Fire Control Panels
UL, ULC Listed; FM, CSFM, Addressable Fire Detection and Control
and MEA (NYC) Approved* MINIPLEX
Features
4100U Series MINIPLEX transponders allow
remotely located initiating and notification
functions:
x Transponder operation is available as standard or with
local mode operation
x Communications with the host fire alarm control panel
use the Remote Unit Interface (RUI) format
Initiating functions include:
x Conventional initiating device circuit (IDC) support
x Addressable device support including TrueAlarm
analog sensor compatibility**
Notification functions include:
x Conventional DC notification appliance circuits
x Emergency voice/alarm communications
x TrueAlert
Local mode operation provides:
x Default local initiating and notification operation in the
event of a communications loss with the host control panel
x Enabling of an optional Local Mode Controller with a
local alarm sounder, LED status indicators, and
keyswitch enabled control switches
x Support for IDNet™ addressable devices, conventional
and TrueAlert addressable notification appliances, and
default output tones from local amplifiers**
Optional modules include:
x Digital or Analog audio riser modules for connection to
system audio signals
x Digital or analog input audio amplifiers with integral
on-board NACs
x Power supplies with or without battery chargers
x City Connect modules and RS-232 ports for printers or
maintenance terminals
x Alarm relays, auxiliary relays, additional IDC modules,
and NAC expansion modules
Cabinets are equipped with solid doors (beige or
red) and in two or three bay sizes
Listed to:
x UL Std. 864, Fire Detection and Control (UOJZ), and
Smoke Control Service (UUKL)
x UL Std. 2017, Process Management Equipment (QVAX)
x UL Std. 1076, Proprietary Alarm Units-Burglar (APOU)
x UL Std. 1730, Smoke Detector Monitor (UULH)
x ULC Std. S527-99
* See pages 4 and 5 for product that is listed as UL or ULC. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health
and Safety Code. See CSFM Listing 7165-0026:251 (non-high rise) and 7170-0026:250 (high
rise) for allowable values and/or conditions concerning material presented in this document. It
is subject to re-examination, revision, and possible cancellation. Accepted for use – City of
New York Department of Buildings – MEA35-93E. Additional listings may be applicable;
contact your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
®
addressable strobe and horn notification
®
Transponders
MINIPLEX transponder
Addressable devices
ALARMFIRE
PULL DOWN
Audio NAC
®
SYSTEM IS NORMAL
08:23:43 am MON 11-DEC-00
ALARMS
SYSTEM WARNINGS
Alarm Silenced
Fire Alarm Priority 2 Alarm
Supervisory Trouble
Fire Alarm
Priority 2
Supv
Trouble
Alarm
Ack
Ack
Ack
Ack
Silence
Event
More
Time
Info
Menu
On
Enable
Arm
Off
Lamp
Disable
Auto
Disarm
Test
Emergency Operating Instructions
Alarm or Warning Condit io n
System indicator flashing. Tone On. Press Alarm Silence.
How to Acknowledge / V i ew Ev e n t s
Press ACK located under flashing indicator.
Repeat operation until all events are acknowledged.
Local tone will sil ence.
AC Power
System
Reset
Previous
Next
C
A
U
T
I
O
N
AB C
D E F G H I
ZONE1SIG2AUX
3
JK L M N O P Q R
FB4IO5IDNet
6
S T U V W X Y Z /
P7A8L
9
'SP' ( ) , 0 :
NET ADDR
DEL
0
Enter C/Exit
How to Silence Building Signals
How to Reset System
Press System Reset.
Press Ack to silence tone device.
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
Fire Control
DISCONNECT
A.C. POWER
AND
N
BATTERY
BEFORE
O
SERVICING
I
T
U
A
SERVICING
BEFORE
C
BATTERY
AND
A.C. POWER
DISCONNECT
Strobe NAC
Fire Alarm Local Mode Controller
Alarm
Local
Mode
Alarm
Control
CONTROL
Silenced
ENABLE
Local
Mode
Active
Alarm
Silence
Reset
Power
On
Local mode
controller
4100U Fire Alarm Control Panel
with Voice Control
Typical 4100U MINIPLEX System One-Line Drawing
Introduction
4100U MINIPLEX transponders connect to a host
4100U Fire Alarm Control Panel using Simplex
unit interface (RUI) communications. At the transponder,
RUI communications are received by the transponder
interface module and translated into the same internal
communications format that is used in the host control
panel.
Remotely located modules. With RUI
communications, the transponder can remotely provide
the same initiating and notification functions that occur at
the host control panel without requiring multiple long
distance wiring runs. Connections to the host panel are
low current communications and audio wiring with
distances up to 2500 ft (762 m).
Software Revisions. Some of the features detailed and
products listed in this document require 4100U System
Software Revision 11.08 or higher. For pre-11.08 system
expansion options, hardware updates may be required.
Contact your local Simplex
** Simplex fire alarm technology is protected by the following U.S. Patent Numbers:
TrueAlarm analog smoke detection: 5,155,468; 5,173,683 and 5,543,777. IDNet and
MAPNET II addressable communications; 4,796,025. TrueAlert addressable notification;
6,313,744 and 6,426,697. SmartSync horn/strobe control; 6,281,789. Flex-35 and Flex-50
amplifier operation; 6,452,491.
®
product supplier for details.
S4100-0035-6 4/2005
®
remote
Introduction (Continued)
Please refer to document S4100-0031 and the other
documents listed on page 3 for additional information
concerning the extensive initiating and notification
features of the 4100U fire alarm control panels.
Module Bay Description
Transponder model 4100-9600 includes a bay
assembly, a power distribution interface module (PDI), a
Basic Transponder Interface Module, and an interconnect
harness. Communications with the host fire alarm control
panel are via a Remote Unit Interface (RUI) connection
that allows for up to 2500 ft (762 m) distance. RUI can
communicate with up to a total of 31 remote devices and
can be either Style 4 or Style 7 communications.
Transponder model 4100-9601 substitutes a Local
Mode Transponder Module for the Basic Transponder
Module.
Optional Expansion Bays each include a PDI and
accept a variety of optional modules (refer to list starting
on page 4).
The Battery Compartment (bottom) accepts two
batteries, up to 50 Ah, that can be mounted within the
cabinet. Battery mounting does not interfere with
available module space. A power supply with battery
charger is required for each battery set.
Packaging Availability
Local Mode Control Operation (Continued)
Notification Operation. Fire alarm conditions reported
against a fire alarm point type within a transponder in
local mode will cause all notification appliance circuits in
that transponder to:
x Sound a general alarm temporal pattern horn tone
x Activate visible notification appliance circuits
Local Mode Module Support. Local mode operation
provides support for the following 4100U modules:
x System Power Supplies (SPS), Expansion Power
Supplies (XPS), and Remote Power Supplies (RPS),
including on-board notification appliance circuits
(NACs) and expansion signal modules, operated at a
temporal pattern,
x TrueAlert Power Supplies (TPS) including the on-board
signaling line circuits (SLCs)
x IDNet addressable device circuits, including those
on-board the SPS, IDNet expansion modules, and the
quad isolator when used for IDNet communications
x 4100U amplifiers will provide their on-board horn tones
(500 Hz) at a temporal pattern through their on-board
amplifier NACs
Local Mode Operation Module Exclusion. Modules
not listed above but that are listed as compatible with
MINIPLEX transponders per this document, do not
interfere with local mode operation but are not supported
during local mode operation.
x Modules are power-limited (except as noted, such as
relay modules)
x Enclosure are available for either two or three bay
sizes or for cabinet rack mounting
x Boxes and solid doors are available in beige or red
(ordered separately)
x Up to eight close-nippled cabinets can be connected at
one transponder location (close-nippled is mounted
within 20 ft (6 m) and with interconnecting wiring
enclosed in conduit)
x Refer to document S4100-0037 for enclosure details
Local Mode Control Operation
Default Stand-Alone Operation. In the event of a
communications loss with the host fire alarm control
panel, model 4100-9601 MINIPLEX Local Mode
Transponders provide fire alarm response default
operation for its connected devices and appliances per the
following.
Input Operation. During local mode operation,
TrueAlarm initiating devices connected to the transponder
will cause an alarm at their least sensitive alarm threshold.
x Photoelectric sensors will alarm at 3.7%/ft smoke
obscuration
x Ionization sensors will alarm at 1.3%/ft obscuration
x Heat sensors will alarm at a fixed temperature of 135° F
(57° C)
x TrueAlarm device LEDs will be activated to indicate a
device in alarm
2 S4100-0035-6 4/2005
Local Mode Controller
Operation. During local mode operation, an optional
Local Mode Controller will indicate status (see illustration
below) and can be enabled using a keyswitch to perform
local alarm silence or reset. If alarms occurring during local
mode are reset using a Local Mode Controller, upon
restoration of communications, those alarms will not be
sent to the master controller. If alarms are still present
upon restoration of communications, then the alarm
condition will be reported and host fire alarm control panel
programmed alarm functions will occur. When
communications are re-established, the local mode
transponder restores automatically.
Mounting. Local Mode Controllers are mounted on
three-gang plates, are available in beige or red, and for
either flush or semi-flush mounting. (See page 7 for
details).
Fire Alarm Local Mode Controller
Local
Mode
CONTROL
ENABLE
Local Mode Controller Module
Control
Alarm
Silence
Reset
See Operating Instruction 579-343
Alarm
Alarm
Silenced
Local
Mode
Active
Power
On
Typical Multi-Floor MINIPLEX Audio System
ALARMFIRE
PULL DOWN
Seventh floor
Legend:
Sixth floor
Fifth floor
Fourth floor
Third floor
PULL DOWN
PULL DOWN
PULL DOWN
PULL DOWN
PULL DOWN
ALARMFIRE
DISCONNECT
A.C. POWER
AND
N
BATTERY
C
BEFORE
O
SERVICING
A
I
U
T
T
U
I
A
SERVICING
O
BEFORE
BATTERY
C
AND
MINIPLEX transponder
N
A.C. POWER
DISCONNECT
Strobe NAC
Speaker NAC
ALARMFIRE
TrueAlarm sensors
and IDNet/MAPNET II
ALARMFIRE
PULL DOWN
addressable circuits
Audio riser wiring,
ALARMFIRE
twisted pair
RUI communications
wiring, twisted, shielded
pair
ALARMFIRE
ALARMFIRE
DISCONNECT
A.C. POWER
AND
N
BATTERY
C
BEFORE
O
SERVICING
A
I
U
T
T
U
I
A
SERVICING
O
BEFORE
C
BATTERY
MINIPLEX transponder
N
AND
A.C. POWER
DISCONNECT
Emergency Operating Instructions
08:23:43 am MON 11-DEC-00
ALARMS
Fire Alarm Pri ority 2 Alarm
Fire Alarm
Priority 2
Ack
Ack
Event
Time
On
Enable
Arm
Off
Disable
Disarm
SYSTEM IS NORMAL
Auto
SYSTEM WARNINGS
Supervisory Trouble
Supv
Trouble
Ack
Ack
More
Info
Lamp
Test
Alarm or Warning Condition
System indicator flashing. Tone On. Press Alarm Silence.
How to Acknowledge / View Events
Press ACK located under flashing indicator.
Repeat operation until all events are acknowl edged.
Local tone will silence.
A B C
D E F G H I
ZONE1SIG2AUX
3
J K L M N O P Q R
FB4IO5IDNet
6
AC Power
S T U V W X Y Z /
Alarm Silenced
P7A8L
9
'SP' ( ) , 0 :
Alarm
System
NET ADDR
Silence
Reset
DEL
0
Enter C/Exit
Previous
Menu
Next
How to Silence Building Signals
How to Reset System
Press System Reset.
Press Ack to silence tone device.
Second floor
First floor
Additional 4100U Data Sheet Reference
Subject Data Sheet Subject Data Sheet
Enclosures S4100-0037 Basic Panel Modules and Accessories S4100-0031
LED/Switch Modules S4100-0032 Network Display Unit (NDU) S4100-0036
4100U Audio/Phone Modules S4100-0034 Remote Annunciators S4100-0038
TrueAlert Addressable Products S4009-0003 Remote Battery Charger S4081-0002
IDNet+ Module with Quad Isolator S4100-0046
3 S4100-0035-6 4/2005
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
Fire Control
4100U Fire Alarm Control Panel
with Voice Control