Cabinets are equipped with solid doors (beige or
red) and in two or three bay sizes
Listed to:
x UL Std. 864, Fire Detection and Control (UOJZ), and
Smoke Control Service (UUKL)
x UL Std. 2017, Process Management Equipment (QVAX)
x UL Std. 1076, Proprietary Alarm Units-Burglar (APOU)
x UL Std. 1730, Smoke Detector Monitor (UULH)
x ULC Std. S527-99
* See pages 4 and 5 for product that is listed as UL or ULC. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health
and Safety Code. See CSFM Listing 7165-0026:251 (non-high rise) and 7170-0026:250 (high
rise) for allowable values and/or conditions concerning material presented in this document. It
is subject to re-examination, revision, and possible cancellation. Accepted for use – City of
New York Department of Buildings – MEA35-93E. Additional listings may be applicable;
contact your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
®
addressable strobe and horn notification
®
Transponders
MINIPLEX transponder
Addressable devices
ALARMFIRE
PULL DOWN
Audio NAC
®
SYSTEM IS NORMAL
08:23:43 am MON 11-DEC-00
ALARMS
SYSTEM WARNINGS
Alarm Silenced
Fire Alarm Priority 2 Alarm
Supervisory Trouble
Fire Alarm
Priority 2
Supv
Trouble
Alarm
Ack
Ack
Ack
Ack
Silence
Event
More
Time
Info
Menu
On
Enable
Arm
Off
Lamp
Disable
Auto
Disarm
Test
Emergency Operating Instructions
Alarm or Warning Condit io n
System indicator flashing. Tone On. Press Alarm Silence.
How to Acknowledge / V i ew Ev e n t s
Press ACK located under flashing indicator.
Repeat operation until all events are acknowledged.
Local tone will sil ence.
AC Power
System
Reset
Previous
Next
C
A
U
T
I
O
N
AB C
D E F G H I
ZONE1SIG2AUX
3
JK L M N O P Q R
FB4IO5IDNet
6
S T U V W X Y Z /
P7A8L
9
'SP' ( ) , 0 :
NET ADDR
DEL
0
Enter C/Exit
How to Silence Building Signals
How to Reset System
Press System Reset.
Press Ack to silence tone device.
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
On
On
Off
Off
Auto
Auto
Fire Control
DISCONNECT
A.C. POWER
AND
N
BATTERY
BEFORE
O
SERVICING
I
T
U
A
SERVICING
BEFORE
C
BATTERY
AND
A.C. POWER
DISCONNECT
Strobe NAC
Fire Alarm Local Mode Controller
Alarm
Local
Mode
Alarm
Control
CONTROL
Silenced
ENABLE
Local
Mode
Active
Alarm
Silence
Reset
Power
On
Local mode
controller
4100U Fire Alarm Control Panel
with Voice Control
Typical 4100U MINIPLEX System One-Line Drawing
Introduction
4100U MINIPLEX transponders connect to a host
4100U Fire Alarm Control Panel using Simplex
unit interface (RUI) communications. At the transponder,
RUI communications are received by the transponder
interface module and translated into the same internal
communications format that is used in the host control
panel.
Remotely located modules. With RUI
communications, the transponder can remotely provide
the same initiating and notification functions that occur at
the host control panel without requiring multiple long
distance wiring runs. Connections to the host panel are
low current communications and audio wiring with
distances up to 2500 ft (762 m).
Software Revisions. Some of the features detailed and
products listed in this document require 4100U System
Software Revision 11.08 or higher. For pre-11.08 system
expansion options, hardware updates may be required.
Contact your local Simplex
** Simplex fire alarm technology is protected by the following U.S. Patent Numbers:
TrueAlarm analog smoke detection: 5,155,468; 5,173,683 and 5,543,777. IDNet and
MAPNET II addressable communications; 4,796,025. TrueAlert addressable notification;
6,313,744 and 6,426,697. SmartSync horn/strobe control; 6,281,789. Flex-35 and Flex-50
amplifier operation; 6,452,491.
®
product supplier for details.
S4100-0035-6 4/2005
®
remote
Introduction (Continued)
Please refer to document S4100-0031 and the other
documents listed on page 3 for additional information
concerning the extensive initiating and notification
features of the 4100U fire alarm control panels.
Module Bay Description
Transponder model 4100-9600 includes a bay
assembly, a power distribution interface module (PDI), a
Basic Transponder Interface Module, and an interconnect
harness. Communications with the host fire alarm control
panel are via a Remote Unit Interface (RUI) connection
that allows for up to 2500 ft (762 m) distance. RUI can
communicate with up to a total of 31 remote devices and
can be either Style 4 or Style 7 communications.
Transponder model 4100-9601 substitutes a Local
Mode Transponder Module for the Basic Transponder
Module.
Optional Expansion Bays each include a PDI and
accept a variety of optional modules (refer to list starting
on page 4).
The Battery Compartment (bottom) accepts two
batteries, up to 50 Ah, that can be mounted within the
cabinet. Battery mounting does not interfere with
available module space. A power supply with battery
charger is required for each battery set.
Packaging Availability
Local Mode Control Operation (Continued)
Notification Operation. Fire alarm conditions reported
against a fire alarm point type within a transponder in
local mode will cause all notification appliance circuits in
that transponder to:
x Sound a general alarm temporal pattern horn tone
Local Mode Module Support. Local mode operation
provides support for the following 4100U modules:
x System Power Supplies (SPS), Expansion Power
Supplies (XPS), and Remote Power Supplies (RPS),
including on-board notification appliance circuits
(NACs) and expansion signal modules, operated at a
temporal pattern,
x TrueAlert Power Supplies (TPS) including the on-board
signaling line circuits (SLCs)
x IDNet addressable device circuits, including those
on-board the SPS, IDNet expansion modules, and the
quad isolator when used for IDNet communications
x 4100U amplifiers will provide their on-board horn tones
(500 Hz) at a temporal pattern through their on-board
amplifier NACs
Local Mode Operation Module Exclusion. Modules
not listed above but that are listed as compatible with
MINIPLEX transponders per this document, do not
interfere with local mode operation but are not supported
during local mode operation.
x Modules are power-limited (except as noted, such as
relay modules)
x Enclosure are available for either two or three bay
sizes or for cabinet rack mounting
x Boxes and solid doors are available in beige or red
(ordered separately)
x Up to eight close-nippled cabinets can be connected at
one transponder location (close-nippled is mounted
within 20 ft (6 m) and with interconnecting wiring
enclosed in conduit)
x Refer to document S4100-0037 for enclosure details
Local Mode Control Operation
Default Stand-Alone Operation. In the event of a
communications loss with the host fire alarm control
panel, model 4100-9601 MINIPLEX Local Mode
Transponders provide fire alarm response default
operation for its connected devices and appliances per the
following.
Input Operation. During local mode operation,
TrueAlarm initiating devices connected to the transponder
will cause an alarm at their least sensitive alarm threshold.
x Photoelectric sensors will alarm at 3.7%/ft smoke
obscuration
x Ionization sensors will alarm at 1.3%/ft obscuration
x Heat sensors will alarm at a fixed temperature of 135° F
(57° C)
x TrueAlarm device LEDs will be activated to indicate a
device in alarm
2 S4100-0035-6 4/2005
Local Mode Controller
Operation. During local mode operation, an optional
Local Mode Controller will indicate status (see illustration
below) and can be enabled using a keyswitch to perform
local alarm silence or reset. If alarms occurring during local
mode are reset using a Local Mode Controller, upon
restoration of communications, those alarms will not be sent to the master controller. If alarms are still present
upon restoration of communications, then the alarm
condition will be reported and host fire alarm control panel
programmed alarm functions will occur. When
communications are re-established, the local mode
transponder restores automatically.
Mounting. Local Mode Controllers are mounted on
three-gang plates, are available in beige or red, and for
either flush or semi-flush mounting. (See page 7 for
details).
Fire Alarm Local Mode Controller
Local
Mode
CONTROL
ENABLE
Local Mode Controller Module
Control
Alarm
Silence
Reset
See Operating Instruction 579-343
Alarm
Alarm
Silenced
Local
Mode
Active
Power
On
Typical Multi-Floor MINIPLEX Audio System
ALARMFIRE
PULL DOWN
Seventh floor
Legend:
Sixth floor
Fifth floor
Fourth floor
Third floor
PULL DOWN
PULL DOWN
PULL DOWN
PULL DOWN
PULL DOWN
ALARMFIRE
DISCONNECT
A.C. POWER
AND
N
BATTERY
C
BEFORE
O
SERVICING
A
I
U
T
T
U
I
A
SERVICING
O
BEFORE
BATTERY
C
AND
MINIPLEX transponder
N
A.C. POWER
DISCONNECT
Strobe NAC
Speaker NAC
ALARMFIRE
TrueAlarm sensors
and IDNet/MAPNET II
ALARMFIRE
PULL DOWN
addressable circuits
Audio riser wiring,
ALARMFIRE
twisted pair
RUI communications
wiring, twisted, shielded
pair
ALARMFIRE
ALARMFIRE
DISCONNECT
A.C. POWER
AND
N
BATTERY
C
BEFORE
O
SERVICING
A
I
U
T
T
U
I
A
SERVICING
O
BEFORE
C
BATTERY
MINIPLEX transponder
N
AND
A.C. POWER
DISCONNECT
Emergency Operating Instructions
08:23:43 am MON 11-DEC-00
ALARMS
Fire Alarm Pri ority 2 Alarm
Fire Alarm
Priority 2
Ack
Ack
Event
Time
On
Enable
Arm
Off
Disable
Disarm
SYSTEM IS NORMAL
Auto
SYSTEM WARNINGS
Supervisory Trouble
Supv
Trouble
Ack
Ack
More
Info
Lamp
Test
Alarm or Warning Condition
System indicator flashing. Tone On. Press Alarm Silence.
How to Acknowledge / View Events
Press ACK located under flashing indicator.
Repeat operation until all events are acknowl edged.
Local tone will silence.
A B C
D E F G H I
ZONE1SIG2AUX
3
J K L M N O P Q R
FB4IO5IDNet
6
AC Power
S T U V W X Y Z /
Alarm Silenced
P7A8L
9
'SP' ( ) , 0 :
Alarm
System
NET ADDR
Silence
Reset
DEL
0
Enter C/Exit
Previous
Menu
Next
How to Silence Building Signals
How to Reset System
Press System Reset.
Press Ack to silence tone device.
Second floor
First floor
Additional 4100U Data Sheet Reference
Subject Data Sheet Subject Data Sheet
Enclosures S4100-0037 Basic Panel Modules and Accessories S4100-0031
LED/Switch Modules S4100-0032 Network Display Unit (NDU) S4100-0036
Local Mode Controller Selection (order as District P.O. from Space Age Electronics)
ModelDescription Supv. Alarm
4601-9108 Flush mount
4601-9109 Surface mount
4601-9110 Flush mount
4601-9111 Surface mount
Communication Modules
ModelDescription SizeSupv. Alarm
4100-6031City Circuit, with disconnect switches20 mA 36 mA
4100-6032City Circuit, without disconnect switches
4100-6033
4100-6038 Dual RS-232 Interface 1 Slot132 mA 132 mA
4100-6045 Decoder Module 3 Slots85 mA 163 mA
4100-6048 VESDA® Aspiration System Interface 1 Slot132 mA 132 mA
4100-9816 Master Clock Interface Module with one standard RS-232 port (see S4100-0033) 1 Slot132 mA 132 mA
Expansion, System, Remote, and TrueAlert Power Supplies and Accessories
ModelVoltage/Listing Description SizeSupv. Alarm
4100-5101 120 VAC UL
4100-5103 120 VAC, Canadian ULC
4100-5102 220-240 VAC UL
4100-5115
4100-5111 120 VAC UL
4100-5112 120 VAC, Canadian ULC
4100-5113 220-240 VAC UL
4100-5125 120 VAC UL
4100-5126 120 VAC, Canadian ULC
4100-5127 220-240 VAC UL
4100-5120 120 VAC UL
4100-5121 120 VAC, Canadian ULC
4100-5122 220-240 VAC UL
4100-5124
4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum
4100-0636
Miscellaneous Options and Accessories
ModelDescription
4100-1290
4100-0632
4100-0633 Door Tamper Switch, connects into Transponder Interface Module, one per cabinet assembly if required
4100-0634 120 VAC
4100-0635 220/230/240 VAC
4100-9837
2081-9031
* Power supply NACs can provide synchronized strobe or SmartSync, two-wire operation. Continued on next page
Basic Transponder, includes bay equipment with power distribution interface, and 4100-0620
Basic Transponder Interface Module mounted in Block A
Local Mode Transponder, includes bay equipment with power distribution
interface, and 4100-0625 Local Mode Transponder Interface Module mounted in
Block A
Red with white
lettering
Beige with
black lettering
Local Mode Controller, 3-gang plate mounted;
flush mount requires a 1-1/2” (38 mm) deep
3-gang box; surface mount controllers include
a matching mounting box; refer to page 7 for
details
For use with SPS
Select one per SPS
only, not RPS
Alarm Relay, 3 Form C relays, 2 A @ 32 VDC; for SPS or RPS
normal 87 mA 87 mA
in local mode 112 mA 112 mA
normal 10 mA 10 mA
in local mode 20 mA 60 mA
Mounts
on SPS
or RPS
87 mA 87 mA
20 mA 36 mA
15 mA 37 mA
Expansion Power Supply (XPS); 9 A output, 3
built-in Class A/B NACs; Canadian models have low
2 Blocks50 mA 50 mA
battery cutout*
NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only
N.A. 25 mA 25 mA
System Power Supply (SPS); 9 A power
supply/charger with 250 point IDNet channel, 3 Class
A/B NACs, and expansion slot for City Circuit or Alarm
4 Blocks175 mA 225 mA
Relay option; Canadian model has low battery cutout*
Remote Power Supply (RPS); 9 A power
supply/charger similar to SPS except no IDNet
channel or City Circuits, will accept one 4100-6033;
4 Blocks150 mA 185 mA
Canadian model has low battery cutout*
TrueAlert Power Supply (TPS); 3 built-in Class B
addressable Signaling Line Circuits (SLCs) rated 3 A
each, built-in battery charger, with 2 A auxiliary power
4 Blocks88 mA 100 mA
output tap; Canadian model has low battery cutout
TrueAlert SLC Class A Adapter for all 3 SLCs, mounts on TPS only
N.A. 7 mA 7 mA
Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet
24 Point I/O Module for external connections, select each point as either a switch input (momentary or maintained) or
an output (for lamp/LED/relay); requires 1 Slot (refer to data sheet S4100-0032 for additional information)
Terminal Block Utility Module; provides 2, 16 position terminal blocks mounted on 4” x 5” single block size, capable of
up to 12 AWG wire (3.31 mm
2
)
Power Distribution Module (PDM) select per system voltage; one required per box
Green LED Power-on Indicator Kit, required for
ULC listing of MINIPLEX transponder
Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper)
470 , 1 W, encapsulated, two 18 AWG leads (0.82 mm
Mounts using knockout provided in solid door
2
), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)
Analog Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible*
ModelDescription Details
4100-1361 25 VRMS output NAC rating = 1.4 A
4100-1362 70.07 VRMS output
4100-1312 25 VRMS output NAC rating = 2 A
4100-1313 70.7 VRMS output
100 W Analog Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
25 VRMS70.7 VRMS
4100-1314 4100-1315 120 VAC, 60 Hz UL
4100-1316
4100-1318
4100-1320
4100-1322
4100-1324
Digital Emergency Voice/Alarm Communications Equipment*
ModelDescription Details
4100-1363 25 VRMS output NAC rating = 1.4 A
4100-1364 70.07 VRMS output
4100-1326 25 VRMS output NAC rating = 2 A
4100-1327 70.7 VRMS output
100 W Digital Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
25 VRMS70.7 VRMS
4100-1328 4100-1329 120 VAC, 60 Hz UL
4100-1330 4100-1331 120 VAC, 60 Hz ULC
4100-1332 4100-1333 220/230/240 VAC, 50/60 Hz UL
4100-1334 4100-1335 120 VAC, 60 Hz UL
4100-1336 4100-1337 120 VAC, 60 Hz ULC
4100-1338 4100-1339 220/230/240 VAC, 50/60 Hz UL
Options for use with either Analog or Digital Amplifiers
ModelDescriptionDetails and Mounting Reference
4100-1245
4100-1246
4100-1248
4100-1249
4100-1259
4100-1260
Firefighters Telephone Options
ModelDescriptionSizeSupv. In Use
4100-1272
4100-1273 Telephone Class A Adapter Module; mounts on 4100-1272; no additional current required
* Refer to document S4100-0034 for additional audio information. Continued on next page
5 S4100-0035-6 4/2005
Dual Channel Analog Audio Riser Module; accepts one or two separate audio signals from
host control panel; mounts in Block B, is controlled by Transponder Interface Module
3-8 Channel Digital Audio Riser Module; similar to analog module, except receives and
decodes a digital input signal with up to eight audio channels; with Non-Alarm Audio input
Flex-35, 35 W Amplifier, constant
supervision compatible
Flex-50, 50 W Amplifier, constant
supervision compatible
Power Supply Input/Listing Description Details
4100-1317
4100-1319
4100-1321
4100-1323
4100-1325
Flex-35/50 Expansion NAC Module; adds three
Class B audio NACs
Flex-35/50 Class A Adapter Module; converts
three on-board NACS to Class A operation
100 W Amplifier Expansion NAC Module; NAC
ratings = 1.5 A, 50 W, or 100 speakers max.
100 W Class A Adapter Module; NAC ratings =
2 A, 50 W, or 100 speakers max.
25 VRMS Output; NAC
rating = 2 A, 50 W, or 100
speakers max.
70.7 VRMS Output; NAC
rating = 0.707 A, 50 W, or
100 speakers max.
Expansion Telephone Control Module with three Class B telephone NACS; required when
telephone circuits are mounted in transponder;
120 VAC, 60 Hz ULC
220/230/240 VAC, 50/60 Hz UL
120 VAC, 60 Hz UL
120 VAC, 60 Hz ULC
220/230/240 VAC, 50/60 Hz UL
Flex-35, 35 W Amplifier, constant
supervision compatible
Flex-50, 50 W Amplifier, constant
supervision compatible
Power Supply Input/Listing Description Details
Choose
one per
amplifier
Choose
one per
amplifier
Constant Supervision
Adapter for three NACs;
select per amplifier output
(not compatible with amplifier
NAC expansion modules)
1 Block 0 mA 0 mA
1 Block 50 mA 50 mA
Includes three on-board
Class B audio NACs;
power is supplied from
an XPS, RPS, or SPS
Primary
100 W
Amplifier
Backup
100 W
Amplifier
Includes three on-board
Class B audio NACs;
power is supplied from
an XPS, RPS, or SPS
Primary
100 W
Amplifier
Backup
100 W
Amplifier
Mounts on Flex-35/50 assembly; NAC ratings = 1.5 A, 35/50 W,
or 100 speakers maximum; Supv = 0.6 mA, Alarm = 60 mA
Mounts on Flex-35/50 assembly; NAC ratings = 2 A, 50 W, or
100 speakers maximum; Supv = 0, Alarm = 30 mA
Provides six additional Class B audio NACs, mounts on 100 W
amplifier assembly; Supv = 1.2 mA, Alarm = 120 mA
Converts six on-board NACs to Class A operation, mounts on
100 W amplifier assembly; Supv = 0, Alarm = 60 mA
Supv = 10 mA
Alarm = 35 mA
Supv = 38 mA
Alarm = 60 mA
Includes six, Class B audio NACs;
NAC rating = 50 W or 100 speakers
maximum; 2 A @ 25 VRMS;
1.4 A @ 70.7 VRMS
Uses the six Class B NACs of primary
amplifier
Includes six, Class B audio NACs;
NAC rating = 50 W or 100 speakers
maximum; 2 A @ 25 VRMS;
1.4 A @ 70.7 VRMS
Uses the six Class B NACs of primary
amplifier
NAC rating = 0.5 A
NAC rating = 0.707 A
NAC rating = 0.5 A
NAC rating = 0.707 A
Converts three Class B audio NACS to
Class A or Class B Constant Supervision
NACs; mounts on Flex-35/50 or 100 W
amplifier assembly; use two for the six NACs
on 100 W amplifiers;
Converts one NAC input to three NAC outputs; selects between two
inputs; for Flex-35/50 amplifiers only, two input NACs are required; Single
Block module mounts in expansion bay; Supv = 18 mA; Alarm with 100 W
amplifiers = 52 mA; Alarm with Flex-35/50 amplifiers = 80 mA
Expands module capacity to six, Class B NACs;
Supv = 0.6 mA; Alarm = 60 mA
Converts 3 Class B, NACs to Class A; Supv = 0.6 mA;
Alarm = 30 mA
NAC rating = 1.4 A, 50 W, or 100 speakers max.;
Current vs operating voltage: 25 VRMS Supv = 10 mA;
25 VRMS Alarm = 35 mA; 70.7 VRMS Supv = 38 mA;
70.7 VRMS Alarm = 60 mA
These
modules
mount on the
4100-5116;
select one
max. per
4100-5116
as required
4100-5116
4100-1266
4100-1267
4100-1268
Expansion Signal Module; three, 1.5 A Class B
NACs for Audio applications; up to five maximum
per amplifier; NAC rating = 1.5 A, 50 W, or 100
speakers maximum
Expansion Signal Module NAC Expander; NAC
rating = 1.5 A, 50 W, or 100 speakers max.
Expansion Signal Module Class A Adapter; NAC
rating = 1.5 A, 50 W, or 100 speakers max.
Expansion Signal Module Constant Supervision
Adapter; Converts 3 Class B NACs to Constant
Supervision Class B or Class A NACs; for
25 VRMS or 70.7 VRMS audio
General Audio Options
ModelDescription
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 k:, 1 W
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
Initiating Device Circuits (IDCs)
ModelDescription SizeSupv. Alarm
4100-5005 Eight zones, Class B 1 Slot 75 mA 195 mA
4100-5015 Eight zones, Class A 1 Slot 75 mA 195 mA
Addressable Interface Modules
ModelDescription SizeSupv. Alarm
4100-3101 IDNet Module, 250 point capacity With 250 IDNet devices, add – 200 mA 250 mA
4100-3104 IDNet Module, 127 point capacity With 127 IDNet devices, add – 102 mA 127 mA
4100-3105 IDNet Module, 64 point capacity With 64 IDNet devices, add – 51 mA 64 mA
IDNet Modules, Specifications for each capacity; Module size = 1 Block
ModelDescription SizeSupv. Alarm
4100-3102
4100-3103
MAPNET II
Module size = 2 Slots; Loading per MAPNET II device = 1.7 mA
Isolator Module for MAPNET II or IDNet communications; converts one SLC into four
isolated Class A or Class B outputs; up to two Modules can be connected to one SLC;
NOTE: Compatible with MAPNET II Remote Isolators only; for quad isolation with IDNet
®
Module, 127 point capacity, add devices separately;
Module without devices – 75 mA 115 mA
Loading per IDNet device – 0.8 mA 1 mA
Module without devices – 270 mA290 mA
Fully loaded module, total – 470 mA490 mA
1 Slot 50 mA 50 mA
Remote Isolators, use 4100-3107 IDNet+ Module (refer to data sheet S4100-0046 for
details)
4100-3202 4 DPDT w/feedback 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA
4100-3204 4 DPDT w/feedback 2 A 30 VDC/VAC 1/2 A 30 VDC/120 VAC 1 Block 18 mA 70 mA
4100-3206 8 SPDT 3 A 30 VDC/120 VAC 1-1/2 A 30 VDC/120 VAC 1 Block 16 mA 200 mA
Current Calculation Notes:
1. For total supervisory current, add panel module currents to base system value and add all external loads panel-powered loads.
2. For total alarm current, add panel module currents to base system alarm current and add all panel NAC loads and all external loads
powered from panel power supplies.
General Specifications
Input Power [System (SPS); Expansion (XPS);
Remote (RPS); TrueAlert Power Supplies (TPS);
and 100 W amplifiers]
Power Supply Output
Ratings (System,
Expansion, and Remote
Power Supplies)
Battery Charger
(System and Remote
Power Supply)
Environmental
6 S4100-0035-6 4/2005
Total Power Supply
Output Rating
Auxiliary Power Tap 2 A maximum @ nominal 28 VDC
NACs Programmed
for Auxiliary Power
Battery capacity range
Charger characteristics
and performance
Operating Temp. Range 32° to 120°F (0° to 49° C)
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
120 VAC Models 3.5 A maximum @ 102 to 132 VAC, 60 Hz
220-240 VAC Models
9 A total @ nominal 28 VDC, including module currents and
auxiliary power outputs
2 A maximum per NAC, 5 A maximum @ nominal 28 VDC
6.2 Ah to 50 Ah; selectable via programming for batteries below 18 Ah; the SPS is UL
listed for up to 110 Ah battery charging for remotely located batteries
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per
UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
1.75 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Output switches to
battery backup
during mains AC
failure or brownout
conditions
Local Mode Controller Detail
4601-9109 (red) and 4601-9111 (beige); for semi-flush models 4601-9108
(red) and 4601-9810 (beige), use a 1-1/2" (38 mm) minimum depth, 3-gang box
Matching box is supplied with surface mount models
Box dimensions, 6-1/2" (165 mm)
1" (25.4 mm)
Fire Alarm Local Mode Controller
Local
Mode
CONTROL
ENABLE
Control
Alarm
Silence
Reset
See Operating Instruction 579-343
Local Mode Controller dimensions, 6-3/8" (162 mm)
Local Mode Controller to Transponder Wiring:
1. Wire close-nippled to transponder, maximum distance = 20 ft (6.1 m).
2. Nine wires required: 24 VDC (2), one per LED indicator (4), and one per switch (3).
3. Wire size, 18 AWG (0.82 mm² ).
Alarm
Alarm
Silenced
Local
Mode
Active
Power
On
4-1/2"
(114 mm)
into box
4-5/8"
(117 mm)
1-3/4"
(44 mm)
Expansion Bay Module Loading Reference
Slot 1Slot 8Slot 7Slot 6Sl ot 5Slot 4Slot 3Slot 2
Block A
Block B
Size Definitions: Block = 4” W x 5” H (102 mm x 127 mm) card area
Slot = 2” W x 8” H (51 mm x 203 mm) motherboard with daughter card
7 S4100-0035-6 4/2005
Block C
Block D
Expansion Bay Chassis
Block E
Block F
Block G
Block H
Description Mounting
Transponder Interface Modules Block A
Audio Riser Modules Block B
Terminal Block Module 1 Block
IDNet Modules 1 Block
4, 2 A Relays 1 Block
4, 10 A Relays 4”, 2 Slots
8, 3 A Relays
NON
Power-limited
1 Block
VESDA Interface 2”, 1 Slot
Class B IDC 2”, 1 Slot
Class A IDC 2”, 1 Slot
MAPNET II Module 4”, 2 Slots
MAPNET II/IDNet Isolator 2”, 1 Slot
Decoder Module 6”, 3 Slots
System, Remote, or TrueAlert
Power Supply
Blocks E, F, G & H
ONLY
Expansion Power Supply Blocks G & H ONLY
NAC Expansion Module On XPS ONLY
Flex-35 Amplifiers, 2 max /bay*
Blocks E & F; C & D;
or A & B
Flex-50 Amplifiers, 2 max/bay* Blocks E & F or C & D
100 W Amplifiers, 1 max/bay Blocks E, F, G & H
100 W Backup Amplifiers, 1 max.
per bay with primary amplifier
Blocks A, B, C & D
Telephone Expansion Module 1 Block
Expansion Signal Module 1 Block
* NOTE: When mounting dual Flex amplifiers on an
expansion bay, special mounting rules apply.
Enclosure Installation Reference
Front view, box outline without doorSide view with door attached
Wall board reference
for semi-flush
mounting, 6" stud
24" (610 mm)
NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection
shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
Tyco, Simplex, the Simplex logo, MAPNET II, IDNet, TrueAlarm, SmartSync, MINIPLEX, and TrueAlert are trademarks of Tyco International Services AG or its affiliates in the
U.S. and/or other countries. VESDA is a trademark of Vision Products Pty Ltd.