to five maximum per amplifier; NAC rating = 1.5 A, 50 W, or 100 speakers maximum
Expansion Signal Module NAC Expander; NAC rating =
1.5 A, 50 W, or 100 speakers max. Expansion Signal Module Class A Adapter; NAC rating =
1.5 A, 50 W, or 100 speakers maximum Expansion Signal Module Constant Supervision Adapter;
Converts 3 Class B NACs to Constant Supervision Class B or Class A NACs; for 25 or 70.7 VRMS audio
General Audio Options
Model Description
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 k, 1 W 4100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition 4100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
Addressable Interface Modules
Model Description Supv. Alarm
With 250 IDNet devices, and 20 device LEDs in alarm 292 mA 510 mA
Module without devices 92 mA 115 mA
Loading per IDNet device (no LEDs on) 0.8 mA 1 mA
75 mA 115 mA
4100-3108
4100-3107
IDNet 1+ Module, 250 point capacity with isolated output, 1 block
Quad IDNet Isolator Module; converts a single connected SLC into four isolated outputs selectable as Class A or Class B, provides advanced diagnostics for use with retrofit wiring; dual horizontal block module; (see data sheet S4100-0046 for additional details)
NOTE: This module is compatible with IDNet Remote Isolators
Relay Modules; Nonpower-Limited
Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm
4100-3202 4 DPDT w/feedback 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA 4100-3204 4 DPDT w/feedback 2 A 30 VDC/VAC ½ A 30 VDC/120 VAC 1 Block 15 mA 60 mA 4100-3206 8 SPDT 3 A 30 VDC/120 VAC 1 ½ A 30 VDC/120 VAC 1 Block 15 mA 190 mA
Current Calculation Notes:
1. For total supervisory current, add panel module currents to base system value and add all external panel-powered loads.
2. For total alarm current, add panel module currents to base system alarm current and add all panel SLC/NAC loads and all external
loads powered from panel power supplies.
General Specifications
Enhanced Power Supplies,
Input Power
Expansion Power Supply (XPS)
Power Supply Output Ratings for EPS/EPS+
Power Supply Output Ratings for XPS
(nominal 28 VDC on AC; 24 VDC on battery backup)
Compatible Special Application Appliances
Battery Charger Ratings for EPS/EPS+
(sealed lead-acid batteries)
Environmental
Installation Instruction Reference 574-844, Transponder Interface Cards 579-343, Local Mode Controller
IDNAC Output Voltage Regulated 29 VRMS
Auxiliary Power Tap 2 A maximum
Auxiliary Power Tap 2 A maximum
Battery capacity range
Charger characteristics
Operating Temp. Range 32° to 120°F (0° to 49° C)
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
EPS/EPS+
100 W Amplifiers
Total Power Supply
Output Rating
Total Power Supply
Output Rating
NACs Programmed
for Auxiliary Power
and performance
120 VAC Models
220-240 VAC Models
120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz
220-240 VAC Models
Including module currents and auxiliary power outputs; 9 A total for “Special Application” appliances
9 A total including module currents and auxiliary power outputs
2 A maximum per NAC; 5 A maximum total
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
4.6 A maximum @ 102 to 132 VAC, 50/60 Hz
2.3 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC
2 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC
Output switches to battery backup during mains AC failure or brownout conditions
Rated 19.1 to 31.1 VDC
6 S4100-0103 5/2013
Local Mode Controller Detail
4601-9109 (red) and 4601-9111 (beige); for semi-flush models 4601-9108
Matching box is supplied with surface mount models
(red) and 4601-9110 (beige), use a 1-1/2" (38 mm) minimum depth, 3-gang box
Box dimensions, 6-1/2" (165 mm)
Fire Alarm Local Mode Controller
Local Mode
CONTROL
ENABLE
Local Mode Controller dimensions, 6-3/8" (162 mm)
Control
Alarm
Reset
Silence
See Operating Instruction 579-343
Alarm
Alarm
Silenced
Local Mode Acti ve
Power
On
4-1/2"
(114 mm)
1" (25.4 mm)
into box
4-5/8"
(117 mm)
1-3/4"
(44 mm)
Local Mode Controller to Transponder Wiring:
1. Wire close-nippled to transponder, maximum distance = 20 ft (6.1 m).
2. Nine wires required: 24 VDC (2), one per LED indicator (4), and one per switch (3).
3. Wire size, 18 AWG (0.82 mm² ).
Expansion Bay Module Loading Reference
Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2
Block A
Block B
Block C
Block D
Expansion Bay Chassis
Block E
Block F
Block G
Block H
Size Definitions:
= 4” W x 5.65” H (102 mm x 144 mm); (often
1 Block
called 4 x 5 modules)
1 Slot
= 2” W x 11.3” H (51 mm x 287 mm), typically a
motherboard with daughter card
7 S4100-0103 5/2013
Enclosure Installation Reference
Front view, box outline without door Side view with door attached
3 Bay height =
56" (1422 mm)
Door thickness
4-3/4"(121 mm)
Knockout screw/nail holes (for semi-flush mounting)
2 Bay height =
40" (1016 mm)
1 Bay height =
22" (559 mm)
Doors can be hinged left or right
Exposed cabinet for semi-flush mounting
1-3/8" (35 mm)
minimum
Exposed door and cabinet
for semi-flush mounting
6-1/8" (156 mm) minimum
Optional semi-flush
trim kit reference
Wall board reference for semi-flush mounting, 6" stud
Stud alignment markers, each side
6" stud
4" stud
24" (610 mm)
6-29/32"
(175 mm)
11-11/16" (296 mm)
NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection
shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. VESDA is a trademark of Xtralis Pty Ltd.
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4100-0103 5/2013
www.simplexgrinnell.com
© 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.