Simplex IDNet 4090-9002 Installation Instructions Manual

Features
Model
Description
4090-9002
Relay IAM
Optional Trim Plates
Model
Description
4090-9801
For semi-flush mounted box
Trim plate, galvanized steel, with LED viewing window; includes mounting screws
4090-9802
For surface mounted box
5
6
7
8
1
2
3
4
SIMPLEX TIME RECORDER CO.
4090-9002
RELAY IAM
INST. INSTR. 574-184
DATE CODE:
1
+IDNET
- IDNET
1 2 3 4
5 6 7 8
N.C. N.O.
COM
-
-
-
Communications
4100ES, 4100U, 4010ES or 4010 IDNet communications, 1 address per device
Relay IAM Power
Supplied by IDNet communications
Contact Ratings* (not rated for incandescent switching)
Type
Form C, SPDT
Power-Limited 2 A @ 24 VDC, resistive
from listed fire alarm supply
1 A @ 24 VDC, inductive
Nonpower-Limited
0.5 A @ 120 VAC, resistive
* Provide circuit fusing and transient suppression as
required per application. DC inductive loads can typically be diode suppressed; 120 VAC loads may require RC networks or varistors, depending on device type. Refer to Installation Instructions 574-184 for additional information.
Wire Connections
Screw terminals for in/out wiring, 18 to 14 AWG wire (0.82 to 2.08 mm2 )
IDNet Wiring Reference
Up to 2500 ft ( 762 m) from control panel
Up to 10,000 ft ( 3048 m) total wiring distance (including T-Taps)
Compatible with Simplex 2081-9044 Overvoltage Protectors
Dimensions
4-1/8” H x 4-1/8” W x 1-3/8” D (105 mm x 105 mm x 35 mm)
Housing Material
Black thermoplastic
Mounting Plate
Sheet metal, galvanized
Temperature Range
32° to 120° F (0° to 49° C), intended for indoor operation
Humidity Range
Up to 93% RH at 100° F (38° C)
Multi-Application Peripherals
UL, ULC Listed; FM, CSFM, IDNet™ Communicating Devices and MEA (NYC) Approved* Model 4090-9002 Relay IAM
Individual Addressable Relay Module (Relay IAM):
IDNet addressable control for use with Simplex® fire
alarm control panel models 4100ES, 4100U, 4010ES and 4010
A single addressable point provides control and status
tracking of a Form “C” contact
Low power latching relay design allows IDNet
communications to supply both data and module power
Compact, sealed construction:
Enclosed design minimizes dust infiltration Mounts in standard 4” (102 mm) square electrical box Screw terminals for wiring connections Visible LED flashes to indicate communications Optional covers are available to allow LED to be
viewed after installation
UL listed to Standard 864
Description
IDNet Relay IAMs allow fire alarm control panels to
control a remotely located Form “C” contact using IDNet
addressable communications for both data and module power. Typical applications would be for switching local power for control functions such as elevator capture, or control of HVAC components, pressurization fans, dampers, etc. Relay status is also communicated requiring only one device address.
4090 Series IDNet Relay IAM Package
(shown approximately 1/2 size)
Specifications
Product Selection
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:223 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
S4090-0002-7
Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, and IDNet are trademarks of Tyco International Ltd. and its affiliates and are used under license.
SimplexGrinnell LP Westminster Westminster, MA 01441-0001 USA S4090-0002-7
www.simplexgrinnell.com
© 2011 Tyco. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
4" (102 mm) square box, 2-1/8" (54 mm) minimum depth, RACO 232 or equal (supplied by others)
Double gang blank cover plate and mounting screws, for use when LED is not required to be externally viewed (supplied by others)
4090-9002 Relay IAM
Address setting under
resealable label
Optional Trim Plates for Visible LED
4090-9802, Trim plate for
surface mounted box
4090-9801, Trim plate for
semi-flush mounted box
Mounting Reference, Double Gang Blank Cover Plate
4-9/16"
(116 mm)
4-9/16" (116 mm)
4-5/16"
(109 mm)
Light pipe for LED viewing
4-5/16" (109 mm)
Relay IAM Mounting Information
Loading...